Dual Maximum VAV Box Controls -...

44
Dual Maximum VAV Box Controls Steven T. Taylor, PE FASHRAE Taylor Engineering LLC staylor@taylorengineering.com ASHRAE Golden Gate Chapter November 13, 2014

Transcript of Dual Maximum VAV Box Controls -...

Dual Maximum VAV Box Controls

Steven T. Taylor, PE FASHRAETaylor Engineering LLCstaylor@taylor‐engineering.com

ASHRAE Golden Gate ChapterNovember 13, 2014

Agenda

VAV Box basics• Sizing VAV Boxes• How low can you go?

VAV Box control logic• Conventional VAV box control logic• “Dual Maximum” control logic• Non-complying dual maximum control logic• Determining setpoints

How well does “Dual Maximum” logic work?• ASHRAE RP-1515 Results

VAV Box Sizing

Oversized box• Less pressure drop• Less noise• Higher box min → more reheat, higher fan energy• Cost more

Undersized box• Higher pressure drop• More noise• Lower box min → less reheat, lower fan energy

VAV Box Sizing: LCC Analysis

Compared ∆TP from 0.3” to 0.8” Low rise office building Sensitivity Analysis

• Climate• Loads• operating schedules• Utility rates• Load calc’ (aggressive, conservative)• 8 bit versus 10 bit A/D converter• SAT (50°F-60°F), SAT reset, SP reset

RESULT: Size VAV Boxes for ~0.5” ∆TP

VPSPTP

VAV Box Sizing: Sample Calc.

Nominal size

Inlet dia. (in.)

Outlet width (in.)

Outlet height

(in.)

∆SP(in.

w.g.)*

∆VP (in.

w.g.)

∆TP(in.

w.g.)

Max CFM

Radiated NC*

4 4 12 8 0.08 0.42 0.50 230 21 5 5 12 8 0.15 0.35 0.50 333 20 6 6 12 8 0.24 0.25 0.49 425 21 7 7 12 10 0.25 0.25 0.50 580 20 8 8 12 10 0.33 0.17 0.50 675 22 9 9 14 13 0.27 0.23 0.50 930 17 10 10 14 13 0.32 0.18 0.50 1100 19 12 12 16 15 0.32 0.17 0.49 1560 19 14 14 20 18 0.31 0.19 0.50 2130 18 16 16 24 18 0.32 0.18 0.50 2730 22

*From selection software using ARI 885-95 and assuming inlet SP = 1.5 and outlet SP = 0.25

What is the lowest minimum?

• Function of–DDC Controller: What’s the lowest

controllable velocity pressure (VP) signal?• DDC velocity pressure transducer accuracy• A/D converter resolution (bits)

–VAV Box: • Amplification factor, F • Inlet size, D

4

2

minminDFPMCFM

FVPFPM min

min 4005

Why Not Just Look in the VAV Box Catalog?

Equates to ~0.03” minimum VP and about 30% of design CFM for typical box selections

Why Not Just Look in the VAV Box Catalog?Still too high

Good Advice! NEVER use Box manufacturer’s minimums!

Controllable VP Minimum

Some manufacturers list the range in catalog

Some you have to ask Most available from ASHRAE RP 1353 and PG&E

research projects (see references)• Almost all controllers ± 10% at 0.003”

Specify allowable setpoint ≤ 0.004”

Typical DDC Performance

Highly accurate down to about 50 CFM (0.003”)

-40

-30

-20

-10

0

10

20

30

0 100 200 300 400 500 600 700 800Reference Flow [cfm]

Flo

w E

rror

[cfm

]

Nailor VAV BoxTitus VAV Box“A”“B”

Flow Probe Amplification

229

358

515

70291611601432

2062

3665

7000

2806

4 inch

5 inch

6 inch

7 inch8 inch9 inch

10 inch

12 inch

14 inch16 inch

22 inch

10

100

1000

10000

0.01 0.1 1Flow Probe Velocity Pressure Signal (Inches W.G.)

CFM

CFM

@ One Inch Signal

Inlet Size

24005

KAF

F = amplification factorK = actual flow in CFM at flow probeoutput of 1.0” w.c.A = is the nominal inlet area in ft2

K

Typical Flow Probe PerformanceV

elo

city

[fp

m]

Flow Grid Pressure [iwc]1.5.1.05.01.005.001

50

100

200

500

1000

2000

6.2~slopeF Specify ≥2.0

Sample Controllable Minimum

FVPFPM min

min 40053.2

004.04005170

Box Inlet Diameter

Maximum CFM at 0.5 in.w.g. 

pressure drop

Minimum CFM at 0.004 in.w.g. sensor 

reading

Minimum Ratio at Highest 

Maximum, %

Minimum Ratio at lowest 

Maximum, %6 425 33 7.8% ‐8 715 58 8.1% 13.6%10 1,100 91 8.3% 12.7%12 1,560 130 8.3% 11.8%14 2,130 177 8.3% 11.3%16 2,730 232 8.5% 10.9%

4

2

minminDFPMCFM

VAV Reheat Control

Q: Why do some buildings use 3 -5 times as much energy as others?

0

500

1,000

1,500

2,000

2,500

Mar-02 Apr-02 May-02 Jun-02 Jul-02

Boi

ler I

nput

(Btu

/sf) Site #1

Site #2

A: Reheat

Conventional VAV Control

Conventional VAV Box Minimum Setpoint

No less than larger of:• Minimum ventilation rate

Per Title 24• Controller minimum

Not an issue for conventional logic – see discussion above• Limit “dumping”

Not an issue – see RP-1515 results below• Limit stratification

No more than 20°F above space temperature (~≤95°F) per Standard 90.1

No more than larger of:• 30% of cooling maximum

Per Title 24/Standard 90.1. Now only allowed for non-DDC controls

• Minimum ventilation rate

Title 24 VAV Control Requirementfor zones with DDC

Dual Maximum Controlper Title 24 and Standard 90.1 for DDC

Dual Maximum Logic in Action

Start heating, increase DAT setpoint

At 50% Heat, start increasing airflow

Sort of Dual Maximum Control (Found in some configurable controllers)

T-24

Sort of Dual Maximum Control (Found in some configurable controllers)

Title 24

VAV Box Dual Maximum Control Setpoints per Title 24 and Standard 90.1

Minimum: 1. No less than larger of:

Minimum ventilation rate for the zone Controller minimum

2. No more than 20% of cooling maximum

Heating Maximum:1. No less than larger of:

Minimum Limit stratification - ≤20°F SAT above space temperature (≤~90°F to 95°F)

2. No more than 50% of cooling maximum Always use Option 1 above

• Do not use code maximum just because it’s legal!• Avoid using %-of-cooling-maximum setpoints – boxes are

usually oversized!

COOL MIN  HEATVR‐101 12 1035 135 260VR‐102 10 810 90 230VR‐103 6 210 50 50

MARK INLET SIZE

DESIGN CFM

What about Standard 62.1 Multiple Spaces compliance?

Oakland Office - VAV System with Outdoor Air Economizer

How Well Does “Dual Max” Logic Actually Work?

RP-1515 results…

RP 1515, "Thermal and Air Quality Acceptability in Buildings that Reduce Energy by Reducing Minimum Airflow from Overhead Diffusers"

Objectives Measure energy savings & validate simulations Identify comfort issues that may occur at low flow

Funding California Energy Commission - PIER ASHRAE UC Berkeley - Center for the Built EnvironmentResearch Team UC Berkeley Taylor Engineering Price Industries

Method Field Study in 7 buildings Background survey “Right now” survey matched to zone trends Energy monitoring

Laboratory Study Air distribution for various diffuser types

Yahoo! Sunnyvale Campus

1073 Zones 3700 Occupants Plaque face diffusers

800 Ferry Building

22 Zones Perforated Diffuser

with blades in face

Measured flow fractions: Yahoo campus

0 20 40 60 80 100

0.00

0.05

0.10

0.15

Warm Season All Occupied Hours

Flow Fraction [%]

Den

sity

Low Minimum30% Minimum

0 20 40 60 80 100

0.00

0.05

0.10

0.15

Cool Season All Occupied Hours

Flow Fraction [%]

Den

sity

Low Minimum30% Minimum

Total Electricity Usage

Energy Savings

Occupant Comfort Survey

Questions• When the logic changed from conventional

(High minimum) to Dual Maximum (Low minimum): Did occupants become less comfortable? Was their sense of air movement stronger due to

“dumping”?

Approach• 3 surveys:

Yahoo warm and cool seasons 800 Ferry building warm season

• 3 – 4 weeks of surveying each season• Switched between high and low minimum

operation in the middle of each survey period

• Surveys administered 3 times/day About 10,000 responses received

% Dissatisfied peopleHIGH

ConventionalLOW

Dual Maximum

800 Ferry Building 27.3% 12.5%

Yahoo! cool season 8.7% 9.4%

Yahoo! warm season 20.1% 10.3%

249

1408

681

463

1793 766

0.0%

5.0%

10.0%

15.0%

20.0%

25.0%

30.0%

800 Ferry Building Yahoo! Cool season Yahoo! Warm season

% dissatisfie

d of peo

ple

"How satisfied are you with the temperature in your workspace?“

HIGH min flow rate LOW min flow rate

Thermal sensation distribution (Yahoo! warm season)

Loads are very low!

0.2 0.5 1 CFM/FT2 at 20˚F ∆T

140 Zones, 2 buildings, 1 warm month (Sept)

What happens when load is less than airflow minimum?

Actual Required CFM

Conventional Logic

Dual Max Logic

Air temperature(800 Ferry building)

09/

22

09/

23

09/

26

09/

27

09/

28

09/

29

09/

30

10/

03

10/

04

10/

05

10/

06

10/

07

10/

10

10/

11

10/

12

10/

13

10/

14

10/

17

10/

18

10/

19

10/

20

60

65

70

75

80

85

Dates

zone

tem

pera

ture

[F]

1.4 2 1.8 1.5 1.6 1.5 1.4 1.8 1.6 1.5 2 0.89 1.6 1.5 1.1 1.9 1.1 1.4 1.3 1.2 2.172 72 71 71 72 71 71 71 70 71 71 72 73 74 74 73 74 74 75 75 7314 27 23 35 45 36 35 41 47 34 65 23 30 51 45 64 25 37 67 27 48

sdMean

N

HIGH minimum flow rateLOW minimum flow rate

High flow: average Tair = 71.2ºF Low flow: average Tair = 73.3ºF

How about Drafts?(800 Ferry building)

Perceived air quality

CBE background survey results

Price Lab Tests

Perforated diffusers with blades in the neck, Cooling Mode.

Results:• Negligible impact on ADPI – all near 1• Negligible impact on ACE – all near 1

Dual Maximum VAV Box Logic Summary

Title 24 requires Dual Maximum logic for VAV zones with DDC Setpoints

• Set minimum and heating-maximum setpoints as low as possible Minimum allowed by controls is seldom a factor if box properly sized Do not use maximum allowed by T-24 just because it is legal

Cost impact• Requires discharge temperature sensor

This is nice for diagnostics anyway• Usually requires programmable zone controller

Configurable controller programming should soon catch up

Performance• Thermal comfort improves with low flow operation• Dumping & draft are not an issue at low flow• Energy savings are significant and similar to simulation predictions

Bibliography

Taylor S., Stein J.; “Sizing VAV Boxes”, ASHRAE Journal, March 2004

Dickerhoff D., Stein J.; “Stability and Accuracy of VAV Terminal Units at Low Flow”, PG&E 0514, http://www.etcc-ca.com/reports/stability-and-accuracy-vav-terminal-units-low-flow

Lui R., Wen J.; Stability and Accuracy of VAV Box Control at Low Flows”, ASHRAE 1353-RP

Taylor S. “Dual Maximum VAV Box Logic”, ASHRAE Journal, December 2012

Questions?

Steve [email protected]