Dse701 mk11 data sheet

2
The DSE701 MKII controller can be user-configured for Auto or Manual Start operation using the DSE Configuration Suite Lite PC Software. Alternatively the controller can be ordered pre-configured. The DSE701 MKII offers an excellent range of engine monitoring and protection features. The module offers inputs to monitor low oil pressure, high engine temperature and overspeed and the manual start version also has a user-defined auxiliary input. Auto Start versions also include an input option for a start signal from a remote location. When the module detects any of the above faults it will automatically shut down the engine. The module also has the capability to monitor battery charging by utilising the WL terminal on the charge alternator. On detecting a battery charging fault, it will light the warning LED on the front panel. The Auto Start version can be user-configured for Manual Start operation and the Manual Start version can be user-configured for Auto Start operation. DSE701 MKII MANUAL AND AUTO START CONTROL MODULE DSEGenset ® 1ph 1 - PRE-HEAT OUTPUT REMOTE START ON AUTO START/AUX INPUT ON MANUAL START LOP SWITCH TEMP SWITCH DC POWER SUPPLY 8-35V FUEL & CRANK OUTPUTS CHARGE FAIL GENERATOR SPEED SENSING ISSUE 1 D + W/L COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY OF GEN-SET APPLICATIONS 7 OTHER DSE701 MKII - FEATURES ENVIRONMENTAL TESTING STANDARDS ELECTRO-MAGNETIC COMPATIBILITY BS EN 61000-6-2 EMC Generic Immunity Standard for the Industrial Environment BS EN 61000-6-4 EMC Generic Emission Standard for the Industrial Environment ELECTRICAL SAFETY BS EN 60950 Safety of Information Technology Equipment, including Electrical Business Equipment TEMPERATURE BS EN 60068-2-1 Ab/Ae Cold Test -30 o C BS EN 60068-2-2 Bb/Be Dry Heat +70 o C VIBRATION BS EN 60068-2-6 Ten sweeps in each of three major axes 5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn HUMIDITY BS EN 60068-2-30 Db Damp Heat Cyclic 20/55 o C @ 95% RH 48 Hours BS EN 60068-2-78 Cab Damp Heat Static 40 o C @ 93% RH 48 Hours SHOCK BS EN 60068-2-27 Three shocks in each of three major axes 15 gn in 11 mS PC DSE 813 COMMUNICATION MAGNETIC PICK-UP FREQUENCY

description

http://www.esgon-ce.es/files/Deep/dse701-mk11-data-sheet.pdf

Transcript of Dse701 mk11 data sheet

Page 1: Dse701 mk11 data sheet

The DSE701 MKII controller can beuser-configured for Auto or ManualStart operation using the DSEConfiguration Suite Lite PC Software.Alternatively the controller can beordered pre-configured. TheDSE701 MKII offers an excellentrange of engine monitoring andprotection features.

The module offers inputs to monitorlow oil pressure, high enginetemperature and overspeed andthe manual start version also has auser-defined auxiliary input. AutoStart versions also include an inputoption for a start signal from aremote location.

When the module detects any ofthe above faults it will automaticallyshut down the engine.

The module also has the capabilityto monitor battery charging byutilising the WL terminal on thecharge alternator. On detecting abattery charging fault, it will lightthe warning LED on the front panel.

The Auto Start version can be user-configured for Manual Startoperation and the Manual Startversion can be user-configured forAuto Start operation.

DSE701 MKIIMANUAL AND AUTO START CONTROL MODULE

DSEGenset

®

1ph

1

-

PRE-HEATOUTPUT

REMOTE START ONAUTO START/AUX INPUT ON MANUAL START

LOP SWITCH TEMP SWITCH DC POWER SUPPLY 8-35V

FUEL & CRANKOUTPUTS

CHARGE FAILGENERATOR SPEEDSENSING

ISSUE 1

D +W/L

COMPREHENSIVE FEATURE LIST TO SUIT AWIDE VARIETY OF GEN-SET APPLICATIONS

7

OTHER

DSE701 MKII

-

FEATURES

ENVIRONMENTAL TESTING STANDARDS

ELECTRO-MAGNETIC COMPATIBILITYBS EN 61000-6-2EMC Generic Immunity Standard for the Industrial EnvironmentBS EN 61000-6-4EMC Generic Emission Standard for the Industrial Environment

ELECTRICAL SAFETYBS EN 60950Safety of Information Technology Equipment, including Electrical Business Equipment

TEMPERATUREBS EN 60068-2-1Ab/Ae Cold Test -30 oCBS EN 60068-2-2Bb/Be Dry Heat +70 oC

VIBRATIONBS EN 60068-2-6Ten sweeps in each of three major axes5 Hz to 8 Hz @ +/-7.5 mm, 8 Hz to 500 Hz @ 2 gn

HUMIDITYBS EN 60068-2-30Db Damp Heat Cyclic 20/55 oC@ 95% RH 48 HoursBS EN 60068-2-78Cab Damp Heat Static 40 oC@ 93% RH 48 Hours

SHOCKBS EN 60068-2-27Three shocks in each of three major axes15 gn in 11 mS

PC

DSE 813COMMUNICATION

MAGNETIC PICK-UP

FREQUENCY

Page 2: Dse701 mk11 data sheet

DEEP SEA ELECTRONICS PLC UKHighfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PHTELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303EMAIL [email protected] WEBSITE www.deepseaplc.com

DEEP SEA ELECTRONICS INC USA3230 Williams Avenue, Rockford, IL 61101-2668 USATELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708EMAIL [email protected] WEBSITE www.deepseausa.com

055-104/07/11 (1)

KEY FEATURES• Configurable Auto and Manual

Start versions• Remote start input available

(when in Auto Start mode)• Auxiliary shutdown input available

(when in Manual Start mode)• Engine monitoring and

protection• LED status indication• Automatic engine pre-heat• Overspeed protection• Front panel mounting

KEY BENEFITS• The DSE701 MKII comes

pre-configured for frequency(speed fensing) but can be user-configured for magnetic pick-up

• Uses DSE 813 USBCommunications Adaptor andDSE Configuration Suite Lite PCSoftware for simpleconfiguration

• Licence-free PC Software• User-friendly setup and fascia

layout

SPECIFICATION

DC SUPPLYCONTINUOUS VOLTAGE RATING 8 V to 35 V continuous

CRANKING DROPOUTSAble to survive 0 V for 50 mS, providing supply was at least 10 V before dropoutand supply recovers to 5 V. This is achieved without the need for internal batteries.

MAXIMUM OPERATING CURRENT26 mA at 12 V, 27 mA at 24 V

MAXIMUM STANDBY CURRENT20 mA at 12 V, 21 mA at 24 V

CHARGE/FAIL EXCITATION RANGE0 V to 35 V

OUTPUTSSTARTSolid state 1.2 A negative grounding terminal

RUNSolid state 1.2 A negative grounding terminal

PRE-HEATSolid state 1.2 A negative grounding terminal

GENERATORVOLTAGE RANGE 15 V - 333 V AC (L-N)

FREQUENCY RANGE3.5 Hz to 75 Hz

DIMENSIONSOVERALL72 mm x 72 mm x 38 mm 2.8” x 2.8” x 1.5”Excludes key switch

PANEL CUT-OUT68 mm x 68 mm2.7” x 2.7”

MAXIMUM PANEL THICKNESS8 mm0.3”

DSE701 MKIIMANUAL AND AUTO START CONTROL MODULE

®

DSEGenset

RELATED MATERIALSTITLE PART NO’SDSE701 MKII Installation Instructions 053-132DSE701 MKII Operator Manual 057-144DSE701 MKII Software Manual 057-145DSE813 USB Communications Adaptor Data Sheet 055-100

FEATURES

Registered in England & Wales No.01319649VAT No.316923457

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to changethe details shown on this data sheet without prior notice. The contents are intended for guidance only.