earthquake effect on building

download earthquake effect on building

of 11

Transcript of earthquake effect on building

  • 7/30/2019 earthquake effect on building

    1/11

    1

    ANALYSIS OF EARTHQUAKE GROUND

    MOTIONS : STATIC ANALYSIS

    1

    ANALYSIS OF EARTHQUAKE GROUND

    MOTIONS I: STATIC ANALYSIS

    Requirements of Earthquake Resistant

    Design

    Seismic Coefficient Method

    Torsion due to Eccentricities

    2

    orey r a cu a ons

    Appendages

    Numerical Examples

    Requirements of Earthquake Resistant

    Design

    Earthquake can cause damage not only on

    also due to other chain effects like landslides,

    floods, fires and disruption to communication.

    Therefore it is important to take necessary

    3

    structures so that they are safe against such

    secondary effects also.

    6.1.1 The Characteristics (intensity,

    duration, etc) of Seismic Ground

    Vibrations expected

    epen s on

    Magnitude of EQ

    Depth of Focus Distance from Epicenter

    Characteristics of the Path through which seismic waves

    travel

    4

    Soil strata on which the structure stands

  • 7/30/2019 earthquake effect on building

    2/11

    2

    6.1.2 Response of Structures to Ground

    Vibrations is a Function of ---

    Nature of Foundation Soil

    , ,

    Structures

    Duration and Characteristics of Ground Motions

    IS 1893(Part I): 2002 specifies design forces for structures

    standing on Rocks or soils which do not settle, liquefy or

    5

    slide due to loss of strength during ground vibrations.

    6.1.3 Design Approach:

    Structure should-

    Possess at least a minimum strength to withstand minorEQs (= required

  • 7/30/2019 earthquake effect on building

    3/11

    3

    6.3.2 Design Horizontal EQ Load

    When the Lateral Load resisting elements are oriented

    along orthogonal horizontal directions the structure shall

    be designed for the effects due to full Design EQ Load in

    one horizontal direction at time.

    When the lateral load resisting elements are not oriented

    along the orthogonal horizontal directions, the structure

    shall be desi ned for the effects due to full desi n EQ

    9

    load in one horizontal direction plus 30 % of the design

    EQ load in the other direction

    7.5 Design Lateral Force:

    The Design Lateral Force shall first be computed for the

    buildin as a whole..

    This Design Lateral Force shall then be distributed to the

    various floor levels.

    The overall design seismic force thus obtained at each

    10

    floor level, shall then be distributed to individual Lateral

    Load Resisting elements depending on the floor

    diaphragm action.

    7.5.3 Design Seismic Base Shear

    Total Design Lateral Force or Design Seismic BaseShear (Vb) along any principal direction shall be

    determined by

    Vb = Ah * W

    Where,

    Ah = Design Horizontal acceleration spectrum using thefundamental natural Period Ta , as per the considereddirection of vibration

    11

    W = Seismic weight of the building.

    7.6 Fundamental Natural Period (Tn)

    The Approximate Fundamental Natural Period of Vibration (Tn), in seconds, of a Moment-Resisting FrameBuilding Without Brick Infill Panels may be estimated bythe empirical expression

    Tn = 0.075 * h0.75 for RC Frame Building

    = 0.085 * h0.75 for Steel Frame Building

    Where, h Height of Building in m, excludes the basementstoreys, where basement walls are connected with the

    12

    ground floor deck or fitted between the building columns.

  • 7/30/2019 earthquake effect on building

    4/11

    4

    7.6.2 Tn For all Other Buildings

    For Moment-Resisting Frame Buildings with the infill

    anels

    Tn = 0.09 * h / (d)

    Where, h height of building

    d Base dimension of the building at the Plinth Level, in

    m, along the considered direction of the Lateral Force

    13

    6. 4 Design Spectrum

    6.4.2 The Design Horizontal Seismic Coefficient Ah for a

    structure

    Ah = (Z * I * Sa) / (2 * R * g)

    = (Z/2)*(I/R)*(Sa/g)

    Provided that for any structure with T

  • 7/30/2019 earthquake effect on building

    5/11

    5

    7.4 Seismic Weight

    7.4.1 Seismic Weight of Floors

    DL + % of LL

    the Weight of Columns and Walls in any storey shall be

    equally distributed to the floors above and below the

    storey.

    7.4.2 Seismic Weight of Building

    17

    .

    7.4.3 Any Weight supported in between the storeys shall

    be distributed to the floors above and below in Inverse

    proportion to its distance from the floors.

    7.7 Distribution of Design Force

    7.7.1 Vertical Distribution of Base Shear to Different

    Floor Levels

    Qi = (Vb) * (Wi * hi^2)/( Wi * hi^2)

    Qi Design Lateral Force at Floor I,

    Wi Seismic Weight of Floor I,

    hi Height of Floor I measured from Base,

    18

    n num er o oreys n e u ng s e num er of levels at which the masses are located

    7.9 Torsion

    7.9.1 Provision shall be made in all buildings for Increase in SF on the Lateral Force ResistingElements resulting from the Horizontal Torsional

    of Mass and Centre of Rigidity. However, the NegativeTorsional Shear shall be neglected.

    7.9.2 Design Eccentricity ( whichever gives the moresevere effect) e di static eccentricty, distancebetween CM and CR

    19

    Bi Floor Plan dimension perpendicular to thedirection of Force.

    b0.05-eORb0.05e*1.5e isiisidi +=

    7.11 Deformations

    7.11.1 Storey Drift Limitation

    The storey drift in any storey due to minimum specified

    design lateral force with partial factor of 1.0 shall not

    exceed 0.004 times the storey height. No drift l imit for

    single storey building which has been designed to

    accommodate storey drift.

    20

  • 7/30/2019 earthquake effect on building

    6/11

    6

    7.11.2 Deformation Compatibility of Non-Seismicstructures

    For buildings located in seismic zones IV and V, it shallbe ensured that the structural components that are notpart of the seismic Force Resisting System in thedirection under consideration, do not lose their verticalload-carrying capacity under the induced moments

    21

    storey displacements calculated.

    7.12.2 Cantilever Projections

    7.12.2.1 Vertical Projections

    , , ,Other Vertical cantilever projections attached to buildingsand projecting above the roof shall be designed andchecked for stability forFIVE times the design horizontalseismic coefficient Ah. In the analysis of the building, theweight of these projecting elements will be lumped withthe roof weight.

    22

    7.12.2.2 Horizontal Projections

    All Horizontal Projections like cornices and balconies

    shall be designed and checked for stability for FIVE

    7.12.2.3 The increased Design Forces are ONLY for

    designing the projecting parts and their connections with

    the main structures. For the design of the main structure,

    such increase NEED not be considered.

    23

    Calculation of Design Seismic Force by

    Static Analysis

    Problem Statement:

    Consider G+3 Storey building. The building is located in

    seismic zone III. The soil conditions are medium stiff. The

    R.C. frames are infilled with brick masonry. The lumped

    weight due to dead loads is 10 KN/m2 on floors and on

    24

    roof. The floors carry live load of 5 KN/m on floors and

    roof.

  • 7/30/2019 earthquake effect on building

    7/11

    7

    Cases considered for the analysis

    (a) Only Building.

    (b) Building + Vertical Projection --- Water Tank placed concentrically

    (c) Building + Vertical Projection --- Water Tank placed eccentrically.

    (d) Analysis of cantilever portions --- Vertical & horizontal projections.

    25

    3.0

    3.0

    PLAN AND ELEVATION OF A BUILDING

    3.0

    5 @ 5m c/c

    3.0

    3.0

    PLAN

    26

    3.0

    3.0

    5 @ 5m c/c

    ELEVATION

    Case a): Analysis of G + 3 BUILDING

    Design Parameters:

    For seismic zone III, z= 0.16 (Table 2 of IS:1893)

    mpor ance ac or = . esponse e uc on ac or =

    Seismic Weights:

    Floors: Roof:

    Floor area= 25 X 9 = 225 m2 W4 = 225 x 10

    27

    W1 = W2 = W3 = 225 X (10+0.5 X 5) = 2250 KN

    = 3750 KN

    Total Seismic weight of the structure, W = Wi = 3 X 3750+2250 = 13500 KN

    Fundamental Period:

    EQ in X-direction:

    T = 0.09h/d = 0.09 X 12/25 = 0.216 sec.

    Ah = (Z / 2) X (I/R) X (Sa/g) = (0.16/2) X (1/5) X 2.5 = 0.04

    Vb = Ah X W = 0.04 X 13500 = 540 KN.

    EQ in Y-direction:

    T = 0.09h/d = 0.09 X 12/9 = 0.36sec

    28

    Ah = (Z / 2) X (I/R) X (Sa/g) = (0.16/2) X (1/5) X 2.5 = 0.04

    Vb = Ah X W = 0.04 X 13500 = 540 KN.

    Seismic Force is same in both directions.

  • 7/30/2019 earthquake effect on building

    8/11

    8

    Lateral force distribution along height by

    Static Analysis

    Storey

    Level Wi (KN)

    hi

    (m) Wi hi2 Wihi/(Wihi2

    Lateral Force at ith Level

    for EL in X & Y-direction

    (KN)

    4 2250 12 324 0.40678 219.66

    3 3750 9 303.75 0.381356 205.93

    2 3750 6 135 0.169492 91.52

    29

    1 3750 3 33.75 0.042373 22.88

    796.5 1 540

    VERTICAL PROJECTION (WATER TANK) CONCENTRICALLY

    30

    Case b): Building + Vertical Projection --- Water

    Tank placed concentrically

    DL on floors = 10 KN/m2 , LL on floors = 5 kN/m2

    seismic zone III z = 0.16 ; I = 1 : R = 5

    Seismic Weight calculations:

    L = 9m ; b = 25m ; floor area = 225 sq.m

    31

    LL >= 5KN/sqm , 50% LL need to be considered on all floors except roof.

    Seismic weight on floors :

    w1 = 225(10 + 0.5 x 5) = 2812.5 KN = w2 = w3

    Seismic weight on roof:w4 = DL + wt. of tank

    wt. of tank :

    a) Roof slab = 0.120 x 5.2 x 3.2 x 25 =49.92 = 50 KN

    b)Walls - 0.2 x 16 x 2 x 25 = 160 KN

    c)Bottom slab = 0.2 x 5.2 x 3.2 x 25 = 83.2KN

    4)Beams = 0.6 x 0.3 x (5 x 2 + 3 x 2) x 25 = 72 KN

    32

    5)Staging 4-columns 4 x 0.3 x 0.3 x 2.1 = 18.9 = 19 KN

    Total wt. of tank = 384.2 KN ; Total wt. on roof = 2634.2 KN

    Total wt.of structure = 11071.7 KN

  • 7/30/2019 earthquake effect on building

    9/11

    9

    Lateral force distribution along height bystatic method.

    Storey Lateral force at ith

    Le

    vel

    Wi

    (KN)

    hi,

    m

    Wi hi2

    x 1000

    Wihi /

    Wihi2level for EQx

    and EQy (KN)

    4 2634.0 12 379.3 0.520 229.0

    3 2812.5 9 227.8 0.310 137.5

    2 2812.5 6 101.3 0.140 61.1

    33

    1 2812.5 3 25.3 0.034 15.3

    = 733.7 1 442.9

    VERTICAL PROJECTION (WATER TANK) AT ECCENTRICITY

    3.0

    3.0

    3.0

    5 @ 5m c/c

    3.0

    PLAN

    2.1

    2.0

    34

    5 @ 5m c/c

    3.0

    3.0

    3.0

    ELEVATION

    The lumped wt. of tank on roof causes a shift in center of mass of

    roof level whereas the centre of rigidity remains at the geometrical

    Case c): Building + Vertical Projection --- Water

    Tank placed eccentrically.

    center of roof. Thus an eccentricity in both directions is induced which

    creates torsion & increases the shear.

    EQ in X direction:-

    T = 0.09h/d = 0.09 x 1225 = 0.216 Sec.

    35

    Ah = (Z / 2) X( I / R) X (Sa/g) = 0.04

    Design base shear = Ah x W = 442.868 KN

    EQ in Y direction:-Ah = 0.04,

    Design base shear = Ah x W = 442.868 KN

    The center of mass (CM) is calculated as follows

    wt. of tank = 384.2 KN = 25.613 KN/m2

    2 .

    X= 11.55 m, Y= 4.782 m

    CM (11.56 , 4.73) , CR (12.5, 4.5)

    EQ.in x direction :

    Calculatedeccentricit esi = 12.5 - 11.56= 0.94 m

    36

    Design eccentricity edi = 1.5 x esi + 0.05b OR

    edi = esi - 0.05b whichever gives more severe effect

  • 7/30/2019 earthquake effect on building

    10/11

    10

    edi = 1.5 x 0.94+ 0.05 x 25 = 1.41 + 1.25 = 2.66 m OR

    edi = 0.94 - 0.05 x 25 = 0.94 - 1.25 = -0.31m

    edi = 2.66 m

    EQX = 228.95 KN

    Torsional moment T =(EQX) x (edi) = 609.007 KNm

    Additional shear due to torsion is given as Vx = (T / Ip) x (y) x (Kxx)

    2 2 3 4

    37

    , , . ,

    E = 25 X 106 KN/m2 , Kx = 7500 KN/m,

    (Kx) x Y2 = 1923750, ( Ky) x X2 = 13125000, Ip = 15048750.

    For,

    Ist column line, Vx = 8.195 KN

    2nd column line, Vx = 2.730 KN

    3rd column line, Vx = - 2.731 KN

    4th column line, Vx = - 8.195 KN

    The -ve values are to be neglected while +ve shear to be added i.e. force is

    not to be deducted as per IS 1893 2002.

    38

    Similar calculations follow for Y direction .

    Case d): Design of Projection (Tank- Column)

    Design of container Column:

    Wt. of container = 384.2 KN ; Wt.of water = 30 x 10 = 300 KN.

    Total load = 384.2 + 300 = 684.2 KN

    The projection is to be designed for 5 times Ah --- IS 1893 2002

    = 5 x Ah = 5 x 0.04 = 0.2

    Vb = Ah x W = 0.2 x 684.2 = 136.84 KN.

    39

    . . .

    Axial load = 684.2 / 4 = 171.05 KN

    The column is to be checked for,

    Axial load = 166.32 KN Moment = 139.713 KNm. along both directions.

    Case e): Design considerations for horizontal projections

    Design of horizontal projections for vertical earthquake acceleration.

    = = . .

    Consider a horizontal balcony 0f 1m x 1m with a parapet wall of ht = 1m

    M 20 concrete ; Fe 415 Steel

    L / d =7 M.F.= 1.3

    d = 1000/7 x 1.3 = 109.89mm :

    40

    D = 109.89 + 20 = 129.89 mm =130 mm (say)

    d = 110 mm .

  • 7/30/2019 earthquake effect on building

    11/11

    11

    Loading calculation :

    1) DL = 25 x 0.130 + 1.5 = 4.75 kn/m2

    Assume LL = 5 KN / m2

    o a oa = . m

    ultimate load = 1.5 x 9.75 = 14.635 KN/m2

    Wt. of parapet wall = 1 x 0.1 x 25 = 2.5 KN

    Design moment = WuL2 + Wu x L

    = 14.635 x 1 x 1/ 2 + 2.5 x 1 = 9.82 KN m

    41

    Section design ; for given material Ru = 2.76

    dreq =.(9.82 x 106 / 2.76 x 1000) = 59.65 mm < provided. -- o.k.

    For the seismic acceleration in vertical direction the stability is checked

    Av = (2/3) Ah also these projections are designed for five times

    the horizontal accn.hence Av = (10 / 3) x Ah = (10 / 3) x 0.04 = 0.133

    The overturning moment is obtained for a critical or worst combination as

    Mo = w1 (1 + Av)L / 2 + w2 (1+ Av)L

    w1 = 1 x 1 x 0.130 x 25 + LL;

    w2 = 2.5 KN ( Point load of the Parapet wall)

    42