EA660 modular UPS system introductionEA660 modular UPS system introduction
☞ Power range:20-400KVA
☞ Working mode:Intelligent on line (three phases)
☞ Applications :IDC data center,Cl d ti tCloud computing center
☞ Certificate CE
2/35
Battery moduleBattery module
H t bl b tt d l thHot swappable battery module , the same
size as the power module ,completely
compatible with the power module drawercompatible with the power module drawer,
without changing the modular cabinet of
UPS system Supporting online hot swapUPS system. Supporting online hot swap,
easy maintenance, redundant battery
module is available , providing highmodule is available , providing high
availability.
6/35
Features of battery moduleFeatures of battery module
The overall design using the same size as power module, power module
slot compatible.
Each battery module equipped with circuit breaker, with short circuit
protection function, more reliability.
Battery module has low voltage& over discharge protection function.
Battery with hot swap design. Simple operation, easy maintenance.
Hot swappable and parallelizability battery module function, providing
higher availability with redundancy battery module.
Internal battery module using high performance free maintenance lead-
acid batteries, with long service life.
Battery module according to the 2 groups of multiple selection, each
b tt d l t i 2 b tt k b tt k t i i 10
7/35
battery module contains 2 battery pack, battery pack containing 10 pcs
12V/ 9AH batteries.
Modular UPS EA660 advantages reliability
Imports components are used internal
Modular UPS EA660 advantages - reliability
Name Model Brand
Imports components are used internal
DSP TMS320F2812 TI
IGBT IKW40N120H3 INFINEON
IGBT IRG4PF50WPBF IR
SCR CLA50E1200HB IXYS
SCR SK100KQ12 SEMIKRON
Fast recovery RHRG75120 IRFast recovery diode RHRG75120 IR
DC relay T92S7D12-12 TYCO Electronics
8/35
Modular UPS EA660 advantages - reliabilityg yWorld-class brands :IC from American TI,IGBT,SCR from Germany INFINEON
Redundancy control
Dual input
system
Decentralized bypasscontrol
9/35Dust netIndependent air-duct design SPD
Modular UPS EA660 advantages reliabilityModular UPS EA660 advantages - reliability
N+X technology for redundancy
Communicating module
LCD screen
gy y
Battery
moduleINTERFACE
(USB,RS232,RS485,SNMP,dry contact)Charging moduleFuse
Mains
UPS Module 1
UPS Module 2
Breaker
Breker
Load
UPS Module 8
Manuall bypass breaker
10/35
Intelligent battery managementg y g
Battery number can be set 32-40 Intelligent three-stage charging
11/35
Battery self-test Battery compensation, management
Intelligent battery management
battery battery
Faulty battery
Easy maintenance-battery number can be set between 16-20 pcs, faulty batteries can be removed
12/35
IGBT rectifier-Green energy high efficiencyIGBT rectifier Green energy, high efficiency
Input power factor> 0.99,IGBT rectifier Input harmonic current < 3%IGBT rectifier
13/35
Voltage
Current
IGBT rectifier waveformInput harmonic current <3%Input power factor:0.99
6-pulse SCR rectified waveformInput harmonic current >30% Input power factor:0.85
12-pulse SCR rectified waveformInput harmonic current >10% Input power factor:0.90
Advantage of high input power factor and low input harmonic current:
1 Less requirement for transformer and generator before the UPS2 Less requirement for input cables and capacity of the breaker3 Decrease the failure rate from the harmonic current
14/35
3 Decrease the failure rate from the harmonic current
Example :
UPS power 200KVA Remark
Example :
UPS power 200KVA Remark
Rectifier structure IGBT SCR
I t f t 0 99 0 85Input power factor 0.99 0.85
Harmonic current 3% 30%
Capacity ratio 1-1.2:1 3:1
Capacity of generator 240KW 600KW
Cummins generator price 31K USD 74K USD 43K USD
can be saved
Breaker capacity 400A 500A ABB brand
Cables 120 square meters 150 square meters
15/35
UPS t ffi i 93%UPS system efficiency >93%
Efficiency
Efficiency compared with traditional low frequency UPS
Modular UPS
Traditional low frequency UPS
Load rate
16/35
Easy expansion by increasing power module
Load power
Load percentage
Load power
L d t
17/35
Load percentage
E i t H t d f ll th d lEasy maintenance-Hot swapped for all the modules
Maintenance can be finished within 1 minutes
All the modules are hot swapped
18/35
E i t S ll i li ht i htEasy maintenance-Small size, light weight
PK200KVA
PK
2000mm 1950mm
modular tower
Weight 510kg 900kg
A 0 6 2 1 04 2
modular tower
1000mm600mm
860mm 1210mm
Area 0.6m2 1.04m2
19/35
Easy maintenance-Big LCD display
LCD+LED+button, friendly interface operations management
Easy maintenance Big LCD display
LCD LED button, friendly interface operations management
LEDLCD
Button
EPO Cold start
Super LCD screen:5.7 inches
High resolution :320 ×240
Intelligent battery monitoring and management
Function setting
10000 Hi t l
20/35
10000 History log
Extensive monitoring interface for different demandsExtensive monitoring interface for different demands
SNMP RS232 RS485 USB Tem compensation Dry contactp y
Remote monitoring can be
available everywhere and every y y
time
21/35
Modular UPS system configurationDimensions(m WeightName Model Dimensions(m
m)Weight(kg) Configuration
1、Standard configuration is 1 monitoring module,1 charging module;
EA66100 600*1000*1600 225odu e, c a g g odu e;
2、4 modules can be placed;3、Mains input, bypass, output, manual bypass is standard configuration;1 St d d fi ti i 1 it i
System EA66160 600*1000*2000 290
1、Standard configuration is 1 monitoring module,1 charging module;2、8 modules can be placed;3、Mains input, bypass, output, manual 3、 a s pu , bypass, ou pu , a uabypass is standard configuration;
EA66200 600*1000*2000 2801、Standard configuration is 1 monitoring module,1 charging module;2 10 d l b l d2、10 modules can be placed;
EA66400 1200*1000*2000 560
1、Standard configuration is 1 monitoring module,2 charging module;2、20 modules can be placed;2、20 modules can be placed;
Power module
EA66-20PMD 482*590*131 28 Power :20KVA
Charging d l EA66-CM 482*590*131 27 Charging current:30A for each module
23/35
module EA66 CM 482 590 131 27 Charging current:30A for each module
Monitoring module EA66-MM 482*590*131 7
Standard and option configurationStandard and option configurationFunction Explanation Standard Option
C i i RS232、USB、RS485 √Communication port RS232、USB、RS485 √
7 dry contactInverter output、mains input abnormal、overload 、bypass output、system fault、 √7 dry contact overload 、bypass output、system fault、low battery warning、system warning
√
C class SPD To protect UPS from thunderbolt. 20KA impulse can be protected. √p p
Network monitor SNMP card:internal & external √
Charging module can detect theBattery temperature compensation
Charging module can detect the temperature through the interface, providing temperature compensation
√
Control the connection between the battery √Battery breaker Control the connection between the battery and the UPS √
Output distributionIncluding 15 breakers,10-32A optional,breaker brand optional(must be selected √
24/35
Output distribution module
breaker brand optional(must be selected the first time purchase,can’t increase the capacity in the future)
√
Modular UPS specification pPower module:20KVA
Power supply:three phases in three phases out
Input voltage range:204-520Vac, input frequency range:40-70Hz
Input power factor:>0.99, Input harmonic current :<3%
Output power factor:1.0/0.9
Efficiency :>93%
Redundancy parallel:80KVA、160KVA、200KVA can parallel 2 pcs;power more than
200KVA can’t be parallel
Battery number:12V40 pcs(positive and negative,20 pcs for each)32、34、36、38
pcs available;
Ch i t 30A f d l 60A i il bl f 80 200KVA 120A i il blCharging current:30A for one module; 60A is available for 80-200KVA ,120A is available
for that more than 200KVA ;
Low battery alarm point :11VDC*battery number end of discharge:10 2VDC*battery
25/35
Low battery alarm point :11VDC battery number, end of discharge:10.2VDC battery
number
Q&A1. EAST modular UPS static bypass is decentralized controlled, how about the reliability compared with centralized bypass ?
Although centralized bypass control is simple and easy to implement, but single point of
failure can‘t be ignored ,that is why we decide to use decentralized bypass . Currently in
the industry , Eaton, Sakmann, Granville and other modular UPS are all used in a
decentralized bypass technology.
W h t i h d l t k th t d l f lt th thWe have over current in each module, to make sure that once one module fault, the other
can still work.
2 O l h i t li bilit f EAST d l UPS?2. Only one charger is not reliability for EAST modular UPS?
If the charger is dispersed in each power module, once the internal charger is
damaged or short circuit the power module also fails the module does not workdamaged or short circuit, the power module also fails, the module does not work,
with a decline of carrying capacity, which will affect the availability of the entire
system. EAST UPS can use 2 charger for redundancy,200KVA or less can have 2
26/35
chargers, power more than 200KVA can have 4 chargers parallel.