E2 EDGELIGHT LED EXIT SIGN SPU and Axiom Network versions Application: This product is designed and tested to comply with AS/NZS2293.3 as an Emergency Exit sign for single or double-sided applications. It is available for both Single Point Unit (SPU) and for AXIOM Network applications. Selection of mounting location, height and spacings should be undertaken in accordance with the requirements of relevant codes and standards. Emergency Classifications can be determined from Legrand data sheets, web-site or product labeling. This sign is suited to Maintained or Non-Maintained operation according to input connections. Specifications: Catalogue Number Supply Voltage Power Input 684730 / 684740 Recessed mounted. Select Running Man legend required from decals included. May be surface mounted by removing plate. 230-240V a.c. 50 Hz 2.7W (high rate charge) 2.3W (low rate charge) 684731 / 684741 Surface mounted only. Select Running Man legend required from decals included. 684732 / 684742 Surface mounted Edgelight. Order special decal separately eg “On Air”. 684733 / 684743 Theatre style, surface mounted Edgelight (black) includes compliant theatre Running Man decal. Surface-mounted Recessed 1

Transcript of E2 EdgElight lEd Exit sign sPU and Axiom network versions · E2 EdgElight lEd Exit sign sPU and...

Page 1: E2 EdgElight lEd Exit sign sPU and Axiom network versions · E2 EdgElight lEd Exit sign sPU and Axiom network versions ... sPU and Axiom network versions ... be installed in place

E2 EdgElight lEd Exit signsPU and Axiom network versions

Application:

This product is designed and tested to comply with AS/NZS2293.3 as an Emergency Exit sign for single or double-sided applications. It is available for both Single Point Unit (SPU) and for AXIOM Network applications.Selection of mounting location, height and spacings should be undertaken in accordance with the requirements of relevant codes and standards.Emergency Classifications can be determined from Legrand data sheets, web-site or product labeling.This sign is suited to Maintained or Non-Maintained operation according to input connections.

specifications:

Catalogue number supply Voltage Power input

684730 / 684740 Recessed mounted. Select Running Man legend required from decals included. May be surface mounted by removing plate.

230-240V a.c. 50 Hz 2.7W (high rate charge) 2.3W (low rate charge)

684731 / 684741 Surface mounted only. Select Running Man legend required from decals included.

684732 / 684742 Surface mounted Edgelight. Order special decal separately eg “On Air”.

684733 / 684743 Theatre style, surface mounted Edgelight (black) includes compliant theatre Running Man decal.

surface-mounted Recessed

1

Page 2: E2 EdgElight lEd Exit sign sPU and Axiom network versions · E2 EdgElight lEd Exit sign sPU and Axiom network versions ... sPU and Axiom network versions ... be installed in place

surface- and Recessed Mounted

nOtE: To make decal replacement easier, remove body from mounting plate.

Lift tab to release then slide plate from body.

Slide out

Once decal is changed, slide decal assembly over lens

how to replace decal/s before installing body to bracket

step 1: Use 3mm slot screwdriver to detach original decal. Depress metal clips at each end to release the decal cover assembly.

step 4: Decal assembly will lock into place.

step 2: Clean the lens before inserting decal.

Press test switch for local test when installation is complete. Axiom version has 2 LED’s SPU has 1 LED LED colour- refer to separate page.Ensure correct orientation. Terminal Block will be at opposite end to LED & Test Switch.

CLICK

step 3: Once decal is changed, slide decal assembly over lens to click into position.

E2 EdgElight lEd Exit signsPU and Axiom network versions

A new concealed Antenna is fitted within the body of the Axiom versions. Any fitting orientation is allowed.

2

Page 3: E2 EdgElight lEd Exit sign sPU and Axiom network versions · E2 EdgElight lEd Exit sign sPU and Axiom network versions ... sPU and Axiom network versions ... be installed in place

surface Mounted

step 1: Fit the required decal/s as described on page 2.step 2a: Secure the mounting plate to the wall or ceiling.

step 3a: Fit the protective cover to the cableway.

step 3: Terminate supply cables to terminal block. Supply to Unswitched Active is required to charge the batteries. Supply to Switched Active illuminates the sign on mains.

step 4b: Locate and slide cover horizontally towards the terminal block until it connects securely.

Ceiling mounted

! Switched Active and unswitched active must be on same phaseFor 24/7 ‘Maintained’ operation, link switched active with unswitched active

SEE DETAIL A

SCALE 2.000DETAIL A

CLICK

! Switched Active and unswitched active must be on same phaseFor 24/7 ‘Maintained’ operation, link switched active with unswitched active

CLICK

SEE DETAIL A

SCALE 2.000DETAIL A

CLICK

! Switched Active and unswitched active must be on same phaseFor 24/7 ‘Maintained’ operation, link switched active with unswitched active

CLICK

SEE DETAIL A

SCALE 2.000DETAIL A

CLICK

! Switched Active and unswitched active must be on same phaseFor 24/7 ‘Maintained’ operation, link switched active with unswitched active

CLICK

Slide body this way

step 5: Apply power to the sign and confirm that: • Indicator LED is flashing. • Running Man is illuminated on mains when intended.

To remove the body from mounting plate, push tab up and slide out the body as shown.

Slide body

Removal

step 4a: Fit the body to the mounting plate by raising it to ceiling level.

E2 EdgElight lEd Exit signsPU and Axiom network versions

3

Page 4: E2 EdgElight lEd Exit sign sPU and Axiom network versions · E2 EdgElight lEd Exit sign sPU and Axiom network versions ... sPU and Axiom network versions ... be installed in place

E2 EdgElight lEd Exit signsPU and Axiom network versions

LE07

219A

AB

Customer serviceFor all Customer Service and Technical Support enquires please call Monday to Friday during business hours.

HPM Legrand Australia 1300 369 777 www.legrand.com.au

Recessed Edgelight

Product legacy Upgrade Options: Where possible, Legrand develops replacement sub-assemblies of latest generation light source and electronics for the upgrading of obsolete items from previous generations. 682026: A special adaptor plate has been designed enabling the new E2 Recessed Edgelight to be installed in place of the discontinued Optica Bladelight Recessed fluorescent exit sign.

step 5: Terminate the supply cables to the terminal block on the plate provided or fit an Australian approved flex and 3-pin or 4-pin plug as required, enlarging the selected entry hole to suit a cable gland. Include a loop between the Unswitched and Switched Actives if 24/7 operation is required.

step 6: Fit the protective cover to the cableway and secure the slide-on cover to the Exit body as described previously.

Replacement Parts:

step 7: Note the orientation of the plate so that the LED and Test Switch will be most visible and accessible. Plug in the fixture before fixing the luminaire and recessing plate securely to the ceiling using the swing clamps provided.Don’t over-tighten the screws or damage to the ceiling tile may occur.

step 1: Fit the required decal/s as described previously.

step 2: Ensure Unswitched Active is available adjacent to where the sign will be installed.

step 3: Determine a compliant location before cutting.

step 4: Use the cut-out template provided to cut an exact opening.

HPM Legrand New Zealand 0800 476 009 www.legrand.co.nz

ABN: 31 000 102 661

686240 Battery Pack AA4LNICD 686218 Decal - Running Man Left

684736 E2 Recessing Plate Kit WE 686219 Decal - Running Man Right

684737 E2 Mounting Block Kit WE 686220 Decal - Running Man Theatre (Green on Black)

684738 E2 Recessing Plate Kit Black 686219 Decal - Running Man Right

684739 E2 Mounting Block Kit Black 686228 Decal - Opaque (no light transmitted)

685735 Lens Replacement Kit 686229 Decal - Black Opal (translucent)

686217 Decal - Running Man 686230 Decal - Custom Printing

682026 E2 conversion plates (2 pcs) to enable upgrade from discontinued Recessed Optica Bladelight Exit.