    5-75 L/Hr Dosing Unit Issue No 1 May 2007

    The information contained in this document is provided free of charge and is based on technical data that Innospec believes to be reliable. It is intendedfor use by persons having technical skill and at their own discretion and risk. Innospec accepts no liability for any loss, damage or expense arising from, orin connection with, the use of the information. Furthermore, none of the contents of this publication should be taken as a licence to operate under anypatent, nor as a recommendation to infringe any patent.

    Customer Technical Service - Engineering

    Installation, Commissioningand Technical Informationfor the 5 - 75 L/HrMarine Dosing Unit

    Dosing System Manual

    Innospec LimitedPO Box 17

    Oil Sites RoadEllesmere Port

    Cheshire CH65 4EY, U.K.tel: +44 (0)151 355 3611fax: +44 (0)151 356 2349

  • 8/18/2019 dosing manual.pdf

    2/27

     

  • 8/18/2019 dosing manual.pdf

    3/27

     

    5-75 L/Hr Dosing Unit Page 2 of 12 Issue 1 May 2007

    Dosing System Manual

     

    Contents

    Description Page No.

     

    System Specifications 3

    Functional Description 3

    General Layout Drawing 4

    Equipment Overview Drawing 5

    Parts Listing 6

    Electrical Wiring Drawings 7

    Injector Layout Drawing 8

    Installation Procedure 9 - 10

    Commissioning Procedure 10 - 11

    Spare Parts 11

    Technical Information and dosing graphs 12

  • 8/18/2019 dosing manual.pdf

    4/27

     

    5-75 L/Hr Dosing Unit Page 3 of 12 Issue 1 May 2007

    Dosing System Manual

    System Specifications 

    Unit Dimensions : 500 (H) x 400 (W) x 300 (D) (mm)

    Packaged Dimensions: 600 (H) x 500 (W) x 400 (D) (mm) 

    Packaged Weight : ~ 42 Kg’s 

    Power Supply : 115 – 230 – 400 – 440 VAC 50/60 Hz 

    Nom. Back Pressure: 2.0 Barg 

    Maximum Back Pressure : 4.0 Barg at 50 Hz; 3.5 Barg at 60 Hz 

    Functional Description

    The INNOSPEC Marine dosing system is designed to dose into the ship’s main bunkerline. The systemshould be switched ON at start bunkering and switched OFF at end of bunkering of fuel oil.

     As an alternative the system can dose into the suction filter of the transferpump, for automaticStart/Stop an optional External Start/Stop cabinet has to be installed.

    To test the dosing pump or to bleed the system, see under part commissioning (page 10 – 11).

    ALWAYS ENSURE THAT THE CORRECT VOLTAGE IS CONNECTED!

    Power Supply: 115 – 230 – 400 – 440 VAC; 50/60 Hz.

    The selection switch (12) on switch cabinet (11) has to be set accordingly.

  • 8/18/2019 dosing manual.pdf

    5/27

     

    5-75 L/Hr Dosing Unit Page 4 of 12 Issue 1 May 2007

    Dosing System Manual

    General Lay-Out Drawing

  • 8/18/2019 dosing manual.pdf

    6/27

     

    5-75 L/Hr Dosing Unit Page 5 of 12 Issue 1 May 2007

    Dosing System Manual

    Equipment Overview 

  • 8/18/2019 dosing manual.pdf

    7/27

     

    5-75 L/Hr Dosing Unit Page 6 of 12 Issue 1 May 2007

    Dosing System Manual

    Equipment List 

    ITEM QTY DESCRIPTION TYPE ARTICLE CODE

    1 1 Dosing pump DMX 75-4 221-75-10198 GRU-DMX75-4PVT

    2 1 Flow counter VZO 8 VIT-9263000

    3 1 Bleed valve Ball valve 8 mm ALA-74500808

    4 1 Check valve spring loaded Check valve 10 mm; 1 barg SO-47321-10-1 bar

    5 1 Injector with check valve assemblyInjector 1/2"x1/2" Checkvalve 1/2"; 1 barg

     AQ-10700200 +SO-7300-1/2”-1 bar

    6 - 7 1 Suction assemblyHYD-1271983-100+TEE-21042300+AQ-10700185

     AQ-10700XXX

    8 1 Drum closer + Quick connector AQ-10700111+GEH-940206+GEH-940106VIT

     AQ-107000XX

    9 1 Drum Breather Breather 3/4" AQ-10700070

    10 1 Main switch in boxMain switch 3 Phase 20 Amp Ye/Rd

    SOL-5960892

    11 1 Switch cabinet incl. transformer CI2216A + WEC-30000020 AQ-1070XXXX

    12 1 Selection switch M220 61070 219M1 SOL-5960170

  • 8/18/2019 dosing manual.pdf

    8/27

     

    5-75 L/Hr Dosing Unit Page 7 of 12 Issue 1 May 2007

    Dosing System Manual

    Electrical Wiring Drawings 

  • 8/18/2019 dosing manual.pdf

    9/27

     

    5-75 L/Hr Dosing Unit Page 8 of 12 Issue 1 May 2007

    Dosing System Manual

    Injector Layout Drawing 

  • 8/18/2019 dosing manual.pdf

    10/27

     

    5-75 L/Hr Dosing Unit Page 9 of 12 Issue 1 May 2007

    Dosing System Manual

    Installation Procedure

    Securely mount the dosing cabinet, using the fixing brackets supplied, to a suitable location in the vicinity of thefuel transfer pumps.

    Ensure that the Octamar™ product drum is secured tightly to the ship build so free movement isnot possible.

    SECURE

    THE

    OCTAMAR™

    PRODUCT

    DRUM 

     Assemble the suction, bleed and discharge hoses using the components as shown in the EquipmentOverview (page 5).

  • 8/18/2019 dosing manual.pdf

    11/27

     

    5-75 L/Hr Dosing Unit Page 10 of 12 Issue 1 May 2007

    Dosing System Manual

     A. Connect the pump suction side with flexible hose to the suction assembly and drum closer with

    suction filter (6, 7, 8).

    Note: The suction hose should be kept as short as possible (2 metres).

    B. Mount the suction hose with suction assembly, drum-closer and suction filter to the product drum.

    Note: Ensure that the drum-closer is screwed in completely so that the suction valve and filter willhang 1 cm above the bottom of the drum.

    Important: The vertical distance (height) between pump unit and bottom of the product drum mustnot exceed 2 meters (6,5 feet).

    C. Connect the pump discharges with flexible hoses to the injection assembly and fit the injection nozzle in the

    main bunkerline.

    D. Connect the short air bleed hose and place a small container beneath the outlet from the bleed discharge.

    E. Connect a power supply cable to main switch in box (10). The power supply is 2 phases 115 or 230 or 400

    or 440 VAC 50/60 Hz. The power supply is connected directly to the main switch at terminal 1 and 3 and

    Earth (PE).

    F. Before powering up the system check if the selection switch (12) is set at right voltage level.

    Commissioning ProcedureThe INNOSPEC Marine dosing system is designed to dose into the ship’s main bunkerline. The system

    should be switched ON at start bunkering and switched OFF at end of bunkering of fuel oil.

     As an alternative the system can dose into the suction filter of the transferpump, for automaticStart/Stop an optional External Start/Stop cabinet has to be installed.

    Prior to putting the dosage unit into service, the system has to be primed and bled of air. After primingof the unit is completed, setting of the correct chemical dosage rate (flow rate in L/hr) will also be required. You

    will be informed of the recommended flow rate for your installation prior to commissioning.

    Please follow the instructions below.

     A. Make sure all connections are tight.

    B. Make sure the dosing system is switched ON at main switch (10).

    C. Make sure the stroke length of the dosage pump is set at 100%. This is the large knob on the pump

    console. Unscrew the locking screw before turnig the knob.

    D. Open the air bleed valve (3)

  • 8/18/2019 dosing manual.pdf

    12/27

     

    5-75 L/Hr Dosing Unit Page 11 of 12 Issue 1 May 2007

    Dosing System Manual

    E. After a few minutes, chemical will discharge from the air bleed hose.

    F. When there is a constant flow of chemical from the air bleed hose, shut air bleed valve (3).

    G. Adjust the flow rate with the large knob on the pump. See dosing graph on page 12. The knob can be set

    from 0 – 100 % and is locked tight using a locking screw. Loosen this screw before altering the setting.

    Tighten the screw after setting of the desired flowrate. The flow rate can be checked with the flow counter

    (2).

    H. Switch OFF the power to the dosage unit and close the panel door.

    Note: Re-priming of the pump may be necessary after changing the product drum and/or if the pump and hosesare disconnected for maintenance or repair.

    Spare Parts

    If spare parts are required, please contact your nearest Innospec Marine Specialties office. Addressand contact details are on the inside of the cabinet door.

    Please quote the pump serial number, the system serial number and item(s) you require. Please also

    refer to the parts listing shown in the Equipment Overview Drawing and Parts Listing on page 5 - 6 of thismanual.

    USA

    Innospec – Marine SpecialtiesCustomer Service Centre - USA8375 South Willow StreetLittleton, CO 80124USATel: +1 800 441 9547Fax: +1 303 792 5668

    e-mail: [email protected] 

    Greece/Turkey

    Innospec Hellas Ltd.Marine SpecialtiesCustomer Service Centre - Greece & Turkey11, II Merarchias Street185-35 PiraeusGreeceTel: +30 210 411 0727 / 8Fax: +30 210 411 0748e-mail: [email protected] 

    Europe, Middle East, Africa

    Innospec – Marine SpecialtiesCustomer Service Centre - EMEAP.O. Box 53156CY-3301 LimassolCyprusTel: +357 25 762 535Fax: +357 25 762 545

    e-mail: [email protected] 

    Asia Pacific

    Innospec – Marine SpecialtiesCustomer Service Centre - Asia Pacific47 Scotts Road, #02-03 Goldbell TowersSingapore 228233Tel : +65 6336 6286Fax : +65 6336 1692e-mail: [email protected] 

  • 8/18/2019 dosing manual.pdf

    13/27

     

    5-75 L/Hr Dosing Unit Page 12 of 12 Issue 1 May 2007

    Dosing System Manual

    TECHNICAL INFORMATION

    Grundfos Alldos Primus 221 75-4 Motor Driven Dosing Pump

    Note: The pump has been calibrated to operate between 5-75 litres per hour.

    The Grundfos Alldos manual is attached for reference.

  • 8/18/2019 dosing manual.pdf

    14/27

  • 8/18/2019 dosing manual.pdf

    15/27

  • 8/18/2019 dosing manual.pdf

    16/27

  • 8/18/2019 dosing manual.pdf

    17/27

  • 8/18/2019 dosing manual.pdf

    18/27

  • 8/18/2019 dosing manual.pdf

    19/27

  • 8/18/2019 dosing manual.pdf

    20/27

  • 8/18/2019 dosing manual.pdf

    21/27

  • 8/18/2019 dosing manual.pdf

    22/27

  • 8/18/2019 dosing manual.pdf

    23/27

  • 8/18/2019 dosing manual.pdf

    24/27

  • 8/18/2019 dosing manual.pdf

    25/27

  • 8/18/2019 dosing manual.pdf

    26/27

  • 8/18/2019 dosing manual.pdf

    27/27