ds-dv-e-Diastar EN 0a... · 15 16-5 0- 40-3 2000 10 30 50 60 70 80 90 T (°C) 20 60 80 100 120 140...
Transcript of ds-dv-e-Diastar EN 0a... · 15 16-5 0- 40-3 2000 10 30 50 60 70 80 90 T (°C) 20 60 80 100 120 140...
1
e-Diastar
e-DIASTARElectric actuator EA-MT with diaphragm valve Type 514
(threaded sockets)
e-DIASTARElectric actuator EA-MT with diaphragm valve Type 515
(spigots)
Product description Actuator benefits/features
The e-DIASTAR system is based on the diaphragm valve Type
514 (threaded sockets) and Type 515 (spigots), on which the
electric actuator EA-MT is mounted. The diaphragm valve type
517 (flange) can be retrofitted after installation. The electric ac-
tuator EA-MT opens and closes the diaphragm valve fully auto-
matic.
The e-DIASTAR is used to regulate, close and control volume
flows automatically. Especially when transporting contamina-
ted, aggressive or abrasive media, this type of valve has decisi-
ve advantages thanks to its simple function and optimized con-
struction. Only the valve body and the replaceable diaphragm
are in contact with the medium.
• Position feedback (open/close)• Fully automatic end position teach-in• Integrated emergency manual override• Opional: integrated fail-safe unit with battery• Optional: cycle time control• Optional: extension of cycle time• Optional: motor current monitoring• Optinal: positioner 4-20mA with continous position
feedback»
Valve benefits/features• Full plastic valve without metal screws• No corrosion due to aggressive media/environment• Constant leak-tightness in the event of changes in
temperature without tightening screws• Plastic-appropriate, highly stable connection of upper
part and valve body by means of a buttress thread• Maximum flow and linear characteristic curves for
easier control• Diaphragm geometry for longer service life
Applications• Chemical process industry• Microelectronics• Water treatment• Cooling• Control applications
Possible flow media• Contaminated, solid or ultrapure media
2
Technical data
No. Description
1 Electric actuator EA-MT
2 Diaphragm valve
3 Assembly shells
4 Intermediate elements
Specifications diaphragm valve
Dimensions d32/DN25 and d63/DN50
Valve body materials Type 514 PVC-U, PVC-C, ABS, PP-H, PVDF
Retrofittable: PVDF-HP
Type 515 PVC-U, PVC-C, ABS, PP-H, PVDF
Retrofittable: PVDF-HP
Type 517 (only retrofit) PVC-U, PVC-C, PP-H, PVDF
Housing nut materials PPGF 30
Gasket/diaphragm materials EPDM, PTFE/EPDM, NBR, FKM, PTFE/FKM
Pressure levels DN25: PN10
DN50: PN6
Connections Type 514 Screw connection
Type 515 Spigot
Type 517 (only retrofit) Flange
Approvals ACS, FDA, DIBt, CE
1
3
2
4
3
Specifications EA-MTPower input max. 65 VA
Current (calculated) 0.55A at 100V
0.24A at 230V
2.5A at 24V
Power Supply AC: 100 – 230 V, 50/60 Hz
AC/DC: 24 V, 50/60 Hz
Supply voltage toler-ance -10%…+15%
Mechanical interface F05* (WS 11/14)
Duty cycle 50 %
Cycle time open/close DN25: ≈ 85 sec.
DN50: ≈ 130 sec.
Tested cycles (at 20 °C and Mdn) 5000
Weight 2.2 kg / 4.85 lbs
Actuating angle Multiturn
Protection class IP 65 (IP67)1) per EN 60529
Designed for wet & dry locations (NEC), designed for indoor use
(UV light may cause discoloration)
Pollution degree Operation: Pollution Level 3
Commissioning (open housing cover):
Only in controlled environments of pollution level 2
Overload protection Current/time dependent, resetting
Overvoltage category II
Fuse Internal: SMD fuse 2 A, not replaceable.
Req. external breakers on all live wires:
Rated Current: max. 16A
Trip Curve: C,
Standards Compliance: UL489, CSA C22.2 No. 5.1, IEC 60947-2
Ambient temp. -10 °C to +50 °C (14°F to 122°F)
Max. installation altitude 2000m above sea level (AMSL)
Feedback relays Mono-stable change-over contacts
Either max 6A @ 230VAC or 24VDC, no mixed voltage potentials allowed!
Recommended connecting cable AWG 18-16, UL/cUL AWM 4486 min. 125°C 1000V , outside diameter 8-13mm (cable glands),
4-9mm (DIN-connectors)
Allowable humidity Max. 90 % relative humidity, non-condensing
Housing material Housing: PP-GF (POLYFLAM, RPP 4225 CS1)
Inspection glass: Udel P-1700 (CL2611)
Assembly shells and intermediate elements: PPGF 30
1) When used with cable glands and vertical installation.
4
Dimensions
e-Diastar Type 514 with solvent cement sockets metric
d(mm)
DN(mm)
DN(inch)
D1(mm)
H(mm)
H1(mm)
H2 (mm)
H3 (mm)
H4(mm)
M(mm)
L (mm)
L1(mm)
32 25 1 58 286 30 20 256 121 M6 166 180
63 50 2 101 341 52.5 28.5 288.5 176 M8 266 180
d(mm)
DN(mm)
DN(inch)
L2(mm)
L3(mm)
L4(mm)
L5(mm)
L6 (mm)
L7(mm)
L8(mm)
D (mm)
32 25 1 25 122 33 97 82.5 16 49 108.5
63 50 2 45 122 33 97 82.5 16 49 168
5
e-Diastar Type 514 with solvent cement sockets BS
d(mm)
DN(mm)
DN(inch)
D1(mm)
H(mm)
H1(mm)
H2 (mm)
H3 (mm)
H4(mm)
M(mm)
L (mm)
L1(mm)
32 25 1 58 286 30 20 256 121 M6 170 180
63 50 2 101 341 52.5 28.5 288.5 176 M8 265 180
d(mm)
DN(mm)
DN(inch)
L2(mm)
L3(mm)
L4(mm)
L5(mm)
L6 (mm)
L7(mm)
L8(mm)
D (mm)
32 25 1 25 122 33 97 82.5 16 49 108.5
63 50 2 45 122 33 97 82.5 16 49 168
6
e-Diastar Type 514 with solvent cement sockets ASTM
d(mm)
DN(mm)
DN(inch)
D1(mm)
H(mm)
H1(mm)
H2 (mm)
H3 (mm)
H4(mm)
M(mm)
L (mm)
L1(mm)
32 25 1 58 286 30 20 256 121 M6 166 180
63 50 2 101 341 52.5 28.5 288.5 176 M8 266 180
d(mm)
DN(mm)
DN(inch)
L2(mm)
L3(mm)
L4(mm)
L5(mm)
L6 (mm)
L7(mm)
L8(mm)
D (mm)
32 25 1 25 122 33 97 82.5 16 49 108.5
63 50 2 45 122 33 97 82.5 16 49 168
7
e-Diastar Type 514 with solvent cement sockets JIS
d(mm)
DN(mm)
DN(inch)
D1(mm)
H(mm)
H1(mm)
H2 (mm)
H3 (mm)
H4(mm)
M(mm)
L (mm)
L1(mm)
32 25 1 58 286 30 20 256 121 M6 166 180
63 50 2 101 341 52.5 28.5 288.5 176 M8 266 180
d(mm)
DN(mm)
DN(inch)
L2(mm)
L3(mm)
L4(mm)
L5(mm)
L6 (mm)
L7(mm)
L8(mm)
D (mm)
32 25 1 25 122 33 97 82.5 16 49 108.5
63 50 2 45 122 33 97 82.5 16 49 168
8
e-Diastar Type 514 with fusion sockets metric
d(mm)
DN(mm)
DN(inch)
D1(mm)
H(mm)
H1(mm)
H2 (mm)
H3 (mm)
H4(mm)
M(mm)
L (mm)
L1(mm)
32 25 1 62 287 30 20 256 121 M6 166 180
63 50 2 105 341 52.5 28.5 288.5 176 M8 266 180
d(mm)
DN(mm)
DN(inch)
L2(mm)
L3(mm)
L4(mm)
L5(mm)
L6 (mm)
L7(mm)
L8(mm)
D (mm)
32 25 1 25 122 33 97 82.5 16 49 108.5
63 50 2 45 122 33 97 82.5 16 49 168
9
e-Diastar Type 515 with solvent cement spigots metric
d(mm)
DN(mm)
DN(inch)
H(mm)
H1(mm)
H2 (mm)
H3 (mm)
H4(mm)
M(mm)
L (mm)
L1(mm)
32 25 1 286 30 20 256 121 M6 154 180
63 50 2 341 52.5 28.5 288.5 176 M8 223 180
d(mm)
DN(mm)
DN(inch)
L2(mm)
L3(mm)
L4(mm)
L5(mm)
L6 (mm)
L7(mm)
L8(mm)
D (mm)
32 25 1 25 122 33 97 82.5 16 49 108.5
63 50 2 45 122 33 97 82.5 16 49 168
10
e-Diastar Type 51x with socket fusion spigots metric
d(mm)
DN(mm)
DN(inch)
H(mm)
H1(mm)
H2 (mm)
H3 (mm)
H4(mm)
M(mm)
L (mm)
L1(mm)
32 25 1 286 30 20 256 121 M6 154 180
63 50 2 341 52.5 28.5 288.5 176 M8 223 180
d(mm)
DN(mm)
DN(inch)
L2(mm)
L3(mm)
L4(mm)
L5(mm)
L6 (mm)
L7(mm)
L8(mm)
D (mm)
32 25 1 25 122 33 97 82.5 16 49 108.5
63 50 2 45 122 33 97 82.5 16 49 168
Kv 100 values
Diaphragm Valve Type 514-517Dim.(mm)
DN(mm)
Inch(inch)
kv 100(l/min)
Cv 100(gal/min)
kv 100(m³/h)
32 25 1 442 31 27
63 50 2 1575 109 95
11
Pressure-temperature diagramsT Temperature (°C, °F)
P Permissible pressure (bar, psi)
PVC-U PVC-C
0123456789
1011121314151617
-50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90T (°C)
P (b
ar)
020406080100120140160180200220240
-58 -38 -18 2 22 42 62 82 102 122 142 162 182T (°F)
P (p
si)PN 10 2)
PN 6 3)
PVC-UType 514-517
P0900960
PN 16 1)
0123456789
10111213141516
-50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90T (°C)
P (b
ar)
0
20
40
60
80
100
120
140
160
180
200
220
-58 -38 -18 2 22 42 62 82 102 122 142 162 182T (°F)
P (p
si)PN 10
PN 61)
PVC-CType 514-517
P0900561
1) Only with black PPS housing nut for water applications
2) Depending on the connection type and actuator, the nominal
pressure is reduced to PN10
3) Depending on the connection type and actuator, the
nominal pressure is reduced to PN6
1) Depending on the connection type and actuator, the
nominal pressure is reduced to PN6
ABS PP
0123456789
10111213141516
-50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90T (°C)
P (b
ar)
020406080100120140160180200220
-58 -38 -18 2 22 42 62 82 102 122 142 162 182T (°F)
P (p
si)PN 10
PN 6 1)
ABSType 514-517
P0900958 0
123456789
10111213141516
-50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150T (°C)
P (b
ar)
0
20
40
60
80
100
120
140
160
180
200
220
-58 -28 2 32 62 92 122 152 182 212 242 272 302T (°F)
P (p
si)PN 10
PN 6 1)
PPType 514-519
P0900959
1) Depending on the connection type and actuator, the nominal
pressure is reduced to PN6
1) Depending on the connection type and actuator, the
nominal pressure is reduced to PN6
PVDF
0123456789
1011121314151617
-50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150T (°C)
P (b
ar)
020406080100120140160180200220240
-58 -28 2 32 62 92 122 152 182 212 242 272 302T (°F)
P (p
si)
PN 16
PN 10 1)
PVDFType 514-519
P0900962
1) Depending on the connection type and actuator, the nominal
pressure is reduced to PN6
12
Pressure lossesX Flow rate (l/min, US gal/min)
Y Pressure loss Δp (bar, psi)
Diaphragm Valve Type 514-517
0.001
0.01
0.1
1
1 10 100 1'000 10'000
x [l/min]
y [b
ar]
d20 d25 d32 d40 d50 d63
Flow characteristicsX Open angle (%)
Y Kv, Cv value (%)
Diaphragm Valve Type 514-517
0.0
10.0
20.0
30.0
40.0
50.0
60.0
70.0
80.0
90.0
100.0
0 10 20 30 40 50 60 70 80 90 100x
y
13
Accessories• Fail-safe return unit with integrated battery pack• External fail-safe return unit• Positioner 4-20 mA• Monitoring• Profibus• EA Demo Box• Operating time extension, monitoring, operating cycle counting• Motor current monitoring
For further information on accessories, refer to the online product catalog at www.gfps.com
Rev. 0a (4/19)
© Georg Fischer Piping Systems Ltd • Ebnatstrasse 111 • 8201 Schaffhausen • Switzerland • Tel. +41 52 631 11 11 • Fax +41 52 631 28 00 •
www.gfps.com • Contact: Global Sales Support • E-Mail: [email protected]