Product Operation and Setup Instructions 3XC07
Please read and save these instructions. Read carefully before attempting to assemble, install, operate, or maintain theproduct described. Protect yourself and others by observing all safety information. Failure to comply with instructionscould result in personal injury and/or property damage! Retain instructions for future reference.
OMRON E5CS-XE5CS-XTemperature ControllerTemperature Controller
DescriptionOMRON E5CS-X Temperature Controller is a 1/16 DIN sizedmulti-range controller offering selectable control modes and abuilt-in 8-function alarm. Other features include: Field-selectabletemperature ranges in Fahrenheit and Celsius, selectable ON/OFF and PID control, tamper-proof settings, nonvolatile memory
backup, easy-to-read 1 mm high LED display, and a three yearwarranty. Controller is UL Recognized (File number E68481) andCSA Certified (File number LR59623).
Specifications
SENSOR INPUT TYPE
Thermocouple .......... Type J & K(E5CS-_1KJX)
Platinum RTD .......... Pt: 100 ohm(E5CS-_1PX)
Thermistor .......interchangeable type(E5CS-_1GX)
CONTROL OUTPUT
Contact ........ SPDT relay (3A rating)
Voltage ........ 12 VDC, 3mA
ALARM OUTPUT
SPST-NO relay (1A rating)
POWEROperating Voltage .. 100 to 240 VAC
Power Consumption ............... 7VA
Frequency .................... 50/60 Hz
INDICATION ACCURACY
+/- 0.5% of full scale10 scale ranges to choose from.
ENVIRONMENTAL
Operating Temperature ..... -14 to131 degrees F
Storage Temperature ........ -13 to149 degrees F
Humidity ............... 35 to 85% RH
MECHANICAL
Termination .......Screw Terminals
Mounting .....1/16 DIN panelcutout; includes panel mountingadapter.
GENERAL SAFETY
RECOMMENDATIONS
Disconnect power whenconnecting or disconnecting thecontroller or its loads.
Do not change controller switchsettings while the controller. Makesure all settings are set beforeapplying power.
1. This controller should be wiredby qualified personnel accordingto the National Electrical Code(NEC) and local codes.
2. Do not connect input or contactterminals to voltages higher
than those indicated oncontroller.
3. Do not install in damp or moistlocations.
4. Any application of this controllershould be designed to preventbodily injury, or propertydamage, in the event of productfailure or normal wearout of thisproduct.
ERROR MESSAGES
FFFCause: 1.) Temperature has risenbeyond temperature scale range,or 2.) Thermistor has been short-circuited.
- - -Cause: 1.) Temperature hasfallen below temperature scalerange, or 2.) Thermistor has
broken.
FFF (blinking)Cause: 1.) Failure has occurredin thermocouple or platinum RTD,or 2.) Temperaure has risen muchbeyond scale range.
- - - (blinking)Cause: 1.) Failure has occurredin platinum RTD, 2.) Polarities ofthermocuple have been reversed,or 3.) Temperature has fallenmuch below scale range.
CAUTION!
WARNING!
-
8/3/2019 E5CSTempControllerSetupInstructions
2/9
Product Operation and Setup Instructions 3XC07
Nomenclature
AL8.8.88.8.8
ONC
E5CS
Deviation
indicator
Alarm indicator
Main display
Return
KeyUp key
Down key
Control output
indicator
Main display sequentially displays the
present temperature, set temperature, an
an alarm value each time the return key ipressed. Control output indicator lights
when the output is ON. Alarm indicator
lights when the alarm output is ON.Up
key increases the set temperature or
alarm value when pressed. Increases th
value quickly when held down.Down key
decreases the set temperature or alarm
value when pressed. Decreases the val
quickly when held down. Return key
changes the value displayed on the main
display each time pressed. Thehidden
write protection key provides protection
against unauthorized to set temperaturesand is used in conjunction with the intern
"protection" switch. Display data
identifier lights SP when the set
temperature is displayed on the main
display and AL when an alarm value is
displayed. The reddeviation indicators
light an up arrow when the present
temperature is higher than the set
temperature and light a down arrow whe
present value is lower than the set
temperature. The green block indicates
the temperature deviation is within +/- 1of the full scale.
Write
protection
key
SP
Display data
identifier
1 2 3 4 5
6 7 8 9
AC
10
6 7 8
7 8
+_20mA
12 VDC
4 5Alarm output
Contact output(Relay)
1 2 3
1 2
Thermocouple
input
Platinum
RTD
Thermistorinput
TerminalConnections
Voltage output
Supply voltage
100 to 240 VAC50/60 Hz
-
8/3/2019 E5CSTempControllerSetupInstructions
3/9
Product Operation and Setup Instructions 3XC07
nctionelector
witch
6
2
3
4
5
1
62 3 4 51
Function
Control
Mode
PID action
ON/OFF action
Proportional
period
2 seconds
20 seconds
Control
Output
Normal
Reverse
Input Shift
Function
Enabled
Disabled
RTD Sensor
Input Standard
DIN
JIS
Temperature
Scale Display
degrees F
degrees C
1 2 3 4 5 6
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
The Function Selector switch is a 6-pin in-
line DIP switch. The following table shows
the selection options for each pin number.
Settings (before applying power)
To access the switches and selectors pull apart the int ernal mechanism from the housing
Control Mode
ON/OFF Action Move switch 1 to the OFF position to chose ON/OFF action which is the
same type of control used in room thermostats. Once you chose a setpoint (SP) the controller works to maintain the SP, but because ON/OFF does not have as tight ofcontrol as PID, the temperature will tend to continually overshoot and undershoot the SP resulting
in a sine wave shown above. ON/OFF control is fine if your application doesn't require very tight SPaccuracy.
PID Action Using PID allows for a smooth ramping of temperature to SP, with the
minimum amount of over/undershoot. Best type of control when applicationrequires a very tight, smooth, temperature transition to SP with little or no over or undershoot of SP.
SP
62 3 4 51
Switch 1
-
8/3/2019 E5CSTempControllerSetupInstructions
4/9
Product Operation and Setup Instructions 3XC07
Determining Proportional PeriodSet switch 2 of the function selector dipswitch to OFF to select a proportional period of 20 seconds.This is used when the PID control action is performed with the contact output of the temperaturecontroller, or when using an external relay or contactor.When a quick response is required, set switch 2 to ON to select a proportional period of 2seconds. Even when a solid-state relay (SSR) is used, set the 2-second proportional period only
when quick response is essential. Avoid using this setting with a contact output because it willshorten the relay's service life.
Determining Control Output Operation
If the temperature controller is used to control a heater, the control output can be set to perform areverse (inverted) operation. Set switch 3 of the control output mode selector dipswitch to OFF.
By contrast, if the temperature controller is used to control a cooling device such as a chiller orfreezer, set switch 3 to ON.
Auto-tuning of Proportional Band
Upon the initial power-up the proportional band is set to 3%. The optimum proportional band width,however, is automatically calculated and set within the range of 3 to 20%, according to the changesin the temperature of the controlled system. This automatic adjustment of the proportional band is
performed regardless of whether the controlled system is a heating or cooling system.
When the power is turned OFF once, and then ON again, the control action starts with the previousproportional band. However, the new proportional band is automatically calculated and set.
The calculation of the proportional band, however, is not carried out if the temperature of thecontrolled system changes at a rate faster than 7.5% of full scale per 2 seconds (e.g., faster than3.75% degrees C per second with the full scale of 100 degrees C). In this case, the previouslycalculated and set proportional band is used.
The temperature controller has an overshoot suppression function that reduces second and
subsequent overshoots to a level less than the initial overshoot.
62 3 4 51
Switch 2
62 3 4 51
Switch 3
set temperature
Reverseoutput
set temperature
Normaloutput
-
8/3/2019 E5CSTempControllerSetupInstructions
5/9
Product Operation and Setup Instructions 3XC07
Input Shift FunctionThe temperature indication can be shifted by setting switch 4 of the function selector dipswitch toON, and pressing the mode key repeatedly until the message "H0" (indicating 0 input shift) isdisplayed on the main display. Then set the shift value by using the UP or DOWN key.
Fine adjustment of the the temperature indication and the resulting controlled temperature is
possible without changing or affecting the set point.
The input shift value can be set within the range from -99.9 degrees to 99 degrees (F or C). Forranges that have resolution to 0.1 degree, the input shift value can be set within the range from -
99.9 degrees to 9.9 degrees (F or C). The input shift function is useful to make small temperaturecorrections to the control system. "Small" means less than +/- 25 degrees.
IMPORTANT NOTES:
1.) Any offset adjustment greater than +/- 25 degrees is usually not considered an offsetproblem, but a possible problem with the sensor or calibration of this controller.
2.) The offset value remains effective even after switch 4 has been set to OFF. If thecompensation action is not needed, be sure to set the offset value to 0.
3.) Make sure to disable (turn OFF) switch 4 once offset has been correctly set. Keepingswitch 4 enabled during operation has known to cause temperature stability problems in thiscontroller.
RTD Sensor Input StandardUse switch 5 of the function selector dipswitch to match the controller to the thermocouple or RTDsensor to be used. With switch 5 ON, the controller will accept DIN (West German) standard
sensors. With switch 5 OFF, the controller accepts JIS (Japanese) standard sensors.
62 3 4 51
Switch 4
62 3 4 51
Switch 5
Main display Set input shift value Temperature measured by sensor Displayed temperature
H0
H9
0 offset
offset by +9 deg
L9 offset by -9 deg
100 deg C
100 deg C
100 deg C
100 deg C
109 deg C
91 deg C
-
8/3/2019 E5CSTempControllerSetupInstructions
6/9
Product Operation and Setup Instructions 3XC07
Scale IndicationSome dual-scale (C/F) temperature scale ranges may be selected by rotary dipswitch. To specifythe scale indication to be displayed, use switch 6 on the function selector dipswitch.
With switch 6 set to ON, the controller displays Fahrenheit scale. With the switch 6 set to OFF, thecontroller displays Celsius scale.
Selecting A Scale Range
Use the rotary dipswitch to select the temperature scale range. The tables below show the switch
setting number for each range. The temperature indication range is the set temperature range (fullscale) +/-10%, unless otherwise noted. If the set temperature is shifted outside of changing thescale range, the set temperature is displayed. It is then automatically changed to the maximum orminimum value of the newly set temperature scale range. If the alarm value is shifted outside thetemperature scale range as a result of changing the scale range, it is automatically changed to themaximum value of the newly set scale range.
62 3 4 51
Switch 6
Input type
Switch setting
Temperature range
Temp Scale Display
0
0-200
C
1
0-300
C
2
0-400
C/F
3
0-500
C/F C/F C/F
0-600
4 5
0-999
Type K
6 6 7 8 9
0-999 0-200 0-300 0-400 0-500
C/F C/FCCF
Type J
0 12
3456
7
89
Thermocouple Input Type
Platinum RTD Input Type
Switch settingTemperature range
Temp Scale Display
0-50 - 50
C
10.0 - 50.0
C C C/F
-20 - 802 3
0.0 - 99.94 5 6 7
0 to 200 0 - 300 0 - 400 0 to 600
C/F FCC/F
80 to 800
F
Switch setting
Temperature range
Temp Scale Display
0
-50 to
50C
1
0 to
100
2
50 to
150
3
100 to
200
150 to
300
4 5
-50 to
100
6 7 8 9
0 to
200
100 to
300
200 to
400
300 to
600F
Thermistor Input Type
Factory default setting: 2
Factory default setting: 3
Factory default setting: 0
0 12
3456
7
89
0 12
3456
7
89
-
8/3/2019 E5CSTempControllerSetupInstructions
7/9
Product Operation and Setup Instructions 3XC07
SwitchSettings
Mode Alarm Output
0, 9 No alarm OFF
1Upper and lower
limit alarm
X X
2 Upper limit alarm
3 Lower limit alarm
X
4Upper and lowerlimit range alarm
X X
5
Upper and lowerlimit alarm withstandbysequence
X X
X
XUpper limit alarmwith standby
sequence
6
7Lower limit alarmwith standbysequence
X
7Lower limit alarmwith standby
sequence
Y
NOTE:
When the alarm mode selectorswitch is set to position 0 or 9,neither the alarm value isdisplayed nor the AL indicatorlights even when the return keyis pressed.
FOR YOUR INFORMATION
Most common mistake madeby the user regarding alarmsetting:
The alarm triggers off the setpoint (SP) of the controller andNOT a set temperature.
For example:
If your controller's set point is100 degrees and you set thealarm for an upper limit alarm(#2) and you want the alarm togo off if the temperature reach110 degrees or above. You
must set your alarm for 10 (100+ 10 = 110), which is thedifference between set point andesired alarm limit.In this same example, if youmistakenly set the alarm for 11instead of 10, you alarm will noenable until it reaches 220.Which is 110 + 100 (set point)210.
Standby Sequence:
Alarm functions with standbysequence suppresses nuisancealarms when the controller isfirst powered up.The alarm output is suppresseduntil the temperature exceedsthe alarm band or alarm limitone time.
Selecting Alarm Modes
-
8/3/2019 E5CSTempControllerSetupInstructions
8/9
Product Operation and Setup Instructions 3XC07
Wiring Diagrams
1 2 3 4 5
6 7 8 9
AC
10
Thermocouple
input
Chiller
Jumper
wires
DC
Warning
light
1 2 3 4 5
6 7 8 9
AC
10
Thermocoupleinput
Chiller
DC
Warning
light
AC
Figure A
Figure B
Figure A illustrate how to wirecontroller to a control output and utilizethe controller's supply voltage tosupply power to both the control and
alarm outputs.
Figure B illustrates how to wirecontroller to a control output, plus,
power the control and alarm outputsfrom separate power supplies.
-
8/3/2019 E5CSTempControllerSetupInstructions
9/9
PRODUCT WARRANTY
NOTE: Specifications to change without notice.
Omron certifies all of its products either meet or exceed stipulated specifications.
Omron is not liable for stenographic and/or clerical errors.
Omron's obligation under this warranty is limited solely to repair or replacement atOmron's discretion. Omron will not be liable for any design furnished by Buyer andincorporated into equipment.
This warranty is voided if the product is altered in any way or suffers consequential
damage due to negligence or misuse.
Omron is not to suffer risk due to suitability or unsuitability or the results of the use of its
products used in combination with any electrical or electronic components, circuits,systems assemblies, or any other materials or substances or environments.
The foregoing warning is the only warranty which Omron Electronics, Inc. provides with
respect to the products listed herein. No other warranties, expressed, implied, orstatutory shall apply, whether as to merchantability, fitness for a particular purpose,description, or otherwise.
This warranty is extended to three years for temperature and process controllers.
Limitation of Liability: Notwithstanding any other statement herein, OmronElectronics, Inc., its contractors and suppliers, shall not be liable for any special,indirect, incidental, or consequential damages.The remedies of the purchaser set forth herein are exclusive where so stated and thetotal cumulative liability of Omron Electronics, Inc., its contractors and suppliers, withrespect to this contract or anything done in connection therewith, shall not exceedreplacement price reimbursement as to the product on which such liability is based.
Omron Electronics has a calibration procedure for the E5CS-X Temperature Controller.To obtain a fax copy of this document, contact Omron's Fax-On-Demand System @847-843-1963. You may also download this document file from Omron's Internet HomePage (www.oeiweb.omron.com).