Medium VoltageCable Range
Over many years Draka has established a deserved
reputation in the UK as the most trusted and reliable
manufacturer in the Low Voltage cable sector. This
reputation was earned through our constant
commitment to our brand values.
We are capitalising on this vast experience and
expertise to extend the offering of the world’s most
trusted cable brand into the UK medium voltage
market, with products founded on the same core
principles – customer focus, safety, performance
and durability.
Draka UK is introducing a medium voltage cable
range to provide the UK’s leading contractors and
distributors with the highest quality cables for the
industrial and utilities sectors. Our cable exceeds
specification requirements to ensure a life
expectancy in excess of industry standards.
Whether it is utilised for power distribution;
(from wind farms and nuclear power stations
through to substations), or in the industrial sector
(in applications such as rail networks, airports
and major construction developments), our state-of-
the-art manufacturing techniques ensure the highest
calibre cables and deliver unrivalled longevity
and reliability.
Added to the numerous industrial projects currently
in progress throughout the UK, the energy network is
THE CABLE RANGE THATDELIVERS DURABILITYAND TRUST
also being constantly refurbished, upgraded and
maintained to cope with the increased electrical
consumption. This has in turn created an increased
demand for high quality medium voltage cables that
will stand the test of time. Draka has the technical
capability to meet this demand. Not only for the
excellence of our products but also for the technical
guidance and support that we offer.
For the utilities sector, the range includes 11, 22 and
33 kV rated versions with solid aluminium or
stranded copper cores, in both singles and triplex,
normally with polyethylene outer sheaths. In addition
to these variants, a stranded aluminium version is
available in singles. For the industrial sector, there
are 11, 22 and 33 kV versions with PVC or Zero
Halogen, Low Smoke (OHLS) sheathing with stranded
copper or stranded aluminium conductors dependent
on the application.
Draka’s medium voltage product range has been
developed with leading edge technology and is backed
by the resources of one of the world’s major specialist
cable companies. Draka Holding NV is an international
cable manufacturer with a turnover of 2 billion Euros
and 9,000 employees.
Draka as an organisation is passionate about
developing world leading products which deliver
exceptional value. Customer focus, quality and
innovation are at the heart of everything we do. Our
technical experts, research and development and
state-of-the-art manufacturing facility enables the
production of the highest quality cabling systems.
Potential RisksOne of the biggest threats to the effective
performance of medium voltage cables are defects in
the insulation system caused by gas voids or
impurities during the insulation of the cable. The
impact of these defects is magnified with increasing
voltage as the electrical stresses increase and can lead
to degradation of the insulation and in the end a
breakdown of the cable. Given the vast volume of
medium voltage cabling required in UK infrastructure,
and the number of people, businesses and services that
are totally reliant on a continued supply of power, any
failings requiring replacement can be severe and bring
major cost implications.
Built to lastThrough the sophistication of the manufacturing
techniques involved, Draka medium voltage cable
limits the exposure to impurities during the compound
handling process in production and as a result, it’s
durability is unrivalled.
The range is produced at the Nässjö factory in Sweden
which since Draka acquired the site from ABB in 1999,
has seen huge investment as part of a major
refurbishment and extension programme. It now has
the very latest plant and equipment which means it
can be classed amongst the world’s most advanced
Medium Voltage manufacturing factories. Already the
leading medium voltage supplier to the Scandinavian
utilities market, Draka has established a proven
pedigree in the development of high quality products
which are built to last. It is of course to ISO14001 and
ISO9001 certified.
BUILTTOOUTPERFORMDECADEAFTERDECADEAFTERDECADE
1 Fundamental to the development of high quality,
trusted medium voltage cable at Draka’s facility in
Sweden has been the introduction of R3 technology
including clean rooms and closed systems for
materials handling – processes usually reserved for
high voltage cable manufacture. Here, the crucial
areas of the factory are contamination-controlled to
eradicate the risk of environmental pollutants such as
dust, airborne microbes, aerosol particles and
chemical vapours from jeopardising the purity of the
cable construction.
CLEANMANUFACTURIN
Extruder platform
Drum take up
2 Not only does the closed system ensure that the
materials used are not contaminated, those specified
are all of the highest quality. The conductive cores are
formed from copper or aluminium in a comprehensive
range of cross sections.
Another major component is XLPE (cross-linked
polyethylene) – a thermosetting material which is able
to perform in temperatures of up to 90°C without
prematurely degrading. This contributes considerably
to the resilience of the product.
NG. THE SECRET BEHIND
220m in length with a
Curing Line
3 In 2007, Draka made a € 6 million investment
to refurbish and extend the Nässjö site. The
most significant development was the incorporation
of a new peroxide cure CCV-Line for the
insulation of our medium voltage cores. The line has
doubled the capacity of the factory to meet the
growing global demands for 10-36 kV medium
voltage cable.
4 Fed from an extruder platform, the CCV-Line is
220m long with a vertical drop of 20m. It features a
200mm diameter tube through which the cable is
cross linked at high temperature and high pressure.
5 Quality control extends across all aspects of the
manufacturing process and includes stringent testing
THEQUALITYANDLONGE
vertical drop of 20m
procedures including X-rays during production to
confirm the structural integrity of the cable. In
accordance with European and country specific
standards, Draka medium voltage cable is
continuously put through long-term water immersion
tests, followed by high voltage electrical breakdown
testing to ensure the cables will be fully reliable
throughout their expected operational life-span.
All of the above is to ensure that Draka produces the
highest quality medium voltage cables.
ERLIFEOFOURCABLES
Taping machinemeasurement gauge
Caterpillar
Capstan
Application fields1-core armoured power cable.
StandardBS6622/BS7835
Rated voltage6.35/11 (12) kV
Impulse voltage95 kV
Fire propagation classBS EN 50266-2-4.
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during installation: -10ºC. Below 0ºC specialprecautions must be taken.
Bending radiusAt laying: 12 x D. When installed: 8 x DD = Overall diameter of cable
Design
ConductorStranded, round and compacted copper acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nominal thickness = 3.4 mm
Insulation screenExtruded, bonded or strippable
Metallic screenMetallic layer, copper tape
Inner sheathPVC or PE, black
ArmourGalvanized aluminium wires
Outer sheathPVC or halogen free compound, red or black
1 COREARMOUREDCU-XLPE 11 kV
10
www.drakauk.com 01332 34543111
Number of cores xcross-section of
conductormm2
Diameterover insulation
mm
Diameter overinner sheath
(approx.)mm
Diameter of steelwiresmm
Overall diameter(approx.)
mm
Weight(approx.)Kg/100 m
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial temp.
65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Number ofcores
x cross-sectionof conductor
mm2
DC conductorresistance at
20ºCΩ/km
AC conductorresistance at
90ºCΩ/km
InductancemH/km
CapacitanceµF/km
Reactanceat 50 Hz
Ω/km
Chargingcurrent/phase
A/km
1x50 16.0 23 1.6 30 140
1x70 17.6 25 1.6 32 160
1x95 19.3 27 1.6 35 210
1x120 20.6 29 1.6 36 240
1x150 22.2 30 2.0 38 270
1x185 23.8 32 2.0 40 220
1x240 26.1 34 2.0 42 380
1x300 28.4 37 2.0 46 480
1x400 31.2 41 2.0 50 570
1x500 34.2 43 2.5 53 690
1x630 37.8 47 2.5 57 840
1x50 0.387 0.494 0.43 0.24 0.14 0.5
1x70 0.268 0.343 0.40 0.27 0.13 0.5
1x95 0.193 0.248 0.38 0.31 0.12 0.6
1x120 0.153 0.196 0.37 0.33 0.12 0.7
1x150 0.124 0.159 0.36 0.36 0.11 0.7
1x185 0.0991 0.128 0.35 0.40 0.11 0.8
1x240 0.0754 0.098 0.33 0.44 0.10 0.9
1x300 0.0601 0.080 0.32 0.49 0.10 1.0
1x400 0.0470 0.064 0.31 0.55 0.10 1.1
1x500 0.0366 0.051 0.30 0.60 0.09 1.2
1x630 0.0283 0.042 0.29 0.68 0.09 1.4
1x50 205 205 250 7.8 7.1
1x70 255 240 295 11.0 10.0
1x95 295 300 355 14.9 13.6
1x120 335 335 410 18.9 17.2
1x150 380 380 485 23.6 21.5
1x185 425 435 535 29.1 26.5
1x240 485 505 620 47.2 43.0
1x300 545 575 705 46.2 43.0
1x400 625 680 835 62.9 57.4
1x500 695 765 940 78.7 71.7
1x630 755 845 1035 99.1 90.4
Electrical data at +20 °C
Current rating
*Installation conditionsGround temperature: 15°CDepth of laying: 0.65 mGround resistivity: 1.0 m x °K/W
Air temperature 25°CTrefoil with screen grounded at both endsNominal values unless otherwise specified.
Application fields1-core armoured power cable.
StandardBS6622/BS7835
Rated voltage12.7/22 (24) kV
Impulse voltage144 kV
Fire propagation classBS EN 50266-2-4.
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during installation: -10ºC. Below 0ºC specialprecautions must be taken.
Bending radiusAt laying: 12 x D. When installed: 8 x DD = Overall diameter of cable
Design
ConductorStranded, round and compacted copper acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nominal thickness = 5.5 mm
Insulation screenExtruded, bonded or strippable
Metallic screenMetallic layer, copper tape
Inner sheathPVC or PE, black
ArmourGalvanized aluminium wires
Outer sheathPVC or halogen free compound, red or black
1 COREARMOUREDCU-XLPE 22 kV
12
www.drakauk.com 01332 34543113
Number of cores xcross-section of
conductormm2
Diameterover insulation
mm
Diameter overinner sheath
(approx.)mm
Diameter of steelwiresmm
Overall diameter(approx.)
mm
Weight(approx.)Kg/100 m
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial temp.
65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Number ofcores
x cross-sectionof conductor
mm2
DC conductorresistance at
20ºCΩ/km
AC conductorresistance at
90ºCΩ/km
InductancemH/km
CapacitanceµF/km
Reactanceat 50 Hz
Ω/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
Installation conditionsGround temperature: 15°CDepth of laying: 0.65 mGround resistivity: 1.0 m x °K/W
Air temperature 25°CTrefoil grounded at both ends.Nominal values unless otherwise specified.
1x50 18.2 29 1.6 36 170
1x70 19.8 30 2.0 38 200
1x95 21.5 32 2.0 39 240
1x120 22.8 33 2.0 41 300
1x150 24.4 34 2.0 42 350
1x185 26.0 36 2.0 44 440
1x240 28.3 39 2.0 48 510
1x300 30.6 40 2.5 50 610
1x400 33.4 44 2.5 54 730
1x500 36.4 48 2.5 58 890
1x630 40.0 52 2.5 62 1080
1x50 0.387 0.494 0.46 0.17 0.15 0.3
1x70 0.268 0.343 0.43 0.19 0.14 0.4
1x95 0.193 0.248 0.41 0.21 0.13 0.4
1x120 0.153 0.196 0.40 0.22 0.13 0.4
1x150 0.124 0.159 0.38 0.24 0.13 0.5
1x185 0.0991 0.128 0.37 0.26 0.12 0.5
1x240 0.0754 0.098 0.36 0.29 0.12 0.6
1x300 0.0601 0.080 0.34 0.32 0.11 0.6
1x400 0.0470 0.064 0.33 0.36 0.11 0.7
1x500 0.0366 0.051 0.32 0.39 0.11 0.7
1x630 0.0283 0.042 0.31 0.44 0.10 0.7
1x50 205 205 250 7.8 7.1
1x70 255 240 295 11.0 10.0
1x95 295 300 355 14.9 13.6
1x120 335 335 410 18.9 17.2
1x150 380 380 485 23.6 21.5
1x185 425 435 535 29.1 26.5
1x240 485 505 620 47.2 43.0
1x300 545 575 705 46.2 43.0
1x400 625 680 835 62.9 57.4
1x500 695 765 940 78.7 71.7
1x630 755 845 1035 99.1 90.4
Application fields1-core armoured power cable.
StandardBS6622/BS7835
Rated voltage19/33 (36) kV
Impulse voltage194 kV
Fire propagation classBS EN 50266-2-4.
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during installation: -10ºC. Below 0ºC specialprecautions must be taken.
Bending radiusAt laying: 12 x D. When installed: 8 x DD = Overall diameter of cable
Design
ConductorStranded, round and compacted copper acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nominal thickness = 8.0 mm
Insulation screenExtruded, bonded or strippable
Metallic screenMetallic layer, copper tape
Inner sheathPVC or PE, black
ArmourGalvanized aluminium wires
Outer sheathPVC or halogen free compound, red or black
1 COREARMOUREDCU-XLPE 33 kV
14
www.drakauk.com 01332 34543115
Number of cores xcross-section of
conductormm2
Diameterover insulation
mm
Diameter overinner sheath
(approx.)mm
Diameter of steelwiresmm
Overall diameter(approx.)
mm
Weight(approx.)Kg/100 m
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial temp.
65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Number ofcores
x cross-sectionof conductor
mm2
DC conductorresistance at
20ºCΩ/km
AC conductorresistance at
90ºCΩ/km
InductancemH/km
CapacitanceµF/km
Reactanceat 50 Hz
Ω/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Installation conditionsGround temperature: 15°CDepth of laying: 0.65 mGround resistivity: 1.0 m x °K/W
Air temperature 25°CTrefoil with screen grounded at both endsNominal values unless otherwise specified.
1x50 25.2 34 2.0 42 210
1x70 26.8 36 2.0 44 240
1x95 28.5 38 2.0 47 300
1x120 29.8 39 2.0 48 340
1x150 31.4 40 2.5 50 380
1x185 33.0 42 2.5 52 420
1x240 35.3 44 2.5 54 490
1x300 37.6 47 2.5 57 580
1x400 40.4 51 2.5 61 680
1x500 43.4 53 2.5 64 800
1x630 47.0 58 2.5 69 960
1x50 0.387 0.494 0.46 0.16 0.15 0.6
1x70 0.268 0.343 0.45 0.18 0.14 0.7
1x95 0.193 0.248 0.44 0.21 0.14 0.8
1x120 0.153 0.196 0.42 0.23 0.13 0.9
1x150 0.124 0.159 0.41 0.25 0.13 1.0
1x185 0.0991 0.128 0.40 0.27 0.13 1.1
1x240 0.0754 0.098 0.38 0.229 0.12 1.2
1x300 0.0601 0.080 0.37 0.32 0.12 1.3
1x400 0.0470 0.064 0.35 0.36 0.11 1.4
1x500 0.0366 0.051 0.34 0.40 0.11 1.6
1x630 0.0283 0.042 0.33 0.44 0.10 1.8
1x50 205 205 250 7.8 7.1
1x70 255 240 295 11.0 10.0
1x95 295 300 355 14.9 13.6
1x120 335 335 410 18.9 17.2
1x150 380 380 485 23.6 21.5
1x185 425 435 535 29.1 26.5
1x240 485 505 620 47.2 43.0
1x300 545 575 705 46.2 43.0
1x400 625 680 835 62.9 57.4
1x500 695 765 940 78.7 71.7
1x630 755 845 1035 99.1 90.4
Application fields3-core armoured power cable.
StandardBS6622/BS7835
Rated voltage6.35/11 (12) kV
Impulse voltage95 kV
Fire propagation classBS EN 50266-2-4.
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during installation: -10ºC. Below 0ºC specialprecautions must be taken.
Bending radiusAt laying: 12 x D. When installed: 8 x DD = Overall diameter of cable
Design
ConductorStranded, round and compacted copper acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nominal thickness = 3.4 mm
Insulation screenExtruded, bonded or strippable
Core identificationcoloured phasetape under screen
Metallic screenMetallic layer, copper tape, over each individual core
FillerPP yarn
Inner sheathPVC or PE, black
ArmourGalvanized steel wires
Outer sheathPVC or halogen free compound, red or black
3 COREARMOUREDCU-XLPE 11 kV
16
www.drakauk.com 01332 34543117
Number of cores xcross-section of
conductormm2
Diameterover insulation
mm
Diameter overinner sheath
(approx.)mm
Diameter of steelwiresmm
Overall diameter(approx.)
mm
Weight(approx.)Kg/100 m
Number of cores xcrosssectionof conductor
mm2
Current rating at coretemp.
65 ºC in ground*A
Current rating at coretemp. 65 ºC in air*
A
Current rating at coretemp. 90 ºC in air*
A
Max. short-circuitcurrent on the
conductor during 1 s atinitial temp. 90 ºC
kA
Number ofcores
x cross-sectionof conductor
mm2
DC conductorresistance at
20ºCΩ/km
AC conductorresistance at
90ºCΩ/km
InductancemH/km
CapacitanceµF/km
Reactanceat 50 Hz
Ω/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Installation conditionsGround temperature: 15°CDepth of laying: 0.65 mGround resistivity: 1.0 m x °K/W
Air temperature 25°CScreen grounded at both ends.Nominal values unless otherwise specified.
3x50 175 165 205 7.1
3x70 210 205 250 10.0
3x95 250 240 295 13.6
3x120 285 280 340 17.2
3x150 325 320 390 21.5
3x185 360 360 435 26.5
3x240 415 420 515 34.3
3x300 470 480 590 42.9
3x50 0.387 0.494 0.34 0.24 0.11 0.5
3x70 0.268 0.343 0.33 0.27 0.10 0.6
3x95 0.193 0.248 0.31 0.31 0.10 0.7
3x120 0.153 0.196 0.30 0.33 0.09 0.7
3x150 0.124 0.159 0.29 0.36 0.09 0.8
3x185 0.0991 0.128 0.28 0.40 0.09 0.8
3x240 0.0754 0.098 0.27 0.49 0.09 0.9
3x300 0.0601 0.080 0.26 0.55 0.08 1.0
3x50 16.0 44 2.5 54 600
3x70 17.5 47 2.5 58 750
3x95 19.3 51 2.5 62 800
3x120 20.8 55 2.5 67 850
3x150 22.2 58 2.5 69 950
3x185 24.1 61 2.5 73 1100
3x240 26.3 69 3.15 82 1425
3x300 28.6 72 3.15 86 1700
Application fields3-core armoured power cable.
StandardBS6622/BS7835
Rated voltage12.7/22 (24) kV
Impulse voltage144 kV
Fire propagation classBS EN 50266-2-4.
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during installation: -10ºC. Below 0ºC specialprecautions must be taken.
Bending radiusAt laying: 12 x D. When installed: 8 x DD = Overall diameter of cable
Design
ConductorStranded, round and compacted copper acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nominal thickness = 5.5 mm
Insulation screenExtruded, bonded or strippable
Core identificationcoloured phasetape under the copper tape
Metallic screenMetallic layer, copper tape, over each individual core
FillerPP yarn
Inner sheathPVC or PE, black
ArmourGalvanized steel wires
Outer sheathPVC or halogen free compound, red or black
3 COREARMOUREDCU-XLPE 22 kV
18
www.drakauk.com 01332 34543119
Number of cores xcross-section of
conductormm2
Diameterover insulation
mm
Diameter overinner sheath
(approx.)mm
Diameter of steelwiresmm
Overall diameter(approx.)
mm
Weight(approx.)Kg/100 m
Number ofcores
x cross-sectionof conductor
mm2
DC conductorresistance at
20ºCΩ/km
AC conductorresistance at
90ºCΩ/km
InductancemH/km
CapacitanceµF/km
Reactanceat 50 Hz
Ω/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
Installation conditionsGround temperature: 15°CDepth of laying: 0.65 mGround resistivity: 1.0 m x °K/W
Air temperature 25°CScreen grounded at both ends.Nominal values unless otherwise specified.
3x50 20.2 53 2.5 64 700
3x70 21.8 57 2.5 68 780
3x95 23.5 63 2.5 74 900
3x120 24.8 65 3.15 77 1100
3x150 26.4 67 3.15 80 1200
3x185 28.0 72 3.15 84 1400
3x240 30.3 76 3.15 88 1600
3x300 28.6 72 3.15 95 1850
3x50 0.387 0.494 0.37 0.17 0.12 0.7
3x70 0.268 0.343 0.35 0.19 0.11 0.8
3x95 0.193 0.248 0.33 0.21 0.10 0.8
3x120 0.153 0.196 0.32 0.22 0.10 0.9
3x150 0.124 0.159 0.31 0.24 0.10 1.0
3x185 0.0991 0.128 0.30 0.26 0.09 1.0
3x240 0.0754 0.098 0.29 0.29 0.09 1.2
3x300 0.0601 0.080 0.28 0.32 0.09 1.3
3x50 175 165 205 7.1
3x70 210 205 250 10.0
3x95 250 240 295 13.6
3x120 285 280 340 17.2
3x150 325 320 390 21.5
3x185 360 360 435 26.5
3x240 415 420 515 34.3
3x300 470 480 590 42.9
Number of cores xcrosssectionof conductor
mm2
Current rating at coretemp.
65 ºC in ground*A
Current rating at coretemp. 65 ºC in air*
A
Current rating at coretemp. 90 ºC in air*
A
Max. short-circuitcurrent on the
conductor during 1 s atinitial temp. 90 ºC
kA
Application fields3-core armoured power cable.
StandardBS6622/BS7835
Rated voltage19/33 (36) kV
Impulse voltage194 kV
Fire propagation classBS EN 50266-2-4.
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during installation: -10ºC. Below 0ºC specialprecautions must be taken.
Bending radiusAt laying: 12 x D. When installed: 8 x DD = Overall diameter of cable
Design
ConductorStranded, round and compacted copper acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nominal thickness = 8.0 mm
Insulation screenExtruded, bonded or strippable
Core identificationcoloured phasetape under screen
Metallic screenMetallic layer, copper tape, over each individual core
FillerPP yarn
Inner sheathPVC or PE, black
ArmourGalvanized steel wires
Outer sheathPVC or halogen free compound, red or black
3 COREARMOUREDCU-XLPE 33 kV
20
www.drakauk.com 01332 34543121
Number of cores xcross-section of
conductormm2
Diameterover insulation
mm
Diameter overinner sheath
(approx.)mm
Diameter of steelwiresmm
Overall diameter(approx.)
mm
Weight(approx.)Kg/100 m
Number ofcores
x cross-sectionof conductor
mm2
DC conductorresistance at
20ºCΩ/km
AC conductorresistance at
90ºCΩ/km
InductancemH/km
CapacitanceµF/km
Reactanceat 50 Hz
Ω/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Installation conditionsGround temperature: 15°CDepth of laying: 0.65 mGround resistivity: 1.0 m x °K/W
Air temperature 25°CScreen grounded at both ends.Nominal values unless otherwise specified.
Number of cores xcrosssectionof conductor
mm2
Current rating at coretemp.
65 ºC in ground*A
Current rating at coretemp. 65 ºC in air*
A
Current rating at coretemp. 90 ºC in air*
A
Max. short-circuitcurrent on the
conductor during 1 s atinitial temp. 90 ºC
kA
3x50 25.2 60 2.5 83 900
3x70 26.8 64 3.15 87 1100
3x95 28.5 67 3.15 90 1200
3x120 29.8 71 3.15 92 1350
3x150 31.4 72 3.15 94 1450
3x185 33.0 75 3.15 97 1600
3x240 35.3 79 3.15 101 1800
3x50 0.387 0.494 0.41 0.13 0.13 0.8
3x70 0.268 0.343 0.39 0.14 0.12 0.8
3x95 0.193 0.248 0.37 0.16 0.12 1.0
3x120 0.153 0.196 0.36 0.17 0.11 1.0
3x150 0.124 0.159 0.35 0.18 0.11 1.1
3x185 0.0991 0.128 0.33 0.20 0.10 1.2
3x240 0.0754 0.0988 0.32 0.22 0.10 1.3
3x50 175 165 205 7.1
3x70 210 205 250 10.0
3x95 250 240 295 13.6
3x120 285 280 340 17.2
3x150 325 320 390 21.5
3x185 360 360 435 26.5
3x240 415 420 515 34.3
Application fields1-core armoured power cable.
StandardBS6622/BS7835
Rated voltage6.35/11 (12) kV
Impulse voltage95 kV
Fire propagation classBS EN 50266-2-4.
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during installation: -10ºC. Below 0ºC specialprecautions must be taken.
Bending radiusAt laying: 12 x D. When installed: 8 x DD = Overall diameter of cable
Design
ConductorStranded, round and compacted aluminium acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nominal thickness = 3.4 mm
Insulation screenExtruded, bonded or strippable
Metallic screenMetallic layer, copper tape
Inner sheathPVC or PE, black
ArmourGalvanized aluminium wires
Outer sheathPVC or halogen free compound, red or black
1 COREARMOURED
AL-XLPE 11 kV
22
www.drakauk.com 01332 34543123
Number of cores xcross-section of
conductormm2
Diameterover insulation
mm
Diameter overinner sheath
(approx.)mm
Diameter of steelwiresmm
Overall diameter(approx.)
mm
Weight(approx.)Kg/100 m
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial temp.
65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Number ofcores
x cross-sectionof conductor
mm2
DC conductorresistance at
20ºCΩ/km
AC conductorresistance at
90ºCΩ/km
InductancemH/km
CapacitanceµF/km
Reactanceat 50 Hz
Ω/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Installation conditionsGround temperature: 15°CDepth of laying: 0.65 mGround resistivity: 1.0 m x °K/W
Air temperature 25°CTrefoil grounded at both ends.Nominal values unless otherwise specified.
1x50 16.0 23 1.6 30 110
1x70 17.6 25 1.6 32 120
1x95 19.3 27 1.6 35 150
1x120 20.6 29 1.6 36 170
1x150 22.2 30 2.0 38 180
1x185 23.8 32 2.0 40 210
1x240 26.1 34 2.0 42 240
1x300 28.4 72 2.0 46 280
1x400 31.2 41 2.0 50 330
1x500 34.2 43 2.5 53 380
1x630 37.8 47 2.5 57 440
1x50 0.641 0.822 0.43 0.24 0.14 0.5
1x70 0.443 0.568 0.40 0.27 0.13 0.5
1x95 0.320 0.410 0.38 0.31 0.12 0.6
1x120 0.253 0.325 0.37 0.33 0.12 0.7
1x150 0.206 0.265 0.36 0.36 0.11 0.7
1x185 0.164 0.211 0.35 0.40 0.11 0.8
1x240 0.125 0.162 0.33 0.44 0.10 0.9
1x300 0.100 0.130 0.32 0.49 0.10 1.0
1x400 0.0778 0.102 0.31 0.55 0.10 1.1
1x500 0.0605 0.0825 0.30 0.60 0.09 1.2
1x630 0.0469 0.0632 0.29 0.68 0.09 1.4
1x50 155 160 195 5.2 4.7
1x70 200 190 235 7.2 6.6
1x95 235 230 280 9.9 8.9
1x120 265 265 325 12.4 11.3
1x150 300 300 370 15.6 14.2
1x185 330 345 425 19.2 17.5
1x240 385 400 490 25.0 22.7
1x300 435 460 565 31.2 28.3
1x400 510 555 680 41.6 37.8
1x500 570 635 775 52.0 47.2
1x630 635 720 880 65.6 59.5
Application fields1-core armoured power cable.
StandardBS6622/BS7835
Rated voltage12.7/22 (24) kV
Impulse voltage144 kV
Fire propagation classBS EN 50266-2-4.
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during installation: -10ºC. Below 0ºC specialprecautions must be taken.
Bending radiusAt laying: 12 x D. When installed: 8 x DD = Overall diameter of cable
Design
ConductorStranded, round and compacted aluminium acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nominal thickness = 5.5 mm
Insulation screenExtruded, bonded or strippable
Metallic screenMetallic layer, copper tape
Inner sheathPVC or PE, black
ArmourGalvanized aluminium wires
Outer sheathPVC or halogen free compound, red or black
1 COREARMOUREDAL-XLPE 22 kV
24
www.drakauk.com 01332 34543125
Number of cores xcross-section of
conductormm2
Diameterover insulation
mm
Diameter overinner sheath
(approx.)mm
Diameter of steelwiresmm
Overall diameter(approx.)
mm
Weight(approx.)Kg/100 m
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial temp.
65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Number ofcores
x cross-sectionof conductor
mm2
DC conductorresistance at
20ºCΩ/km
AC conductorresistance at
90ºCΩ/km
InductancemH/km
CapacitanceµF/km
Reactanceat 50 Hz
Ω/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
Installation conditionsGround temperature: 15°CDepth of laying: 0.65 mGround resistivity: 1.0 m x °K/W
Air temperature 25°CTrefoil grounded at both ends.Nominal values unless otherwise specified.
1x50 18.2 29 1.6 36 140
1x70 19.8 30 2.0 38 160
1x95 21.5 32 2.0 39 180
1x120 22.8 33 2.0 41 200
1x150 24.4 34 2.0 42 210
1x185 26.0 36 2.0 44 240
1x240 28.3 39 2.0 48 290
1x300 30.6 40 2.5 50 320
1x400 33.4 44 2.5 54 370
1x500 36.4 48 2.5 58 420
1x630 40.0 52 2.5 62 490
1x50 0.641 0.822 0.46 0.17 0.15 0.3
1x70 0.443 0.568 0.43 0.19 0.14 0.4
1x95 0.320 0.410 0.41 0.21 0.13 0.4
1x120 0.253 0.325 0.40 0.22 0.13 0.4
1x150 0.206 0.265 0.38 0.24 0.13 0.5
1x185 0.164 0.211 0.37 0.26 0.12 0.5
1x240 0.125 0.162 0.36 0.29 0.12 0.6
1x300 0.100 0.130 0.34 0.32 0.11 0.6
1x400 0.0778 0.102 0.33 0.36 0.11 0.7
1x500 0.0605 0.0825 0.32 0.39 0.11 0.7
1x630 0.0469 0.632 0.31 0.44 0.10 0.7
1x50 155 160 195 5.2 4.7
1x70 200 190 235 7.2 6.6
1x95 235 230 280 9.9 8.9
1x120 265 265 325 12.4 11.3
1x150 300 300 370 15.6 14.2
1x185 330 345 425 19.2 17.5
1x240 385 400 490 25.0 22.7
1x300 435 460 565 31.2 28.3
1x400 510 555 680 41.6 37.8
1x500 570 635 775 52.0 47.2
1x630 635 720 880 65.6 59.5
Application fields1-core armoured power cable.
StandardBS6622/BS7835
Rated voltage19/33 (36) kV
Impulse voltage194 kV
Fire propagation classBS EN 50266-2-4.
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during installation: -10ºC. Below 0ºC specialprecautions must be taken.
Bending radiusAt laying: 12 x D. When installed: 8 x DD = Overall diameter of cable
Design
ConductorStranded, round and compacted aluminium acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nominal thickness = 8.0 mm
Insulation screenExtruded, bonded or strippable
Metallic screenMetallic layer, copper tape
Inner sheathPVC or PE, black
ArmourGalvanized aluminium wires
Outer sheathPVC or halogen free compound, red or black
1 COREARMOUREDAL-XLPE 33 kV
26
www.drakauk.com 01332 34543127
Number of cores xcross-section of
conductormm2
Diameterover insulation
mm
Diameter overinner sheath
(approx.)mm
Diameter of steelwiresmm
Overall diameter(approx.)
mm
Weight(approx.)Kg/100 m
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial temp.
65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Number ofcores
x cross-sectionof conductor
mm2
DC conductorresistance at
20ºCΩ/km
AC conductorresistance at
90ºCΩ/km
InductancemH/km
CapacitanceµF/km
Reactanceat 50 Hz
Ω/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Installation conditionsGround temperature: 15°CDepth of laying: 0.65 mGround resistivity: 1.0 m x °K/W
Air temperature 25°CTrefoil grounded at both ends.Nominal values unless otherwise specified.
1x50 25.2 34 2.0 42 180
1x70 26.8 36 2.0 44 200
1x95 28.5 38 2.0 47 240
1x120 29.8 39 2.0 48 260
1x150 31.4 40 2.5 50 290
1x185 33.0 42 2.5 52 310
1x240 35.3 44 2.5 54 340
1x300 37.6 47 2.5 57 380
1x400 40.4 51 2.5 61 440
1x500 43.4 53 2.5 64 490
1x630 47.0 58 2.5 69 560
1x50 0.641 0.822 0.46 0.16 0.15 0.6
1x70 0.443 0.568 0.45 0.18 0.14 0.7
1x95 0.320 0.410 0.44 0.21 0.14 0.8
1x120 0.253 0.325 0.42 0.23 0.13 0.9
1x150 0.206 0.265 0.41 0.25 0.13 1.0
1x185 0.164 0.211 0.40 0.27 0.13 1.1
1x240 0.125 0.162 0.38 0.229 0.12 1.2
1x300 0.100 0.130 0.37 0.32 0.12 1.3
1x400 0.0778 0.102 0.35 0.36 0.11 1.4
1x500 0.0605 0.0825 0.34 0.40 0.11 1.6
1x630 0.0469 0.042 0.33 0.44 0.10 1.8
1x50 155 160 195 5.2 4.7
1x70 200 190 235 7.2 6.6
1x95 235 230 280 9.9 8.9
1x120 265 265 325 12.4 11.3
1x150 300 300 370 15.6 14.2
1x185 330 345 425 19.2 17.5
1x240 385 400 490 25.0 22.7
1x300 435 460 565 31.2 28.3
1x400 510 555 680 41.6 37.8
1x500 570 635 775 52.0 47.2
1x630 635 720 880 65.6 59.5
Application fields3-core armoured power cable.
StandardBS6622/BS7835
Rated voltage6.35/11 (12) kV
Impulse voltage95 kV
Fire propagation classBS EN 50266-2-4.
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during installation: -10ºC. Below 0ºC specialprecautions must be taken.
Bending radiusAt laying: 12 x D. When installed: 8 x DD = Overall diameter of cable
Design
ConductorStranded, round and compacted aluminium acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nominal thickness = 3.4 mm
Insulation screenExtruded, bonded or strippable
Core identificationcoloured phasetape under screen
Metallic screenMetallic layer, copper tape, over each individual core
FillerPP yarn
Inner sheathPVC or PE, black
ArmourGalvanized steel wires
Outer sheathPVC or halogen free compound, red or black
3 COREARMOURED
AL-XLPE 11 kV
28
www.drakauk.com 01332 34543129
Number of cores xcross-section of
conductormm2
Diameterover insulation
mm
Diameter overinner sheath
(approx.)mm
Diameter of steelwiresmm
Overall diameter(approx.)
mm
Weight(approx.)Kg/100 m
Number ofcores
x cross-sectionof conductor
mm2
DC conductorresistance at
20ºCΩ/km
AC conductorresistance at
90ºCΩ/km
InductancemH/km
CapacitanceµF/km
Reactanceat 50 Hz
Ω/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Installation conditionsGround temperature: 15°CDepth of laying: 0.65 mGround resistivity: 1.0 m x °K/W
Air temperature 25°CScreen grounded at both ends.Nominal values unless otherwise specified.
Number of cores xcrosssectionof conductor
mm2
Current rating at coretemp.
65 ºC in ground*A
Current rating at coretemp. 65 ºC in air*
A
Current rating at coretemp. 90 ºC in air*
A
Max. short-circuitcurrent on the
conductor during 1 s atinitial temp. 90 ºC
kA
3x50 16.0 44 2.5 54 450
3x70 17.5 47 2.5 58 500
3x95 19.3 51 2.5 62 600
3x120 20.8 55 2.5 67 650
3x150 22.2 58 2.5 69 750
3x185 24.1 61 2.5 73 850
3x240 26.3 69 3.15 82 950
3x300 28.6 72 3.15 86 1100
3x50 0.641 0.822 0.34 0.24 0.11 0.5
3x70 0.443 0.568 0.33 0.27 0.10 0.6
3x95 0.320 0.411 0.31 0.31 0.10 0.7
3x120 0.253 0.325 0.30 0.33 0.09 0.7
3x150 0.206 0.265 0.29 0.36 0.09 0.8
3x185 0.164 0.211 0.28 0.40 0.09 0.8
3x240 0.125 0.162 0.27 0.49 0.09 0.9
3x300 0.100 0.130 0.26 0.55 0.08 1.0
3x50 145 130 160 4.7
3x70 175 155 190 6.6
3x95 205 190 230 8.9
3x120 230 220 265 11.3
3x150 260 250 305 14.2
3x185 290 280 340 17.5
3x240 340 330 400 22.7
3x300 380 375 460 28.3
Application fields3-core armoured power cable.
StandardBS6622/BS7835
Rated voltage12.7/22 (24) kV
Impulse voltage144 kV
Fire propagation classBS EN 50266-2-4.
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during installation: -10ºC. Below 0ºC specialprecautions must be taken.
Bending radiusAt laying: 12 x D. When installed: 8 x DD = Overall diameter of cable
Design
ConductorStranded, round and compacted copper acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nominal thickness = 5.5 mm
Insulation screenExtruded, bonded or strippable
Core identificationcoloured phasetape under the copper tape
Metallic screenMetallic layer, copper tape, over each individual core
FillerPP yarn
Inner sheathPVC or PE, black
ArmourGalvanized steel wires
Outer sheathPVC or halogen free compound, red or black
3 COREARMOUREDAL-XLPE 22 kV
30
www.drakauk.com 01332 34543131
Number of cores xcross-section of
conductormm2
Diameterover insulation
mm
Diameter overinner sheath
(approx.)mm
Diameter of steelwiresmm
Overall diameter(approx.)
mm
Weight(approx.)Kg/100 m
Number ofcores
x cross-sectionof conductor
mm2
DC conductorresistance at
20ºCΩ/km
AC conductorresistance at
90ºCΩ/km
InductancemH/km
CapacitanceµF/km
Reactanceat 50 Hz
Ω/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
Installation conditionsGround temperature: 15°CDepth of laying: 0.65 mGround resistivity: 1.0 m x °K/W
Air temperature 25°CScreen grounded at both ends.Nominal values unless otherwise specified.
Number of cores xcrosssectionof conductor
mm2
Current rating at coretemp.
65 ºC in ground*A
Current rating at coretemp. 65 ºC in air*
A
Current rating at coretemp. 90 ºC in air*
A
Max. short-circuitcurrent on the
conductor during 1 s atinitial temp. 90 ºC
kA
3x50 20.2 53 2.5 64 600
3x70 21.8 57 2.5 68 650
3x95 23.5 63 2.5 74 700
3x120 24.8 65 3.15 77 850
3x150 26.4 67 3.15 80 900
3x185 28.0 72 3.15 84 1000
3x240 30.3 76 3.15 88 1150
3x300 28.6 72 3.15 95 1300
3x50 0.641 0.822 0.37 0.17 0.12 0.7
3x70 0.443 0.568 0.35 0.19 0.11 0.8
3x95 0.320 0.410 0.33 0.21 0.10 0.8
3x120 0.253 0.325 0.32 0.22 0.10 0.9
3x150 0.206 0.265 0.31 0.24 0.10 1.0
3x185 0.164 0.211 0.30 0.26 0.09 1.0
3x240 0.125 0.162 0.29 0.29 0.09 1.2
3x300 0.100 0.130 0.28 0.32 0.09 1.3
3x50 145 130 160 4.7
3x70 175 155 190 6.6
3x95 205 190 230 8.9
3x120 230 220 265 11.3
3x150 260 250 305 14.2
3x185 290 280 340 17.5
3x240 340 330 400 22.7
3x300 380 375 460 28.3
Application fields3-core armoured power cable.
StandardBS6622/BS7835
Rated voltage19/33 (36) kV
Impulse voltage194 kV
Fire propagation classBS EN 50266-2-4.
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during installation: -10ºC. Below 0ºC specialprecautions must be taken.
Bending radiusAt laying: 12 x D. When installed: 8 x DD = Overall diameter of cable
Design
ConductorStranded, round and compacted aluminium acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nominal thickness = 8.0 mm
Insulation screenExtruded, bonded or strippable
Core identificationcoloured phasetape under screen
Metallic screenMetallic layer, copper tape, over each individual core
FillerPP yarn
Inner sheathPVC or PE, black
ArmourGalvanized steel wires
Outer sheathPVC or halogen free compound, red or black
3 COREARMOUREDAL-XLPE 33 kV
32
www.drakauk.com 01332 34543133
Number of cores xcross-section of
conductormm2
Diameterover insulation
mm
Diameter overinner sheath
(approx.)mm
Diameter of steelwiresmm
Overall diameter(approx.)
mm
Weight(approx.)Kg/100 m
Number ofcores
x cross-sectionof conductor
mm2
DC conductorresistance at
20ºCΩ/km
AC conductorresistance at
90ºCΩ/km
InductancemH/km
CapacitanceµF/km
Reactanceat 50 Hz
Ω/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Installation conditionsGround temperature: 15°CDepth of laying: 0.65 mGround resistivity: 1.0 m x °K/W
Air temperature 25°CScreen grounded at both ends.Nominal values unless otherwise specified.
Number of cores xcrosssectionof conductor
mm2
Current rating at coretemp.
65 ºC in ground*A
Current rating at coretemp. 65 ºC in air*
A
Current rating at coretemp. 90 ºC in air*
A
Max. short-circuitcurrent on the
conductor during 1 s atinitial temp. 90 ºC
kA
3x50 145 130 160 4.7
3x70 175 155 190 6.6
3x95 205 190 230 8.9
3x120 230 220 265 11.3
3x150 260 250 305 14.2
3x185 290 280 340 17.5
3x240 340 330 400 22.7
3x300 380 375 460 28.3
3x50 0.641 0.822 0.41 0.13 0.13 0.8
3x70 0.443 0.568 0.39 0.14 0.12 0.8
3x95 0.320 0.410 0.37 0.16 0.12 1.0
3x120 0.253 0.325 0.36 0.17 0.11 1.0
3x150 0.206 0.265 0.35 0.18 0.11 1.1
3x185 0.164 0.211 0.33 0.20 0.10 1.2
3x240 0.125 0.162 0.32 0.22 0.10 1.3
3x50 25.2 60 2.5 83 950
3x70 26.8 64 3.15 87 1050
3x95 28.5 67 3.15 90 1150
3x120 29.8 71 3.15 92 1250
3x150 31.4 72 3.15 94 1400
3x185 33.0 75 3.15 97 1550
3x240 35.3 79 3.15 101 1700
Application fieldsSingle-core, distribution cable for outdoors use in 3-phaseformation. Installation in pipes and ground/water.
StandardBS 7870-4.10
Rated voltage6.35/11 (12) kV
Flame propagation classThe PE sheath is not flame-retardant
Temperature rangeIn continuous operation max 90ºC. Lowest cable temperatureduring installation: -20ºC. Below 0ºC special precautions must betaken.
Impulse voltage95 kV
Bending radiusAt fixed mounting: 10 x D. At laying: 15 x D
Design
ConductorStranded, round and compacted copper acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nom. thickness = 3.4 mm
Insulation screenExtruded bonded
Concentric conductorAnnealed copper wires
SheathMDPE, black
1 CORE
CU-XLPE-CWS-PE 11 kV
34
www.drakauk.com 01332 34543135
Number of coresx cross-section
of conductormm2
Diameterover insulation
mm
Overall diameter(approx.)
mm
Weight(approx.)kg/100 m
Standarddeliverylength
m
Standarddrumsize
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Numberof cores
x cross-sectionof conductor
mm2
Conductorresistance
Ω/km
Screenresistance
Ω/km
Inductancein trefoil/in
plane*mH/km
CapacitanceµF/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Current ratings conditionsAmbient temperature air: 25ºCGround temperature: 15ºCDepth of burial: 0.7 m
Thermal resistance of soil 1.0 ºKm/WTrefoil with screen grounded at both endsNominal values unless otherwise specified.
1x70/35 17.6 27 125 500 K14
1x95/35 19.3 29 150 500 K14
1x120/35 20.6 30 180 500 K14
1x150/35 22.2 32 215 500 K14
1x185/35 23.8 34 250 500 K16
1x240/35 26.1 36 305 500 K16
1x300/35 28.4 38 370 500 K18
1x400/35 31.2 43 465 500 K20
1x500/35 34.2 45 565 500 K20
1x630/35 37.8 50 700 500 K22
1x70/35 0.268 0.542 0.40/0.58 0.27 1.1
1x95/35 0.193 0.542 0.38/0.56 0.31 1.2
1x120/35 0.153 0.542 0.36/0.55 0.33 1.3
1x150/35 0.124 0.542 0.35/0.54 0.36 1.4
1x185/35 0.0991 0.542 0.34/0.53 0.40 1.6
1x240/35 0.0754 0.542 0.33/0.51 0.44 1.8
1x300/35 0.0601 0.542 0.31/0.50 0.49 2.0
1x400/35 0.0470 0.542 0.31/0.49 0.55 2.2
1x500/35 0.0366 0.542 0.29/0.48 0.60 2.4
1x630/35 0.0283 0.542 0.29/0.47 0.68 2.7
1x70/35 255 240 295 11.0 10.0
1x95/35 295 300 355 14.9 13.6
1x120/35 335 335 410 18.9 17.2
1x150/35 380 380 485 23.6 21.5
1x185/35 425 435 535 29.1 26.5
1x240/35 485 505 620 37.7 34.4
1x300/35 545 575 705 47.2 43.0
1x400/35 625 680 835 62.9 57.4
1x500/35 695 765 940 78.7 71.2
1x630/35 755 845 1035 99.1 90.4
Application fieldsSingle-core, distribution cable for outdoors use in 3-phaseformation. Installation in pipes and ground/water.
StandardBS 7870-4.10
Rated voltage12.7/22 (24) kV
Flame propagation classThe PE sheath is not flame-retardant
Temperature rangeIn continuous operation max 90ºC. Lowest cable temperatureduring installation: -20ºC. Below 0ºC special precautions must betaken.
Impulse voltage144 kV
Bending radiusAt fixed mounting: 10 x D. At laying: 15 x D
Design
ConductorStranded, round and compacted copper acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nom. thickness = 5.5 mm
Insulation screenExtruded bonded
Concentric conductorAnnealed copper wires
SheathMDPE, black
36
1 CORE
CU-XLPE-CWS-PE 22 kV
www.drakauk.com 01332 34543137
Number of coresx cross-section
of conductormm2
Diameterover insulation
mm
Overall diameter(approx.)
mm
Weight(approx.)kg/100 m
Standarddeliverylength
m
Standarddrumsize
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Numberof cores
x cross-sectionof conductor
mm2
Conductorresistance
Ω/km
Screenresistance
Ω/km
Inductancein trefoil/in
plane*mH/km
CapacitanceµF/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Current ratings conditionsAmbient temperature air: 25ºCGround temperature: 15ºCDepth of burial: 0.7 m
Thermal resistance of soil: 1.0 ºKm/WTrefoil with screen grounded at both endsNominal values unless otherwise specified.
1x70/35 21.8 31 140 500 K14
1x95/35 23.5 33 165 500 K14
1x120/35 24.8 34 195 500 K14
1x150/35 26.4 35 230 500 K14
1x185/35 28.0 37 265 500 K16
1x240/35 30.3 39 325 500 K16
1x300/35 32.6 42 390 500 K18
1x400/35 35.4 46 490 500 K20
1x500/35 38.4 49 590 500 K20
1x630/35 42.0 53 725 500 K22
1x70/35 0.443 0.542 0.42/0.61 0.19 0.8
1x95/35 0.320 0.542 0.40/0.59 0.21 0.8
1x120/35 0.253 0.542 0.39/0.57 0.22 0.9
1x150/35 0.206 0.542 0.37/0.55 0.24 1.0
1x185/35 0.164 0.542 0.36/0.54 0.26 1.0
1x240/35 0.125 0.542 0.34/0.53 0.29 1.2
1x300/35 0.100 0.542 0.33/0.52 0.32 1.3
1x400/35 0.0778 0.542 0.32/0.51 0.36 1.4
1x500/35 0.0605 0.542 0.31/0.50 0.39 1.6
1x630/35 0.0469 0.542 0.30/0.48 0.44 1.8
1x70/35 255 240 295 11.0 10.0
1x95/35 295 300 355 14.9 13.6
1x120/35 335 335 410 18.9 17.2
1x150/35 380 380 485 23.6 21.5
1x185/35 425 435 535 29.1 26.5
1x240/35 485 505 620 37.7 34.4
1x300/35 545 575 705 47.2 43.0
1x400/35 625 680 835 62.9 57.4
1x500/35 695 765 940 78.7 71.2
1x630/35 755 845 1035 99.1 90.4
38
Application fieldsSingle-core, distribution cable for outdoors use in 3-phaseformation. Installation in pipes and ground/water.
StandardBS 7870-1.10
Rated voltage19/33 (36) kV
Flame propagation classThe PE sheath is not flame-retardant
Temperature rangeIn continuous operation max 90ºC. Lowest cable temperatureduring installation: -10ºC. Below 0ºC special precautions must betaken.
Impulse voltage194 kV
Bending radiusAt fixed mounting: 10 x D. At laying: 15 x D
Design
ConductorStranded, round and compacted copper acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nom. thickness = 8.0 mm
Insulation screenExtruded bonded
Concentric conductorAnnealed copper wires
SheathMDPE, black
1 CORE
CU-XLPE-CWS-PE 33 kV
www.drakauk.com 01332 34543139
Number of coresx cross-section
of conductormm2
Diameterover insulation
mm
Overall diameter(approx.)
mm
Weight(approx.)kg/100 m
Standarddeliverylength
m
Standarddrumsize
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Numberof cores
x cross-sectionof conductor
mm2
Conductorresistance
Ω/km
Screenresistance
Ω/km
Inductancein trefoil/in
plane*mH/km
CapacitanceµF/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Current ratings conditionsAmbient temperature air: 25ºCGround temperature: 15ºCDepth of burial: 0.7 m
Thermal resistance of soil: 1.0 ºKm/WTrefoil with screen grounded at both endsNominal values unless otherwise specified.
1x70/35 26.8 36 180 500 K16
1x95/35 28.5 38 225 500 K18
1x120/35 29.8 39 250 500 K18
1x150/35 31.4 40 280 500 K18
1x185/35 33.0 42 295 500 K20
1x240/35 35.3 44 375 500 K20
1x300/35 37.6 47 430 500 K22
1x400/35 40.4 51 525 500 K22
1x500/35 43.4 55 635 500 K22
1x630/35 47.0 58 775 500 K24
1x70/35 0.443 0.542 0.46/0.66 0.14 0.8
1x95/35 0.320 0.542 0.44/0.62 0.16 1.0
1x120/35 0.253 0.542 0.42/0.60 0.17 1.0
1x150/35 0.206 0.542 0.40/0.59 0.18 1.1
1x185/35 0.164 0.542 0.39/0.57 0.20 1.2
1x240/35 0.125 0.542 0.37/0.55 0.22 1.3
1x300/35 0.100 0.542 0.36/0.54 0.24 1.4
1x400/35 0.0778 0.542 0.34/0.53 0.26 1.6
1x500/35 0.0605 0.542 0.33/0.49 0.29 1.7
1x630/35 0.0469 0.542 0.32/0.48 0.32 1.9
1x70/35 255 240 295 11.0 10.0
1x95/35 295 300 355 14.9 13.6
1x120/35 335 335 410 18.9 17.2
1x150/35 380 380 485 23.6 21.5
1x185/35 425 435 535 29.1 26.5
1x240/35 485 505 620 37.7 34.4
1x300/35 545 575 705 47.2 43.0
1x400/35 625 680 835 62.9 57.4
1x500/35 695 765 940 78.7 71.2
1x630/35 755 845 1035 99.1 90.4
Application fields3-core cable. distribution cable for outdoors use. Installation inpipes and ground.
StandardBS 7870-4.10
Rated voltage6.35/11 (12) kV
Fire propagation classThe PE sheath is not flame-retardant
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during laying -20ºC. Below 0ºC special precautionsmust be taken.
Impulse voltage95 kV
Bending radiusAt fixed mounting: 10 x D. At laying: 15 x D
Design
ConductorStranded, round copper acc. to IEC 60228 class 22
Conductor screenExtruded
InsulationXLPE, nom. thickness = 3.4 mm
Insulation screenExtruded bonded
Concentric conductorAnnealed copper wires
SheathMDPE, black
Laying upThree stranded single-core cables in triplex formation
40
3 CORE
CU-XLPE-CWS-PE TRIPLEX 11 kV
www.drakauk.com 01332 34543141
Number of coresx cross-section of
conductormm2
Conductorresistance
Ω/km
Screenresistance
Ω/km
InductancemH/km
CapacitanceµF/km
Charging current/phaseA/km
Number of cores xcross-section of
conductormm2
Current rating atcore temp. 65 ºC
in groundA
Current rating atcore temp. 65 ºC
in airA
Current rating atcore temp. 90 ºC
in airA
Max. short-circuitcurrent on the
conductor during 1 sat initial temp.
65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Number ofcores x
crosssectionof conductor
mm2
Diameterover insulation
mm
Diameterover sheath
(approx)
Overalldiameter(approx.)
mm
Weight(approx.)kg/100 m
Standarddelivery length
m
Standard drumsize
Electrical data at +20 °C
Current rating
*Current ratings conditionsAmbient temperature air: 25ºCGround temperature: 15ºCDepth of burial: 0.7 m
Thermal resistance of soil: 1.0 ºKm/WScreen grounded at both ends.Nominal values unless otherwise specified.
3x1x70/35 17.6 27 59 375 500 K24
3x1x95/35 19.3 29 63 450 500 K24
3x1x120/35 20.6 30 65 540 500 K24
3x1x150/35 22.2 32 69 645 500 K26
3x1x185/35 23.8 34 74 750 500 K28
3x1x240/35 26.1 36 78 915 500 K28
3x1x70/35 0.268 0.542 0.40 0.27 1.1
3x1x95/35 0.193 0.542 0.38 0.31 1.2
3x1x120/35 0.153 0.542 0.36 0.33 1.3
3x1x150/35 0.124 0.542 0.35 0.36 1.4
3x1x185/35 0.0991 0.542 0.34 0.40 1.6
3x1x240/35 0.0754 0.542 0.33 0.44 1.8
3x1x70/35 255 240 295 11.0 10.0
3x1x95/35 295 300 355 14.9 13.6
3x1x120/35 335 335 410 18.9 17.2
3x1x150/35 380 380 485 23.6 21.5
3x1x185/35 425 425 535 29.1 26.5
3x1x240/35 485 505 620 37.7 34.4
Application fields3-core cable. distribution cable for outdoors use. Installation inpipes and ground.
StandardBS 7870-4.10
Rated voltage12.7/22 (24) kV
Fire propagation classThe PE sheath is not flame-retardant
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during laying -20ºC. Below 0ºC special precautionsmust be taken.
Impulse voltage144 kV
Bending radiusAt fixed mounting: 10 x D. At laying: 15 x D
Design
ConductorStranded, round copper acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nom. thickness = 5.5 mm
Insulation screenExtruded bonded
Concentric conductorAnnealed copper wires
SheathMDPE, black
Laying upThree stranded single-core cables in triplex formation
42
3 CORE
CU-XLPE-CWS-PE TRIPLEX 22 kV
www.drakauk.com 01332 34543143
Number of coresx cross-section of
conductormm2
Conductorresistance
Ω/km
Screenresistance
Ω/km
InductancemH/km
CapacitanceµF/km
Charging current/phaseA/km
Number of cores xcross-section of
conductormm2
Current rating atcore temp. 65 ºC
in groundA
Current rating atcore temp. 65 ºC
in airA
Current rating atcore temp. 90 ºC
in airA
Max. short-circuitcurrent on the
conductor during 1 sat initial temp.
65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Number ofcores x
crosssectionof conductor
mm2
Diameterover insulation
mm
Diameterover sheath
(approx)
Overalldiameter(approx.)
mm
Weight(approx.)kg/100 m
Standarddelivery length
m
Standard drumsize
Electrical data at +20 °C
Current rating
*Current ratings conditionsAmbient temperature air: 25ºCGround temperature: 15ºCDepth of burial: 0.7 m
Thermal resistance of soil: 1.0 ºKm/WScreen grounded at both ends.Nominal values unless otherwise specified.
3x1x70/35 21.8 31 67 285 500 K26
3x1x95/35 23.5 33 72 315 500 K26
3x1x120/35 24.8 34 74 345 500 K26
3x1x150/35 26.4 35 76 405 500 K26
3x1x185/35 28.0 37 80 450 500 K28
3x1x240/35 30.3 39 85 510 500 K28
3x1x70/35 0.268 0.542 0.42 0.19 0.8
3x1x95/35 0.193 0.542 0.40 0.21 0.8
3x1x120/35 0.153 0.542 0.39 0.22 0.9
3x1x150/35 0.124 0.542 0.37 0.24 1.0
3x1x185/35 0.0991 0.542 0.36 0.26 1.0
3x1x240/35 0.0754 0.542 0.34 0.29 1.2
3x1x70/35 255 240 295 11.0 10.0
3x1x95/35 295 300 355 14.9 13.6
3x1x120/35 335 335 410 18.9 17.2
3x1x150/35 380 380 485 23.6 21.5
3x1x185/35 425 425 535 29.1 26.5
3x1x240/35 485 505 620 37.7 34.4
Application fields3-core cable. distribution cable for outdoors use. Installation inpipes and ground.
StandardBS 7870-4.10
Rated voltage19/33 (36) kV
Fire propagation classThe PE sheath is not flame-retardant
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during laying -20ºC. Below 0ºC special precautionsmust be taken.
Impulse voltage194 kV
Bending radiusAt fixed mounting: 10 x D. At laying: 15 x D
Design
ConductorStranded, round copper acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nom. thickness = 8.0 mm
Insulation screenExtruded bonded
Concentric conductorAnnealed copper wires
SheathMDPE, black
Laying upThree stranded single-core cables in triplex formation
44
3 CORE
CU-XLPE-CWS-PE TRIPLEX 33 kV
www.drakauk.com 01332 34543145
Number of coresx cross-section of
conductormm2
Conductorresistance
Ω/km
Screenresistance
Ω/km
InductancemH/km
CapacitanceµF/km
Charging current/phaseA/km
Number of cores xcross-section of
conductormm2
Current rating atcore temp. 65 ºC
in groundA
Current rating atcore temp. 65 ºC
in airA
Current rating atcore temp. 90 ºC
in airA
Max. short-circuitcurrent on the
conductor during 1 sat initial temp.
65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Number ofcores x
crosssectionof conductor
mm2
Diameterover insulation
mm
Diameterover sheath
(approx)
Overalldiameter(approx.)
mm
Weight(approx.)kg/100 m
Standarddelivery length
m
Standard drumsize
Electrical data at +20 °C
Current rating
*Current ratings conditionsAmbient temperature air: 25ºCGround temperature: 15ºCDepth of burial: 0.7 m
Thermal resistance of soil: 1.0 ºKm/WScreen grounded at both ends.Nominal values unless otherwise specified.
3x1x70/35 26.8 36 78 540 500 K28
3x1x95/35 28.5 38 82 675 500 K30
3x1x120/35 29.8 39 85 750 500 K30
3x1x150/35 31.4 40 87 840 500 K30
3x1x185/35 33.0 42 91 885 500 K30
3x1x240/35 35.3 44 95 1125 500 K30
3x1x70/35 0.268 0.542 0.46 0.14 0.8
3x1x95/35 0.193 0.542 0.44 0.16 1.0
3x1x120/35 0.153 0.542 0.42 0.17 1.0
3x1x150/35 0.124 0.542 0.40 0.18 1.1
3x1x185/35 0.0991 0.542 0.39 0.20 1.2
3x1x240/35 0.0754 0.542 0.37 0.22 1.3
3x1x70/35 255 240 295 11.0 10.0
3x1x95/35 295 300 355 14.9 13.6
3x1x120/35 335 335 410 18.9 17.2
3x1x150/35 380 380 485 23.6 21.5
3x1x185/35 425 425 535 29.1 26.5
3x1x240/35 485 505 620 37.7 34.4
Application fieldsSingle-core, distribution cable for outdoors use in 3-phaseformation. Installation in pipes and ground/water.
StandardBS 7870-4.10
Rated voltage6.35/11 (12) kV
Flame propagation classThe PE sheath is not flame-retardant
Temperature rangeIn continuous operation max 90ºC. Lowest cable temperatureduring installation: -20ºC. Below 0ºC special precautions must betaken.
Impulse voltage95 kV
Bending radiusAt fixed mounting: 10 x D. At laying: 15 x D
Design
ConductorStranded, round and compacted aluminium acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nom. thickness = 3.4 mm
Insulation screenExtruded bonded
Concentric conductorAnnealed copper wires
SheathMDPE, black
46
1 CORE
AL-XLPE-CWS-PE 11 kV
www.drakauk.com 01332 34543147
Number of coresx cross-section
of conductormm2
Diameterover insulation
mm
Overall diameter(approx.)
mm
Weight(approx.)kg/100 m
Standarddeliverylength
m
Standarddrumsize
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Numberof cores
x cross-sectionof conductor
mm2
Conductorresistance
Ω/km
Screenresistance
Ω/km
Inductancein trefoil/in
plane*mH/km
CapacitanceµF/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Current ratings conditionsAmbient temperature air: 25ºCGround temperature: 15ºCDepth of burial: 0.7 m
Thermal resistance of soil: 1.0 ºKm/WTrefoil with screen grounded at both endsNominal values unless otherwise specified.
1x70/35 17.6 27 80 500 K14
1x95/35 19.3 29 90 500 K14
1x120/35 20.6 30 100 500 K14
1x150/35 22.2 32 120 500 K14
1x185/35 23.8 34 135 500 K16
1x240/35 26.1 36 150 500 K16
1x300/35 28.4 38 175 500 K18
1x400/35 31.2 43 220 500 K20
1x500/35 34.2 45 255 500 K20
1x630/35 37.8 50 300 500 K22
1x70/35 0.443 0.542 0.40/0.58 0.27 1.1
1x95/35 0.320 0.542 0.38/0.56 0.31 1.2
1x120/35 0.253 0.542 0.36/0.55 0.33 1.3
1x150/35 0.206 0.542 0.35/0.54 0.36 1.4
1x185/35 0.164 0.542 0.34/0.53 0.40 1.6
1x240/35 0.125 0.542 0.33/0.51 0.44 1.8
1x300/35 0.100 0.542 0.31/0.50 0.49 2.0
1x400/35 0.0778 0.542 0.31/0.49 0.55 2.2
1x500/35 0.0605 0.542 0.29/0.48 0.60 2.4
1x630/35 0.0469 0.542 0.29/0.47 0.68 2.7
1x70/35 200 190 235 7.2 6.6
1x95/35 235 230 280 9.9 8.9
1x120/35 265 265 325 12.4 11.3
1x150/35 300 300 370 15.6 14.2
1x185/35 330 345 425 19.2 17.5
1x240/35 385 400 490 25.0 22.7
1x300/35 435 460 565 31.2 28.3
1x400/35 510 555 680 41.6 37.8
1x500/35 570 635 775 52.0 47.2
1x630/35 635 720 880 65.6 59.5
Application fieldsSingle-core, distribution cable for outdoors use in 3-phaseformation. Installation in pipes and ground/water.
StandardBS 7870-4.10
Rated voltage12.7/22 (24) kV
Flame propagation classThe PE sheath is not flame-retardant
Temperature rangeIn continuous operation max 90ºC. Lowest cable temperatureduring installation: -20ºC. Below 0ºC special precautions must betaken.
Impulse voltage144 kV
Bending radiusAt fixed mounting: 10 x D. At laying: 15 x D
Design
ConductorStranded, round and compacted aluminium acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nom. thickness = 5.5 mm
Insulation screenExtruded bonded
Concentric conductorAnnealed copper wires
SheathMDPE, black
48
1 CORE
AL-XLPE-CWS-PE 22 kV
www.drakauk.com 01332 34543149
Number of coresx cross-section
of conductormm2
Diameterover insulation
mm
Overall diameter(approx.)
mm
Weight(approx.)kg/100 m
Standarddeliverylength
m
Standarddrumsize
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Numberof cores
x cross-sectionof conductor
mm2
Conductorresistance
Ω/km
Screenresistance
Ω/km
Inductancein trefoil/in
plane*mH/km
CapacitanceµF/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Current ratings conditionsAmbient temperature air: 25ºCGround temperature: 15ºCDepth of burial: 0.7 m
Thermal resistance of soil: 1.0 ºKm/WTrefoil with screen grounded at both endsNominal values unless otherwise specified.
1x70/35 21.8 31 95 500 K14
1x95/35 23.5 33 105 500 K14
1x120/35 24.8 34 115 500 K14
1x150/35 26.4 35 135 500 K14
1x185/35 28.0 37 150 500 K16
1x240/35 30.3 39 170 500 K16
1x300/35 32.6 42 195 500 K18
1x400/35 35.4 46 245 500 K20
1x500/35 38.4 49 280 500 K20
1x630/35 42.0 53 325 500 K22
1x70/35 0.443 0.542 0.42/0.61 0.19 0.8
1x95/35 0.320 0.542 0.40/0.59 0.21 0.8
1x120/35 0.253 0.542 0.39/0.57 0.22 0.9
1x150/35 0.206 0.542 0.37/0.55 0.24 1.0
1x185/35 0.164 0.542 0.36/0.54 0.26 1.0
1x240/35 0.125 0.542 0.34/0.53 0.29 1.2
1x300/35 0.100 0.542 0.33/0.52 0.32 1.3
1x400/35 0.0778 0.542 0.32/0.51 0.36 1.4
1x500/35 0.0605 0.542 0.31/0.50 0.39 1.6
1x630/35 0.0469 0.542 0.30/0.48 0.44 1.8
1x70/35 200 190 235 7.2 6.6
1x95/35 235 230 280 9.9 8.9
1x120/35 265 265 325 12.4 11.3
1x150/35 300 300 370 15.6 14.2
1x185/35 330 345 425 19.2 17.5
1x240/35 385 400 490 25.0 22.7
1x300/35 435 460 565 31.2 28.3
1x400/35 510 555 680 41.6 37.8
1x500/35 570 635 775 52.0 47.2
1x630/35 635 720 880 65.6 59.5
Application fieldsSingle-core, distribution cable for outdoors use in 3-phaseformation. Installation in pipes and ground/water.
StandardBS 7870-1.10
Rated voltage19/33 (36) kV
Flame propagation classThe PE sheath is not flame-retardant
Temperature rangeIn continuous operation max 90ºC. Lowest cable temperatureduring installation: -20ºC. Below 0ºC special precautions must betaken.
Impulse voltage194 kV
Bending radiusAt fixed mounting: 10 x D. At laying: 15 x D
Design
ConductorStranded, round and compacted aluminium acc. to IEC 60228 class 2
Conductor screenExtruded
InsulationXLPE, nom. thickness = 8.0 mm
Insulation screenExtruded bonded
Concentric conductorAnnealed copper wires
SheathMDPE, black
50
1 CORE
AL-XLPE-CWS-PE 33 kV
www.drakauk.com 01332 34543151
Number of coresx cross-section
of conductormm2
Diameterover insulation
mm
Overall diameter(approx.)
mm
Weight(approx.)kg/100 m
Standarddeliverylength
m
Standarddrumsize
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Numberof cores
x cross-sectionof conductor
mm2
Conductorresistance
Ω/km
Screenresistance
Ω/km
Inductancein trefoil/in
plane*mH/km
CapacitanceµF/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Current ratings conditionsAmbient temperature air: 25ºCGround temperature: 15ºCDepth of burial: 0.7 m
Thermal resistance of soil: 1.0 ºKm/WTrefoil with screen grounded at both endsNominal values unless otherwise specified.
1x70/35 26.8 36 120 500 K16
1x95/35 28.5 38 145 500 K18
1x120/35 29.8 39 155 500 K18
1x150/35 31.4 40 165 500 K18
1x185/35 33.0 42 180 500 K20
1x240/35 35.3 44 220 500 K20
1x300/35 37.6 47 235 500 K22
1x400/35 40.4 51 280 500 K22
1x500/35 43.4 55 325 500 K22
1x630/35 47.0 58 375 500 K24
1x70/35 0.443 0.542 0.46/0.66 0.14 0.8
1x95/35 0.320 0.542 0.44/0.62 0.16 1.0
1x120/35 0.253 0.542 0.42/0.60 0.17 1.0
1x150/35 0.206 0.542 0.40/0.59 0.18 1.1
1x185/35 0.164 0.542 0.39/0.57 0.20 1.2
1x240/35 0.125 0.542 0.37/0.55 0.22 1.3
1x300/35 0.100 0.542 0.36/0.54 0.24 1.4
1x400/35 0.0778 0.542 0.34/0.53 0.26 1.6
1x500/35 0.0605 0.542 0.33/0.49 0.29 1.7
1x630/35 0.0469 0.542 0.32/0.48 0.32 1.9
1x70/35 200 190 235 7.2 6.6
1x95/35 235 230 280 9.9 8.9
1x120/35 265 265 325 12.4 11.3
1x150/35 300 300 370 15.6 14.2
1x185/35 330 345 425 19.2 17.5
1x240/35 385 400 490 25.0 22.7
1x300/35 435 460 565 31.2 28.3
1x400/35 510 555 680 41.6 37.8
1x500/35 570 635 775 52.0 47.2
1x630/35 635 720 880 65.6 59.5
Application fields3-core cable. distribution cable for outdoors use. Installation inpipes and ground.
StandardBS 7870-4.10
Rated voltage6.35/11 (12) kV
Flame propagation classThe PE sheath is not flame-retardant
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during installation: -20ºC. Below 0ºC specialprecautions must be taken.
Impulse voltage95 kV
Bending radiusAt fixed mounting: 10 x D. At laying: 15 x D
Design
ConductorSolid, round aluminium acc. to IEC 60228 class 1
Conductor screenExtruded
InsulationXLPE, nom. thickness = 3.4 mm
Insulation screenExtruded bonded
Concentric conductorAnnealed copper wires
SheathMDPE, black
Laying upThree stranded single-core cables in triplex formation
52
3 CORE
AL-XLPE-CWS-PE TRIPLEX 11 kV
www.drakauk.com 01332 34543153
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Numberof cores
x cross-sectionof conductor
mm2
Conductorresistance
Ω/km
Screenresistance
Ω/km
Inductancein trefoil/in
plane*mH/km
CapacitanceµF/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Current ratings conditionsAmbient temperature air: 25ºCGround temperature: 15ºCDepth of burial: 0.7 m
Thermal resistance of soil: 1.0 ºKm/WScreen grounded at both ends.Nominal values unless otherwise specified.
Number ofcores x
crosssectionof conductor
mm2
Diameterover insulation
mm
Diameterover sheath
(approx)
Overalldiameter(approx.)
mm
Weight(approx.)kg/100 m
Standarddelivery length
m
Standard drumsize
3x1x70/35 200 190 235 7.2 6.6
3x1x95/35 235 230 280 9.9 8.9
3x1x120/35 265 265 325 12.4 11.3
3x1x150/35 300 300 370 15.6 14.2
3x1x185/35 330 345 425 19.2 17.5
3x1x240/35 385 400 490 25.0 22.7
3x1x70/35 0.443 0.542 0.40 0.27 1.1
3x1x95/35 0.320 0.542 0.38 0.31 1.2
3x1x120/35 0.253 0.542 0.36 0.33 1.3
3x1x150/35 0.206 0.542 0.35 0.36 1.4
3x1x185/35 0.164 0.542 0.34 0.40 1.6
3x1x240/35 0.125 0.542 0.33 0.44 1.8
3x1x70/35 17.6 27 59 240 500 K24
3x1x95/35 19.3 29 63 270 500 K24
3x1x120/35 20.6 30 65 300 500 K24
3x1x150/35 22.2 32 69 360 500 K26
3x1x185/35 23.8 34 74 405 500 K28
3x1x240/35 26.1 36 78 450 500 K28
Application fields3-core cable. distribution cable for outdoors use. Installation inpipes and ground.
StandardBS 7870-4.10
Rated voltage12.7/22 (24) kV
Flame propagation classThe PE sheath is not flame-retardant
Temperature rangeIn continuous operation max. conductor temp 90ºC. Lowest cabletemperature during laying -20ºC. Below 0ºC special precautionsmust be taken.
Impulse voltage144 kV
Bending radiusAt fixed mounting: 10 x D. At laying: 15 x D
Design
ConductorSolid, round aluminium acc. to IEC 60228 class 1
Conductor screenExtruded
InsulationXLPE, nom. thickness = 5.5 mm
Insulation screenExtruded bonded
Concentric conductorAnnealed copper wires
SheathMDPE, black
Laying upThree stranded single-core cables in triplex formation
54
3 CORE
AL-XLPE-CWS-PE TRIPLEX 22 kV
www.drakauk.com 01332 34543155
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Numberof cores
x cross-sectionof conductor
mm2
Conductorresistance
Ω/km
Screenresistance
Ω/km
Inductancein trefoil/in
plane*mH/km
CapacitanceµF/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Current ratings conditionsAmbient temperature air: 25ºCGround temperature: 15ºCDepth of burial: 0.7 m
Thermal resistance of soil: 1.0 ºKm/WScreen grounded at both ends.Nominal values unless otherwise specified.
Number ofcores x
crosssectionof conductor
mm2
Diameterover insulation
mm
Diameterover sheath
(approx)
Overalldiameter(approx.)
mm
Weight(approx.)kg/100 m
Standarddelivery length
m
Standard drumsize
3x1x70/35 21.8 31 67 285 500 K26
3x1x95/35 23.5 33 72 315 500 K26
3x1x120/35 24.8 34 74 345 500 K26
3x1x150/35 26.4 35 76 405 500 K26
3x1x185/35 28.0 37 80 450 500 K28
3x1x240/35 30.3 39 85 510 500 K28
3x1x70/35 0.443 0.542 0.42 0.19 0.8
3x1x95/35 0.320 0.542 0.40 0.21 0.8
3x1x120/35 0.253 0.542 0.39 0.22 0.9
3x1x150/35 0.206 0.542 0.37 0.24 1.0
3x1x185/35 0.164 0.542 0.36 0.26 1.0
3x1x240/35 0.125 0.542 0.34 0.29 1.2
3x1x70/35 200 190 235 7.2 6.6
3x1x95/35 235 230 280 9.9 8.9
3x1x120/35 265 265 325 12.4 11.3
3x1x150/35 300 300 370 15.6 14.2
3x1x185/35 330 345 425 19.2 17.5
3x1x240/35 385 400 490 25.0 22.7
Application fields3-core cable. distribution cable for outdoors use. Installation inpipes and ground.
StandardBS 7870-4.10
Rated voltage19/33 (36) kV
Flame propagation classThe PE sheath is not flame-retardant
Temperature rangeIn continuous operation max. conductor temp 90 ºC. Lowest cabletemperature during laying -20ºC. Below 0ºC special precautionsmust be taken.
Impulse voltage194 kV
Bending radiusAt fixed mounting: 10 x D. At laying: 15 x D
Design
ConductorSolid, round aluminium acc. to IEC 60228 class 1
Conductor screenExtruded
InsulationXLPE, nom. thickness = 8.0 mm
Insulation screenExtruded bonded
Concentric conductorAnnealed copper wires
SheathMDPE, black
Laying upThree stranded single-core cables in triplex formation
56
3 CORE
AL-XLPE-CWS-PE TRIPLEX 33 kV
www.drakauk.com 01332 34543157
Number of cores xcrosssection
ofconductor
mm2
Current rating atcore temp.
65 ºC in ground*A
Current rating atcore temp. 65 ºC
in air*A
Current rating atcore temp. 90 ºC
in air*A
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 65 ºC kA
Max. short-circuitcurrent on the
conductor during 1s at initial
temp. 90 ºC kA
Numberof cores
x cross-sectionof conductor
mm2
Conductorresistance
Ω/km
Screenresistance
Ω/km
Inductancein trefoil/in
plane*mH/km
CapacitanceµF/km
Chargingcurrent/phase
A/km
Electrical data at +20 °C
Current rating
*Current ratings conditionsAmbient temperature air: 25ºCGround temperature: 15ºCDepth of burial: 0.7 m
Thermal resistance of soil: 1.0 ºKm/WScreen grounded at both ends.Nominal values unless otherwise specified.
Number ofcores x
crosssectionof conductor
mm2
Diameterover insulation
mm
Diameterover sheath
(approx)
Overalldiameter(approx.)
mm
Weight(approx.)kg/100 m
Standarddelivery length
m
Standard drumsize
3x1x70/35 26.8 36 78 360 500 K28
3x1x95/35 28.5 38 82 435 500 K30
3x1x120/35 29.8 39 85 465 500 K30
3x1x150/35 31.4 40 87 495 500 K30
3x1x185/35 33.0 42 91 540 500 K30
3x1x240/35 35.3 44 95 660 500 K30
3x1x70/35 0.443 0.542 0.46 0.14 0.8
3x1x95/35 0.320 0.542 0.44 0.16 1.0
3x1x120/35 0.253 0.542 0.42 0.17 1.0
3x1x150/35 0.206 0.542 0.40 0.18 1.1
3x1x185/35 0.164 0.542 0.39 0.20 1.2
3x1x240/35 0.125 0.542 0.37 0.22 1.3
3x1x70/35 200 190 235 7.2 6.6
3x1x95/35 235 230 280 9.9 8.9
3x1x120/35 265 265 325 12.4 11.3
3x1x150/35 300 300 370 15.6 14.2
3x1x185/35 330 345 425 19.2 17.5
3x1x240/35 385 400 490 25.0 22.7
THEWORLD’SMOST
TRUSTEDCABLEBRANDAt Draka we work hard to
drive standards of design and
manufacture higher so that our
customers can enjoy the benefits
of products they can rely on,
totally. If you share the same
high standards, always specify
the brand you can trust – Draka.