    Product Operation and Setup Instructions 3XC07

    Please read and save these instructions. Read carefully before attempting to assemble, install, operate, or maintain theproduct described. Protect yourself and others by observing all safety information. Failure to comply with instructionscould result in personal injury and/or property damage! Retain instructions for future reference.

    OMRON E5CS-XE5CS-XTemperature ControllerTemperature Controller

    DescriptionOMRON E5CS-X Temperature Controller is a 1/16 DIN sizedmulti-range controller offering selectable control modes and abuilt-in 8-function alarm. Other features include: Field-selectabletemperature ranges in Fahrenheit and Celsius, selectable ON/OFF and PID control, tamper-proof settings, nonvolatile memory

    backup, easy-to-read 1 mm high LED display, and a three yearwarranty. Controller is UL Recognized (File number E68481) andCSA Certified (File number LR59623).

    Specifications

    SENSOR INPUT TYPE

    Thermocouple .......... Type J & K(E5CS-_1KJX)

    Platinum RTD .......... Pt: 100 ohm(E5CS-_1PX)

    Thermistor .......interchangeable type(E5CS-_1GX)

    CONTROL OUTPUT

    Contact ........ SPDT relay (3A rating)

    Voltage ........ 12 VDC, 3mA

    ALARM OUTPUT

    SPST-NO relay (1A rating)

    POWEROperating Voltage .. 100 to 240 VAC

    Power Consumption ............... 7VA

    Frequency .................... 50/60 Hz

    INDICATION ACCURACY

    +/- 0.5% of full scale10 scale ranges to choose from.

    ENVIRONMENTAL

    Operating Temperature ..... -14 to131 degrees F

    Storage Temperature ........ -13 to149 degrees F

    Humidity ............... 35 to 85% RH

    MECHANICAL

    Termination .......Screw Terminals

    Mounting .....1/16 DIN panelcutout; includes panel mountingadapter.

    GENERAL SAFETY

    RECOMMENDATIONS

    Disconnect power whenconnecting or disconnecting thecontroller or its loads.

    Do not change controller switchsettings while the controller. Makesure all settings are set beforeapplying power.

    1. This controller should be wiredby qualified personnel accordingto the National Electrical Code(NEC) and local codes.

    2. Do not connect input or contactterminals to voltages higher

    than those indicated oncontroller.

    3. Do not install in damp or moistlocations.

    4. Any application of this controllershould be designed to preventbodily injury, or propertydamage, in the event of productfailure or normal wearout of thisproduct.

    ERROR MESSAGES

    FFFCause: 1.) Temperature has risenbeyond temperature scale range,or 2.) Thermistor has been short-circuited.

    - - -Cause: 1.) Temperature hasfallen below temperature scalerange, or 2.) Thermistor has

    broken.

    FFF (blinking)Cause: 1.) Failure has occurredin thermocouple or platinum RTD,or 2.) Temperaure has risen muchbeyond scale range.

    - - - (blinking)Cause: 1.) Failure has occurredin platinum RTD, 2.) Polarities ofthermocuple have been reversed,or 3.) Temperature has fallenmuch below scale range.

    CAUTION!

    WARNING!

  • 8/3/2019 E5CSTempControllerSetupInstructions

    2/9

    Product Operation and Setup Instructions 3XC07

    Nomenclature

    AL8.8.88.8.8

    ONC

    E5CS

    Deviation

    indicator

    Alarm indicator

    Main display

    Return

    KeyUp key

    Down key

    Control output

    indicator

    Main display sequentially displays the

    present temperature, set temperature, an

    an alarm value each time the return key ipressed. Control output indicator lights

    when the output is ON. Alarm indicator

    lights when the alarm output is ON.Up

    key increases the set temperature or

    alarm value when pressed. Increases th

    value quickly when held down.Down key

    decreases the set temperature or alarm

    value when pressed. Decreases the val

    quickly when held down. Return key

    changes the value displayed on the main

    display each time pressed. Thehidden

    write protection key provides protection

    against unauthorized to set temperaturesand is used in conjunction with the intern

    "protection" switch. Display data

    identifier lights SP when the set

    temperature is displayed on the main

    display and AL when an alarm value is

    displayed. The reddeviation indicators

    light an up arrow when the present

    temperature is higher than the set

    temperature and light a down arrow whe

    present value is lower than the set

    temperature. The green block indicates

    the temperature deviation is within +/- 1of the full scale.

    Write

    protection

    key

    SP

    Display data

    identifier

    1 2 3 4 5

    6 7 8 9

    AC

    10

    6 7 8

    7 8

    +_20mA

    12 VDC

    4 5Alarm output

    Contact output(Relay)

    1 2 3

    1 2

    Thermocouple

    input

    Platinum

    RTD

    Thermistorinput

    TerminalConnections

    Voltage output

    Supply voltage

    100 to 240 VAC50/60 Hz

  • 8/3/2019 E5CSTempControllerSetupInstructions

    3/9

    Product Operation and Setup Instructions 3XC07

    nctionelector

    witch

    6

    2

    3

    4

    5

    1

    62 3 4 51

    Function

    Control

    Mode

    PID action

    ON/OFF action

    Proportional

    period

    2 seconds

    20 seconds

    Control

    Output

    Normal

    Reverse

    Input Shift

    Function

    Enabled

    Disabled

    RTD Sensor

    Input Standard

    DIN

    JIS

    Temperature

    Scale Display

    degrees F

    degrees C

    1 2 3 4 5 6

    ON

    OFF

    ON

    OFF

    ON

    OFF

    ON

    OFF

    ON

    OFF

    ON

    OFF

    The Function Selector switch is a 6-pin in-

    line DIP switch. The following table shows

    the selection options for each pin number.

    Settings (before applying power)

    To access the switches and selectors pull apart the int ernal mechanism from the housing

    Control Mode

    ON/OFF Action Move switch 1 to the OFF position to chose ON/OFF action which is the

    same type of control used in room thermostats. Once you chose a setpoint (SP) the controller works to maintain the SP, but because ON/OFF does not have as tight ofcontrol as PID, the temperature will tend to continually overshoot and undershoot the SP resulting

    in a sine wave shown above. ON/OFF control is fine if your application doesn't require very tight SPaccuracy.

    PID Action Using PID allows for a smooth ramping of temperature to SP, with the

    minimum amount of over/undershoot. Best type of control when applicationrequires a very tight, smooth, temperature transition to SP with little or no over or undershoot of SP.

    SP

    62 3 4 51

    Switch 1

  • 8/3/2019 E5CSTempControllerSetupInstructions

    4/9

    Product Operation and Setup Instructions 3XC07

    Determining Proportional PeriodSet switch 2 of the function selector dipswitch to OFF to select a proportional period of 20 seconds.This is used when the PID control action is performed with the contact output of the temperaturecontroller, or when using an external relay or contactor.When a quick response is required, set switch 2 to ON to select a proportional period of 2seconds. Even when a solid-state relay (SSR) is used, set the 2-second proportional period only

    when quick response is essential. Avoid using this setting with a contact output because it willshorten the relay's service life.

    Determining Control Output Operation

    If the temperature controller is used to control a heater, the control output can be set to perform areverse (inverted) operation. Set switch 3 of the control output mode selector dipswitch to OFF.

    By contrast, if the temperature controller is used to control a cooling device such as a chiller orfreezer, set switch 3 to ON.

    Auto-tuning of Proportional Band

    Upon the initial power-up the proportional band is set to 3%. The optimum proportional band width,however, is automatically calculated and set within the range of 3 to 20%, according to the changesin the temperature of the controlled system. This automatic adjustment of the proportional band is

    performed regardless of whether the controlled system is a heating or cooling system.

    When the power is turned OFF once, and then ON again, the control action starts with the previousproportional band. However, the new proportional band is automatically calculated and set.

    The calculation of the proportional band, however, is not carried out if the temperature of thecontrolled system changes at a rate faster than 7.5% of full scale per 2 seconds (e.g., faster than3.75% degrees C per second with the full scale of 100 degrees C). In this case, the previouslycalculated and set proportional band is used.

    The temperature controller has an overshoot suppression function that reduces second and

    subsequent overshoots to a level less than the initial overshoot.

    62 3 4 51

    Switch 2

    62 3 4 51

    Switch 3

    set temperature

    Reverseoutput

    set temperature

    Normaloutput

  • 8/3/2019 E5CSTempControllerSetupInstructions

    5/9

    Product Operation and Setup Instructions 3XC07

    Input Shift FunctionThe temperature indication can be shifted by setting switch 4 of the function selector dipswitch toON, and pressing the mode key repeatedly until the message "H0" (indicating 0 input shift) isdisplayed on the main display. Then set the shift value by using the UP or DOWN key.

    Fine adjustment of the the temperature indication and the resulting controlled temperature is

    possible without changing or affecting the set point.

    The input shift value can be set within the range from -99.9 degrees to 99 degrees (F or C). Forranges that have resolution to 0.1 degree, the input shift value can be set within the range from -

    99.9 degrees to 9.9 degrees (F or C). The input shift function is useful to make small temperaturecorrections to the control system. "Small" means less than +/- 25 degrees.

    IMPORTANT NOTES:

    1.) Any offset adjustment greater than +/- 25 degrees is usually not considered an offsetproblem, but a possible problem with the sensor or calibration of this controller.

    2.) The offset value remains effective even after switch 4 has been set to OFF. If thecompensation action is not needed, be sure to set the offset value to 0.

    3.) Make sure to disable (turn OFF) switch 4 once offset has been correctly set. Keepingswitch 4 enabled during operation has known to cause temperature stability problems in thiscontroller.

    RTD Sensor Input StandardUse switch 5 of the function selector dipswitch to match the controller to the thermocouple or RTDsensor to be used. With switch 5 ON, the controller will accept DIN (West German) standard

    sensors. With switch 5 OFF, the controller accepts JIS (Japanese) standard sensors.

    62 3 4 51

    Switch 4

    62 3 4 51

    Switch 5

    Main display Set input shift value Temperature measured by sensor Displayed temperature

    H0

    H9

    0 offset

    offset by +9 deg

    L9 offset by -9 deg

    100 deg C

    100 deg C

    100 deg C

    100 deg C

    109 deg C

    91 deg C

  • 8/3/2019 E5CSTempControllerSetupInstructions

    6/9

    Product Operation and Setup Instructions 3XC07

    Scale IndicationSome dual-scale (C/F) temperature scale ranges may be selected by rotary dipswitch. To specifythe scale indication to be displayed, use switch 6 on the function selector dipswitch.

    With switch 6 set to ON, the controller displays Fahrenheit scale. With the switch 6 set to OFF, thecontroller displays Celsius scale.

    Selecting A Scale Range

    Use the rotary dipswitch to select the temperature scale range. The tables below show the switch

    setting number for each range. The temperature indication range is the set temperature range (fullscale) +/-10%, unless otherwise noted. If the set temperature is shifted outside of changing thescale range, the set temperature is displayed. It is then automatically changed to the maximum orminimum value of the newly set temperature scale range. If the alarm value is shifted outside thetemperature scale range as a result of changing the scale range, it is automatically changed to themaximum value of the newly set scale range.

    62 3 4 51

    Switch 6

    Input type

    Switch setting

    Temperature range

    Temp Scale Display

    0

    0-200

    C

    1

    0-300

    C

    2

    0-400

    C/F

    3

    0-500

    C/F C/F C/F

    0-600

    4 5

    0-999

    Type K

    6 6 7 8 9

    0-999 0-200 0-300 0-400 0-500

    C/F C/FCCF

    Type J

    0 12

    3456

    7

    89

    Thermocouple Input Type

    Platinum RTD Input Type

    Switch settingTemperature range

    Temp Scale Display

    0-50 - 50

    C

    10.0 - 50.0

    C C C/F

    -20 - 802 3

    0.0 - 99.94 5 6 7

    0 to 200 0 - 300 0 - 400 0 to 600

    C/F FCC/F

    80 to 800

    F

    Switch setting

    Temperature range

    Temp Scale Display

    0

    -50 to

    50C

    1

    0 to

    100

    2

    50 to

    150

    3

    100 to

    200

    150 to

    300

    4 5

    -50 to

    100

    6 7 8 9

    0 to

    200

    100 to

    300

    200 to

    400

    300 to

    600F

    Thermistor Input Type

    Factory default setting: 2

    Factory default setting: 3

    Factory default setting: 0

    0 12

    3456

    7

    89

    0 12

    3456

    7

    89

  • 8/3/2019 E5CSTempControllerSetupInstructions

    7/9

    Product Operation and Setup Instructions 3XC07

    SwitchSettings

    Mode Alarm Output

    0, 9 No alarm OFF

    1Upper and lower

    limit alarm

    X X

    2 Upper limit alarm

    3 Lower limit alarm

    X

    4Upper and lowerlimit range alarm

    X X

    5

    Upper and lowerlimit alarm withstandbysequence

    X X

    X

    XUpper limit alarmwith standby

    sequence

    6

    7Lower limit alarmwith standbysequence

    X

    7Lower limit alarmwith standby

    sequence

    Y

    NOTE:

    When the alarm mode selectorswitch is set to position 0 or 9,neither the alarm value isdisplayed nor the AL indicatorlights even when the return keyis pressed.

    FOR YOUR INFORMATION

    Most common mistake madeby the user regarding alarmsetting:

    The alarm triggers off the setpoint (SP) of the controller andNOT a set temperature.

    For example:

    If your controller's set point is100 degrees and you set thealarm for an upper limit alarm(#2) and you want the alarm togo off if the temperature reach110 degrees or above. You

    must set your alarm for 10 (100+ 10 = 110), which is thedifference between set point andesired alarm limit.In this same example, if youmistakenly set the alarm for 11instead of 10, you alarm will noenable until it reaches 220.Which is 110 + 100 (set point)210.

    Standby Sequence:

    Alarm functions with standbysequence suppresses nuisancealarms when the controller isfirst powered up.The alarm output is suppresseduntil the temperature exceedsthe alarm band or alarm limitone time.

    Selecting Alarm Modes

  • 8/3/2019 E5CSTempControllerSetupInstructions

    8/9

    Product Operation and Setup Instructions 3XC07

    Wiring Diagrams

    1 2 3 4 5

    6 7 8 9

    AC

    10

    Thermocouple

    input

    Chiller

    Jumper

    wires

    DC

    Warning

    light

    1 2 3 4 5

    6 7 8 9

    AC

    10

    Thermocoupleinput

    Chiller

    DC

    Warning

    light

    AC

    Figure A

    Figure B

    Figure A illustrate how to wirecontroller to a control output and utilizethe controller's supply voltage tosupply power to both the control and

    alarm outputs.

    Figure B illustrates how to wirecontroller to a control output, plus,

    power the control and alarm outputsfrom separate power supplies.

  • 8/3/2019 E5CSTempControllerSetupInstructions

    9/9

    PRODUCT WARRANTY

    NOTE: Specifications to change without notice.

    Omron certifies all of its products either meet or exceed stipulated specifications.

    Omron is not liable for stenographic and/or clerical errors.

    Omron's obligation under this warranty is limited solely to repair or replacement atOmron's discretion. Omron will not be liable for any design furnished by Buyer andincorporated into equipment.

    This warranty is voided if the product is altered in any way or suffers consequential

    damage due to negligence or misuse.

    Omron is not to suffer risk due to suitability or unsuitability or the results of the use of its

    products used in combination with any electrical or electronic components, circuits,systems assemblies, or any other materials or substances or environments.

    The foregoing warning is the only warranty which Omron Electronics, Inc. provides with

    respect to the products listed herein. No other warranties, expressed, implied, orstatutory shall apply, whether as to merchantability, fitness for a particular purpose,description, or otherwise.

    This warranty is extended to three years for temperature and process controllers.

    Limitation of Liability: Notwithstanding any other statement herein, OmronElectronics, Inc., its contractors and suppliers, shall not be liable for any special,indirect, incidental, or consequential damages.The remedies of the purchaser set forth herein are exclusive where so stated and thetotal cumulative liability of Omron Electronics, Inc., its contractors and suppliers, withrespect to this contract or anything done in connection therewith, shall not exceedreplacement price reimbursement as to the product on which such liability is based.

    Omron Electronics has a calibration procedure for the E5CS-X Temperature Controller.To obtain a fax copy of this document, contact Omron's Fax-On-Demand System @847-843-1963. You may also download this document file from Omron's Internet HomePage (www.oeiweb.omron.com).

    File

    Fax

    Product Operation and Setup Instructions 3XC07