Dosing system for dosing fire fighting foam standard unit of 0,5 to 24 l/min Kompletteinheit.

6
Dosing system for dosing fire fighting foam standard unit of 0,5 to 24 l/min Kompletteinheit

Transcript of Dosing system for dosing fire fighting foam standard unit of 0,5 to 24 l/min Kompletteinheit.

Page 1: Dosing system for dosing fire fighting foam standard unit of 0,5 to 24 l/min Kompletteinheit.

Dosing system for dosing fire fighting foamstandard unit of 0,5 to 24 l/min

Kompletteinheit

Page 2: Dosing system for dosing fire fighting foam standard unit of 0,5 to 24 l/min Kompletteinheit.

Dosing system for dosing fire fighting foamstandard unit of 0,5 to 24 l/min

→ highest foam performance up to 24 l/min at 24 V DC

→ world wide unique foam dosing system with “extern prime function“

→ high precision dosing by using VS flow meter measurement

→ no flushing necessary

→ large extent independent of viscosity

→ easiest handling

→ meet greatest demands by using external gear pumps

→ unique pressure dosing unit with the widest available range in one unit

→ continuously adjustable in ratio water stream to foam.

Page 3: Dosing system for dosing fire fighting foam standard unit of 0,5 to 24 l/min Kompletteinheit.

Dosing system for dosing fire fighting foamstandard unit of 0,5 to 24 l/min

technical data:

foam dosing pump: external gear pump made in bronze with internal parts in stainless steel

drive: 24 V DC / 12 V DC / AC-motors

kind of dosing: volumetric dosing by injecting foam into the fire water stream

flow measurement: fire water AND foam medium

measurement range: fire water: 50 - 2400 l/min // faom: 0.5 – 24 l/min

dosing range: 0,1 - 6 % - infinitely variable

foam: Class A and B; inclusive shear thinning foam

special solution with 100 bar inlet pressure possible

Page 4: Dosing system for dosing fire fighting foam standard unit of 0,5 to 24 l/min Kompletteinheit.

Dosing system for dosing fire fighting foamfurther units – still growing…

Kompletteinheit BILD

Page 5: Dosing system for dosing fire fighting foam standard unit of 0,5 to 24 l/min Kompletteinheit.

Dosing system for dosing fire fighting foaminclusive flow measurement via VS flow meter

available sizes:

dosing range drive power

0,25 - 10 l/min DC-motor 12 VDC 0,55 kW

0,4 - 16 l/min DC-motor 12 VDC 0,55 kW

0,5 - 24 l/min DC-motor 24 VDC 0,75 kW

0,9 - 36 l/min AC-motor with FD / 230 VAC 1,5 kW

Page 6: Dosing system for dosing fire fighting foam standard unit of 0,5 to 24 l/min Kompletteinheit.

Dosing system for dosing fire fighting foamwithout flow measurement

available sizes:

dosing range drive power

12 - 60 l/min AC-motor with FD / 400 VAC 3 kWor hydraulic-motor

34 - 170 l/min hydraulic-motor 15 kW

100 - 500 l/min hydraulic-motor 37 kW

140 - 700 l/min hydraulic-motor 50 kW