I. GENERAL REQUIREMENTS
1. GENERAL CONDITIONS: ALL CONDITIONS AND REQUIREMENTS UNDER THE
"GENERAL CONDITIONS", THE "SUPPLEMENTARY GENERAL CONDITIONS", THE
"SPECIAL CONDITIONS" SHALL BECOME A PART OF THIS SPECIFICATION, AND
BIDDERS WILL EXAMINE ALL DRAWINGS AND READ ALL PARTS OF THE
SPECIFICATIONS TO AVOID OMISSIONS, DUPLICATIONS AND TO INSURE COMPLETE
EXECUTION OF ALL WORK FOR ELECTRICAL.
2. GENERAL: THE WORK UNDER THIS SECTION SHALL INCLUDE ALL LABOR,
MATERIALS AND EQUIPMENT AND INCIDENTAL COSTS NECESSARY TO FURNISH AND
INSTALL ALL ELECTRICAL WORK, EQUIPMENT, LAMPS, ETC. INDICATED ON THE
DRAWINGS, AS SPECIFIED HEREIN, OR BOTH.
3. THE TENANT'S GENERAL CONTRACTOR AND/OR HIS ELECTRICAL
SUBCONTRACTOR IS TO VERIFY ALL EQUIPMENT SPECIFICATIONS AND
REQUIREMENTS WITH THE TENANT OR THE TENANT'S CONSTRUCTION
REPRESENTATIVE PRIOR TO START OF CONSTRUCTION. THIS CONTRACTOR TO
VERIFY AMPERAGE AND VOLTAGE SPECIFICATIONS AND REQUIREMENTS (SERVICE
AND PANEL SPECIFICATION) WITH THE ELECTRICAL SUBCONTRACTOR IN
COORDINATION WITH EQUIPMENT SPECIFICATIONS FOR EQUIPMENT SUPPLIED BY
THE TENANT, THE CONTRACTORS OR OTHER SOURCES (AS SPECIFIED BY THE
ARCHITECT) AS A DOUBLE CHECK TO ASCERTAIN PROPER INSTALLATION OF
EQUIPMENT AT THE CORRECT VOLTAGE/AMPERAGE.
4. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR OBTAINING APPROVAL FROM
THE BUILDING AND ELECTRICAL INSPECTORS FOR ALL CONCEALED WORK PRIOR TO
CLOSING UP WALLS, FLOORS AND CEILINGS.
5. TENANT'S GENERAL CONTRACTOR SHALL BRING IN ALL ADDITIONAL SERVICES,
ADEQUATE FOR TENANT'S NEEDS AS REQUIRED, INCLUDING BUT NOT LIMITED TO
ELECTRIC, SPRINKLER, SOIL (WASTE), DOMESTIC WATER LINES, OUTSIDE TOILET
EXHAUST AIR AND FIRE ALARM.
6. SCOPE: FURNISH LABOR, MATERIALS, TOOLS, EQUIPMENT, ETC., REQUIRED FOR A
COMPLETE INSTALLATION OF ELECTRICAL SYSTEMS AND WORK, IN ACCORDANCE
WITH LOCAL CODES AND GOVERNING BODIES HAVING JURISDICTION, AS SHOWN ON
DRAWINGS, AND AS SPECIFIED, INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
A. NEW SERVICE -- TENANT'S CONTRACTOR IS TO REUSE EXISTING ELECTRICAL
SERVICE OR CONDUIT ONLY; FURNISH AND INSTALL NEW ELECTRICAL SERVICE WIRE
AND EXTEND BOTH CONDUIT AND WIRE TO POINT OF ALL NEW PANELS,
TRANSFORMERS, WIREWAYS, TROUGHS, TIME CLOCKS, ETC.. SINCE SPACE MAY OR
MAY NOT BE MEASURED OR REVIEWED BY TENANT'S ARCHITECT, THE ACTUAL
LOCATION OF SERVICE AND PANEL LOCATIONS MAY NOT BE KNOWN. THE
ELECTRICAL SUBCONTRACTOR, IN REVIEW OF THE PREMISES, IS REQUIRED TO
INSTALL PANELS IN LOCATION AS NOTED ON DRAWINGS AND MUST INCLUDE IN HIS
BID ANY EXTENSION OF CONDUIT AND WIRE, NEW DISCONNECTS, RELOCATION OR
INSTALLATION OF PANELS, TROUGHS, WIREWAYS, ETC. TO MAKE THE SYSTEM
WHOLE AND TO UPGRADE AS NECESSARY TO MEET CODE REQUIREMENTS. INSTALL
NEW SERVICE INCLUDING CONDUIT AND WIRE FROM DEMISED PREMISES TO
LANDLORD'S ELECTRICAL ROOM IF THE EXISTING SERVICE NEEDS TO BE
UPGRADED FROM WHAT TENANT WAS ORIGINALLY TOLD SERVICE WOULD BE, OR
THE SERVICE NEEDS TO BE MOVED BECAUSE IT'S EITHER SHOWN TO BE MOVED OR
IS EXISTING NOW IN THE PATH OF FUTURE PARTITION OR OTHER SERVICES.
B. EXISTING SERVICE -- TENANT'S CONTRACTOR IS TO REUSE EXISTING ELECTRICAL
SERVICE WIRE, CONDUIT AND ELECTRICAL EQUIPMENT; CUT AND EXTEND TO POINT
OF NEW ELECTRICAL EQUIPMENT. ALL EXISTING ELECTRICAL EQUIPMENT WHICH IS
REUSED TO BE BROUGHT UP TO "LIKE NEW" CONDITION AND THE LATEST N.E.C.
STANDARD. SINCE SPACE MAY OR MAY NOT BE MEASURED OR REVIEWED BY
TENANT'S ARCHITECT, THE ACTUAL LOCATION OF SERVICE AND PANEL LOCATIONS
MAY NOT BE KNOWN. THE ELECTRICAL SUBCONTRACTOR, IN REVIEW OF THE
PREMISES IS REQUIRED TO INSTALL PANELS IN LOCATION AS NOTED ON DRAWINGS
AND MUST INCLUDE IN HIS BID ANY EXTENSION OF CONDUIT AND WIRE, NEW
DISCONNECTS, RELOCATION OR INSTALLATION OF PANELS, TROUGHS, WIREWAYS,
ETC. TO MAKE SYSTEM WHOLE AND TO UPGRADE AS NECESSARY TO MEET CODE
REQUIREMENTS. INSTALL NEW SERVICE INCLUDING CONDUIT AND WIRE FROM
DEMISED PREMISES TO LANDLORD'S ELECTRICAL ROOM IF THE EXISTING SERVICE
NEEDS TO BE UPGRADED FROM WHAT TENANT WAS ORIGINALLY TOLD SERVICE
WOULD BE, OR THE SERVICE NEEDS TO BE MOVED BECAUSE IT'S EITHER SHOWN TO
BE MOVED OR IS EXISTING NOW IN THE PATH OF FUTURE PARTITION OR OTHER
SERVICES. IF SERVICE IS ADEQUATE BUT MUST BE RELOCATED, CUT AND EXTEND
EXISTING WIRE AND CONDUIT TO POINT OF ALL NEW PANELS, DISCONNECTS,
TROUGHS, TIME CLOCKS, ETC.
C. POWER DISTRIBUTION SYSTEMS AND TRANSFORMER.
D. LIGHTING SYSTEMS (ALSO SEE REFLECTED CEILING PLAN).
E. ELECTRICAL ENERGIZING - MISCELLANEOUS FAN AND MOTOR.
F. MOTOR POWER WIRING SYSTEM.
G. TELEPHONE EMPTY CONDUIT SYSTEM (INCLUDING TERMINAL BOXES AND
OUTLETS).
H. CONVENIENCE RECEPTACLE SYSTEM, DOOR ALARM / ENTRY SYSTEM / SECURITY.
I. SOUND SYSTEM, INTERCOM SYSTEM - FURNISHED AND INSTALLED BY THIS
CONTRACTOR IF REQUIRED BY CLIENT; EMERGENCY LIGHT SYSTEM AND BATTERIES
FURNISHED BY CLIENT AND INSTALLED BY THIS CONTRACTOR.
J. GROUNDING IN ACCORDANCE WITH NATIONAL ELECTRIC CODE AND ALL MALL
REQUIREMENTS.
K. NIGHT LIGHT CIRCUITING THROUGHOUT PREMISES AS PER CODE WHETHER
SHOWN OR NOT ON DRAWINGS.
L. LOCK OUTS FOR EXIT / EMERGENCY LIGHTING, ALARM SYSTEMS, CASH
REGISTERS, GRILLE AT ENTRY (IF APPLICABLE) AS REQUIRED. SEE PANEL
SCHEDULE FOR CIRCUITS.
M. SMOKE DETECTORS FURNISHED AND INSTALLED WITHIN STORE TO INCLUDE
LOCATIONS AND INTERNAL / EXTERNAL WIRING IF REQUIRED BY LANDLORD OR FIRE
MARSHAL.
N. ELECTRICAL SUBCONTRACTOR, WHEN BIDDING THIS WORK, TO CHECK TO MAKE
SURE THAT SERVICE WIRE, CONDUIT, DISCONNECTS, ETC., ARE ADEQUATE FOR
TENANT'S NEEDS -- IF ADDITIONAL SERVICE IS REQUIRED, INCLUDE NEW CONDUIT
AND SERVICE FEED OR DISCONNECTS, METER BASE AND METER (IF APPLICABLE),
ETC., TO BRING SUCH SERVICE UP TO TENANT'S NEEDS.
O. FURNISH AND INSTALL ALL CONDUIT AND WIRING, DISCONNECTS, BREAKERS,
BALANCING OF LOADS, ETC. FOR HOOKUP OF ALL H.V.A.C. EQUIPMENT, UNIT(S), OR
INLINE HEATERS WHETHER SUCH HEATERS OR EQUIPMENT / UNITS ARE SHOWN OR
NOT.
P. FURNISH AND INSTALL A TWENTY FOUR (24) HOUR, SEVEN (7) DAY TIME CLOCK
INCLUDING ALL INTEGRAL WIRING AND LOAD BALANCING (PANEL) FOR
CONTROLLING THE STOREFRONT SIGN AND SHOW WINDOW LIGHTING, WHETHER
SUCH WORK IS OR IS NOT SHOWN ON PLANS / OR SPECIFICATIONS.
Q. ALL ELECTRICAL ROUGH-IN TO BE NEW AND THE ORIGINAL SERVICES TO THE
DEMISED PREMISES TO BE REUSED; CUT AND EXTEND TO POINT OF ALL NEW
ELECTRICAL EQUIPMENT (IF ANY EQUIPMENT IS REUSED, UPGRADE SAME TO "LIKE
NEW" CONDITION AND THE LATEST N.E.C. STANDARDS) BY THE TENANT'S
CONTRACTOR UNLESS NOTED OTHERWISE ON DRAWINGS. TENANT'S GENERAL
CONTRACTOR TO FIELD VERIFY THAT ALL UTILITY LINES ARE AT OR ADJACENT TO
TENANT'S SPACE AS NOTED AND AT THE SIZE SPECIFIED. IF THE UTILITIES ARE NOT
IN LOCATIONS AS NOTED ON THE DRAWINGS OR OF A SIZE LARGER OR SMALLER
THAN NOTED, THIS CONTRACTOR IS TO NOTIFY THE TENANT'S ARCHITECT
IMMEDIATELY.
R. THE TENANT'S ELECTRICAL SUBCONTRACTOR IS TO PROVIDE A NEW CIRCUIT
DIRECTORY(S) WITH PROPER PHASING AND BALANCING, WHICH IS TO CONFORM TO
THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND UNDERWRITER'S
CODE.
S. THE SIGN(S) JUNCTION BOX PERMIT IS TO BE INCLUDED IN THE WORK FOR THE
ELECTRICAL SUBCONTRACTOR AND THE BOX IS TO BE SUPPLIED BY THIS
CONTRACTOR AND PROPERLY LABELED.
T. FURNISH AND INSTALL NEW (OR REFURBISH IF EXISTING) TOILET EXHAUST WITH
ASSOCIATED DUCTWORK, ROOF PENETRATIONS, OR HOOK UP TO COMMON
EXHAUST DUCT WITH BACKDRAFT DAMPER ETC., INCLUDING ASSOCIATED
ELECTRICAL HOOKUP AND PANEL CONNECTIONS, WHETHER SUCH WORK IS SHOWN
OR NOT SHOWN ON PLANS AND SPECIFICATIONS.
U. IF A SMOKE EVACUATION AND/OR DETECTION SYSTEM OCCURS FOR THIS SPACE,
IT SHALL BE LEFT INTACT DURING CONSTRUCTION AND ANY NEW WORK,
MODIFICATIONS AND/OR REWIRING TO BE COMPLETED DURING CONSTRUCTION
PHASE TO POINT OF NEW PANELS, WHETHER SHOWN OR NOT SHOWN ON PLANS
AND SPECIFICATIONS.
V. ENGINEER, FURNISH AND INSTALL ANY AND ALL REQUIRED SMOKE EVACUATION,
SMOKE DETECTION AND FIRE ALARM SYSTEMS, INCLUDING ANY AND ALL PARTS AND
LABOR, TO MEET LOCAL CODE, LANDLORD REQUIREMENTS AND FIRE MARSHAL
SPECIFICATIONS WHETHER SHOWN OR NOT SHOWN ON PLANS AND
SPECIFICATIONS.
7. THE TENANT'S GENERAL CONTRACTOR AND / OR ELECTRICAL SUBCONTRACTOR IS
TO INSTALL EMERGENCY AND EXIT LIGHTING, AS REQUIRED BY LOCAL CODE OR
AGENCIES HAVING JURISDICTION OVER THE PROJECT. THE EXIT / EMERGENCY
LIGHTING SHOULD BE PROPERLY LABELED AND APPROVED TYPE LOCKOUTS
INSTALLED.
8. SUBSTITUTIONS: CATALOG AND MANUFACTURER'S NUMBERS IN THIS SECTION
AND ON THE DRAWINGS ARE FOR THE PURPOSE OF ESTABLISHING STANDARDS OF
QUALITY AND TYPE OF MATERIALS TO BE USED. PRODUCTS OR OTHER
MANUFACTURERS MAY BE USED IF SIMILAR AND EQUAL IN QUALITY AND DESIGN IN
THE OPINION OF THE OWNER OR OWNER'S ARCHITECT AND ARE SPECIFICALLY
APPROVED BY THE OWNER OR OWNER'S ARCHITECT, IN WRITING, PRIOR TO CLOSE
OF BIDDING. REQUESTS FOR APPROVAL OF SUBSTITUTIONS SHALL BE IN WRITING,
AND SHALL INCLUDE REPORTS OF TESTS, PERFORMANCE DATA OR OTHER PROOF
OF EQUALITY TO THE ITEM SPECIFIED.
9. SHOP DRAWINGS: PRIOR TO THE COMMENCEMENT OF WORK, SUBMIT ONE (1) SET
OF THE FOLLOWING ITEMS TO THE OWNER'S ARCHITECT IN THE FORM OF SHOP
DRAWINGS, DETAILS OR CATALOG CUTS FOR THE RECORD: LIGHTING AND POWER
PANELS, WIRING DEVICES, SAFETY SWITCHES, TRANSFORMER, TIME CLOCKS AND
ANY OTHER ITEMS AS REQUESTED BY THE OWNER OR THE OWNER'S ARCHITECT.
10. WORKMANSHIP:
A. USE EXPERIENCED, WELL QUALIFIED CRAFTSMEN, IN GOOD STANDING WITH
THEIR RESPECTIVE LABOR UNIONS.
B. USE CAPABLE AND EXPERIENCED SUPERINTENDENTS, AUTHORIZED BY THE
CONTRACTOR TO INSTRUCT WORK, MAKE JOB DECISIONS AND ACT FOR THE
CONTRACTOR IN ALL MATTERS PERTAINING TO THE CONTRACT.
11. PERMITS, TESTS AND INSPECTIONS:
A. APPLY FOR, SECURE AND PAY FOR ALL REQUIRED PERMITS, FEES, LICENSES AND
ROYALTIES TO ACCOMPLISH THE WORK.
B. APPLY FOR, SECURE AND PAY FOR ALL REQUIRED TESTS AND INSPECTIONS TO
ACCOMPLISH THE WORK IN CONFORMANCE WITH ALL CODES AND JURISDICTIONS.
C. FURNISH SIGNED CERTIFIED AND ACCEPTABLE COPIES OF ALL ITEMS COVERED IN
(A) AND (B) ABOVE TO THE OWNER FOR HIS RECORDS.
D. COMPLY WITH RULES AND REGULATIONS OF JURISDICTIONAL AUTHORITIES AND
MALL OR LEASE SPECIFICATIONS AND REPORT ANY DEVIATIONS ON DRAWINGS TO
OWNER.
12. CODES, RULES AND REGULATION: INCLUDE IN ELECTRICAL BID ANY ADDITIONAL
MATERIALS AND LABOR, THAT MAY BE REQUIRED FOR COMPLIANCE WITH ALL
GOVERNING LAWS, RULES AND REGULATIONS, EVEN THOUGH THE WORK IS NOT
MENTIONED IN THESE SPECIFICATIONS OR SHOWN ON THE DRAWINGS. NOTHING IN
THE PLANS OR SPECIFICATIONS SHALL BE DEEMED AS AUTHORITY TO VIOLATE ANY
GOVERNING CODE.
13. ACCURACY OF DATA:
A. THE DATA GIVEN HEREIN AND ON THE DRAWINGS ARE AS EXACT AS COULD BE
SECURED, BUT THEIR ABSOLUTE ACCURACY IS NOT GUARANTEED. THE
SPECIFICATIONS AND DRAWINGS ARE FOR THE ASSISTANCE AND GUIDANCE OF THE
CONTRACTOR. EXACT LOCATIONS, DISTANCES, LEVELS, ETC., WILL BE GOVERNED
BY THE BUILDING AND THE CONTRACTOR SHALL USE THE DATA CONTAINED HEREIN
WITH THIS UNDERSTANDING.
B. THE EXACT LOCATION OF EACH AND EVERY OUTLET OF EACH WIRING SYSTEM,
NOT DIMENSIONED ON THE DRAWINGS, SHALL BE AS DIRECTED BY THE OWNER, THE
OWNER'S ARCHITECT OR HIS SELECTED REPRESENTATIVE.
14. CLEANUP: REMOVE ALL SURPLUS MATERIAL, EQUIPMENT AND DEBRIS
INCIDENTAL TO THIS WORK AND LEAVE THE PREMISES IN A CONDITION ACCEPTABLE
TO THE OWNER.
15. GUARANTEE: FURNISH A WRITTEN CERTIFIED GUARANTEE, IN ACCEPTABLE FORM
TO THE OWNER, AGAINST ANY DEFECTIVE WORKMANSHIP, MATERIAL AND
OPERATING EQUIPMENT. THIS GUARANTEE SHALL BE IN FULL FORCE AND
EFFECTIVE FOR A PERIOD OF ONE (1) YEAR AFTER ACCEPTANCE OF THE
INSTALLATION
16. TEMPORARY ELECTRIC SERVICE: THE ELECTRICAL CONTRACTOR SHALL
PROVIDE TEMPORARY ELECTRICAL WIRING FOR CONSTRUCTION USE AS FOLLOWS:
THE SERVICE ENTRANCE AND FEEDER SHALL BE 60 AMPS, SINGLE PHASE, 3 WIRE
120/208 VOLT FUSED MAIN DISCONNECT. THE FEEDER TO SERVE THE TEMPORARY
DISTRIBUTION WIRING PROVIDING TEMPORARY LIGHTING IN ALL AREAS AS
INDICATED ON DRAWINGS AND WHEREVER REQUIRED FOR THE OPERATION OF 120
VOLT SINGLE PHASE PORTABLE TOOLS AND EQUIPMENT NOT TO EXCEED 1 H.P.. THE
WIRING SHOULD BE EXTENDED ALSO, SO THERE IS A 120 VOLT SINGLE PHASE
OUTLET WITHIN 75 FEET OF ANY PORTION OF THE BUILDING. PROVIDE GROUND
FAULT PROTECTION FOR ALL REQUIRED RECEPTACLES NOT TO BECOME A
PERMANENT PART OF THE INSTALLATION.
17. STRUCTURAL CONDITIONS: NOTCHING AND BORING OF STRUCTURAL MEMBERS
WILL NOT BE PERMITTED. IF CONDUIT, BOXES, ETC. NEED TO BE HUNG FROM
STRUCTURAL STEEL, ONLY HANG FROM TOP FLANGE OF BEAMS AND TOP CHORDS
AND ONLY AT PANEL POINTS OF JOISTS / TRUSSES.
18. COOPERATION WITH OTHER CONTRACTORS: THIS CONTRACTOR SHALL
COOPERATE WITH ALL OTHER CONTRACTORS FURNISHING LABOR MATERIALS AND
ALL WORK, SO THAT THE WORK AS A WHOLE SHALL BE EXECUTED AND COMPLETED
WITHOUT CONFLICT OR DELAY. IN THE EVENT OF ANY MECHANICAL OBSTRUCTION,
AS PLUMBING OR AIR CONDITIONING DUCTS IN WAY OF ELECTRICAL EQUIPMENT, IT
IS THE RESPONSIBILITY OF THIS CONTRACTOR TO NOTIFY THE OWNER'S ARCHITECT
BEFORE COMMENCING ANY WORK.
II. BASIC MATERIALS AND METHODS
1. RACEWAYS AND BOXES
A. WHERE SIZES OF RACEWAY OR BOXES ARE NOT INDICATED, THE CONTRACTOR
SHALL SIZE THESE ITEMS AS REQUIRED FOR THE INSTALLATION.
B. FLEXIBLE METAL CONDUIT AS ALLOWABLE BY CODE SHALL BE USED FOR FINAL
CONNECTION OF LIGHTING FIXTURES AND WIRING DEVICES TO BE INSTALLED IN
HUNG CEILINGS.
C. WORK INSTALLED IN METAL PARTITIONS SHALL BE RUN IN CONCEALED ELECTRIC
METALLIC TUBING OR FLEXIBLE CONDUIT AS REQUIRED BY GOVERNING CODE AND
LANDLORD.
D. BRANCH CIRCUIT WORK CHASED INTO EXISTING CONSTRUCTION FOR
CONCEALMENT UNDER PATCHED FINISHES, MAY BE INSTALLED IN RIGID CONDUIT,
OR EMT.
E. CONDUITS THAT RUN EXPOSED ON EXTERIOR OF BUILDING SHALL BE RIGID
CONDUIT WITH WEATHER TIGHT, CORROSION RESISTANT FITTINGS.
F. FLEXIBLE STEEL CONDUITS SHALL BE USED IN MAKING UP SHORT, FLEXIBLE
CONNECTIONS TO ROTATING OR VIBRATING MACHINERY, MINIMUM 12" LENGTH AND
FOR CONNECTIONS BETWEEN JUNCTION BOXES IN HUNG OR FURRED CEILING
FIXTURES.
G. ALL INTERIOR FEEDERS OR EXPOSED FEEDERS TO THE PUBLIC'S EYE, SHALL BE
INSTALLED IN RIGID CONDUIT OR EMT.
H. MINIMUM SIZE CONDUIT SHALL BE 3/4" TRADE SIZE UNLESS OTHERWISE
INDICATED ON THE DRAWINGS.
I. ALL WORK RUN IN UNEXCAVATED AREAS, CRAWL SPACES, TUNNELS, OR
UNDERGROUND SHALL BE INSTALLED IN RIGID CONDUIT.
J. ALL WORK RUN EXPOSED WITHIN THE BUILDING MAY BE INSTALLED IN RIGID
STEEL CONDUIT OR ELECTRICAL METALLIC TUBING.
K. ALL WORK RUN CONCEALED WITHIN HUNG OR FURRED CEILINGS, METAL STUD
PARTITIONS AND THE LIKE, MAY BE INSTALLED IN RIGID STEEL CONDUIT, ELECTRIC
METALLIC TUBING EXCEPT THAT WIRING IN OR THROUGH SLABS SHALL BE IN RIGID
CONDUIT.
L. GALVANIZED PRESSED STEEL OUTLET BOXES OF PROPER SIZE AND TYPE AS
REQUIRED BY THE BUILDING CONDITIONS SHALL BE PROVIDED FOR ALL INTERIOR
OUTLETS FOR LIGHTING, SWITCHES, RECEPTACLES, CLOCKS, SIGNALS, AND THE
LIKE.
M. PROVIDE GALVANIZED FITTINGS FOR EXPOSED WORK, THREADED FOR CONDUIT
CONNECTIONS AND PROVIDE WITH SUITABLE COVERS.
N. THE OUTLETS FOR LOCAL SWITCHES SHALL BE INSTALLED ADJACENT TO THE
TRIM ON THE STRIKING SIDE OF THE DOOR, REGARDLESS OF THE LOCATIONS
INDICATED ON THE DRAWINGS; THEREFORE, CHECK ALL DOOR SWINGS BEFORE
INSTALLATION CONDUIT AND OUTLETS.
2. GROUNDING:
A. ALL MAJOR PARTS NOT CARRYING CURRENT, INCLUDING THE FOLLOWING ITEMS,
SHALL BE PROPERLY GROUNDED.
1. SECONDARY FEEDER CONDUIT AND EQUIPMENT ENCLOSURES.
2. PANEL BOARD ENCLOSURES, PULL AND JUNCTION BOXES, CABLE TROUGHS.
3. ALL CONDUITS, METAL MOLDING AND OUTLETS BOXES.
4. FAN AND EQUIPMENT HOUSINGS EXPOSED ON THE STRUCTURE OR ON GRADE.
B. ALL CASH REGISTER OUTLETS TO BE ISOLATED AND SEGREGATED.
3. SAFETY SWITCHES:
PROVIDE WHERE SHOWN OR AS REQUIRED, HEAVY-DUTY, METAL ENCLOSED,
EXTERNALLY OPERATED FUSED, OR UNFUSED, SAFETY SWITCHES, OF SUCH TYPE
AND SIZE AS REQUIRED TO PROPERLY PROTECT OR DISCONNECT THE LOAD FOR
WHICH THEY ARE INTENDED. THE OPERATING MECHANISM SHALL BE SO DESIGNED
THAT THE SWITCHES MAY BE LOCKED IN THE "ON" OR "OFF" POSITIONS. WHERE
"WEATHERPROOF" SAFETY SWITCHES ARE INDICATED OR REQUIRED, THESE SHALL
BE AS SPECIFIED ABOVE EXCEPT ENCLOSURES SHALL BE NEMA III, RAINTIGHT.
4. MOTOR AND OTHER WIRING:
A. PROVIDE ALL REQUIRED CONDUIT, WIRING AND SAFETY SWITCHES FOR ALL
MOTORS, AND ANY OTHER ELECTRICAL EQUIPMENT INSTALLED OR CONNECTED
UNDER THIS DIVISION.
B. ALL MOTORS WILL BE FURNISHED AND SET UNDER OTHER DIVISION, THE WORK
OF THIS DIVISION SHALL INCLUDE PROVIDING ALL CONNECTIONS SO AS TO BE
COMPLETE.
C. ALL STARTING DEVICES, MOTOR CONTROLLERS, FLOAT SWITCHES, LEVEL
SENSORS, ALARM DEVICES, REMOTE CONTROL PUSH BUTTONS, ETC., WILL BE
FURNISHED BY THE VARIOUS CONTRACTORS, UNLESS OTHERWISE NOTED HEREIN,
BUT THIS CONTRACTOR SHALL SET THESE DEVICES AND PROVIDE ALL
CONNECTIONS.
D. FOR EACH THERMOSTAT (BY H.V.A.C.), PROVIDE 4" X 4" OUTLET BOX WITH 3/4"
EMPTY CONDUIT STUBBED UP INTO CEILING AND BUSHED. PROVIDE STEEL DRAG
WIRE FOR EACH LOCATION.
5. WIRING DEVICES:
A. COMPUTER RECEPTACLES AT CASH WRAP AREA SHALL BE HUBBELL #IG5262,
COMPUTER GRADE WITH "ISOLATED" GROUND LUGS.
B. ALL WIRING DEVICES INSTALLED IN THIS BUILDING SHALL BE "SPECIFIED GRADE,"
MANUFACTURED BY ARROW, HART AND HEGEMAN, HUBBELL, GENERAL ELECTRIC,
OR EQUAL.
C. LOCAL SWITCHES SHALL BE TOGGLE TYPE, A.C. RATED 20 AMPERES, 125 VOLTS,
QUIET-TYPE WITH SILENT OPERATING MECHANISM, TOTAL CLOSED IN A MOLDED
COMPOSITION BASE. SWITCHES SHALL BE SINGLE POLE, THREE OR FOUR-WAY AS
INDICATED. WHERE LOCK TYPE LOCAL SWITCHES ARE INDICATED, THESE SHALL BE
SIMILAR TO ABOVE SPECIFICATION WITH KEY OPERATOR; PROVIDE TO OWNER TWO
(2) KEYS FOR EACH SWITCH INSTALLED.
D. ALL RECEPTACLES INSTALLED IN THIS BUILDING SHALL BE OF THE GROUNDING
TYPE, WITH GROUNDING PIN SLOT CONNECTED TO DEVICE GROUND SCREW FOR
GROUND WIRE CONNECTION TO CONDUIT SYSTEM.
6. WIRES AND CABLES:
A. ALL WIRE FOR LIGHT AND POWER INSTALLATIONS SHALL BE HIGH CONDUCTIVITY
COPPER, 600 VOLT INSULATED IN ACCORDANCE WITH THE NATIONAL BOARD OF FIRE
UNDERWRITERS STANDARDS FOR TYPE "THW" WIRES, EXCEPT AS NOTED ON THE
DRAWINGS OR OTHERWISE SPECIFIED HEREIN.
B. NO WIRE SHALL BE SMALLER THAN ON. 12 A.W.G. ALL WIRE NO. 8 AND LARGER
SHALL BE STRANDED.
C. WIRES SHALL BE COLOR CODED.
D. ALL WIRES SHALL BE POLARIZED.
E. CIRCUIT WORK BETWEEN OUTLET BOXES AND EACH RECESSED LIGHTING
FIXTURE SHALL BE TYPE 'MC' WIRE.
F. HOME RUNS AND BRANCH WIRING FOR 120 VOLT 16 AMP CIRCUITS SHALL BE AS
FOLLOWS TO ACCOUNT FOR VOLTAGE DROP:
LENGTH HOME RUN WIRE SIZE CIRCUIT WIRE SIZE
1' TO 65' 12 12
66' TO 104' 10 12
105' TO 156' 8 12
157' TO 263' 6 12
264' TO 419' 4 12
7. LIGHTING AND POWER PANELS:
A. PANELS SHALL BE CIRCUIT BREAKER TYPE INSTALLED IN CODE GAUGE
GALVANIZED SHEET STEEL CABINETS, FLUSH OR SURFACE MOUNTED AS INDICATED
ON THE DRAWINGS. THE PANEL SECTIONS SHALL BE MOUNTED AWAY FROM THE
BACK OF THE CABINETS IN SUCH A MANNER THAT THERE WILL BE NO SPACE
BETWEEN THE CABINET TRIMS AND FRAMES. THE GUTTER SPACES ON ALL SIDES,
TOPS AND BOTTOMS SHALL BE OF SUFFICIENT SIZE TO PREVENT OVERCROWDING
OF WIRES AND CABLES AND TO PROVIDE SUFFICIENT VENTILATION TO PREVENT
OVERHEATING OF THE CIRCUIT BREAKERS. EACH CABINET SHALL BE COMPLETE
WITH HINGED DOORS, CYLINDER LOCK, DIRECTORY FRAME AND NEATLY TYPED
DIRECTORY CHARTS. ALL PANELS SHALL BE KEYED ALIKE. INSTALL AN ANGLE PIECE
ON INSIDE OF EACH TRIM FOR EASE OF INSTALLATION.
B. THE BRANCH CIRCUIT BREAKERS, IN GENERAL, SHALL BE MOLDED CASE, BOLT-ON
TYPE, RATED 10,000 AIC ON 120/208V, 100 AMPERE FRAME, THERMAL MAGNETIC TRIP
SINGLE, TWO OR THREE POLE AS SHOWN ON THE DRAWINGS. ALL MULTIPLE POLE
BREAKERS FOR PANELS WHERE INDICATED ON THE DRAWING SCHEDULES. MAIN
BREAKER CHARACTERISTICS SHALL BE AS INDICATED ON THE DRAWINGS. MAIN
BUSS WORK OF ALL PANELS SHALL, AS A MINIMUM, BE DESIGNED TO CARRY THE
FULL RATING OF THE FEEDER SWITCH SUPPLYING THE PANEL. BUSS WORK SHALL
BE HIGH CONDUCTIVITY COPPER. (277/480V CIRCUIT BREAKERS SHALL BE RATED
14,000 A.I.C.)
C. PANEL SECTIONS SHALL BE SUCH THAT NO LIVE PARTS ARE EXPOSED AFTER
INSTALLATION. THEY SHALL BE SO ARRANGED THAT EACH BREAKER IS READILY
REMOVABLE FROM THE PANEL WITHOUT DISTURBING ADJACENT BREAKERS.
ELECTRICAL CONTRACTOR TO PROVIDE TYPED BREAKER LIST.
D. PHASE LEGS SHALL BE ALTERNATELY BUSSED TO EACH CIRCUIT BREAKER IN A
MANNER TO AFFECT BALANCING THE BRANCH CIRCUIT CONNECTIONS AS NEARLY
AS POSSIBLE OVER EACH PHASE.
8. DRY TYPE TRANSFORMERS (IF NEW IS REQUIRED):
A. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL A DRY TYPE AIR
COOLED INDOOR POWER TRANSFORMER, AS RATED ON THE DRAWINGS AND
HEREINAFTER SPECIFIED.
B. THE TRANSFORMER SHALL BE PROVIDED WITH SUITABLE VIBRATION DAMPERS.
SAME TO BE PLACED BETWEEN THE CORE AND THE COILS OF THE ENCLOSURE.
C. THE TRANSFORMER SHALL HAVE CLASS H INSULATION, AND THE WIRING
TEMPERATURE RISE SHALL NOT EXCEED 150 DEGREES C UNDER FULL LOAD IN AN
AMBIENT OF 40 DEGREES C.
D. THE TRANSFORMER ENCLOSURE SHALL BE PRIMED INSIDE AND OUT WITH A ZINC
COATED CHROMATE IRON OXIDE RUST INHIBITING PRIMER AND FINISHED ASAG1
GRAY ENAMEL.
E. THE MAXIMUM ACCEPTABLE NOISE LEVEL SHALL NOT EXCEED THE FOLLOWING:
0 TO 150 kVA - 50 dB
9. LIGHTING FIXTURES:
A. ALL LIGHTING FIXTURES AND LAMPS SHALL BE SUPPLIED BY THE TENANT AND /
OR TENANT'S LIGHT FIXTURE AND LAMP SUPPLIER UNLESS OTHERWISE NOTED, AND
SHALL BE DELIVERED HANDLED, ASSEMBLED AND INSTALLED AT THE SITE BY THE
ELECTRICAL CONTRACTOR. THE ELECTRICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR THE UNLOADING, STORAGE AND PROTECTION OF ALL ITEMS
FOUND TO BE DEFECTIVE AND SHALL BE REPLACED BY THE ELECTRICAL
CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.
B. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL THE NECESSARY LABOR AND
MATERIALS FOR THE COMPLETE INSTALLATION OF THE LIGHTING FIXTURES AS
INDICATED ON THE DRAWINGS.
C. ALL FLUORESCENT AND INCANDESCENT LAMPS SHALL BE AS NOTED ON PLANS
AND SPECIFICATIONS AND SHALL BE PROVIDED BY THE TENANT AND/OR TENANT'S
LIGHT FIXTURE AND LAMP SUPPLIER AND INSTALLED BY THE ELECTRICAL
CONTRACTOR.
D. SEE ELECTRICAL DRAWING FOR LIGHTING FIXTURE DESCRIPTIONS.
III. SPECIFIC ELECTRICAL SPECIFICATIONS:
1. SEE ELECTRICAL DRAWINGS:
LANDLORD'S CRITERIA THE ELECTRICAL CONTRACTOR IS TO BECOME FAMILIARIZED
WITH LANDLORD'S CRITERIA FOR THIS LOCATION AND INCLUDE ANY WORK
REQUIRED OF THIS CRITERIA, WHICH IS NOT SPECIFICALLY NOTED IN THESE
DRAWINGS AND SPECIFICATIONS.
IV. TELEPHONE:
1. PROVIDE 3/4" EMT IN WALLS WITH DRAG STRING AT EACH LOCATION.
V. MISCELLANEOUS:
1. ALUMINUM WIRE IS STRICTLY PROHIBITED FOR THIS PROJECT.
2. DURING DEMOLITION, ANY ELECTRICAL EQUIPMENT, FIXTURE SYSTEMS, CONDUIT
AND WIRE TO BE REMOVED AND NOT REUSED - THIS EQUIPMENT, FIXTURING
SYSTEMS, CONDUIT, AND WIRE MAY NOT BE ABANDONED AND LEFT WITHIN THE
SPACE, IT MUST BE REMOVED TO AN APPROVED DISPOSAL SITE.
E-1.0
ELECTRICAL
NOTES
N.N.
K.F.
1
ELECTRICAL NOTES
SCALE: NONE
DATE:02-03-20
ISSUE/REVISION:ISSUED TO CLIENT
PROJECT NAME:
LOCATION
PROJECT INFORMATION:
DRAWING NUMBER
DRAWING TITLE
ENGINEER'S SIGNATURE
BELMONT PROPERTIESTHE PRIME @LYNDHURST
205-211STUYVESANT AVE.
TOWNSHIP OFLYNDHUSRT
BERGEN COUNTY, NJ
PROJECT #:
PROJECT DATE:
DRAWN BY:
CHECKED BY:
19108
02-03-20
ustomesigning &
Engineering, PC153 East Main St.
Rockaway, NJ 07866Tel: 973-784-4258
www.customdande.com
KENNETH A. FULLER, P.E., LEED APN.J. LICENSE NUMBER: 24GE03240100
EXPIRES 4-30-20COA NUMBER 24GA28170100
EXPIRES 8-31-20
UP
16r
F.E.C.
GFCI
GFCI
HP-1
ELEVATOR CAR LIGHT
DISCONNECT
HP-64,66
30 AMP
DISC SW.
WH-B
GFCI
S
3
GFCIS
FUSED
DISCONNECT
FOR ELEVATOR
GFCI
GFCI
GFCI
WH-2
ELEVATOR
SUMP
PUMP
HP-69,71
30 AMP
DISC SW.
GFCI
4
GFCI
'HP'
HP-57
HP-59
HP-63
METERBANK
HP-51,53,55
1
GFCI
E-2.0
BASEMENT POWER
PLAN
N.N.
K.F.
1
BASEMENT POWER PLAN
SCALE: 1/4" = 1'-0"
DATE:02-03-20
ISSUE/REVISION:ISSUED TO CLIENT
PROJECT NAME:
LOCATION
PROJECT INFORMATION:
DRAWING NUMBER
DRAWING TITLE
ENGINEER'S SIGNATURE
BELMONT PROPERTIESTHE PRIME @LYNDHURST
205-211STUYVESANT AVE.
TOWNSHIP OFLYNDHUSRT
BERGEN COUNTY, NJ
PROJECT #:
PROJECT DATE:
DRAWN BY:
CHECKED BY:
19108
02-03-20
ustomesigning &
Engineering, PC153 East Main St.
Rockaway, NJ 07866Tel: 973-784-4258
www.customdande.com
KENNETH A. FULLER, P.E., LEED APN.J. LICENSE NUMBER: 24GE03240100
EXPIRES 4-30-20COA NUMBER 24GA28170100
EXPIRES 8-31-20
HOME RUN.
DUPLEX RECEPTACLE @ 18" A.F.F. U.N.O. MOUNTED AT
CODE HEIGHT.
GROUND FAULT PROTECTED DUPLEX RECEPTACLE.
SYMBOL DESCRIPTION
ELECTRICAL LEGEND
JUNCTION BOX.
GROUND FAULT PROTECTED QUAD RECEPTACLE.
LIGHT SWITCH.
ELECTRICAL PANEL.
DISCONNECT SWITCH.
DATA RECEPTACLE.
TELEPHONE RECEPTACLE.
QUAD RECEPTACLE @ 18" A.F.F. U.N.O. MOUNTED AT CODE
HEIGHT.
GFCI
GFCI
J
TELEPHONE / DATA COMBINATION RECEPTACLE.
S
(E) - EXISTING TO REMAIN.
(R) - EXISTING TO BE RELOCATED.
(N) - NEW FIXTURE.
WP - WEATHERPROOF
DIMMER SWITCH.
THREE WAY LIGHT SWITCH.
(4W - FOUR WAY SWITCH ).
S
3W
WALL MOUNTED OCCUPANCY SENSOR.
S
OS
OS
CEILING MOUNTED OCCUPANCY SENSOR.
NOTES
D
DEDICATED SIMPLEX RECEPTACLE.
HALF SWITCHED DUPLEX RECEPTACLE.
KEY NOTES:
ELEVATOR CAR POWER. PROVIDE NEMA 1, XXA, FUSED DISCONNECT SWITCH
WITH XXA CURRENT-LIMITING FUSES AS REQUIRED BY XXXXXXXXX ELEVATOR
CORP. PROVIDE ADDITIONAL POWER AND CONTROLS WIRING FOR ELEVATOR AND
ELEVATOR CONTROLS AS REQUIRED BY XXXXXXXXX. COORDINATE ALL
ELECTRICAL WITH XXXXXXXXX FIELD SUPERVISOR.
PROVIDE 3 #4 & 1 #8 GROUND IN 1"C TO HOISTWAY DISCONNECT SWITCH
LOCATED AT TOP OF ELEVATOR SHAFT.
SERVICE RECEPTACLE AND LIGHT FIXTURE. CONTRACTOR TO VERIFY EXACT
LOCATION.
AN ELECTRICAL CONNECTION FOR THE PIT SUMP PUMP MUST BE PROVIDED IN
THE PIT. THE PUMP MUST BE PERMANENTLY WIRED AND MAY NOT BE
CONNECTED TO A G.F.C.I PROTECTED OUTLET.
1
2
3
4
UP
21r
DN
16r
RAMP
UP 18"
98
7
6
5 4
3
F.E.C.
MAILBOXES
PACKAGE SHELF
F.E.C.
T
GFCI
GFCI
AHU-1
J
CH-1-1
CH-1-2
CH-1-2
RP-38,40,42
100 AMP
DISC SW.
HP-56
30 AMP
DISC SW.
TAHU-1
SDT
HP-68,70
30 AMP
DISC SW.
RP-36
SMOKE DETECTOR TEST
STATION. REFER TO
MECHANICAL DRAWINGS
FOR MORE INFORMATION.
WH-1-1
HP-58
30 AMP
DISC SW.
THERMOSTAT
(TYP)
T
CH-1-1
'RP'
J
1
WH-1
RP-32,34
30 AMP
DISC SW.
RP-5
RP-7
HP-3
HP-23
RP-3
RP-1
RP-9
RP-18
RP-3
RP-1
WP
GFCI
HP-29
E-2.1
GROUND FLOOR
POWER PLAN
N.N.
K.F.
1
GROUND FLOOR POWER PLAN
SCALE: 1/4" = 1'-0"
DATE:02-03-20
ISSUE/REVISION:ISSUED TO CLIENT
PROJECT NAME:
LOCATION
PROJECT INFORMATION:
DRAWING NUMBER
DRAWING TITLE
ENGINEER'S SIGNATURE
BELMONT PROPERTIESTHE PRIME @LYNDHURST
205-211STUYVESANT AVE.
TOWNSHIP OFLYNDHUSRT
BERGEN COUNTY, NJ
PROJECT #:
PROJECT DATE:
DRAWN BY:
CHECKED BY:
19108
02-03-20
ustomesigning &
Engineering, PC153 East Main St.
Rockaway, NJ 07866Tel: 973-784-4258
www.customdande.com
KENNETH A. FULLER, P.E., LEED APN.J. LICENSE NUMBER: 24GE03240100
EXPIRES 4-30-20COA NUMBER 24GA28170100
EXPIRES 8-31-20
HOME RUN.
DUPLEX RECEPTACLE @ 18" A.F.F. U.N.O. MOUNTED AT
CODE HEIGHT.
GROUND FAULT PROTECTED DUPLEX RECEPTACLE.
SYMBOL DESCRIPTION
ELECTRICAL LEGEND
JUNCTION BOX.
GROUND FAULT PROTECTED QUAD RECEPTACLE.
LIGHT SWITCH.
ELECTRICAL PANEL.
DISCONNECT SWITCH.
DATA RECEPTACLE.
TELEPHONE RECEPTACLE.
QUAD RECEPTACLE @ 18" A.F.F. U.N.O. MOUNTED AT CODE
HEIGHT.
GFCI
GFCI
J
TELEPHONE / DATA COMBINATION RECEPTACLE.
S
(E) - EXISTING TO REMAIN.
(R) - EXISTING TO BE RELOCATED.
(N) - NEW FIXTURE.
WP - WEATHERPROOF
DIMMER SWITCH.
THREE WAY LIGHT SWITCH.
(4W - FOUR WAY SWITCH ).
S
3W
WALL MOUNTED OCCUPANCY SENSOR.
S
OS
OS
CEILING MOUNTED OCCUPANCY SENSOR.
NOTES
D
DEDICATED SIMPLEX RECEPTACLE.
HALF SWITCHED DUPLEX RECEPTACLE.
KEY NOTES:
TWO-WAY COMMUNICATION SYSTEM AT AREA OF REFUGE. G.C TO PROVIDE SIGNAGE
REQUIRED BY BUILDING CODES, ADA AND NFPA 101 REGULATIONS, TO ENSURE THE CALL
STATIONS AND SAFE REFUGE AREAS CAN BE READILY FOUND. CONTRACTOR TO VERIFY
POWER REQUIREMENTS AND LOCATION FOR COMMUNICATION SYSTEM PRIOR TO BID.
NOTES:
1. POWER BATHROOM EXHAUST FAN VIA UNSWITCHED LEG OF LIGHTING CIRCUIT.
PROVIDE SWITCH UNDER SAME WALL PLATE AS LOCAL LIGHT SWITCH.
2. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CODE, LOCAL CODE OR ANY OTHER AUTHORITY HAVING JURISDICTION
THEREOF.
1
UP
19r
DN
21r
UP
4"
T
2A-19
HP-19
WP
GFCI
GFCI
GFCI
CH
GFCI
CH
GFCI
1
GFCI
GFCI
GFCI
CH
GFCI
CH
GFCI
2A-7
CH
GFCI
GFCI
GFCI
1
GFCI
GFCI
GFCI
CH
GFCI
CH
GFCI
1
GFCI
GFCI
GFCI
GFCI
20A
PERPENDICULAR
OUTLET
CH-2-6
CH-2-6
30A
LARGE TANDEM
OUTLET
30A
LARGE TANDEM
OUTLET
30A
LARGE TANDEM
OUTLET
30A
LARGE TANDEM
OUTLET
P2-3-1
P2-3-2
P2-2-2
20A
PERPENDICULAR
OUTLET
P2-2-1
30A
LARGE TANDEM
OUTLET
P2-1-1
30A
LARGE TANDEM
OUTLET
P2-1-2
20A
PERPENDICULAR
OUTLET
T
T
T
T
P2-2-1
P2-2-2
P2-1-1
P2-1-2
THERMOSTAT
(TYP)
P2-4-2
P2-4-3
'2B'
'2A'
'2C'
2B-8,10
2B-12,14
2A-12,14
2A-8,10
2C-12,14
2C-8,10
T
T
T
T
T
T
T
T
T
T
P2-3-1
P2-4-1
P2-4-1
P2-4-2
CH-2-4
CH-2-4
P2-4-3
CH-2-5
CH-2-5
P2-3-2
CH-2-3
CH-2-3
CH-2-2
CH-2-1
CH-2-1
2A-20
30 AMP
DISC SW.
HP-60
30 AMP
DISC SW.
2B-20
30 AMP
DISC SW.
CH-2-2
2B-19
HP-72,74
HP-76,78
HP-80,82
HP-5
HP-7
HP-13
HP-15
HP-17
HP-17
HP-50
30 AMP
DISC SW
HP-48
30 AMP
DISC SW
HP-11HP-9
2A-3
2A-1
2A-13
2A-11
2A-21
2A-17
2A-5
2B-132B-11
2B-21
2B-17
2B-1
2B-3
2B-15
2A-15
2C-15
2C-17
2C-21
2C-1
2C-3
2C-5
2C-20
30 AMP
DISC SW.
2C -11
2C-13
2C-19
2B-5
2B-7
2C-7
2A-16,18
60 AMP
DISC SW.
2B-16,18
60 AMP
DISC SW.
2C-16,18
60 AMP
DISC SW.
HP-65,67
60 AMP
DISC SW.
S
CH
GFCI
2A-25
GFCI
2A-27
GFCI
2B-27
CH
GFCIGFCI
2C-272C-23
HP-25
S
S
2B-1
E-2.2
SECOND LEVEL
FLOOR POWER
PLAN
N.N.
K.F.
1
SECOND FLOOR POWER PLAN
SCALE: 1/4" = 1'-0"
DATE:02-03-20
ISSUE/REVISION:ISSUED TO CLIENT
PROJECT NAME:
LOCATION
PROJECT INFORMATION:
DRAWING NUMBER
DRAWING TITLE
ENGINEER'S SIGNATURE
BELMONT PROPERTIESTHE PRIME @LYNDHURST
205-211STUYVESANT AVE.
TOWNSHIP OFLYNDHUSRT
BERGEN COUNTY, NJ
PROJECT #:
PROJECT DATE:
DRAWN BY:
CHECKED BY:
19108
02-03-20
ustomesigning &
Engineering, PC153 East Main St.
Rockaway, NJ 07866Tel: 973-784-4258
www.customdande.com
KENNETH A. FULLER, P.E., LEED APN.J. LICENSE NUMBER: 24GE03240100
EXPIRES 4-30-20COA NUMBER 24GA28170100
EXPIRES 8-31-20
KEY NOTES:
1 RECEPTACLE FOR DISHWASHER TO BE IN ADJACENT CABINET AND BE ACCESSIBLE.
NOTES:
1. POWER BATHROOM EXHAUST FAN VIA UNSWITCHED LEG OF LIGHTING CIRCUIT.
PROVIDE SWITCH UNDER SAME WALL PLATE AS LOCAL LIGHT SWITCH.
2. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CODE, LOCAL CODE OR ANY OTHER AUTHORITY HAVING JURISDICTION
THEREOF.
HOME RUN.
DUPLEX RECEPTACLE @ 18" A.F.F. U.N.O. MOUNTED AT
CODE HEIGHT.
GROUND FAULT PROTECTED DUPLEX RECEPTACLE.
SYMBOL DESCRIPTION
ELECTRICAL LEGEND
JUNCTION BOX.
GROUND FAULT PROTECTED QUAD RECEPTACLE.
LIGHT SWITCH.
ELECTRICAL PANEL.
DISCONNECT SWITCH.
DATA RECEPTACLE.
TELEPHONE RECEPTACLE.
QUAD RECEPTACLE @ 18" A.F.F. U.N.O. MOUNTED AT CODE
HEIGHT.
GFCI
GFCI
J
TELEPHONE / DATA COMBINATION RECEPTACLE.
S
(E) - EXISTING TO REMAIN.
(R) - EXISTING TO BE RELOCATED.
(N) - NEW FIXTURE.
WP - WEATHERPROOF
DIMMER SWITCH.
THREE WAY LIGHT SWITCH.
(4W - FOUR WAY SWITCH ).
S
3W
WALL MOUNTED OCCUPANCY SENSOR.
S
OS
OS
CEILING MOUNTED OCCUPANCY SENSOR.
NOTES
D
DEDICATED SIMPLEX RECEPTACLE.
HALF SWITCHED DUPLEX RECEPTACLE.
DN
19r
UP
4"
RO
OF
HA
TC
H
T
3A-19
S
GFCI
GFCI
CH
GFCI
CH
GFCI
1
GFCI
GFCI
GFCI
CH
GFCI
CH
GFCI
3A-7
CH
GFCI
GFCI
GFCI
1
GFCI
GFCI
GFCI
CH
GFCI
CH
GFCI
1
GFCI
GFCI
GFCI
GFCI
20A
PERPENDICULAR
OUTLET
GFCI
1
3D-25
WP
GFCI
CU-1
HP-75,77,79
60 AMP WP
DISC SW.
WP/
GFCI
CH-3-6
CH-3-6
CH-3-4
CH-3-5
CH-3-1
CH-3-2
CH-3-3
GFCI
3D-20
30 AMP
DISC SW.
30A
LARGE TANDEM
OUTLET
20A
PERPENDICULAR
OUTLET
3A-12,14
3A-8,10
P3-1-1
P3-1-2
P3-2-2
20A
PERPENDICULAR
OUTLET
P3-2-1
30A
LARGE TANDEM
OUTLET
3B-8,10
3B-12,14
3B-20
30 AMP
DISC SW
3A-20
30 AMP
DISC SW
30A
LARGE TANDEM
OUTLET
P3-3-1
P3-3-2
3C-12,14
3C-8,10
3C-20
30 AMP
DISC SW
30A
LARGE TANDEM
OUTLET
20A
PERPENDICULAR
OUTLET
20A
PERPENDICULAR
OUTLET
P3-4-3
P3-4-1
3D-8,10
P3-4-2
3D-12,14
3D-24,26
3D-28
30 AMP
DISC SW.
HP-62
30 AMP
DISC SW.
T
T
T
T
T
T
T
T
T
T
T
T
T
T
P3-4-3
P3-4-1
P3-3-1
P3-3-2
P3-2-2
P3-2-1
P3-1-1
P3-1-2
THERMOSTAT
(TYP)
THERMOSTAT
(TYP)
P3-4-2
CH-3-4
CH-3-5
CH-3-3
CH-3-2
CH-3-1
HP-21
HP-73
3A-5
3A-1
'3A'
3A-3
3A-17
3A-15
3A-13
3A-11
3A-21
'3B'
3B-1
3B-33B-13
3B-11
3B-15
3B-17
3B-21
3B-7
3B-19
3B-5
3C-13
3C-19
3C-7
'3C'
3C-3
3C-5
3C-17
3C-21
3C-11
3C-15
3C-1
'3D'
3D-1
3D-3
3D-5
3D-15
3D-13 3D-11
3D-21
3D-17
3D-27
3D-7
3D-7
3A-16,18
60 AMP
DISC SW.
3B-16,18
60 AMP
DISC SW.
S
S
S
CH
GFCI
3A-25
CH
GFCI
3D-23
S
GFCI
3D-33
GFCI
3B-27
GFCI
3C-27
CH
GFCI
3C-25
GFCI
3A-27
3D-19
3C-16,18
60 AMP
DISC SW.
3D-16,18
60 AMP
DISC SW.
E-2.3
THIRD FLOOR
POWER PLAN
N.N.
K.F.
1
THIRD FLOOR POWER PLAN
SCALE: 1/4" = 1'-0"
DATE:02-03-20
ISSUE/REVISION:ISSUED TO CLIENT
PROJECT NAME:
LOCATION
PROJECT INFORMATION:
DRAWING NUMBER
DRAWING TITLE
ENGINEER'S SIGNATURE
BELMONT PROPERTIESTHE PRIME @LYNDHURST
205-211STUYVESANT AVE.
TOWNSHIP OFLYNDHUSRT
BERGEN COUNTY, NJ
PROJECT #:
PROJECT DATE:
DRAWN BY:
CHECKED BY:
19108
02-03-20
ustomesigning &
Engineering, PC153 East Main St.
Rockaway, NJ 07866Tel: 973-784-4258
www.customdande.com
KENNETH A. FULLER, P.E., LEED APN.J. LICENSE NUMBER: 24GE03240100
EXPIRES 4-30-20COA NUMBER 24GA28170100
EXPIRES 8-31-20
KEY NOTES:
1 RECEPTACLE FOR DISHWASHER TO BE IN ADJACENT CABINET AND BE ACCESSIBLE.
NOTES:
1. POWER BATHROOM EXHAUST FAN VIA UNSWITCHED LEG OF LIGHTING CIRCUIT. PROVIDE SWITCH UNDER SAME WALL PLATE AS
LOCAL LIGHT SWITCH.
2. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE, LOCAL CODE OR ANY OTHER
AUTHORITY HAVING JURISDICTION THEREOF.
HOME RUN.
DUPLEX RECEPTACLE @ 18" A.F.F. U.N.O. MOUNTED AT
CODE HEIGHT.
GROUND FAULT PROTECTED DUPLEX RECEPTACLE.
SYMBOL DESCRIPTION
ELECTRICAL LEGEND
JUNCTION BOX.
GROUND FAULT PROTECTED QUAD RECEPTACLE.
LIGHT SWITCH.
ELECTRICAL PANEL.
DISCONNECT SWITCH.
DATA RECEPTACLE.
TELEPHONE RECEPTACLE.
QUAD RECEPTACLE @ 18" A.F.F. U.N.O. MOUNTED AT CODE
HEIGHT.
GFCI
GFCI
J
TELEPHONE / DATA COMBINATION RECEPTACLE.
S
(E) - EXISTING TO REMAIN.
(R) - EXISTING TO BE RELOCATED.
(N) - NEW FIXTURE.
WP - WEATHERPROOF
DIMMER SWITCH.
THREE WAY LIGHT SWITCH.
(4W - FOUR WAY SWITCH ).
S
3W
WALL MOUNTED OCCUPANCY SENSOR.
S
OS
OS
CEILING MOUNTED OCCUPANCY SENSOR.
NOTES
D
DEDICATED SIMPLEX RECEPTACLE.
HALF SWITCHED DUPLEX RECEPTACLE.
MA
IN
TE
NA
NC
E
CL
OS
ET
U
NF
IN
IS
HE
D
BA
SE
ME
NT
A
RE
A
UP
16r
EL
EV
AT
OR
EQ
UIP
ME
NT
ST
AIR
filled area
filled area
EXIT
±8
'-8"
un
de
r de
cking
EL
EC
TR
IC
SE
RV
IC
ES
WA
TE
R
ME
TE
R
RO
OM
S
OS
S
S
HP-22
OS
OS
OS
S
OS
S
OS
HP-2
HP-2
HP-6
HP-6
HP-6
HP-2
HP-2
HP-2
HP-2
HP-22
HP-22
HP-22
··
EXIT
DATE:02-03-20
ISSUE/REVISION:ISSUED TO CLIENT
PROJECT NAME:
LOCATION
PROJECT INFORMATION:
DRAWING NUMBER
DRAWING TITLE
ENGINEER'S SIGNATURE
BELMONT PROPERTIESTHE PRIME @LYNDHURST
205-211STUYVESANT AVE.
TOWNSHIP OFLYNDHUSRT
BERGEN COUNTY, NJ
PROJECT #:
PROJECT DATE:
DRAWN BY:
CHECKED BY:
19108
02-03-20
ustomesigning &
Engineering, PC153 East Main St.
Rockaway, NJ 07866Tel: 973-784-4258
www.customdande.com
KENNETH A. FULLER, P.E., LEED APN.J. LICENSE NUMBER: 24GE03240100
EXPIRES 4-30-20COA NUMBER 24GA28170100
EXPIRES 8-31-20
E-3.0
BASEMENT
ELECTRICAL
LIGHTING PLAN
N.N.
K.F.
1
BASEMENT LIGHTING PLAN
SCALE: 1/4" = 1'-0"
LIGHTING NOTE:
NEC 2014 SECTION 700.12 (F)
ALL UNIT EQUIPMENT (EMERGENCY LIGHTING) SHALL BE WIRED AHEAD OF SWITCH
OR CONTROL OF NORMAL LIGHTING CIRCUIT SERVING THAT AREA. THE BRANCH
CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS
THAT SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY
LOCAL SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT SHALL BE
CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
IN A SEPARATE AND UNINTERRUPTED AREA SUPPLIED BY A MINIMUM OF THREE
NORMAL LIGHTING CIRCUITS, A SEPARATE BRANCH CIRCUIT FOR UNIT EQUIPMENT
SHALL BE FROM THE SAME PANELBOARD AS THAT OF THE NORMAL LIGHTING
CIRCUITS AND PROVIDED WITH A LOCK-ON FEATURE.
CO
VE
RIN
G A
T E
NT
RY
CO
VE
RIN
G A
T E
NT
RY
ST
AIR
CORRIDOR
EN
TR
Y
VE
ST
IB
UL
E
UT
IL
IT
Y
RE
TA
IL
T
EN
AN
T S
PA
CE
PA
RK
IN
G A
RE
A
HC
L
AV
HC
L
AV
EX
IT
EX
IT
EX
IT
EXIT
EXIT
EXIT
PA
RK
IN
G A
RE
A
S
S
S
3W
S
J J
EF-1-2EF-1-1
HP-22
RP-12
RP-2
RP-6
RP-4
RP-4
RP-2
HP-8
HP-8
HP-8
HP-8
HP-8
HP-8
HP-10
HP-6
HP-6
HP-6
HP-84
OS
OS
OS
S
3W
S
3W
S
3W
·
·
EXIT
DATE:02-03-20
ISSUE/REVISION:ISSUED TO CLIENT
PROJECT NAME:
LOCATION
PROJECT INFORMATION:
DRAWING NUMBER
DRAWING TITLE
ENGINEER'S SIGNATURE
BELMONT PROPERTIESTHE PRIME @LYNDHURST
205-211STUYVESANT AVE.
TOWNSHIP OFLYNDHUSRT
BERGEN COUNTY, NJ
PROJECT #:
PROJECT DATE:
DRAWN BY:
CHECKED BY:
19108
02-03-20
ustomesigning &
Engineering, PC153 East Main St.
Rockaway, NJ 07866Tel: 973-784-4258
www.customdande.com
KENNETH A. FULLER, P.E., LEED APN.J. LICENSE NUMBER: 24GE03240100
EXPIRES 4-30-20COA NUMBER 24GA28170100
EXPIRES 8-31-20
E-3.1
GROUND FLOOR
LIGHTING PLAN
N.N.
K.F.
1
GROUND FLOOR LIGHTING PLAN
SCALE: 1/4" = 1'-0"
LIGHTING NOTE:
NEC 2014 SECTION 700.12 (F)
ALL UNIT EQUIPMENT (EMERGENCY LIGHTING) SHALL BE WIRED AHEAD OF SWITCH
OR CONTROL OF NORMAL LIGHTING CIRCUIT SERVING THAT AREA. THE BRANCH
CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS
THAT SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY
LOCAL SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT SHALL BE
CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
IN A SEPARATE AND UNINTERRUPTED AREA SUPPLIED BY A MINIMUM OF THREE
NORMAL LIGHTING CIRCUITS, A SEPARATE BRANCH CIRCUIT FOR UNIT EQUIPMENT
SHALL BE FROM THE SAME PANELBOARD AS THAT OF THE NORMAL LIGHTING
CIRCUITS AND PROVIDED WITH A LOCK-ON FEATURE.
UP
19r
DN
21r
LO
UN
GE
A
RE
A
GY
M A
RE
A
UP
4"
HC
L
AV
HC
L
AV
WO
ME
N'S
ME
N'S
DIN
IN
G A
RE
A
OP
TIO
NA
L
ST
OR
AG
E /
ME
CH
AN
IC
AL
KIT
CH
EN
CO
VE
RE
D B
AL
CO
NY
BE
DR
OO
M
KIT
CH
EN
LIV
IN
G A
RE
A
DIN
IN
G A
RE
A
OP
TIO
NA
L
HA
LL
LIGHT WELL
BA
TH
ST
AIR
LIV
IN
G A
RE
A
HA
LL
KIT
CH
EN
BA
TH
KIT
CH
EN
BE
DR
OO
M
DIN
IN
G A
RE
A
LIV
IN
G A
RE
A
CL
OS
HA
LL
OP
TIO
NA
L
CL
OS
BA
TH
HA
LL
BE
DR
OO
M
COMMON
CORRIDOR
UN
IT
2A
UN
IT
2B
UN
IT
2C
EXIT
EX
IT
EX
IT
CL
OS
S
S
S
S
S
S
S
S
S
S S
S
S
S
S
S
S
S
S
S
S
S
S
3W
S
3W
3W
S
3W
S
S
S
S
S
J
J
J
J
S
3W
S
3W
J
EF-2-3
EF-2-2
EF-2-1
EF-2-5
EF-2-4
2B-6
2B-4
2B-4
2B-2
2B-2
2B-2
2B-2
HP-22
HP-24
HP-24
HP-24
HP-14
HP-16
HP-26
HP-26
HP-18
HP-18
HP-6
HP-14
HP-26
HP-26
HP-6
HP-6
2C-2
2C-2
2C-2
2C-4
2C-4
2C-6
2A-2
2A-2
2A-2
2A-4
2A-4
2A-6
S
S
2B-2
S
S
2A-2
S
S
HP-18
HP-20
S
AUX. FAN
(TYP)
2A-2
S
HP-14
KF-2-1
KF-2-2
S
2B-2
KF-2-3
S
2C-2
KF-2-4
··
EXIT
DATE:02-03-20
ISSUE/REVISION:ISSUED TO CLIENT
PROJECT NAME:
LOCATION
PROJECT INFORMATION:
DRAWING NUMBER
DRAWING TITLE
ENGINEER'S SIGNATURE
BELMONT PROPERTIESTHE PRIME @LYNDHURST
205-211STUYVESANT AVE.
TOWNSHIP OFLYNDHUSRT
BERGEN COUNTY, NJ
PROJECT #:
PROJECT DATE:
DRAWN BY:
CHECKED BY:
19108
02-03-20
ustomesigning &
Engineering, PC153 East Main St.
Rockaway, NJ 07866Tel: 973-784-4258
www.customdande.com
KENNETH A. FULLER, P.E., LEED APN.J. LICENSE NUMBER: 24GE03240100
EXPIRES 4-30-20COA NUMBER 24GA28170100
EXPIRES 8-31-20
E-3.2
SECOND FLOOR
LIGHTING PLAN
N.N.
K.F.
1
SECOND FLOOR LIGHTING PLAN
SCALE: 1/4" = 1'-0"
LIGHTING NOTE:
NEC 2014 SECTION 700.12 (F)
ALL UNIT EQUIPMENT (EMERGENCY LIGHTING) SHALL BE WIRED AHEAD OF SWITCH
OR CONTROL OF NORMAL LIGHTING CIRCUIT SERVING THAT AREA. THE BRANCH
CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS
THAT SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY
LOCAL SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT SHALL BE
CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
IN A SEPARATE AND UNINTERRUPTED AREA SUPPLIED BY A MINIMUM OF THREE
NORMAL LIGHTING CIRCUITS, A SEPARATE BRANCH CIRCUIT FOR UNIT EQUIPMENT
SHALL BE FROM THE SAME PANELBOARD AS THAT OF THE NORMAL LIGHTING
CIRCUITS AND PROVIDED WITH A LOCK-ON FEATURE.
BE
DR
OO
M
DN
19r
BA
TH
GU
ES
T
BA
TH
CL
OS
BE
DR
OO
M
HA
LL
LIV
IN
G A
RE
A
DIN
IN
G A
RE
A
OP
TIO
NA
L
KIT
CH
EN
UP
4"
RO
OF
HA
TC
H
UN
IT
3D
CO
VE
RE
D B
AL
CO
NY
EXIT
DIN
IN
G A
RE
A
OP
TIO
NA
L
ST
OR
AG
E /
ME
CH
AN
IC
AL
BE
DR
OO
M
KIT
CH
EN
LIV
IN
G A
RE
A
DIN
IN
G A
RE
A
OP
TIO
NA
L
HA
LL
LIGHT WELL
BA
TH
ST
AIR
CL
OS
LIV
IN
G A
RE
A
HA
LL
BA
TH
BE
DR
OO
M
DIN
IN
G A
RE
A
LIV
IN
G A
RE
A
CL
OS
HA
LL
OP
TIO
NA
L
CL
OS
BA
TH
HA
LL
BE
DR
OO
M
COMMON
CORRIDOR
UN
IT
2A
UN
IT
2B
UN
IT
2C
9'-0"
ceiling
9'-0"
ceiling
9'-0"
ceiling
9'-0"
ceiling
9'-0"
ceiling
9'-2"
ceiling
KIT
CH
EN
KIT
CH
EN
3D-2
S
3W
S
S
S
S
S
S
S
S
S
S
S S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
3W
S
3W
S
3W
S
3W
S
S
S
S
S
J
J
J
J
J
S
3W
S
3W
HP-22
3D-6
3D-4
3D-4
3D-4
3D-22
3D-6
3D-2
3D-32
3D-32
HP-6
HP-6
HP-6
HP-24
3C-4
3C-4
3C-2
3C-2
3C-2
3C-6
3B-4
3B-4
3B-2
3B-2
3B-2
3B-2
3B-6
3A-4
3A-4
3A-2
3A-2
3A-2
3A-6
HP-24
HP-24
S
3B-2
S
S
S
S
S
S
3A-2
S
3A-2
S
3B-2
KF-3-2
KF-3-1
S
KF-3-3
3C-2
EF-3-3
EF-3-2
EF-3-1
EF-3-5
EF-3-4
KF-3-4
S
3D-32
··
EXIT
DATE:02-03-20
ISSUE/REVISION:ISSUED TO CLIENT
PROJECT NAME:
LOCATION
PROJECT INFORMATION:
DRAWING NUMBER
DRAWING TITLE
ENGINEER'S SIGNATURE
BELMONT PROPERTIESTHE PRIME @LYNDHURST
205-211STUYVESANT AVE.
TOWNSHIP OFLYNDHUSRT
BERGEN COUNTY, NJ
PROJECT #:
PROJECT DATE:
DRAWN BY:
CHECKED BY:
19108
02-03-20
ustomesigning &
Engineering, PC153 East Main St.
Rockaway, NJ 07866Tel: 973-784-4258
www.customdande.com
KENNETH A. FULLER, P.E., LEED APN.J. LICENSE NUMBER: 24GE03240100
EXPIRES 4-30-20COA NUMBER 24GA28170100
EXPIRES 8-31-20
E-3.3
THIRD FLOOR
LIGHTING PLAN
N.N.
K.F.
1
THIRD FLOOR LIGHTING PLAN
SCALE: 1/4" = 1'-0"
LIGHTING NOTE:
NEC 2014 SECTION 700.12 (F)
ALL UNIT EQUIPMENT (EMERGENCY LIGHTING) SHALL BE WIRED AHEAD OF SWITCH
OR CONTROL OF NORMAL LIGHTING CIRCUIT SERVING THAT AREA. THE BRANCH
CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS
THAT SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY
LOCAL SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT SHALL BE
CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
IN A SEPARATE AND UNINTERRUPTED AREA SUPPLIED BY A MINIMUM OF THREE
NORMAL LIGHTING CIRCUITS, A SEPARATE BRANCH CIRCUIT FOR UNIT EQUIPMENT
SHALL BE FROM THE SAME PANELBOARD AS THAT OF THE NORMAL LIGHTING
CIRCUITS AND PROVIDED WITH A LOCK-ON FEATURE.
ELECTRIC SERVICE ROOMEXTERIOR
TC
NEW WIRING
(4)#1 + #6 GRD.
IN A 1-1/2" CONDUIT
BASEMENT
100A
M
(HOUSE PANEL)
SQUARE D
ELECTRIC PANEL
120/208V 3Ø 4W
225 AMP / 200 MCB
PANEL
"RP"
(RETAIL PANEL)
ELECTRIC PANEL
SQUARE D
120/208V 3Ø 4W
225 AMP / 200 MCB
TENANT SPACE
INCREASE FEEDER SIZE TO
(4) #1/0 + #6 GRD AL
SER CABLE FOR ALL
FEEDER LENGTHS OF
200'-0" AND GREATER.
(4)#3/0 + #3 GRD.
IN A 2" CONDUIT
AHU-1
(3) #3 + #8 GRD.
IN A 1-1/4" CONDUIT
CU-1
WITH (3) #8 + #10 GRD.
IN A 1" CONDUIT
WITH WP/GFCI OUTLET
CH-1-1,2, CH-2-4,5,6, & CH-3-6
EACH WITH 30AMP DISC. SW.
EACH WITH (2)#12 + #12 GRD.
EACH IN A 3/4" CONDUIT
TIMECLOCK -
TORK DLC-400BP
(7) DAY CALENDAR
(4 POLE 10 AMP)
PANEL
"HP"
200
AMPS
MAIN BREAKER
1000 AMP
100A
100A
100A
100A
M
M
M
M
EATON MODULAR METER CENTER,1200 AMP,
120/208V, 3Ø, 4W , 42KAIC. CAT. (2 SOCKET)
# 3MM212R/ (4 SOCKET) 3MM412R
ALL DWELLING UNIT METERS SHALL BE
SIZED FOR 100A MAXIMUM SERVICE SIZE
TO EXISTING
ELECTRIC
SERVICE
M
200A
3P
HOUSE
PANEL
(3 SETS)
(4) #400 KCMIL + #2/0 GRD.
IN A 3-1/2" CONDUIT
L.L
M
M
100A
100A
GROUND FLOOR
ELECTRIC PANEL
SQUARE D
120/208V 3Ø 4W
125 AMP / 100 MCB
(TYP. OF 3)
RETAIL
PANEL
200A
3P
TC
TIMECLOCK -
TORK DLC-400BP
(7) DAY CALENDAR
(4 POLE 10 AMP)
WH-B & WH-1-1
EACH WITH (2)#10 + #12 GRD.
EACH IN A 3/4" CONDUIT
M
RETAIL SPACE
2ND FLOOR
PANEL
"2A"
3RD FLOOR
TENANT SPACE
ELECTRIC PANEL
SQUARE D
120/208V 3Ø 4W
125 AMP / 100 MCB
(TYP. OF 4)
PANEL
"3A"
NEW WIRING
(4)#1 + #6 GRD.
IN A 1-1/2" CONDUIT
INCREASE FEEDER SIZE TO
(4) #1/0 + #6 GRD AL
SER CABLE FOR ALL
FEEDER LENGTHS OF
200'-0" AND GREATER.
NEW WIRING
(4) #3/0 + #4 GRD.
IN A 2" CONDUIT
200
AMPS
100
AMPS
100
AMPS
E-4.0
ELECTRICAL
ONE-LINE
DIAGRAM
N.N.
K.F.
1
ELECTRICAL ONE-LINE DIAGRAM
SCALE: NONE
DATE:02-03-20
ISSUE/REVISION:ISSUED TO CLIENT
PROJECT NAME:
LOCATION
PROJECT INFORMATION:
DRAWING NUMBER
DRAWING TITLE
ENGINEER'S SIGNATURE
BELMONT PROPERTIESTHE PRIME @LYNDHURST
205-211STUYVESANT AVE.
TOWNSHIP OFLYNDHUSRT
BERGEN COUNTY, NJ
PROJECT #:
PROJECT DATE:
DRAWN BY:
CHECKED BY:
19108
02-03-20
ustomesigning &
Engineering, PC153 East Main St.
Rockaway, NJ 07866Tel: 973-784-4258
www.customdande.com
KENNETH A. FULLER, P.E., LEED APN.J. LICENSE NUMBER: 24GE03240100
EXPIRES 4-30-20COA NUMBER 24GA28170100
EXPIRES 8-31-20
SERVICE EQUIPMENT
3/0 AWG Cu GROUNDING ELECTRODE
CONDUCTOR
CONCRETE ENCASED
ELECTRODE
GROUND RING NO
LESS THAN 2 AWG
Cu
4 AWG Cu BONDING
JUMPER
COPPER BONDING JUMPER
NO LESS THAN GROUND RING
CONDUCTOR SIZE
4 AWG Cu BONDING JUMPER
BUILDING STEEL
UNDERGROUND METAL
WATER PIPE
GROUND ROD
6 AWG Cu BONDING JUMPER
NEUTRAL
SERVICE ENTRANCE
CONDUCTORS
METAL GAS
PIPING.
4 AWG Cu BONDING JUMPER
2
SERVICE GROUNDING DETAIL
SCALE: N.T.S
E-4.1
ELECTRICAL
PANEL
SCHEDULES
N.N.
K.F.
1
ELECTRICAL PANEL SCHEDULES & LOAD SUMMARY
SCALE: NONE
DATE:02-03-20
ISSUE/REVISION:ISSUED TO CLIENT
PROJECT NAME:
LOCATION
PROJECT INFORMATION:
DRAWING NUMBER
DRAWING TITLE
ENGINEER'S SIGNATURE
BELMONT PROPERTIESTHE PRIME @LYNDHURST
205-211STUYVESANT AVE.
TOWNSHIP OFLYNDHUSRT
BERGEN COUNTY, NJ
PROJECT #:
PROJECT DATE:
DRAWN BY:
CHECKED BY:
19108
02-03-20
ustomesigning &
Engineering, PC153 East Main St.
Rockaway, NJ 07866Tel: 973-784-4258
www.customdande.com
KENNETH A. FULLER, P.E., LEED APN.J. LICENSE NUMBER: 24GE03240100
EXPIRES 4-30-20COA NUMBER 24GA28170100
EXPIRES 8-31-20