EA200 - Elec.ru · 2020. 8. 26. · Self-diagnosis at UPS Start Up. The UPS will perform advanced...

10
EA200 EA200 series 500 - 3000VA The EA200 supplies your company, home office or satellite locations of your enterprise, through the use of the latest line interactive AVR technologies with clean and stable power 24/7.

Transcript of EA200 - Elec.ru · 2020. 8. 26. · Self-diagnosis at UPS Start Up. The UPS will perform advanced...

Page 1: EA200 - Elec.ru · 2020. 8. 26. · Self-diagnosis at UPS Start Up. The UPS will perform advanced self-diagnostics . to ensure the functionality of the UPS system and batteries, and

EA200EA200 series500 - 3000VA

The EA200 supplies your company, home office or satellite locations of your enterprise, through the use of the latest line interactive AVR technologies with clean and stable power 24/7.

Page 2: EA200 - Elec.ru · 2020. 8. 26. · Self-diagnosis at UPS Start Up. The UPS will perform advanced self-diagnostics . to ensure the functionality of the UPS system and batteries, and

EA200 series500 - 3000VA

Table of contents

5 Introduction

8 EA200N series

9 Outdoor series

10 Technical data sheets EA200 LED

12 Technical data sheets EA200 LCD

14 Technical data sheets EA200N LCD

16 Technical data sheets Outdoor UPS

17 Notes

Page 3: EA200 - Elec.ru · 2020. 8. 26. · Self-diagnosis at UPS Start Up. The UPS will perform advanced self-diagnostics . to ensure the functionality of the UPS system and batteries, and

Introduction

The EA200 is the ideal solution for providing back-ups for small companies, home offices and the satellite locations of large enterprises.

The user is ensured of high quality power through the utilization of the latest line interactive AVR technologies, which protect connected devices from interference and over and under voltage. Through the employment of UPS software, users are able to ensure a controlled shutdown of a connected computer in the event of a power failure.

Line Interactive

The EA200 adopts the latest AVR line interactive technolgy, detecting a power outage and switching to battery in only a few milliseconds. The line-interactive UPS interacts with the AC power line to smooth out waveforms and correct the rise and fall of the voltage, utilizing the automatic voltage regulator (AVR) to maintain a constant voltage level, without any need for human intervention.

Wide Input Voltage Range

The EA200 provides stable power to connected devices in unstable power conditions. It is capable of handling a wide input voltage range, supplying clean power in extreme circumstances.

Cold Start

In the absence of any AC input, the cold start function allows users to start the UPS with the batteries, and without any damage to them or the circuits. This means that users can easily configure the UPS, even if no AC input is available.

Fanless Design

The unique fanless design of the EA200 is possible because the aluminum chassis acts as a heat sink with which to dissipate internal heat. The result is a noise-free operation which does not attract dust. This makes the EA200 UPS system perfect for harsh environments.

5EA200 SERIES / www.eastpwr.com4 EA200 SERIES / www.eastpwr.com

Where will you be when the lights go out?

Page 4: EA200 - Elec.ru · 2020. 8. 26. · Self-diagnosis at UPS Start Up. The UPS will perform advanced self-diagnostics . to ensure the functionality of the UPS system and batteries, and

Self-diagnosis at UPS Start Up

The UPS will perform advanced self-diagnostics to ensure the functionality of the UPS system and batteries, and to anticipate events before they occur.

Lightning and Surge Protection

The EA200 UPS systems come with lightning and surge protection as standard, thus protecting the equipment against voltage spikes.

Short Circuit and Overload Protection

A short circuit is an abnormal connection between two nodes of an electrical circuit, and can cause huge damage to the UPS and any equipment attached to it. The EA200 circuit protection device will protect against potential short circuit damage, overheating, fire, or even explosions. The UPS is also equipped with overload protection, meaning that the fuse will automatically be triggered when a load exceeds its value. Both protection devices ensure the safety and reliability of the UPS and any equipment that is attached to it.

6 7EA200 SERIES / www.eastpwr.com EA200 SERIES / www.eastpwr.com

Standard Shutdown Software

The EA200 software is able to automatically shut down the server or computer when a power failure occurs. It allows the UPS to instruct the operating systems to close down a PC when it is running unattended. Users can set the parameters with which to schedule when the computer or server should shutdown, making sure that no significant data is lost and important backups are created. Updates will be automatically sent by email, so that users are always aware of what is happening, even at remote locations.

User Friendly LCD Display

The user friendly LCD display, which is situated at the front of the EA200 LCD series, provides instantaneous information. The user is able to observe values such as input and output voltage, input and output frequency, load in percentage terms, and available battery capacity.

User friendly LED display

The user friendly LED display, which is situatedat the front of the EA200 LED 1500VA and up, provides instantaneous information. The user is able to observe values such as running on battery, load in percentage terms, and available battery capacity.

Rack Mountable

The EA200 LCD is also available as a 19 inch rack mountable device. Due to its small depth, it is easily deployable in smaller, wall-mountedcabinets, making it the ideal solution for telecom systems and in decentralized locations of your organization.

The LED display will supply the user of relevant information

Surge protection also for your Telephone and Network connection

The front side of the EA200 LCD Rack mountable

The backside of the EA200 LCD Rack mountable

The LCD display providing the user with all relevant information

The backside conveniently equipped with IEC plugsThe fronts of the EA200 LED and LCD.

Page 5: EA200 - Elec.ru · 2020. 8. 26. · Self-diagnosis at UPS Start Up. The UPS will perform advanced self-diagnostics . to ensure the functionality of the UPS system and batteries, and

The request to have more functionalities without losing the origin and basics of the EA200 series was needed to comply with customers’ requirements. Therefor we have designed the EA200N series; the same principles as the EA200 series only including a wave filter for a pure sine wave ups system, availabe in rack and tabletop and the option to have software via SNMP included, both in and external.

SNMP Card (optional)

The SNMP card allows users to connect the EA200N directly to the ethernet network and the internet. This solution means that you can conveniently monitor and manage the UPS with a standard web browser, while simultaneously being able to shutdown multiple computers andoperating systems over the network.

Relay I/O Card (optional)

The Relay I/O card can be inserted in the SNMP slot at the back of the UPS, providing dry contact relay outputs for custom-wired applications and delivering support for the built-in shutdown of AS/400 systems. This option provides contact closures for the remote monitoring of alarm conditions in the UPS, delivering signals for On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS.

Rackmountable

To complete the EA200N series the unit is available in table and rackmount make.Making this configuration suitable for all smaller locations, including smaller telecom applications, servers and office configurations.

8 9EA200 SERIES / www.eastpwr.com EA200 SERIES / www.eastpwr.com

Outdoor SeriesEA200N Series

The EA200N series are designed to fit all locations and environments; even the outdoor ones. Providing a complete solution for your outdoor applications without making any compromises.

IP65

The IP65 protection level of the cabinets are built and designed for applications where a sealed environment from water, dust and wind is required.

Features and Benefits• Fully tested to IP65 AS 1939-1990 Category 1• Gland plates standard to maintain IP65 integrity

Door

The outdoor mounted unit is designed to open sideways, making it accessible and convenient for maintenance. What’s more, the option of installing cabinets next to each other, thus avoiding problems with the accessibility of connection cables, making this an extra safety feature.

Lock

The EA200N is equipped with a door lock, preventing the unauthorized operation of the system and ensuring safety in the EA200N and, more importantly, the equipment attached to it.

Color

Standard any RAL color is available. on request Camouflage or other special colors can be ordered as an option.

The SNMP card

The front side of the EA200N Rack mountable

The front side of the EA200N Table Top

Pure Sine-wave versus Modified Square-wave

Time

240

160

80

0

-80

-160

-2400 10 20 30 40 50

Vol

ts

Page 6: EA200 - Elec.ru · 2020. 8. 26. · Self-diagnosis at UPS Start Up. The UPS will perform advanced self-diagnostics . to ensure the functionality of the UPS system and batteries, and

EAST Power N.V. technical data sheet EA200 LED [Line Interactive 500VA - 850VA, single phase]

Model EA250-LED EA265-LED EA280-LED EA285-LED

VA Rating 500 VA 650 VA 800 VA 850 VA

Real Power Rating 300 Watt 390 Watt 480 Watt 510 Watt

INPUT

Phase Single Phase + N

Voltage 100V/110V/120V or 220V/230V/240V ± 25%

Frequency 50/60Hz ± 10%

OUTPUT

Voltage 100/110/120V or 220/230/240V ± 10%

Waveform Sine Wave [Mains]; Square Wave [Battery]

Frequency 50/60Hz ± 1% [Battery]

Crest Factor 3:1

Power Factor 0.6

Transfer time ≤ 10 ms

Sockets IEC C13 [multi-type sockets optional]

BATTERY

Model Maintenance Free Sealed Lead-Acid

DC Voltage 12VDC 24VDC

Configuration 1x 12V/7Ah 1x 12V/8Ah 2x 12V/7Ah

Recharge time 90% Capacity after 8 Hours

Backup Time [Full load] 10 ~ 20 minutes, Depending on Load and Model

PANEL DISPLAY

LED AC Normal; Battery charging; On battery

GENERAL

Transformer E Transformer

Communication RS232/USB

Noise < 45db [1 Meter]

Temperature 0 ~ 40 °C

Humidity 20 ~ 90% [non-condensing]

Dimension [mm] [H x W x D] 165 x 95 x 340

Net weight [Kg] 4.5 5.6 6.7 6.7

Packing dimension [mm] [H x W x D] 230 x 145 x 375

Gross weight [Kg] 4.8 6.1 7.2 7.2

10 EA200 SERIES / www.eastpwr.com 11EA200 SERIES / www.eastpwr.com

Product Specifications are subject to change without further notice, © EAST Power N.V.

Technical data sheet EA200 LED (500-1500 VA)EAST Power N.V. technical data sheet EA200 LED [Line Interactive 1000VA - 1500VA, single phase]

Model EA2100-LED EA2120-LED EA2150-LED

VA Rating 1000 VA 1200 VA 1500 VA

Real Power Rating 600 Watt 720 Watt 900 Watt

INPUT

Phase Single Phase + N

Voltage 100V/110V/120V or 220V/230V/240V ± 25%

Frequency 50/60Hz ± 10%

OUTPUT

Voltage 100/110/120V or 220/230/240V ± 10%

Waveform Sine Wave [Mains]; Square Wave [Battery]

Frequency 50/60Hz ± 1% [Battery]

Crest Factor 3:1

Power Factor 0.6

Transfer time ≤ 10 ms

Sockets IEC C13 [multi-type sockets optional]

BATTERY

Model Maintenance Free Sealed Lead-Acid

DC Voltage 24VDC

Configuration 2x 12V/7Ah 2x 12V/8Ah

Recharge time 90% Capacity after 8 Hours

Backup Time [Full load] 10 ~ 20 minutes, Depending on Load and Model

PANEL DISPLAY

LED AC Normal; Battery charging; On battery

GENERAL

Transformer E Transformer

Communication RS232/USB

Noise < 45db [1 Meter]

Temperature 0 ~ 40 °C

Humidity 20 ~ 90% [non-condensing]

Dimension [mm] [H x W x D] 220 x 125 x 400

Net weight [Kg] 10.1 10.3 13.5

Packing dimension [mm] [H x W x D] 295 x 180 x 450

Gross weight [Kg] 10.6 10.9 14.0

Product Specifications are subject to change without further notice, © EAST Power N.V.

Page 7: EA200 - Elec.ru · 2020. 8. 26. · Self-diagnosis at UPS Start Up. The UPS will perform advanced self-diagnostics . to ensure the functionality of the UPS system and batteries, and

EAST Power N.V. technical data sheet EA200[R] LCD [Line Interactive 1000VA - 1500VA]

Model EA2100[R]-LCD EA2120[R]-LCD EA2150[R]-LCD

VA Rating 1000 VA 1200 VA 1500 VA

Real Power Rating 6000 Watt 720 Watt 900 Watt

INPUT

Phase Single Phase + N

Voltage 100V/110V/120V or 220V/230V/240V ± 25%

Frequency 45 ~ 55 ± 1Hz / 55 ~ 65 ± 1Hz

OUTPUT

AVR Yes

Voltage 100V/110V/120V or 220V/230V/240V ± 10%

Frequency AC Mode; Track the Utility Battery Mode; 50 ± 0.5Hz/60 ±

Waveform Sine Wave [Mains]; Modified Sine Wave [Battery]

Short Circuit Protection AC Mode: Fuse Battery Mode: Shutdown immediately and switch to Fault Mode

Crest Factor 3:1 [Max]

Transfer time Typical Value 2 ~ 7 ms, Max: 10ms

SURGE PROTECTION

Telephone/LAN RJ11 & RJ45 for Modem and LAN

BATTERY

Model Maintenance Free Sealed Lead-Acid

DC Voltage 24VDC

Configuration 2 x 12V/7Ah 2x 12V/8Ah

Charge Current 350mA ~ 1.2 A

Backup Time [Full load] ≥ 3 min.

PANEL DISPLAY

LCD Battery capacity; Load percentage; Output voltage; Input voltage/frequency; alarm

GENERAL

Communication RS232/USB [optional]

Audible Noise [1m] ≤ 45db

Temperature 0 ~ 40 °C

Relative Humidity 0 ~ 90% [non-condensing]

Altitude ≤ 1500 meter

Storage Temperature -25 ~ 55 °C

Dimension [mm] [H x W x D] 220 x 125 x 400

Rack Mount [mm] [H x W x D] 150 x 480 x 350

Net weight [Kg] 10.1 10.3 13.5

Rack Mount Net Weight [Kg] 12.4 12.6 15.8

Packing Dimension [mm] [H x W x D] 295 x 180 x 450

Packing Dimensions Rack Mount [mm] [H x W x D]

180 x 535 x 400 230 x 535 x 400

Gross weight [Kg] 10.6 10.9 14.0

Rack Mount Gross weight [Kg] 12.9 13.2 16.3

EAST Power N.V. technical data sheet EA200[R] LCD [Line Interactive 500VA - 850VA]

Model EA250[R]-LCD EA265[R]-LCD EA280[R]-LCD EA285[R]-LCD

VA Rating 500 VA 650 VA 800 VA 850 VA

Real Power Rating 300 Watt 390 Watt 480 Watt 510 Watt

INPUT

Phase Single Phase + N

Voltage 100V/110V/120V or 220V/230V/240V ± 25%

Frequency 45 ~ 55 ± 1Hz / 55 ~ 65 ± 1Hz

OUTPUT

AVR Yes

Voltage 100V/110V/120V or 220V/230V/240V ± 10%

Frequency AC Mode; Track the Utility Battery Mode; 50 ± 0.5Hz/60 ±

Waveform Sine Wave [Mains]; Modified Sine Wave [Battery]

Short Circuit Protection AC Mode: Fuse Battery Mode: Shutdown immediately and switch to Fault Mode

Crest Factor 3:1 [Max]

Transfer time Typical Value 2 ~ 7 ms, Max: 10ms

SURGE PROTECTION

Telephone/LAN RJ11 & RJ45 for Modem and LAN

BATTERY

Model Maintenance Free Sealed Lead-Acid

DC Voltage 12VDC

Configuration 1 x 12V/7Ah 1x 12V/8Ah

Charge Current 350mA ~ 1.2 A

Backup Time [Full load] ≥ 3 min.

PANEL DISPLAY

LCD Battery capacity; Load percentage; Output voltage; Input voltage/frequency; alarm

GENERAL

Communication RS232/USB [optional]

Audible Noise [1m] ≤ 45db

Temperature 0 ~ 40 °C

Relative Humidity 0 ~ 90% [non-condensing]

Altitude ≤ 1500 meter

Storage Temperature -25 ~ 55 °C

Dimension [mm] [H x W x D] 165 x 95 x 340

Rack Mount [mm] [H x W x D] 88 x 480 x 350

Net weight [Kg] 5.5 5.8 6.8 6.8

Rack Mount Net Weight [Kg] 7.8 7.9 9.0 9.0

Packing Dimension [mm] [H x W x D] 230 x 145 x 375

Packing Dimensions Rack Mount [mm] [H x W x D]

180 x 535 x 400

Gross weight [Kg] 5.7 6.3 7.3 7.3

Rack Mount Gross weight [Kg] 8.2 8.3 9.4 9.4

12 EA200 SERIES / www.eastpwr.com

Product Specifications are subject to change without further notice, © EAST Power. N.V.

13EA200 SERIES / www.eastpwr.com

Product Specifications are subject to change without further notice, © EAST Power N.V.

Technical data sheet EA200[R]-LCD (500-1500 VA)

Page 8: EA200 - Elec.ru · 2020. 8. 26. · Self-diagnosis at UPS Start Up. The UPS will perform advanced self-diagnostics . to ensure the functionality of the UPS system and batteries, and

Technical data sheet EA200N[R]-LCD (1000-3000 VA)EAST Power N.V. technical data sheet EA200N LCD [Line Interactive Pure Sine Wave 1000VA - 3000VA]

Model EA210N EA215N EA220N EA230N

VA Rating 1000 VA 1500 VA 2000 VA 3000 VA

Real Power Rating 600 Watt 900 Watt 1.200 Watt 1.800 Watt

DISPLAY

Indicators LED display/LED + LCD display

AC MODE

Input Voltage 100/110/120 VAC or 220/230/240 VAC ± 25%

Input Frequency 45 ~ 65Hz [transfer to battery mode when out of this range]

Max Efficiency > 98% [AC mode]

Overload capability in AC mode

110% transfer to bypass within 60 seconds

120% transfer to bypass within 30 seconds

Automatic recovery when load comes back within acceptable range

Short Circuit Protected by input fuse

INVERTER MODE

Output Voltage 220 VAC ± 5% or 110 VAC ± 10%

Output Frequency 50Hz/60Hz ± 1% [auto detection]

Output Power Factor > 0.6

Output Waveform Pure Sine Wave

Waveform Distortion < 5% [Linear Load]

Transfer Time Typical: 5ms, Max: 8ms

Max Efficiency > 85% [Inverter mode]

Overload Inverter Mode110% Shut Down within 60 seconds

120% Shut Down within 5 seconds

Short Circuit> > 20ms System Shut Down automatically

ALARM

AC Abnormal Once every 4 seconds, silence after 40 seconds

Battery Low Once every 0.2 seconds

Overload Once every 1 second

BATTERY

DC Voltage 24V 24V 36V 48V

Configuration 2x 12V/7Ah 2x 12V/8Ah 3x 12V/8Ah 4x 12V/8Ah

Charger Current 1.2A

Recharge Time 90% capacity after 8 hours

Communication RS232, USB, SNMP [optional]

GENERAL

IP Level IP20

Ambient Temperature 0 ~ 40 ˚C

Relative Humidity 10 ~ 90% [non-condensing]

Noise < 50dBA

Dimensions [mm] [H x W x D] 215 x 145 x 360 215 x 145 x 430 337 x 200 x 475

Packing Dimensions [mm] [H x W x D] 316 x 236 x 427 320 x 240 x 510 462 x 320 x 592

Net Weight [kg] 14.5 15.5 18.5 27.0

Gross Weight [kg] 15.5 16.5 19.5 28.6

EAST Power N.V. technical data sheet EA200NR LCD [Line Interactive Pure Sine Wave 1000VA - 3000VA]

Model EA210NR EA215NR EA220NR EA230NR

VA Rating 1000 VA 1500 VA 2000 VA 3000 VA

Real Power Rating 600 Watt 900 Watt 1.200 Watt 1.800 Watt

DISPLAY

Indicators LED display/LED + LCD display

AC MODE

Input Voltage 100/110/120 VAC or 220/230/240 VAC ± 25%

Input Frequency 45 ~ 65Hz [transfer to battery mode when out of this range]

Max Efficiency > 98% [AC mode]

Overload capability in AC mode

110% transfer to bypass within 60 seconds

120% transfer to bypass within 30 seconds

Automatic recovery when load comes back within acceptable range

Short Circuit Protected by input fuse

INVERTER MODE

Output Voltage 220 VAC ± 5% or 110 VAC ± 10%

Output Frequency 50Hz/60Hz ± 1% [auto detection]

Output Power Factor > 0.6

Output Waveform Pure Sine Wave

Waveform Distortion < 5% [Linear Load]

Transfer Time Typical: 5ms, Max: 8ms

Max Efficiency > 85% [Inverter mode]

Overload Inverter Mode110% Shut Down within 60 seconds

120% Shut Down within 5 seconds

Short Circuit> > 20ms System Shut Down automatically

ALARM

AC Abnormal Once every 4 seconds, silence after 40 seconds

Battery Low Once every 0.2 seconds

Overload Once every 1 second

BATTERY

DC Voltage 24V 24V 36V 48V

Configuration 2x 12V/7Ah 2x 12V/8Ah 3x 12V/8Ah 4x 12V/8Ah

Charger Current 1.2A

Recharge Time 90% capacity after 8 hours

Communication RS232, USB, SNMP [optional]

GENERAL

IP Level IP20

Ambient Temperature 0 ~ 40 ˚C

Relative Humidity 10 ˜~90% [non-condensing]

Noise < 50dBA

Dimensions [mm] [H x W x D] 88 x 438 x 308.5 132 x 438 x 360

Packing Dimensions [mm] [H x W x D] 185 x 525 x 395 225 x 525 x 455

Net Weight [kg] 15.0 16.0 21.0 26.0

Gross Weight [kg] 16.0 17.0 22.0 27.0

Product Specifications are subject to change without further notice, © EAST Power. N.V. Product Specifications are subject to change without further notice, © EAST Power N.V.

14 EA200 SERIES / www.eastpwr.com 15EA200 SERIES / www.eastpwr.com

Page 9: EA200 - Elec.ru · 2020. 8. 26. · Self-diagnosis at UPS Start Up. The UPS will perform advanced self-diagnostics . to ensure the functionality of the UPS system and batteries, and

Technical data sheet Outdoor UPS (1000-3000 kVA)EAST Power N.V. technical data sheet Outdoor UPS [True Online Double Conversion 1000VA - 3000VA]

Model EA1K-HW EA2K-HW EA3K-HW

VA Rating 1 kVA 2 kVA 3 kVA

Real Power Rating 800 Watt 1.600 Watt 2.400 Watt

INPUT

Phase Single Phase + N + G

Voltage Range 110 ~ 300 VAC

Frequency Range 45 ~ 55Hz or 55 ~ 65Hz

Frequency Tracking Speed 1Hz/s

Input Power Factor > 0.98 [Full Load]

DC INPUT

DC Power Supply Voltage 24 VDC 48 VDC 72 VDC

Float Voltage 27.5 ± 0.4 VDC 55.0 ± 0.6 VDC 82.5 ± 0.9 VDC

Battery Type Maintenance Free Sealed Lead-Acid

Battery Capacity Compatible [12V/65AH ~ 12V/120AH]

OUTPUT

Power Factor 0.8

Rated Voltage 220 VAC

Rated Frequency 50Hz/60Hz

Voltage Precision 220 VAC ± 2%

Frequency Precision 50Hz ± 0.2%

Waveform Pure Sine Wave

Wave Form Distortion < 3% [Linear Load]; < 5% [ Non-Linear Load]

Efficiency > 90%

Current Crest Factor 3 : 1

Overload Capacity > 110%: transfer to bypass after 1 min.; > 150%: transfer to bypass after 200ms

Transfer Time 0ms

GENERAL

Protection Degree IP55

Lightning Protection Class C

Operating Temperature -20 ~ 50 ˚C

Storage Temperature -25 ~ 60 ˚C

Relative Humidity 0 ~ 95% [non-condensing]

ProtectionI/P Over/Under Voltage, O/P Over/Under Voltage, Short Circuit, Inverter Overtemperature,

Battery Low Voltage, Surge Protection

Communication RS232/Dry Contact

Alarm Signals AC Supply out of tolerance, Battery Low Voltage, Overtemperature, Lightning Protection Failure

Input Isolation Transformer Yes

Bypass Static and Manual Bypass Switch

Cooling Forced Air [Load Dependend]

Noise < 45dBA

Dimensions [mm] [H x W x D]1 kVA [incl. 2pcs battery] 2 kVA [incl. 4pcs battery] 3 kVA [incl. 6pcs battery]

1000 x 660 x 700 1400 x 660 x 900 1400 x 660 x 900

Product Specifications are subject to change without further notice, © EAST Power. N.V.

16 EA200 SERIES / www.eastpwr.com 17EA200 SERIES / www.eastpwr.com

Notes..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

..................................................................................................................................................

Page 10: EA200 - Elec.ru · 2020. 8. 26. · Self-diagnosis at UPS Start Up. The UPS will perform advanced self-diagnostics . to ensure the functionality of the UPS system and batteries, and

EAST UPS Middle East Trading FZE

P.O. Box 10559Ras Al KhaimahUnited Arab Emirates

T +971 (0)72 076 609F +971 (0)72 041 010

www.eastpwr.com

EAST Power N.V.

Weiland 1C6666 MH HeterenThe Netherlands

T +31 (0)26 47 90 790F +31 (0)26 47 43 704

www.eastpwr.com

EAST Power France/Africa

197, Avenue des Grésillons92230 GennevilliersFrance

T +33 (0)18 28 85 551 F +33 (0)97 21 64 530

www.eastpwr.com