E0.2E
LEC
TRIC
AL
CO
MP
LIA
NC
E F
OR
MS
Bldg. 2
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
NOTE: NOT ALL SYMBOLS USED
CONDUIT IN OR UNDERFLOOR
CONDUIT HOMERUN TO PANEL - GND,HOT, NEUTRAL
CONDUIT HOMERUN - IG, EQUIPMENTGND, HOT, NEUTRAL
CONDUIT STUBBED UP
CONDUIT STUBBED DOWN
CONDUIT
FLUORESCENT LIGHTING FIXTURE
FLUORESCENT LIGHTING FIXTURE, WALLMOUNTED
TELEPHONE SYSTEM CONDUIT
WALL EXIT LIGHT FIXTURE - SINGLE FACE
EXIT LIGHT FIXTURE - DOUBLE FACE
EMERGENCY BATTERY PACK LIGHT
LIGHTING TRACK WITH TRACK FIXTURES
SINGLE POLE TOGGLE SWITCH
EXIT LIGHT FIXTURE - SINGLE FACE
THREE - WAY TOGGLE SWITCH
FOUR - WAY TOGGLE SWITCH
LOW VOLTAGE CONTROL SWITCH
MOMENTARY CONTROL SWITCH
TOGGLE SWITCH WITH PILOT LIGHT
TOGGLE SWITCH WITH THERMALOVERLOAD
DIMMER SWITCH
CEILING OCCUPANCY SENSOR
WALL OCCUPANCY SENSOR
DUPLEX RECEPTACLE - STANDARDMOUNTING HEIGHT (18" AFF UNO)
DUPLEX RECEPTACLE ABOVE COUNTER
OCCUPANCY SENSOR TOGGLE SWITCH
ISOLATED GROUND DUPLEX RECEPTACLEMOUNTING HEIGHT (18" AFF UNO)
QUADRUPLEX RECEPTACLE MOUNTINGHEIGHT (18" AFF UNO)
CEILING MOUNTED DUPLEX RECEPTACLE
SIMPLEX RECEPTACLE
GROUND FAULT CIRCUIT INTERRUPTERRECEPTACLE MOUNTING HEIGHT (18"AFFUNO)
SPECIAL RECEPTACLE AS NOTED
SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
WALL LIGHTING FIXTURE
CEILING LIGHTING FIXTURE - WALLWASHER
CELING LIGHTING FIXTURE
CEILING LIGHTING FIXTURE - EMERGENCY
EMERGENCY LIGHTING FIXTURE
SWITCH WITH TIMER
KEY OPERATED SWITCH
COMMUNICATION WALL OUTLET
TELEPHONE WALL OUTLET
FLOOR MOUNTED FURNITURECONNECTION
WALL MOUNTED FURNITURE CONNECTION
DUPLEX FLOOR RECEPTACLE
TELEPHONE FLOOR OUTLET
COMMUNICATIONTELEPHONE/COMMUNICATION OUTLET
FURNITURE / EQUIPMENT CONNECTION
POWER POLE
WALL SPEAKER ASSEMBLY
FLOOR MICROPHONE OUTLET
CEILING SPEAKER ASSEMBLY
QUADRUPLEX FLOOR RECEPTACLE
QUAD FLOOR OUTLET COMBINATIONPOWER/COMMUNICATION
COMMNICATION FLOOR OUTLET
FLOOR OUTLET COMBINATIONPOWER/COMMUNICATION
FLOOR TV OUTLET
WALL TV OUTLET
PROGRAM BELL
PHOTOCELL
EMERGENCY POWER OFF PUSHBUTTON
MOTOR CONNECTION
FUSED DISCONNECT SWITCH
DISCONNECT SWITCH
PROGRAM CLOCK
CARD READER
WALL VOLUME CONTROL OUTLET
WALL MICROPHONE OUTLET
PUSHBUTTON STATION
BUZZER
TRANSFORMER
GROUND CONNECTION
PANELBOARD FLUSH MOUNTED
ELECTRICAL METER
JUNCTION BOX
WALL JUNCTION BOX
PANELBOARD
DISTRIBUTION PANEL / SWITCHBOARD
COMBINATION MAGNETIC STARTER /DISCONNECT SWITCH
MAGNETIC MOTOR STARTER
THREE (3) ONE-POLE CIRCUITS
ONE (1) THREE-POLE CIRCUITH - 1/3/5
H - 1,3,5
ELECTRICAL SYMBOL LEGEND
S
S
S
S
S
S
S
S
S
S
S
CEILING MOUNTED SMOKE DETECTOR
DUCT MOUNTED SMOKE DETECTOR
CEILING MOUNTED HEAT DETECTOR
EMERGENCY TELEPHONE / FIRE STATION
FIRE ALARM CONTROL PANEL
FIRE SYSTEM ANNUNCIATOR PANEL
ELECTRIC DOOR HOLDER
BEAM DETECTORS - RECEIVER
PRESSURE SWITCH (SUPERVISORY)
PRESSURE SWITCH (SUPERVISORY)
WATERFLOW SWITCH
BEAM DETECTORS - TRANSMITTER
DESCRIPTIONSYMBOL
FIRE ALARM SYMBOLS
FIRE ALARM SPEAKER / HORN
MANUAL PULL STATION
S
H
S
S D
P
S D
DH
BR
P
BT
COMBINATION FIRE ALARM AUDIO /VISUAL SIGNAL
FIRE ALARM SPEAKER / HORN - CEILINGMOUNT
FIRE ALARM CEILING MOUNT VISUALSIGNAL
FIRE ALARM SPEAKER / HORN WITHVISUAL SIGNAL
UNDERFLOOR DUCT MOUNTEDSMOKE DETECTOR
UNDERFLOOR MOUNTED SMOKEDETECTOR
FARA
W
TS
P
FACP
FTS
BUILDING CODES:
CITY OF SAN MARCOS, TX AMENDMENTS ADOPTEDSEPTEMBER 1, 2015.
2015 INTERNATIONAL BUILDING CODE2015 INTERNATIONAL FIRE CODE2015 INTERNATIONAL FUEL CODE2015 INTERNATIONAL PLUMBING CODE2015 INTERNATIONAL MECHANICAL CODE2009 INTERNATIONAL ENERGY CONSERVATION CODE2014 NEC
E0.1E
LEC
TRIC
AL
CO
VE
R S
HE
ET
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
E0.3E
LEC
TRIC
AL
CO
MP
LIA
NC
E F
OR
MS
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
+ HB
D
U
M
P
S
T
E
R
A
R
E
A
R
E
C
Y
C
.
T
R
A
S
H
+ HB
MA
RQ
UIS
S
IG
N
E-3TAP CAN
E-4
A
A
J
LRC-1, 22#8, 1#10G., 1"C.
LRC-3, 42#10, 1#10G., 1"C.
H H
H H
H
HH
H
LRC-62#10, 1#10G., 3/4"C.
E-6E-7
E-13
E-13
E-2
E-8
E-9
B
E-11
J
J
LRC-52#10, 1#10G., 1"C.
E-5
E-1E-10
LRC-1, 22#8, 1#10G., 1"C.
LRC-62#10, 1#10G., 3/4"C.E-7
E-13
A
J
E1.1S
ITE
PLA
NE
LEC
TRIC
AL
01E1.1
SITE PLAN - BLDG. 2 - ELECTRICALSCALE : 1/16" = 1'-0"
N
PROPOSED LOCATION FOR POWER COMPANY PADMOUNTED TRANSFORMER. CONFIRM EASEMENT SIZEWITH POWER COMPANY AND LOCATION WITH CIVILENGINEER.
PRIMARY UNDERGROUND ELECTRICAL SERVICE, TWO (2)5" UNDERGROUND IN 10'-0" WIDE EASEMENT. PROPOSEDSERVICE ROUTING, COORDINATE WITH POWER COMPANYEXACT REQUIREMENTS AND CIVIL ENGINEER FOR EXACTROUTING.
MAIN GROUNDING ELECTRODE. REFER TO MAIN SERVICEENTRANCE GROUNDING DIAGRAM (DETAIL E3.1/02).INSTALL IN LANDSCAPE AREA (NOT BELOW CONCRETE).
PROPOSED ROUTING FOR TWO (2) 4" UNDERGROUNDCONDUITS FOR TELEPHONE AND CABLE TV SERVICES.EQUIP WITH PULL STRING, TURNED UP SHAFT. MAKE ALLTURNS WITH LONG RADIUS ELBOWS. DEPTH OF CONDUITSHALL BE PER LOCAL UTILITY REQUIREMENTS. IFTELEPHONE CONDUIT SHARES A TRENCH WITH OTHERUTILITY SERVICES, PROVIDE AT LEAST 12" SEPARATIONBETWEEN UTILITY CONDUITS. COORDINATE EXACTROUTING AND REQUIREMENTS WITH LOCAL PROVIDERBEFORE ROUGH-IN.
POLE MOUNTED LIGHTING TO BE CONTROLLED THROUGHA LIGHTING RELAY CABINET.
ALL SIGNAGE LIGHTING SHALL BE CONTROLLED VIA APHOTOCELL AND TIME CLOCK THROUGH THE LIGHTINGRELAY CABINET
WIRE SIZE INDICATED IS TO FIRST POLE. THE CONTRACTORMAY USE #10 CONDUCTORS FOR THE REMAINDER OF THEBRANCH CIRCUIT.
NEW UTILITY RISER POLE, COORDINATE EXACT LOCATIONWITH ELECTRICAL UTILITY COMPANY.
COORDINATE EXACT NUMBER OF CONDUITS FOR PRIMARYSERVICE WITH UTILITY COMPANY. ELECTRICALCONTRACTOR TO INSTALL AND UTILITY COMPANY TO PULLWIRE.
CONTRACTOR TO INSTALL UTILITY TRANSFORMER PAD PERELECTRICAL UTILITY SPECIFICATIONS, UTILITY COMPANYTO SET THE TRANSFORMER.
PROVIDE SPARE 2" CONDUIT TO EACH LIGHT POLE FORFUTURE SECURITY, REFER TO E3.1/05 FOR LIGHT POLEDETAIL.
NOT USED.
POLE MOUNTED LIGHTING TO BE CONTROLLED THROUGHA LIGHTING RELAY CABINET. THE FIXTURES ARE TO HAVETWO (2) RELAY SWITCH LEGS TO EACH FIXTURE TO TURNHALF THE FIXTURE OFF TO MEET THE CITY LIGHTINGORDNANCE STANDARDS FOR AFTER HOURS OPERATION.
E-1
E-2
E-3
E-4
POWER: MEGAN WILLIS - SAN MARCOS POWER COMPANYPHONE: 512-393-8307
EMAIL : [email protected]
TELEPHONE AND CATV: FIELD COORDINATED BY THE CONTRACTOR WITH LOCAL SERVICE PROVIDERS
1. CONDUIT FROM TELEPHONE UTILITY POINT OF SERVICESHALL BE FURNISHED AND INSTALLED BY ELECTRICALCONTRACTOR, CABLE SHALL BE PROVIDED BY THETELEPHONE COMPANY.
2. CONDUIT FROM MAIN CATV UTILITY SHALL BE PROVIDED BYELECTRICAL CONTRACTOR, CABLE SHALL BE PROVIDED ANDINSTALLED BY CATV COMPANY.
3. FINAL EQUIPMENT LOCATIONS, SERVICE CONNECTIONPOINTS AND ALL REQUIREMENTS SHALL BE COORDINATEDWITH THE RESPECTIVE UTILITY COMPANIES. LOCATIONSSHOWN ARE PRELIMINARY AND REQUIRE FIELDCOORDINATION PRIOR TO CONSTRUCTION.
4. DO NOT USE THIS PLAN FOR LOCATION OF POLE LIGHTING.COORDINATE WITH ARCHITECTURAL PLANS FORDIMENSIONED PLANS AND EXACT LOCATIONS.
ELECTRICAL NOTES BY SYMBOL
ELECTRICAL GENERAL NOTES
UTILITY COMPANY CONTACTS
E-5
E-6
E-7
E-8
E-9
E-10
E-11
E-12
E-13
CITY COMMENTS2/19/16
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
LP
LP
+ H
B
D
U
M
P
S
T
E
R
A
R
E
A
R
E
C
Y
C
.
T
R
A
S
H
XF
MR
+ H
B
MARQUIS SIGN
TO
-G
O
WIN
DO
W
LP
LP
LP
LOADING ZONE
BU
IL
DIN
G 2
PROPERTY
LINE
B
MH: 22.5
A
MH: 22.5
A
MH: 22.5
J
MH: 15
J
MH: 15
J
MH: 15
J
MH: 15
A
MH: 22.5
0.0 0.0 0.0 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.1 0.1 0.2 0.2 0.2 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.1 0.2 0.3 0.3 0.3 0.4 0.5 0.4 0.2 0.1 0.1 0.1 0.1 0.1 0.3 0.4 0.5 0.3 0.2 0.2 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0
0.0 0.2 0.4 0.9 1.2 1.9 1.9 2.6 2.4 1.7 1.5 0.6 0.6 0.7 1.6 1.8 2.5 2.5 1.9 1.8 0.8 0.5 0.2 0.2 0.2 0.2 0.2 0.1 0.1 0.0 0.0 0.0 0.0 0.0
0.1 0.3 0.8 1.3 1.9 3.2 5.7 10.6 9.2 4.7 2.2 0.9 0.6 1.0 2.6 5.1 10.0 9.9 5.3 2.7 1.3 0.6 0.4 0.3 0.3 0.3 0.3 0.2 0.1 0.1 0.0 0.0 0.0 0.0
0.1 0.6 1.3 1.6 1.3 1.0 1.4 3.6 2.9 0.8 0.3 0.2 0.2 0.2 0.4 1.0 3.3 3.3 1.3 0.7 0.7 0.6 0.6 0.6 0.5 0.5 0.4 0.3 0.2 0.1 0.0 0.0 0.0 0.0
0.1 1.1 2.3 2.5 1.8 1.1 0.7 0.7 0.6 0.2 0.1 0.0 0.0 0.0 0.1 0.3 0.7 0.8 0.7 0.7 0.9 0.9 0.9 0.9 0.9 0.8 0.6 0.4 0.2 0.1 0.0 0.0 0.0 0.0
0.0 1.4 3.0 3.3 2.2 1.1 0.5 0.2 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.1 0.3 0.5 0.7 1.0 1.3 1.3 1.4 1.3 1.3 1.2 0.9 0.6 0.3 0.1 0.1 0.0 0.0 0.0
0.0 2.2 3.4 3.6 2.3 1.1 0.4 0.2 0.4 0.8 1.3 1.6 1.8 1.9 1.9 1.7 1.6 1.3 0.7 0.3 0.1 0.0 0.0 0.0 0.0
0.0 2.3 3.4 3.5 2.3 1.1 0.4 0.2 0.4 1.0 1.7 2.1 2.4 2.3 2.3 2.4 2.0 1.6 0.8 0.3 0.1 0.0 0.0 0.0 0.0
0.0 2.1 3.4 3.6 2.4 1.1 0.4 0.2 0.4 1.0 1.9 2.3 2.9 3.2 3.2 2.9 2.2 1.7 0.9 0.3 0.1 0.0 0.0 0.0 0.0
0.1 1.3 2.9 3.1 2.2 1.2 0.5 0.2 0.4 1.0 1.8 2.4 3.2 4.8 4.7 3.1 2.3 1.7 0.9 0.3 0.1 0.0 0.0 0.0 0.0
0.1 1.0 2.1 2.4 1.8 1.1 0.5 0.2 0.4 1.0 1.8 2.4 3.2 5.1 4.8 3.1 2.3 1.7 0.9 0.4 0.1 0.0 0.0 0.0 0.0
0.1 0.6 1.4 1.8 1.4 0.9 0.5 0.2 0.4 1.0 1.9 2.4 2.9 3.4 3.3 2.9 2.3 1.7 0.9 0.4 0.1 0.1 0.0 0.0 0.0
0.1 0.6 1.4 1.7 1.3 0.9 0.5 0.2 0.4 1.0 1.8 2.2 2.5 2.5 2.5 2.5 2.1 1.6 0.9 0.4 0.1 0.1 0.0 0.0 0.0
0.1 0.7 1.6 1.9 1.5 0.9 0.5 0.3 0.5 0.9 1.5 1.7 1.9 2.0 2.0 1.8 1.7 1.4 0.8 0.4 0.2 0.1 0.1 0.0 0.0
0.2 1.2 2.6 2.7 1.9 1.1 0.5 0.3 0.5 0.9 1.3 1.6 1.6 1.7 1.7 1.7 1.5 1.2 0.8 0.5 0.2 0.1 0.1 0.0 0.0
0.1 1.6 3.2 3.3 2.3 1.1 0.4 0.5 0.6 0.9 1.4 1.8 1.8 1.8 1.8 1.8 1.7 1.3 0.9 0.5 0.3 0.2 0.1 0.1 0.0
0.0 2.3 3.6 3.6 2.3 1.1 0.4 0.6 0.8 1.2 1.7 2.4 2.5 2.5 2.5 2.6 2.3 1.6 1.0 0.7 0.4 0.2 0.1 0.1 0.0
0.0 2.3 3.6 3.5 2.2 1.1 0.4 0.6 0.9 1.4 2.2 3.1 3.7 3.6 3.6 3.6 2.8 1.9 1.2 0.7 0.4 0.2 0.1 0.1 0.0
0.0 2.2 3.5 3.6 2.3 1.1 0.5 0.6 0.9 1.4 2.3 3.3 3.9 4.0 4.0 3.7 3.0 1.8 1.0 0.6 0.3 0.2 0.1 0.1 0.0
0.1 1.2 2.9 3.0 2.1 1.2 1.0 0.4 0.9 1.4 1.4 1.6 2.4 2.5 2.5 2.1 1.5 0.9 0.6 0.3 0.1 0.1 0.1 0.0 0.0
0.2 0.9 2.1 2.3 1.9 1.9 3.4 4.8 1.9 0.7 0.3 0.2 0.1 0.1 0.2 0.4 1.1 3.1 4.8 2.1 1.0 0.5 0.3 0.2 0.2 0.3 0.3 0.2 0.1 0.1 0.0 0.0 0.0 0.0
0.1 0.5 1.3 2.1 3.0 5.1 8.8 11.0 6.0 3.2 1.3 0.5 0.1 0.2 0.8 2.1 4.5 8.4 11.0 6.0 3.3 1.4 0.5 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.3 0.8 1.2 1.8 1.6 2.1 2.1 1.5 1.2 0.7 0.3 0.1 0.2 0.5 1.2 1.2 1.9 2.0 1.5 1.2 0.7 0.4 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.1 0.3 0.5 0.4 0.4 0.5 0.4 0.2 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.2 0.3 0.3 0.2 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.1 0.2 0.2 0.2 0.2 0.2 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.0 0.1 0.1 0.1 0.1 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
E1.2S
ITE
PLA
NP
HO
TOM
ETR
IC
01E1.2
SITE PLAN - BLDG. 2 - PHOTOMETRICSSCALE : 1" = 20'-0"
N
ISSUED FOR INFORMATION ONLY
1 CITY COMMENTSXXXX
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
Luminaire Schedule
SymbolType
Qty Manufacturer / Catalog Number Total Lumen Output Total Input Watts Ballast Factor Light Lost Factor User Defined Factor
A 3 LITHONIA_DSX0 LED P6 40K BLC MVOLT 13088 134 1.000 0.808 1.000
B 1 LITHONIA_DSX0 LED P6 40K T3M MVOLT 31014 268 1.000 0.808 1.000
C 4 HESS_SR600 3LVC NW T2 UNA A 17RC GG OPTION 8096 108 1.000 0.808 1.000
Calculation Summary
Calculation Grid Location Calc. Height (Ft.)Units Avg Max Min
Avg/Min
GRADE_Planar0 Fc
0.8711.0 0.0 N.A.
PARKING+DRIVE_StatAreaFc
1.60 11.0 0.0N.A.
STOP
STOP
LP
E-8(TYPICAL)
E-1(TYPICAL)
E-5(TYPICAL)
E-4
E-3(TYPICAL)
PANEL "HPB"
X
X
XXX
TELEPHONE SERVICEENCLOSURE
E-7
TAP CANREFER: E3.1/02
X
X
XX
G
GC
C
C
C
C
C
C
C
C
C
C
C
C C C C C
C C C C C
C C C C C C C C C
C
C
C
C
C
C
C
C
C
C
C
F
F
F
F
F
F
F
F
F
F
F
F
F
F
FF
F
E-2HPB-6
F
E-10HPB-10
E-9E-6
FACP
HPB-13
HPB-15HPB-17
HPB-4
WIRED FOR PATIOCEILING FANS
LRC
EUH-A
30/3/20AF
HPB-14/16/18E-11
(TYPICAL)
E-11(TYPICAL)
E2.1FL
OO
R P
LAN
BU
ILD
ING
'B'
ELE
CTR
ICA
L
01E2.2
FLOOR PLAN BUILDING '2' - ELECTRICALSCALE : 1/8" = 1'-0"
N
ALL EXIT LIGHT SIGNS SERVED BY UN-SWITCHED CIRCUIT WITH2#10, 1#10G., 3/4"C., FROM LIFE SAFETY CIRCUIT HPB-8.
'F' FIXTURES SHALL BE OPERATED VIA CIRCUIT BREAKER INHOUSE PANEL.
WALL/ CEILING MOUNTED AUDIO/VISUAL FIRE ALARMANNUNCIATION DEVICES ARE SHOWN FOR COORDINATIONWITH OTHER TRADES AND FOR GENERAL TAS/ADACONFORMANCE ONLY AND NOT FOR PLANNING THE SYSTEM.FIRE ALARM SYSTEM SHALL BE DESIGNED BY LICENSEDINDIVIDUAL IN FIRE ALARM SYSTEM DESIGN. REFER TOELECTRICAL SPECIFICATIONS FOR ADDITIONALREQUIREMENTS. PROVIDE CODE MINIMUM FIRE ALARMDEVICES.
TENANT SPACE FIRE ALARM SYSTEM AND DEVICES SHALL BEINSTALLED AND FURNISHED BY THE FUTURE TENANTS PERNEC AND AHJ.
TENANT LIGHTING AND OTHER ELECTRICAL WORK SHALL BEINSTALLED AND FURNISHED BY THE FUTURE TENANTS.
CONTRACTOR SHALL INSTALL FIRE ALARM CONTROL PANEL INSPRINKLER ROOM. CONNECT CONTROL WIRING FROMSPRINKLER SYSTEM VALVES TO FIRE ALARM PANEL FLOW ANDTAMPER INPUTS. CONTROL PANEL SHALL AUTOMATICALLYNOTIFY FIRE ALARM DEPARTMENT AND BUILDING OWNER INTHE EVENT OF AN ALARM.
CONTRACTOR TO ROUTE ONE (1) 2" CONDUIT WITH THREE (3)PULLSTRINGS FROM TELEPHONE SERVICE ENTRY TO EACHTENANT SPACE. COORDINATE WITH LANDLORD FOR EXACTFUTURE TENANTS.
JUNCTION BOX FOR FUTURE TENANT SIGNAGE. COORDINATEEXACT QUANTITY AND LOCATIONS IN FIELD WITH LANDLORD.FUTURE SIGNAGE BRANCH CIRCUIT TO BE PROVIDED BYTENANT.
STUB ONE (1) 1" CONDUIT FROM FIRE SPRINKLER ROOM INTOLANDSCAPE AREA FOR IRRIGATION CONTROLLER WIRING.COORDINATE EXACT LOCATIONS WITH IRRIGATION SYSTEMCONTRACTOR.
ALL CAN LIGHTING SHALL BE CONTROLLED VIA A PHOTOCELLAND TIME CLOCK.
CONTRACTOR TO INSTALL ONE (1) 2" CONDUIT FROM TENANTMETER WIREWAY TO EACH TENANT SPACE FOR FUTURETENANT ELECTRICAL PANEL.
E-1
ELECTRICAL NOTES BY SYMBOL
E-2
E-3
E-4
E-5
E-6
E-7
E-8
E-9
E-10
CITY COMMENTS2/19/16
E-11
REVISION3/17/16
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
UTILITY METER
FUTURE TENANT METERS
NEMA 3RWIREWAY
3 SETS (4#300, 2-1/2"C.)
4#1/0, 1#6G., 1-1/2"C.
BY UTILITY1
CONTRACTOR TO VERIFY WITH THE LANDLORD THE ELECTRICALSERVICE SIZE AND NUMBER OF METERS BASED ON THE ANTICIPATEDTENANT'S AND THEIR REQUIREMENTS, PRIOR TO SUBMITTING BIDAND INSTALLATION.
SITE LIGHTING RELAY CABINET EQUAL TO ACUITY CONTROLS BLUEBOX LT:ENCLOSURE # CR1408 LT ENC - SMNE4INTERIOR # GR1408 LT INT DTC DV
NOTES:
1
2
NO SCALE02
E3.1
GRADE4/0 CU
CONNECT TO UNDERGROUNDMETAL WATER PIPEPER NEC 250-52 (A)(1)
MAIN GROUND BUSN
G
SERVICE ENCLOSURE
MAIN SERVICE ENTRANCE GROUNDING DIAGRAMNO SCALE
BUILDING STEEL
4/0 CU OR EQUIVALENT BUSMAIN BONDING JUMPERPER NEC 250-28
4/0 CU SUPPLY SIDEBONDING JUMPER PER NEC250-92(A)
ENCLOSURE (TYPICAL)
03E3.1
NOTE:
NO SCALEGROUND BUS DETAIL
1. ALL TRANSFORMERS SHALL BE GROUNDED TO THE GROUND BUS PERTRANSFORMER GROUNDING DETAIL. PROVIDE ONE (1) GROUND BUSBAR IN THE FOLLOWING ROOMS:
A. ALL ELECTRICAL ROOMS
EXTEND TO ALLGROUND BUS LOCATIONS
1-3/4"
2"
COPPER BAR 24" x 4" x 1/4"
CADWELD CONNECTION TO GROUND BUS.EXTEND 1 #4/0 COPPER CONDUCTOR TOMAIN GROUNDING ELECTRODE
RED STANDOFF INSULATOR,POLYESTER / FIBERGLASS(TYPICAL)
STAINLESS STEEL MOUNTINGBRACKET (TYPICAL)
01E3.1
ELECTRODE PER NEC 250-52 (c)
MAIN GROUNDING 10 FT.
GRADE
TELEPHONE SERVICE DETAILNO SCALE
04E3.1
MAINTELEPHONE
SERVICEBACKBOARD
FIRE RATED PLYWOOD BACKBOARD PAINTED TO MATCH WALLS.
PROVIDE #6 CU. TO MAIN BUILDING GROUND. LEAVE 6' OF SLACKWIRE AT BACKBOARD.
PROVIDE TWO (2) 4" CONDUITS WITH PULL STRINGS TO PROVIDEDPOINT OF SERVICE AT PROPERTY LINE. PROVIDE CONDUIT,TRENCHING AND BACKFILL BY CONTRACTOR PER PROVIDERSPECIFICATIONS AND REQUIREMENTS.
NOTES:
1
2
1
2
3
3
200AS/150AF/ 3P SERVICEDISCONNECT (NEMA 3R)
FUTURE TENANT SERVICEDISCONNECTS
PROVIDE SERVICE ENCLOSUREPER LOCAL POWER COMPANYREQUIREMENTS. (NEMA 3R)ASC: 19,319
UTILITY COMPANYTRANSFORMER480-208/120V
UNDERGROUND PRIMARYSERVICE PER POWER COMPANYREQUIREMENTS.
#2/0G. GROUNDPER NEC
"BUILDING A & B" ELECTRICAL RISER DETAIL
HPA
NEMA 3R
UTILITY METER
FUTURE TENANT METERS
NEMA 3RWIREWAY
3 SETS (4#300, 2-1/2"C.)
4#1/0, 1#6G., 1-1/2"C.
GROUND
BY UTILITY
2
1
200AS/150AF/ 3P SERVICEDISCONNECT (NEMA 3R)
FUTURE TENANT SERVICEDISCONNECTS
PROVIDE SERVICE ENCLOSUREPER LOCAL POWER COMPANYREQUIREMENTS. (NEMA 3R)ASC: 30,380
#2/0G. GROUNDPER NEC
HPB
NEMA 3R
IN FIRERISERROOM
11
DETAIL INDICATES ELECTRICAL REQUIREMENTS ONLY. REFER TOARCHITECT'S DETAIL FOR ADDITIONAL INFORMATION.
ALL NIPPLES (HOLES), SHALL BE FACTORY MADE. THE FACTORY SHALLPROVIDE CERTIFIED SHOP DRAWINGS FOR EACH APPLICATION.
RUN ALL RACEWAYS (POWER AND SECURITY, EXCEPT SERVICES), IN THESAME TRENCH.
NEMA 3R ENCLOSURE WITH VENTILATED OPENINGS, MOUNTED ON THEPOLE, ON THE OPPOSITE SIDE OF THE POLE HANDHOLE, AND A MINIMUMOF 18" ABOVE GROUND. THE ENCLOSURE SHALL CONTAIN ONETRANSFORMER WITH 277V PRIMARY AND 120V SECONDARY WITH PRIMARYAND SECONDARY FUSE. FOR THE SECURITY CAMERA, PROVIDE: 12"x6"x6"ENCLOSURE, 750 VA TRANSFORMER, G.E. VACUUM IMPREGNATED OREQUAL, WITH 4A FUSE PRIMARY AND 10A FUSE SECONDARY. WIRE THEDUPLEX RECEPTACLE FOR THE CAMERA (19' ABOVE) TO 120V SIDE WITH2#12, 1#12G CABLE, THROUGH THE POLE SHAFT. FOR THE EMERGENCYPHONE, PROVIDE: 8"x6"x6" ENCLOSURE. 250 VA TRANSFORMER, G.E.ENCAPSULATED OR EQUAL WITH FACTORY INSTALLED FUSES, 2.5A PRIMARYAND 3A SECONDARY.
NO SCALE
4
3
2
1
NOTE:
GROUND ROD
3/4" x 8'-0"COPPERCLAD
POLE LIGHTING BRANCHCIRCUIT.
POLE LIGHTING BRANCH
EMERGENCY PHONE ASSECURITY CAMERA OR120 V CIRCUIT TO THE NEXT
CIRCUIT.
TYPICAL FOR ALL POLES
(WITH SECURITY CAMERA)TYPICAL FOR ALL POLES
CONCRETE POLE BASEBY GENERAL CONTRACTOR
GROUT ALL AROUNDLEVEL NUT
2" C. TO CLOSEST
12" BENDING RADIUS.SECURITY MANHOLE: MINIMUM
GROUND CONDUCTOR
CONNECT TO GROUND
BASE PLATE
LUG OF POLEALL POLESTYPICAL FOR
VENTILATED OPENING WITH ONE 15A
POLE
HANDHOLEBASE COVER
DUPLEX RECEPTACLE.
AT 19 FT. ABOVE GROUND, ALIGNED3/4" NIPPLE (HOLE) FOR THE POWER
6"x6"x6" NEMA 3R ENCLOSURE WITH
WITH THE POLE HANDHOLE
WITH THE POLE HANDHOLE
OR EMERGENCY PHONE).POLES (WITH SECURITY CAMERANOTE 4, TYPICAL FOR ALL
AT 20 FT. ABOVE GROUND, ALIGNED1/2" NIPPLE (HOLE) FOR FIBER OPTIC CABLE
POLE MOUNTED SECURITY CAMERAAND SECURITY PHONE REQUIREMENTS DETAIL05
E3.1
24" HIGH(VERIFY)CONCRETE POLE BASE BY
GENERAL CONTRACTOR
ASC:
16,
136
ASC:
23,
596
LRCUTILITY METER
600A
MAIN CIRCUIT BREAKER FORBUILDING B
UTILITY METER600A
MAIN CIRCUIT BREAKER FORBUILDING A
2 2
E3.1E
LEC
TRIC
AL
DE
TAIL
S &
RIS
ER
S
1 CITY COMMENTSXXXX
11
1
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
E4.1E
LEC
TRIC
AL
SC
HE
DU
LES
PANEL HPA
SERVICE:
LOAD CAT.
LLSSSSGGGSSSSSS
LOAD CATEGORYCONNECTED VADESIGN FACTORDESIGN VA
TOTAL CONNECTED VA:
TOTAL DESIGN VA:
LOAD DESCRIPTION
STRIP LIGHTSCAN LIGHTSSPARESPARESPARESPAREFACPIRIGATIONSECURITY SYSTEMSPARESPARESPARESPARESPARESPARESPACE ONLYSPACE ONLYSPACE ONLYSPACE ONLYSPACE ONLYSPACE ONLY
208/120V,3PH,4W+EQPMT. GND. BUS
LOAD SERVING A
1,008
500
500
500
500
LIGHTS2,1581.25
2,698
8,659
14,449
VAB
650
500
500
500
500
REC0
NEC0
C
500
500
500
500
500
GEN1,5001.00
1,500
AMPS &
POLES
20/120/120/120/120/120/120/120/120/120/120/120/120/120/120/1
DATA0
1.000
MOUNTING SURFACESECTION 1 OF 1
CKTNO
13579
11131517192123252729313335373941
A
*
*
*
*
*
*
*
MTRS01.000
B
*
*
*
*
*
*
*
C
*
*
*
*
*
*
*
CONNECTED AMPS:
DESIGN AMPS:
CKTNO
2468
1012141618202224262830323436384042
LGST MTR0
0.250
AMPS &
POLES
20/120/120/120/120/120/120/3
--
20/120/120/120/120/120/1
MAINS:
LOAD SERVING A
500
500
1,667
500
500
COOL0
0.000
IC:
MLO
VAB
500
500
1,667
500
500
HEAT5,0011.00
5,001
24
40
42,000
C
500
500
1,667
500
500
KTCHN0
NEC0
AMPS RMS SYM
AMPS:
LOAD DESCRIPTION
EXIT LIGHTSSPARESPARESPARESPARESPAREEUH-A(5KW)-SPARESPARESPARESPARESPARESPARESPACE ONLYSPACE ONLYSPACE ONLYSPACE ONLYSPACE ONLYSPACE ONLY
OTHER0
1.000
150
SPARE-----0.50
5,250
LOAD CAT.
LSSSSSHHHSSSSSS
LIGHTING RELAY CABINET SCHEDULECABINET NAME:
LOCATION:
RELAY #
1
2
3
4
5
6
7
8NOTES:1. PHOTOCELL ON, PHOTOCELL OFF CONTROL. 2. TIMECLOCK ON, TIMECLOCK OFF. WITH MANUAL OVERRIDE AT EACH FLOOR.3. PHOTOCELL ON, TIMECLOCK OFF. (TIME CLOCK OFF TO MEET CITY AFTER HOURS OPERATION)
PNL & CKT
HPB-1
HPB-3
HPB-5
HPB-7
HPB-9
HPB-2
LRC
FIRE RISER ROOM
DESCRIPTION
FRONT SITE LIGHTING
FRONT SITE LIGHTING
BACK SITE LIGHTINGS
BACK SITE LIGHTINGS
SITE LIGHTING
SIGNAGE LIGHTING
SPARE
SPARE
CONTROL / OVERRIDE SWITCH NOTES
1
2
1
2
2
2
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
AC
AHU
AIR CONDITIONING UNIT
AIR HANDLING UNIT
AP
AS
BD
CHWP
CP
CT
CU
CV
CWP
DB
DIFF
DX
EA
EAT
ECH
EDH
EF
ELEV
ESP
ET
EUH
FCU
FD
FPB
FSD
GI
H
LAT
NC
ACCESS PANEL
AIR SEPARATOR
BACKDRAFT DAMPER
CHILLED WATER PUMP
CONDENSATE PUMP
COOLING TOWER
CONDENSING UNIT
CONSTANT VOLUME
CONDENSER WATER PUMP
DIFFUSER
DIRECT EXPANSION COOLING COIL
EXHAUST AIR
ENTERING AIR TEMPERATURE
ELECTRIC CABINET HEATER
ELECTRIC DUCT HEATER
EXHAUST FAN
ELEVATION
EXTERNAL STATIC PRESSURE
EXPANSION TANK
ELECTRIC UNIT HEATER
FAN COIL UNIT
FIRE DAMPER
FAN POWERED BOX
COMBINATION FIRE/SMOKE DAMPER
GRAVITY INTAKE
HUMIDIFIER
LEAVING AIR TEMPERATURE
NORMALLY CLOSED
NO NORMALLY OPEN
OA OUTSIDE AIR
OAF OUTSIDE AIR FAN
OAU OUTSIDE AIR UNIT
RA RETURN AIR
RH RELIEF HOOD
RTU ROOFTOP UNIT
SA SUPPLY AIR
SD SMOKE DAMPER
SF SUPPLY FAN
SG SUPPLY GRILLE
TAG TRANSFER AIR GRILLE
TEF TOILET EXHAUST FAN
TO TRANSFER OPENING
TYP TYPICAL
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
WCC WATER COOLED CHILLER
WB WET BULB
DRY BULB
DESCRIPTIONABBREVIATION DESCRIPTIONABBREVIATION
MECHANICAL ABBREVIATIONS
CLG CEILING
CFM CUBIC FEET PER MINUTE
HX HEAT EXCHANGER
KEF KITCHEN EXHAUST FAN
M/MOT MOTORIZED
NC
MAU MAKEUP AIR UNIT
UNO UNLESS NOTED OTHERWISE
CRACCOMPUTER ROOM AIR CONDITIONINGUNIT
P PUMP
TOD TOP OF DUCT
BOD BOTTOM OF DUCT
BUILDING CODES:
CITY OF SAN MARCOS, TX AMENDMENTS ADOPTEDSEPTEMBER 1, 2015.
2015 INTERNATIONAL BUILDING CODE2015 INTERNATIONAL FIRE CODE2015 INTERNATIONAL FUEL CODE2015 INTERNATIONAL PLUMBING CODE2015 INTERNATIONAL MECHANICAL CODE2009 INTERNATIONAL ENERGY CONSERVATION CODE2014 NEC
CO
B
HVAC DUCT SYMBOLS TEMPERATURE/CONTROL MONITORING
COMBINATION FIRE/SMOKE DAMPER
EXHAUST DUCT DOWN
FIRE DAMPER
MOTORIZED DAMPER
BALANCING DAMPER
RETURN DUCT DOWN
SMOKE DAMPER
SUPPLY DUCT DOWN
SUPPLY DUCT UP
CARBON DIOXIDE SENSOR
CARBON MONOXIDE SENSOR
FLOW SENSOR
FLOAT SWITCH
FLOW METER
BTU METER
PRESSURE SENSOR
SMOKE DETECTOR
TEMPERATURE SENSOR
THERMOSTAT
HUMIDISTAT
EXHAUST DUCT UP
RETURN DUCT UP
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
BACKDRAFT DAMPER
F
CO2
H
P
S
TS
T
M
ROUND FLEXIBLE DUCT
SYMBOL DESCRIPTION
HVAC SINGLE LINE DUCT SYMBOLS
POINT OF NEW CONNECTION
S
FD
SD
M
FS
BD
NOTE: NOT ALL SYMBOLS USED
AUTOMATIC (MOTOR-OPERATED) DAMPER
SUPPLY RECTANGULAR ELBOW DOWN
SUPPLY RECTANGULAR ELBOW UP
ROUND ELBOW DOWN
RECTANGULAR ELBOW WITH TURNING VANES
ROUND RADIUS ELBOW R = 1.5
90 STRAIGHT TEE
90 CONICAL TEE
45 LATERAL CONICAL TEE
45 LATERAL CONICAL TEE
SIZE OR SHAPE TRANSITION
ROUND ELBOW UP
COMBINATION FIRE/SMOKE DAMPER
FIRE DAMPER
MOTORIZED DAMPER
BALANCING DAMPER
SMOKE DAMPER
BACKDRAFT DAMPER
FD
SD
M
FS
BD
RETURN RECTANGULAR ELBOW DOWN
SUPPLY RECTANGULAR ELBOW UP
ROUND FLEXIBLE DUCT
M0.
1
HV
AC
CO
VE
R S
HE
ET
ELECTRIC UNIT HEATER BASIS OF DESIGN MANUFACTURERTAGkWCFMVOLTAGE/PHASEAMPSDIMENSIONS W x D x H (IN)WEIGHT (LBS)MODELDISCHARGENOTES:1. PROVIDE MOUNTING BRACKET2. PROVIDE DISCONNECT SWITCH3. PROVIDE IN BUILT THERMOSTAT
EUH-A5
400208/39.17
14 X 6.5 X 17.7525
5100HORIZONTAL
CITY COMMENTS
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
M0.
2HV
AC
SP
EC
IFIC
ATI
ON
S
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
STOP
M-3
M-3
M-3 M-1
M-2
M-1M-1
EUH-A
T
M2.
1FLO
OR
PLA
NB
UIL
DIN
G '2
'H
VA
C
01M2.1
FLOOR PLAN BUILDING 2 - HVACSCALE : 1/8" = 1'-0"
N
PROVIDE ROOF CURB FOR DOWN FLOW 5 TON UNIT EQUALTO TRANE YHC063 FOR FUTURE ROOF TOP UNIT. ROOF CURBSHALL BE CAPPED.
PROVIDE ROOF CURB FOR DOWN FLOW 7.5 TO UNIT EQUALTO TRANE YHC092 FOR FUTURE ROOF TOP UNIT. ROOF CURBSHALL BE CAPPED.
PROVIDE ROOF CURB FOR DOWN FLOW 10 TO UNIT EQUALTO TRANE YHC120 FOR FUTURE ROOF TOP UNIT. ROOF CURBSHALL BE CAPPED.
PROVIDE HEATERS FOR FREEZE PROTECTION. INSTALLHEATERS AT 12'-0" A.F.F.. HEATERS SHALL BE RELOCATED BYTENANT ONCE SPACE IS FINISHED OUT TO PREVENT FREEZEOF ADJACENT VACANT SPACES.
M-1
HVAC NOTES BY SYMBOL
M-2
M-3
M-4
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
AD
AFC
AFF
AHR
AP
BD
BH
BV
CB
CD
CI
CL
CO
CW
DCO
DF
DS
DSN
ET
EWC
EWH
FD
FL. EL.
FS
HB
HD
HW
L
MH
MB
MUV
AREA DRAIN
AUTOMATIC FLOW CONTROL
ABOVE FINISHED FLOOR
AIR HOSE REEL
ACCESS PANEL
BLOWDOWN
BOX HYDRANT
BALANCE VALVE
CATCH BASIN
CONDENSATE
CAST IRON
CENTERLINE
CLEANOUT
DOMESTIC COLD WATER
DOUBLE CLEANOUT
DRINKING FOUNTAIN
DOWNSPOUT
DOWNSPOUT NOZZLE
EXPANSION TANK
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FLOOR DRAIN
FLOW LINE ELEVATION
FLOOR SINK
HOSE BIBB
HUB DRAIN
DOMESTIC HOT WATER
INVERT ELEVATION
LAVATORY
MANHOLE
MOP BASIN
AUTOMATIC MAKE-UP VALVE
INV. EL.
NFWH
OD
OFD
OSD
OS&Y
PIV
RD
RECIRC
RIV
RRV
SH
SHDR
SK
SS
TD
TP
TYP
UR
V
VS
VTR
W
WC
WCO
WH
WHA
WS
YH
NON -FREEZE WALL HYDRANT
OUTSIDE DIAMETER
OVERFLOW DRAIN
OPEN SITE DRAIN
OUTSIDE SCREW & YOKE
POST INDICATOR VALVE
ROOF DRAIN
RECIRCULATING
ROOF INTAKE VENT
ROOF RELIEF VENT
SHOWER HEAD
SHOWER DRAIN
SINK
SERVICE SINK
TRENCH DRAIN
TRAP PRIMER
TYPICAL
URINAL
SANITARY VENT
VENT STACK
VENT THRU ROOF
WASTE
WATER CLOSET
WALL CLEANOUT
WATER HEATER
WATER HAMMER ARRESTOR
WASTE STACK
YARD HYDRANT
DESCRIPTIONABBREVIATION DESCRIPTIONABBREVIATION
PLUMBING ABBREVIATIONS
WB WASHER BOX
ETP ELECTRONIC TRAP PRIMER
BP BOOSTER PUMP
FCO FLOOR CLEAN OUT
FP FIRE PUMP
JP JOCKEY PUMP
BT BATH TUB
WHT WALL HYDRANT
HWRP HOT WATER RETURN PIPING
GCO GROUND CLEAN OUT
HSA HYDRAULIC SHOCK ABSORBER
RPBP REDUCED PRESSURE BACKFLOWPREVENTER
A
G
D
SD
CD
MG
A
GW
AW
AV
SS
FDC
TH
SP
F
M
PLUMBING PIPE FITTINGSSYMBOL DESCRIPTION
PLUMBING PIPINGSYMBOL DESCRIPTION
PLUMBING VALVE SYMBOLSSYMBOL DESCRIPTION
AUTOMATIC AIR VENT
CLEANOUT
CONCENTRIC REDUCER
ECCENTRIC REDUCER
ELBOW DOWN
TEE UP
TEE DOWN
ELBOW
END CAP
EXPANSION JOINT
FLANGED CONNECTION
FLEX CONNECTOR
FLOW ARROW
PIPE ANCHOR
PRESSURE GAUGE
STRAINER
TEE
THERMOMETER
UNION
WATER HAMMER ARRESTER
FLOOR DRAIN
ELBOW UP
SYMBOL DESCRIPTION
FIRE PROTECTION SYSTEM
ACID WASTE
COMPRESSED AIR
CONDENSATE DRAIN
DOMESTIC HOT WATER SUPPLY
DRAIN LINE
EXISTING TO BE REMOVED
DOMESTIC COLD WATER
EXISTING TO REMAIN
GAS: LOW PRESSURE
GAS: MEDIUM PRESSURE
GREASE WASTE
POINT OF NEW CONNECTION
STORM DRAIN
SANITARY SEWER
VENT
ACID VENT
BALL VALVE
CHECK VALVE
GATE VALVE
GLOBE VALVE
GAS COCK, GAS STOP
BACKFLOW PREVENTER
PLUG VALVE
PRESSURE-REDUCING VALVE
PRESSURE-RELIEF VALVE
THERMOSTATIC MIXING VALVE
SOLENOID VALVE
TEST HEADER PIPING
STANDPIPE
FIRE LINE
FIRE HYDRANT
SIAMESE HOSE CONNECTION
FIRE DEPARTMENT CONNECTION PIPING
DOMESTIC HOT WATER RETURN
BUILDING CODES:
CITY OF SAN MARCOS, TX AMENDMENTS ADOPTEDSEPTEMBER 1, 2015.
2015 INTERNATIONAL BUILDING CODE2015 INTERNATIONAL FIRE CODE2015 INTERNATIONAL FUEL CODE2015 INTERNATIONAL PLUMBING CODE2015 INTERNATIONAL MECHANICAL CODE2009 INTERNATIONAL ENERGY CONSERVATION CODE2014 NEC
P0.1
PLU
MB
ING
CO
VE
R S
HE
ET
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
P0.2P
LUM
BIN
GS
PE
CIF
ICA
TIO
NS
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
P0.3P
LUM
BIN
GS
PE
CIF
ICA
TIO
NS
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
STOP
LP
3"
P-3
6"
P-4
F
P-6
P-7
G
4"
P-1
REF: P2.3/01
P-2
P1.1
SIT
E P
LAN
PLU
MB
ING
01
P1.1
SITE PLAN - BLDG. 2. - PLUMBING
SCALE : 1/16" = 1'-0"
N
4" SANITARY SEWER REFER TO CIVIL PLANS FOR CONTINUATION I.E. +/- 4'-0" B.F.F.
FIRE DEPARTMENT CONNECTION COORDINATE EXACT LOCATION WITH HOSE LAY LENGTH REQUIREMENTS OF AHJ.
6" FIRE SERVICE ENTRANCE REFER TO CIVIL PLANS FOR CONTINUATION.
3" DOMESTIC WATER SERVICE ENTRANCE REFER TO CIVIL PLANS FOR CONTINUATION.
GAS METER MANIFOLD BY GAS COMPANY ESTIMATED LOAD 4,000 CFH.
GAS SERVICE ENTRANCE BY GAS COMPANY
GAS METER MANIFOLD BY GAS COMPANY ESTIMATED LOAD 4,500 CFH.
P-1
PLUMBING NOTES BY SYMBOL
P-2
P-3
P-4
P-5
P-6
P-7
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
D
U
M
P
S
T
E
R
A
R
E
A
XFMR
STOP
LP
4"
4"
GW
P-7 P-6
P-3
6"
P-2
F
P-4
4" DCOP-1
G
FCO
4"4"
FCO
GCO
4"
4"
3"
P-5
DCO
4"
2"
FCO
P2.1
UN
DE
RFL
OO
R P
LAN
BU
ILD
ING
'2'
PLU
MB
ING
01P2.1
UNDERFLOOR PLAN BUILDING '2' - PLUMBINGSCALE : 1/8" = 1'-0"
N
4" SANITARY SEWER REFER TO CIVIL PLANS FORCONTINUATION I.E. +/- 4'-0" B.F.F.
6" FIRE SERVICE ENTRANCE. REFER TO CIVIL PLANS FORCONTINUATION.
3" DOMESTIC WATER ENTRANCE REFER TO CIVIL PLANSCONTINUATION
GAS SERVICE BY GAS COMPANY
UP TO GAS METER MANIFOLD BY GAS COMPANY
1,500 GALLON GREASE TRAP.
SAMPLE WELL.
P-1
PLUMBING NOTES BY SYMBOL
P-2
GAS: DEVIN KLEINFELDER- CENTER POINT ENERGY PHONE: 830-643-6938 EMAIL: [email protected]
UTILITY COMPANY CONTACTS
P-3
P-4
P-5
P-6
P-7
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
P-7
P-5P-3
P-6
3"
2"
P-8
2-1/2"
P-1
1-1/2" 1" 1"
P-9
1"
P-9P-9
2" 2" 1-1/2"1-1/2"
P-1
P-10
2" VTR
P2.2FL
OO
R P
LAN
BU
ILD
ING
'2'
PLU
MB
ING
01P2.2
FLOOR PLAN BUILDING '2' - PLUMBINGSCALE : 1/8" = 1'-0"
N
1-1/2" TENANT DOMESTIC WATER CONNECTION.
3" DOMESTIC WATER BACKFLOW PREVENTER. EQUAL TOAPOLLO # DCDALF-4AN
MAIN DOMESTIC WATER SHUT-OFF VALVE.
FIRE SPRINKLER RISER.
FIRE DEPARTMENT CONNECTION.
PROVIDE PRO-SET TRAP GUARD FOR FLOOR DRAIN TRAP SEAL.
GAS METER MANIFOLD BY GAS COMPANY, ESTIMATEDBUILDING TOTAL DEMAND: 4,000 CFH.
2" TENANT DOMESTIC WATER CONNECTION PROVIDETENANT SUB-METER WITH REMOTE READ OUT.
1" TENANT DOMESTIC WATER CONNECTION.
PROVIDE SUB METER WITH REMOTE READ OUT.
P-1
PLUMBING NOTES BY SYMBOL
P-2
P-3
P-4
P-5
P-6
P-7
P-8
P-9
GAS: DEVIN KLEINFELDER- CENTER POINT ENERGY PHONE: 830-643-6938 EMAIL: [email protected]
UTILITY COMPANY CONTACTS
P-10
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851
Bldg. 2
GRADE CLEANOUT DETAILNO SCALE
06P3.1
GRADE TWO-WAY CLEANOUT DETAILNO SCALE
05P3.1
CAST IRON LONG SWEEP 1/4BEND OR COMBINATION WYE"& 1/8 BEND
HEAVY DUTY CAST IRON CLEANOUTCOVER WITH "C.O." DESIGNATION
FINISHED GRADE
6" THICK x 18" SQUARE CONCRETEPAD SET AT AN ELEVATION SUITABLEFOR PASSOVER OF LAWN MOWERS(TROWEL SMOOTH & EDGE)
BUILDING DRAIN OR SEWERSIZE & MATERIAL AS SPECIFIED
REF: PLAN FOR INVERT
CAST IRON LONG SWEEP 1/4BEND OR COMBINATION WYE"& 1/8 BEND
HEAVY DUTY CAST IRON CLEANOUTCOVER WITH "C.O." DESIGNATION
FINISHED GRADE
6" THICK x 18" SQUARE CONCRETEPAD SET AT AN ELEVATION SUITABLEFOR PASSOVER OF LAWN MOWERS(TROWEL SMOOTH & EDGE)
BUILDING DRAIN OR SEWERSIZE & MATERIAL AS SPECIFIED
REF: PLAN FOR INVERT
GAS MANIFOLD DETAILNO SCALE
02P3.1
GRADE
GAS SERVICE LINE (CAPABLE OF 5-PSI SERVICE) AND GAS METERMANIFOLD PER ATMOS ENERGY REQUIREMENTS.
TYPICAL FUTURE RETAIL TENANT GAS METER.
ITEM DESCRIPTION
NATURAL GAS DIAGRAM SYMBOL KEYAPPLIES TO GAS DIAGRAM THIS SHEET ONLY)
P-2
P-1
P-2
P-1
GAS COCK
TEE WITH BUSHING
UNION
NOTES
1. THE GAS METER MANIFOLD IS TO BE USED FOR REFERENCE ONLY. CONTRACTOR SHALLCOORDINATE FINAL DESIGN OF MANIFOLD WITH GAS COMPANY. CONTRACTOR SHALLCOORDINATE WITH OWNER NUMBER OF METERS REQUIRED. INSTALLATION SHALL COMPLYWITH NFPA, INTERNATIONAL PLUMBING CODE AND GAS COMPANY INSTALLATIONREQUIREMENTS. PIPING SIZES SHALL BE COORDINATED WITH GAS COMPANY.
FIRE PROTECTION RISER DETAILSNO SCALE
03P3.1
D
ITEM DESCRIPTION
NOTES
1. FIRE PROTECTION DIAGRAM DOES NOT SHOW ALL REQUIRED TRIM AND/OR COMPONENTS.SUCH AS TAMPER SWITCHES, FLOW SWITCHES, PRESSURE GAUGES, VALVES, DRAIN CUPS ETC.ALL REQUIRED TRIM COMPONENTS SHALL BE PROVIDED AS REQUIRED BY NFPA-13. REFER TOSPECIFICATIONS FOR ADDITIONAL DETAILS.
2. DUCTILE IRON PIPE BELOW BUILDING TO BE PROVIDED WITH POLY WRAP.
3. FLOW SWITCHES AND TAMPER SWITCHES TO BE CONNECTED TO FIRE ALARM/SECURITYSYSTEM WITH LISTED 24 HOUR CENTRAL STATION SUPERVISION.
WEATHERPROOF HORN AND STROBE - REFER TO SITE PLAN NOTES.
NOT USED.
GALVANIZED, COATED RODDING PER NFPA 24
THRUST BLOCKING PER NFPA 24
ANSI A21.51 DUCTILE IRON SERVICE PIPING WITH POLY WRAP BELOWBUILDING.
DOUBLE CHECK UL/FM BACKFLOW DEVICE LISTED FOR FIRE PROTECTION.PROVIDE TAMPER SWITCHES FOR BACKFLOW DEVICE VALVES. BACKFLOWPREVENTER LOCATED IN EXTERIOR VAULT. REFER TO CIVIL. (NOTE 3).
SPRINKLER RISER ASSEMBLY (NOTE 1)
MAIN DRAIN VALVE (NOTE 1)
FLOW SWITCH (NOTE 3)
MAIN DRAIN DISCHARGED TO EXTERIOR TO SPLASH BLOCK AT GRADEUSING GALVANIZED FITTINGS.
FLANGED CONNECTION
NOT USED
REFER TO SITE UTILITY DOCUMENTS FOR FIRE PROTECTION WATER ANDFIRE DEPARTMENT CONNECTION PIPING EXTERIOR OF BUILDING.
TO FLOOR DRAIN.FLOOR
FIRE PROTECTION NOTES BY SYMBOL(APPLIES TO DIAGRAMS THIS SHEET ONLY)
FP-1
FP-2
FP-3
FP-4
FP-5
FP-6
FP-7
FP-8
FP-9
FP-10
FP-11
FP-12
FP-13
FP-8
FP-11
FP-3
FP-1
FP-9
FP-7
FP-4FP-5
FP-13
FP-14
FP-14
FP-6
1. SAMPLE WELL TO BE EQUAL TO PARK ENVIRONMENTAL MODELSWB-156.
2. SAMPLING WELL MUST BE INSTALLED UNDER A SEPARATEPLUMBING PERMIT.
3. USE 15" T&G R.C.P. FOR INSTALLATION 6'-0" DEEP AND LESS.
4. USE 24" T&G R.C.P. FOR INSTALLATION GREATER THAN 6'-0" DEEP.(STD RING AND M.H. COVER REQUIRED)
5. SAMPLING WELL MUST BE SET IN A CIRCULAR OR SQUARECONCRETE PAD ( 1'-0" GREATER THAN OUTSIDE DIAMETER OF PIPE.)
6. LAWN INSTALLATION SHALL BE 4" ABOVE FINISHED GRADE.
7. DRIVE & SIDEWALK INSTALLATION SHALL BE BROUGHT TO FINISHEDGRADE
GENERAL NOTES:
18"
30"
24"30"
FRONT VIEW4"
6" INLET
SIDE VIEW
VARIES
PAVEMENT
INLET
FLOW
NOTE:INVERT ELEVATIONS TO BETHE SAME ON INLET ANDOUTLET OF SAMPLE WELL
PAVEMENT
SAMPLE WELL BASIN DETAILNO SCALE
04P3.1
CAST IRON FRAMEAND COVER
RISER SECTION RCPPIPE
15" DIA. ID
JOINT SEALED WITHNONSHRINK GROUT
SCH 40 PVC SLEEVE(TYPICAL)
CONCRETE BASE
6" INLET FROMINTERCEPTOR
6" OUTLETTO SEWER
FLOW
CAST IRON FRAMEAND COVER
RISER SECTION RCPPIPE
JOINT SEALED WITHNONSHRINK GROUT
OUTLET
PLAN VIEW
FIRE SPRINKLER DDCAIN VERTICAL RISER
FROM WATERSUPPLY(NOTE 2)
TO SPRI
NKL
ERS
FFDC
4"
P3.1P
LUM
BIN
GD
ETA
ILS
&S
CH
ED
ULE
S
01P3.1
GREASE INTERCEPTOR - GT-1500 & GT-2500NO SCALE
Bldg. 2
Mechanical, Plumbing and Electrical
Engineering Consultants
5600 Tennyson Parkway, Suite 290
Plano, Texas 75024
214.509.8263
www.pqrus.com
Texas Registered Engineering
Firm F-16851