earthquake effect on building
-
Upload
saurabh-badjate -
Category
Documents
-
view
215 -
download
0
Transcript of earthquake effect on building
-
7/30/2019 earthquake effect on building
1/11
1
ANALYSIS OF EARTHQUAKE GROUND
MOTIONS : STATIC ANALYSIS
1
ANALYSIS OF EARTHQUAKE GROUND
MOTIONS I: STATIC ANALYSIS
Requirements of Earthquake Resistant
Design
Seismic Coefficient Method
Torsion due to Eccentricities
2
orey r a cu a ons
Appendages
Numerical Examples
Requirements of Earthquake Resistant
Design
Earthquake can cause damage not only on
also due to other chain effects like landslides,
floods, fires and disruption to communication.
Therefore it is important to take necessary
3
structures so that they are safe against such
secondary effects also.
6.1.1 The Characteristics (intensity,
duration, etc) of Seismic Ground
Vibrations expected
epen s on
Magnitude of EQ
Depth of Focus Distance from Epicenter
Characteristics of the Path through which seismic waves
travel
4
Soil strata on which the structure stands
-
7/30/2019 earthquake effect on building
2/11
2
6.1.2 Response of Structures to Ground
Vibrations is a Function of ---
Nature of Foundation Soil
, ,
Structures
Duration and Characteristics of Ground Motions
IS 1893(Part I): 2002 specifies design forces for structures
standing on Rocks or soils which do not settle, liquefy or
5
slide due to loss of strength during ground vibrations.
6.1.3 Design Approach:
Structure should-
Possess at least a minimum strength to withstand minorEQs (= required
-
7/30/2019 earthquake effect on building
3/11
3
6.3.2 Design Horizontal EQ Load
When the Lateral Load resisting elements are oriented
along orthogonal horizontal directions the structure shall
be designed for the effects due to full Design EQ Load in
one horizontal direction at time.
When the lateral load resisting elements are not oriented
along the orthogonal horizontal directions, the structure
shall be desi ned for the effects due to full desi n EQ
9
load in one horizontal direction plus 30 % of the design
EQ load in the other direction
7.5 Design Lateral Force:
The Design Lateral Force shall first be computed for the
buildin as a whole..
This Design Lateral Force shall then be distributed to the
various floor levels.
The overall design seismic force thus obtained at each
10
floor level, shall then be distributed to individual Lateral
Load Resisting elements depending on the floor
diaphragm action.
7.5.3 Design Seismic Base Shear
Total Design Lateral Force or Design Seismic BaseShear (Vb) along any principal direction shall be
determined by
Vb = Ah * W
Where,
Ah = Design Horizontal acceleration spectrum using thefundamental natural Period Ta , as per the considereddirection of vibration
11
W = Seismic weight of the building.
7.6 Fundamental Natural Period (Tn)
The Approximate Fundamental Natural Period of Vibration (Tn), in seconds, of a Moment-Resisting FrameBuilding Without Brick Infill Panels may be estimated bythe empirical expression
Tn = 0.075 * h0.75 for RC Frame Building
= 0.085 * h0.75 for Steel Frame Building
Where, h Height of Building in m, excludes the basementstoreys, where basement walls are connected with the
12
ground floor deck or fitted between the building columns.
-
7/30/2019 earthquake effect on building
4/11
4
7.6.2 Tn For all Other Buildings
For Moment-Resisting Frame Buildings with the infill
anels
Tn = 0.09 * h / (d)
Where, h height of building
d Base dimension of the building at the Plinth Level, in
m, along the considered direction of the Lateral Force
13
6. 4 Design Spectrum
6.4.2 The Design Horizontal Seismic Coefficient Ah for a
structure
Ah = (Z * I * Sa) / (2 * R * g)
= (Z/2)*(I/R)*(Sa/g)
Provided that for any structure with T
-
7/30/2019 earthquake effect on building
5/11
5
7.4 Seismic Weight
7.4.1 Seismic Weight of Floors
DL + % of LL
the Weight of Columns and Walls in any storey shall be
equally distributed to the floors above and below the
storey.
7.4.2 Seismic Weight of Building
17
.
7.4.3 Any Weight supported in between the storeys shall
be distributed to the floors above and below in Inverse
proportion to its distance from the floors.
7.7 Distribution of Design Force
7.7.1 Vertical Distribution of Base Shear to Different
Floor Levels
Qi = (Vb) * (Wi * hi^2)/( Wi * hi^2)
Qi Design Lateral Force at Floor I,
Wi Seismic Weight of Floor I,
hi Height of Floor I measured from Base,
18
n num er o oreys n e u ng s e num er of levels at which the masses are located
7.9 Torsion
7.9.1 Provision shall be made in all buildings for Increase in SF on the Lateral Force ResistingElements resulting from the Horizontal Torsional
of Mass and Centre of Rigidity. However, the NegativeTorsional Shear shall be neglected.
7.9.2 Design Eccentricity ( whichever gives the moresevere effect) e di static eccentricty, distancebetween CM and CR
19
Bi Floor Plan dimension perpendicular to thedirection of Force.
b0.05-eORb0.05e*1.5e isiisidi +=
7.11 Deformations
7.11.1 Storey Drift Limitation
The storey drift in any storey due to minimum specified
design lateral force with partial factor of 1.0 shall not
exceed 0.004 times the storey height. No drift l imit for
single storey building which has been designed to
accommodate storey drift.
20
-
7/30/2019 earthquake effect on building
6/11
6
7.11.2 Deformation Compatibility of Non-Seismicstructures
For buildings located in seismic zones IV and V, it shallbe ensured that the structural components that are notpart of the seismic Force Resisting System in thedirection under consideration, do not lose their verticalload-carrying capacity under the induced moments
21
storey displacements calculated.
7.12.2 Cantilever Projections
7.12.2.1 Vertical Projections
, , ,Other Vertical cantilever projections attached to buildingsand projecting above the roof shall be designed andchecked for stability forFIVE times the design horizontalseismic coefficient Ah. In the analysis of the building, theweight of these projecting elements will be lumped withthe roof weight.
22
7.12.2.2 Horizontal Projections
All Horizontal Projections like cornices and balconies
shall be designed and checked for stability for FIVE
7.12.2.3 The increased Design Forces are ONLY for
designing the projecting parts and their connections with
the main structures. For the design of the main structure,
such increase NEED not be considered.
23
Calculation of Design Seismic Force by
Static Analysis
Problem Statement:
Consider G+3 Storey building. The building is located in
seismic zone III. The soil conditions are medium stiff. The
R.C. frames are infilled with brick masonry. The lumped
weight due to dead loads is 10 KN/m2 on floors and on
24
roof. The floors carry live load of 5 KN/m on floors and
roof.
-
7/30/2019 earthquake effect on building
7/11
7
Cases considered for the analysis
(a) Only Building.
(b) Building + Vertical Projection --- Water Tank placed concentrically
(c) Building + Vertical Projection --- Water Tank placed eccentrically.
(d) Analysis of cantilever portions --- Vertical & horizontal projections.
25
3.0
3.0
PLAN AND ELEVATION OF A BUILDING
3.0
5 @ 5m c/c
3.0
3.0
PLAN
26
3.0
3.0
5 @ 5m c/c
ELEVATION
Case a): Analysis of G + 3 BUILDING
Design Parameters:
For seismic zone III, z= 0.16 (Table 2 of IS:1893)
mpor ance ac or = . esponse e uc on ac or =
Seismic Weights:
Floors: Roof:
Floor area= 25 X 9 = 225 m2 W4 = 225 x 10
27
W1 = W2 = W3 = 225 X (10+0.5 X 5) = 2250 KN
= 3750 KN
Total Seismic weight of the structure, W = Wi = 3 X 3750+2250 = 13500 KN
Fundamental Period:
EQ in X-direction:
T = 0.09h/d = 0.09 X 12/25 = 0.216 sec.
Ah = (Z / 2) X (I/R) X (Sa/g) = (0.16/2) X (1/5) X 2.5 = 0.04
Vb = Ah X W = 0.04 X 13500 = 540 KN.
EQ in Y-direction:
T = 0.09h/d = 0.09 X 12/9 = 0.36sec
28
Ah = (Z / 2) X (I/R) X (Sa/g) = (0.16/2) X (1/5) X 2.5 = 0.04
Vb = Ah X W = 0.04 X 13500 = 540 KN.
Seismic Force is same in both directions.
-
7/30/2019 earthquake effect on building
8/11
8
Lateral force distribution along height by
Static Analysis
Storey
Level Wi (KN)
hi
(m) Wi hi2 Wihi/(Wihi2
Lateral Force at ith Level
for EL in X & Y-direction
(KN)
4 2250 12 324 0.40678 219.66
3 3750 9 303.75 0.381356 205.93
2 3750 6 135 0.169492 91.52
29
1 3750 3 33.75 0.042373 22.88
796.5 1 540
VERTICAL PROJECTION (WATER TANK) CONCENTRICALLY
30
Case b): Building + Vertical Projection --- Water
Tank placed concentrically
DL on floors = 10 KN/m2 , LL on floors = 5 kN/m2
seismic zone III z = 0.16 ; I = 1 : R = 5
Seismic Weight calculations:
L = 9m ; b = 25m ; floor area = 225 sq.m
31
LL >= 5KN/sqm , 50% LL need to be considered on all floors except roof.
Seismic weight on floors :
w1 = 225(10 + 0.5 x 5) = 2812.5 KN = w2 = w3
Seismic weight on roof:w4 = DL + wt. of tank
wt. of tank :
a) Roof slab = 0.120 x 5.2 x 3.2 x 25 =49.92 = 50 KN
b)Walls - 0.2 x 16 x 2 x 25 = 160 KN
c)Bottom slab = 0.2 x 5.2 x 3.2 x 25 = 83.2KN
4)Beams = 0.6 x 0.3 x (5 x 2 + 3 x 2) x 25 = 72 KN
32
5)Staging 4-columns 4 x 0.3 x 0.3 x 2.1 = 18.9 = 19 KN
Total wt. of tank = 384.2 KN ; Total wt. on roof = 2634.2 KN
Total wt.of structure = 11071.7 KN
-
7/30/2019 earthquake effect on building
9/11
9
Lateral force distribution along height bystatic method.
Storey Lateral force at ith
Le
vel
Wi
(KN)
hi,
m
Wi hi2
x 1000
Wihi /
Wihi2level for EQx
and EQy (KN)
4 2634.0 12 379.3 0.520 229.0
3 2812.5 9 227.8 0.310 137.5
2 2812.5 6 101.3 0.140 61.1
33
1 2812.5 3 25.3 0.034 15.3
= 733.7 1 442.9
VERTICAL PROJECTION (WATER TANK) AT ECCENTRICITY
3.0
3.0
3.0
5 @ 5m c/c
3.0
PLAN
2.1
2.0
34
5 @ 5m c/c
3.0
3.0
3.0
ELEVATION
The lumped wt. of tank on roof causes a shift in center of mass of
roof level whereas the centre of rigidity remains at the geometrical
Case c): Building + Vertical Projection --- Water
Tank placed eccentrically.
center of roof. Thus an eccentricity in both directions is induced which
creates torsion & increases the shear.
EQ in X direction:-
T = 0.09h/d = 0.09 x 1225 = 0.216 Sec.
35
Ah = (Z / 2) X( I / R) X (Sa/g) = 0.04
Design base shear = Ah x W = 442.868 KN
EQ in Y direction:-Ah = 0.04,
Design base shear = Ah x W = 442.868 KN
The center of mass (CM) is calculated as follows
wt. of tank = 384.2 KN = 25.613 KN/m2
2 .
X= 11.55 m, Y= 4.782 m
CM (11.56 , 4.73) , CR (12.5, 4.5)
EQ.in x direction :
Calculatedeccentricit esi = 12.5 - 11.56= 0.94 m
36
Design eccentricity edi = 1.5 x esi + 0.05b OR
edi = esi - 0.05b whichever gives more severe effect
-
7/30/2019 earthquake effect on building
10/11
10
edi = 1.5 x 0.94+ 0.05 x 25 = 1.41 + 1.25 = 2.66 m OR
edi = 0.94 - 0.05 x 25 = 0.94 - 1.25 = -0.31m
edi = 2.66 m
EQX = 228.95 KN
Torsional moment T =(EQX) x (edi) = 609.007 KNm
Additional shear due to torsion is given as Vx = (T / Ip) x (y) x (Kxx)
2 2 3 4
37
, , . ,
E = 25 X 106 KN/m2 , Kx = 7500 KN/m,
(Kx) x Y2 = 1923750, ( Ky) x X2 = 13125000, Ip = 15048750.
For,
Ist column line, Vx = 8.195 KN
2nd column line, Vx = 2.730 KN
3rd column line, Vx = - 2.731 KN
4th column line, Vx = - 8.195 KN
The -ve values are to be neglected while +ve shear to be added i.e. force is
not to be deducted as per IS 1893 2002.
38
Similar calculations follow for Y direction .
Case d): Design of Projection (Tank- Column)
Design of container Column:
Wt. of container = 384.2 KN ; Wt.of water = 30 x 10 = 300 KN.
Total load = 384.2 + 300 = 684.2 KN
The projection is to be designed for 5 times Ah --- IS 1893 2002
= 5 x Ah = 5 x 0.04 = 0.2
Vb = Ah x W = 0.2 x 684.2 = 136.84 KN.
39
. . .
Axial load = 684.2 / 4 = 171.05 KN
The column is to be checked for,
Axial load = 166.32 KN Moment = 139.713 KNm. along both directions.
Case e): Design considerations for horizontal projections
Design of horizontal projections for vertical earthquake acceleration.
= = . .
Consider a horizontal balcony 0f 1m x 1m with a parapet wall of ht = 1m
M 20 concrete ; Fe 415 Steel
L / d =7 M.F.= 1.3
d = 1000/7 x 1.3 = 109.89mm :
40
D = 109.89 + 20 = 129.89 mm =130 mm (say)
d = 110 mm .
-
7/30/2019 earthquake effect on building
11/11
11
Loading calculation :
1) DL = 25 x 0.130 + 1.5 = 4.75 kn/m2
Assume LL = 5 KN / m2
o a oa = . m
ultimate load = 1.5 x 9.75 = 14.635 KN/m2
Wt. of parapet wall = 1 x 0.1 x 25 = 2.5 KN
Design moment = WuL2 + Wu x L
= 14.635 x 1 x 1/ 2 + 2.5 x 1 = 9.82 KN m
41
Section design ; for given material Ru = 2.76
dreq =.(9.82 x 106 / 2.76 x 1000) = 59.65 mm < provided. -- o.k.
For the seismic acceleration in vertical direction the stability is checked
Av = (2/3) Ah also these projections are designed for five times
the horizontal accn.hence Av = (10 / 3) x Ah = (10 / 3) x 0.04 = 0.133
The overturning moment is obtained for a critical or worst combination as
Mo = w1 (1 + Av)L / 2 + w2 (1+ Av)L
w1 = 1 x 1 x 0.130 x 25 + LL;
w2 = 2.5 KN ( Point load of the Parapet wall)
42