DRY & WET DRY & WET
RISER RISER
SYSTEMSSYSTEMS
![Page 2: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/2.jpg)
Who to decide on the nos. of wet riser main/Dry riser system to be installed ?
• Architect
Where to locate the wet/dry riser ?
• To be decided by Architect
![Page 3: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/3.jpg)
Design Criteria
Numbers of rising mains depend on :
• Each rising main serves not more than 930m2 of floor area
• Cover a distance of 38m from a landing valve
![Page 4: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/4.jpg)
The riser and landing valves shall be housed in:
• A protected area or lobby or shaft
![Page 5: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/5.jpg)
Where to locate the breeching inlet
Design Criteria
Breeching inlet shall be less than 18m from the fire engine hard standing
Conspicuous position and accessible to the fireman
![Page 6: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/6.jpg)
TYPE OF THE SYSTEMTYPE OF THE SYSTEM
LANDING LANDING VALVEVALVE
Dry Riser SystemDry Riser System
BREECHING INLETBREECHING INLET
AIR AIR RELEASEDVALVERELEASEDVALVE
![Page 7: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/7.jpg)
Requirement of dry riser installation
• For residential building height more than 45m but less than 60m, or with basement or commercial building
• Ø100mm dry riser main pipe is for building height from 10m to 45m
• Ø150mm dry riser main pipe is for building height from 45m to 60m
![Page 8: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/8.jpg)
Requirement of dry riser installation
•2- way breeching inlet for Ø100mm rising main
•4- way breeching inlet for Ø 150mm rising main
![Page 9: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/9.jpg)
Breeching Inlet
![Page 10: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/10.jpg)
![Page 11: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/11.jpg)
Air Release valve
Hand Wheel
Landing Valve
Anti-Thief Device
![Page 12: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/12.jpg)
FSSB SUBMISSION IS NOT REQUIRED FSSB SUBMISSION IS NOT REQUIRED
LOCAL AUTHORITIES SUBMISSIONLOCAL AUTHORITIES SUBMISSION
Submission
![Page 13: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/13.jpg)
![Page 14: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/14.jpg)
![Page 15: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/15.jpg)
ConventionalConventional
PUMP FEED
GRAVITY FEED
TRANSFER PUMP
WET RISER PUMPS
JOCKEY PUMP
FROM PUB SUPPLY
4 WAY BREECHING INLET
LANDING VALVE
![Page 16: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/16.jpg)
Old designOld design
• Non conventional - phase out
FROM PUB SUPPLY
AIR RELEASE VALVE
LANDING VALVE
DOMESTIC FEED
Tanks
WET RISER PUMP
4 WAY BREECHING INLET WET RISER TANK
![Page 17: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/17.jpg)
Down Comer System Down Comer System
DOMESTIC
21 ST STOREY
25TH STOREY
BREECHING INLET
Ø100mm GI PIPE
1ST STOREY
Between 60m to 70 m
WET RISER
Phase out for New Building (17 Sep’01)
![Page 18: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/18.jpg)
Transfer Water Tank Design
• One rising main = 11.5 m3 (15min) @ 27 l/s
• Two rising main = 23 m3 (15min) @ 38 l/s
![Page 19: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/19.jpg)
Roof top wet riser tank layoutRoof top wet riser tank layout
DIA 3.621m 1m
2m
3m length for pump set
1mRing tanks
3-Rings Tank
3 nos. = 49 m3
5 nos. =75 m3
ACOUSTIC SOUND INSULATION
3
1
12m
7m
4-Rings Tank
2 nos. = 49 m3
3 nos. =75 m3
![Page 20: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/20.jpg)
Wet riser tank capacity
• One rising main capacity = 49 m3 for half hours + 1.1 m3 fire hose reel
• Two rising main capacity=74 m3 for half hours +1.1 m3 fire hose reel
![Page 21: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/21.jpg)
Building Above 120mBuilding Above 120m
FROM PUB SUPPLY
1ST STOREY
Mid-Storey
Roof Storey
WET RISER PUMPHOSEREEL PUMPTRANSFER PUMP
Down feed
Down feed
Transfer tanks
![Page 22: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/22.jpg)
Power required
• PUB supply• Generator - supply to 4 blocks per generator
![Page 23: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/23.jpg)
FSSB SUBMISSION IS REQUIRED FSSB SUBMISSION IS REQUIRED
LOCAL AUTHORITIES SUBMISSIONLOCAL AUTHORITIES SUBMISSION
Submission
![Page 24: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/24.jpg)
![Page 25: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/25.jpg)
50TH STOREY HEIGHT BUILDING50TH STOREY HEIGHT BUILDING
![Page 26: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/26.jpg)
WET RISER AND HOSEREEL SERVICE WET RISER AND HOSEREEL SERVICE DUCTDUCT
![Page 27: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/27.jpg)
TESTING AND TESTING AND
COMMISSIONING OF WET COMMISSIONING OF WET
RISERRISER
![Page 28: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/28.jpg)
WET RISER REQUIREMENTSWET RISER REQUIREMENTS
RESIDENTIAL COMMERCIAL & ANY MIXED BUILDING FLOW RATE 27L/S FOR FIRST 38L/S FOR THE FIRST RISING MAIN RISING MAIN 19L/S FOR EACH ADDITIONAL 13.5L/S FOR EACH RISING MAIN ADDITIONAL RISING MAIN MAXIMUM SUPPLY RATE OF 190L/S MAXIMUM SUPPLY RATE OF 135 L/S
RUNNING PRESSURE 3.5BAR TO 5.5 BAR 3.5 BAR TO 5.5 BAR
STATIC PRESSURE 8 BAR 8 BAR
![Page 29: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/29.jpg)
PLAN VIEW FOR WET RISER AND PLAN VIEW FOR WET RISER AND HOSE REELHOSE REEL
![Page 30: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/30.jpg)
Check Valve
Gate Valve
Drain Cock
![Page 31: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/31.jpg)
Check Valve
Rubber Expansion Joint
Gate Valve c/w
limit switch
![Page 32: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/32.jpg)
Pilot Valve
![Page 33: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/33.jpg)
Motorize Valve
Pressure Relief Valve
Bypass system
![Page 34: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/34.jpg)
Flow Meter
![Page 35: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/35.jpg)
Motorize Valve
Gate Valve
Down feed
![Page 36: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/36.jpg)
Pilot Valve
![Page 37: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/37.jpg)
Check Valve
Flow Switch
Down feed Pipe
![Page 38: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/38.jpg)
Duty Pump
Standby Pump
![Page 39: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/39.jpg)
Fire Pump
![Page 40: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/40.jpg)
Jockey Pump
![Page 41: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/41.jpg)
Level Indicator
![Page 42: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/42.jpg)
Landing ValveStrap Lock
![Page 43: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/43.jpg)
Air Release
valve
![Page 44: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/44.jpg)
Drain Cock
Limit Switch
Butterfly valve
![Page 45: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/45.jpg)
Check Valve
![Page 46: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/46.jpg)
Piping
![Page 47: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/47.jpg)
Pressure Switches
Pressure Gauge
![Page 48: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/48.jpg)
![Page 49: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/49.jpg)
Limit Switch Indicator Panel
Alarm Bell
Fire Extinguisher
![Page 50: Dry & Wet Riser Systems](https://reader034.fdocuments.in/reader034/viewer/2022052118/58f9ad53760da3da068b9715/html5/thumbnails/50.jpg)
Wet Riser Control Panel