Dominion® PX User Guide Release 1.1.0 Copyright © 2008 Raritan, Inc. DPX0GE March 2008 25580608000

Transcript of Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... ·...

Page 1: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Dominion® PX

User Guide Release 1.1.0

  

Copyright © 2008 Raritan, Inc. DPX‐0G‐E March 2008 

255‐80‐6080‐00 

Page 2: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

This document contains proprietary information that is protected by copyright. All rights reserved. No part of this document may be photocopied, reproduced, or translated into another language without express prior written consent of Raritan, Inc. 

© Copyright 2008 Raritan, Inc., CommandCenter®, Dominion®, Paragon® and the Raritan company logo are trademarks or registered trademarks of Raritan, Inc. All rights reserved. Java® is a registered trademark of Sun Microsystems, Inc. Internet Explorer® is a registered trademark of Microsoft Corporation. Netscape® and Netscape Navigator® are registered trademarks of Netscape Communication Corporation. All other trademarks or registered trademarks are the property of their respective holders. 

FCC Information

This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a commercial installation. This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. Operation of this equipment in a residential environment may cause harmful interference. 

VCCI Information (Japan)

Raritan is not responsible for damage to this product resulting from accident, disaster, misuse, abuse, non‐Raritan modification of the product, or other events outside of Raritanʹs reasonable control or not arising under normal operating conditions. 

 

LISTED

C USLU 1F61I.T.E.

 

Page 3: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

iii

To avoid potentially fatal shock hazard and possible damage to Raritan equipment: 

SYSTEMS SHOULD ONLY BE CONFIGURED BY A COMPETENT PERSON. 

IT IS ESSENTIAL THAT THIS EQUIPMENT IS CONNECTED TO AN ELECTRICAL SUPPLY THAT HAS A PROTECTIVE GROUND CONDUCTOR 

WARNING:  TO ISOLATE THIS EQUIPMENT DISCONNECT POWER SUPPLY PLUG. 

ATTENTION:  AFIN DʹISOLER TOTALEMENT CET APPAREIL DEBRANCHER FICHE DʹALIMENTATION. 

CAUTION: USE ONLY IN DRY LOCATIONS. 

ATTENTION: UTILISER UNIQUEMENT DANS DES EMPLACEMENTS SECS. 

Do not use a 2‐wire power cord in any product configuration. 

Test AC outlets at your computer and monitor for proper polarity and grounding. 

Use only with grounded outlets at both the computer and monitor. When using a backup UPS, power the computer, monitor and appliance off the supply. 

The installation socket outlet used for the power supply to this equipment must be installed near the equipment and must be easily accessible. 

When installing this product, it is essential that the distribution circuit supplying the product is protected by a branch circuit protection device with a maximum rating to suit the product maximum rating. 

This power distribution unit is intended for power supply provision to equipment only. Secondary (Satellite) power strips shall not be connected to the receptacles 

This product has been designed to conform to the latest safety requirements. In addition to compliance with standards for general use, it has been factory configured for use in rack mounting environments aiding the installer to provide systems compliant with relevant standards. 

Safety Guidelines

Page 4: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Product Models

iv

Provide an earthing connection before the mains plug is connected to the mains. And, when disconnecting the earthing connection, be sure to disconnect after pulling out the mains plug from the mains. 

Page 5: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

v

Contents

Safety Guidelines iii

Chapter 1 Introduction 1

Product Models.......................................................................................................................................... 1 Product Photos........................................................................................................................................... 1

Zero U Size ...................................................................................................................................... 2 1U Size ............................................................................................................................................. 2 2U Size ............................................................................................................................................. 3

Product Features........................................................................................................................................ 3 Package Contents ...................................................................................................................................... 4

Zero U Products ............................................................................................................................. 4 1U Products..................................................................................................................................... 4 2U Products..................................................................................................................................... 5

Chapter 2 Rack-Mounting the Dominion PX 6

Rack Mount Safety Guidelines ................................................................................................................ 6 Tool‐less Mounting Instructions.............................................................................................................. 8

Before Beginning: ........................................................................................................................... 8 To Mount: ........................................................................................................................................ 9

Chapter 3 Installation and Configuration 10

Before You Begin ..................................................................................................................................... 10 Unpack the Dominion PX and Components ............................................................................ 10 Prepare the Installation Site ........................................................................................................ 10 Fill Out the Equipment Setup Worksheet................................................................................. 11

Connect the Dominion PX to a Computer ........................................................................................... 11 Connect the Dominion PX to Your Network....................................................................................... 12 Configure the Dominion PX for Network Connectivity .................................................................... 12 Resetting to Factory Defaults................................................................................................................. 16

Chapter 4 Using the Dominion PX 19

Front Panel ............................................................................................................................................... 19 Connection Ports .......................................................................................................................... 19 Blue LED........................................................................................................................................ 20

Page 6: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Contents

vi

Back Panel................................................................................................................................................. 20 Power Cord ................................................................................................................................... 20 Outlets............................................................................................................................................ 21 LED Display.................................................................................................................................. 22

Circuit Breaker ......................................................................................................................................... 24 Beeper........................................................................................................................................................ 25 Measurement Accuracy.......................................................................................................................... 25

Chapter 5 Using the Web Interface 26

Logging into the Web Interface ............................................................................................................. 26 Logging In ..................................................................................................................................... 26 Changing Your Password ........................................................................................................... 30

Using the Web Interface ......................................................................................................................... 30 Menus ............................................................................................................................................ 31 Navigation Path............................................................................................................................ 32 Status Panel ................................................................................................................................... 32 Status Messages............................................................................................................................ 34 Unavailable Options .................................................................................................................... 35 Reset to Defaults........................................................................................................................... 35 Refresh ........................................................................................................................................... 35

Using the Home Window....................................................................................................................... 36 Global Status Panel ...................................................................................................................... 36 Outlets List .................................................................................................................................... 37 All Outlets Control....................................................................................................................... 38

Setting Up User Profiles ......................................................................................................................... 39 Creating a User Profile ................................................................................................................ 39 Copying a User Profile ................................................................................................................ 41 Modifying a User Profile............................................................................................................. 42 Deleting a User Profile................................................................................................................. 42 Setting User Permissions Individually...................................................................................... 42

Setting Up User Groups.......................................................................................................................... 43 Creating a User Group ................................................................................................................ 44 Setting the System Permissions.................................................................................................. 44 Setting the Outlet Permissions ................................................................................................... 47 Copying a User Group ................................................................................................................ 48 Modifying a User Group............................................................................................................. 48 Deleting a User Group................................................................................................................. 49

Setting Up Access Controls .................................................................................................................... 49 Forcing HTTPS Encryption......................................................................................................... 49 Configuring the Firewall ............................................................................................................. 50 Creating Group Based Access Control Rules ........................................................................... 53 Setting Up User Login Controls ................................................................................................. 56

Setting Up a Digital Certificate.............................................................................................................. 59 Creating a Certificate Signing Request...................................................................................... 60 Installing a Certificate.................................................................................................................. 61

Page 7: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Contents

vii

Setting Up External User Authentication............................................................................................. 62 Settings Up LDAP Authentication............................................................................................. 63

Setting Up Outlets and Power Thresholds........................................................................................... 65 Setting the Default Outlet State.................................................................................................. 66 Setting the Dominion PX Thresholds ........................................................................................ 66 Setting the Outlet Power‐Up Sequence..................................................................................... 67 Naming the Outlets...................................................................................................................... 69 Setting the Outlet Thresholds..................................................................................................... 70 Viewing Outlet Details ................................................................................................................ 71 Power Cycling an Outlet ............................................................................................................. 72 Turning an Outlet On or Off....................................................................................................... 72

Environmental Sensors ........................................................................................................................... 72 Connecting the Environmental Sensors .................................................................................... 72 Mapping the Environmental Sensors ........................................................................................ 73 Configuring Environmental Sensors and Thresholds............................................................. 74 Viewing Sensor Readings............................................................................................................ 75

Setting Up Alerts ..................................................................................................................................... 76 Configuring Alert Events ............................................................................................................ 76 Creating Alert Policies................................................................................................................. 78 Specifying the Alert Destination ................................................................................................ 81

Setting Up Event Logging ...................................................................................................................... 82 Configuring the Local Event Log............................................................................................... 83 Viewing the Internal Event Log ................................................................................................. 85 Configuring NFS Logging........................................................................................................... 86 Configuring SMTP Logging........................................................................................................ 87 Configuring SNMP Logging....................................................................................................... 88 Configuring Syslog Forwarding ................................................................................................ 88

Managing the Dominion PX .................................................................................................................. 89 Displaying Basic Device Information ........................................................................................ 89 Displaying Model Configuration Information......................................................................... 91 Displaying Connected Users ...................................................................................................... 91 Naming the Dominion PX........................................................................................................... 92 Modifying the Network Settings................................................................................................ 93 Modifying the Communications, Port and Bandwidth Settings ........................................... 94 Modifying the LAN Interface Settings ...................................................................................... 95 Setting the Date and Time........................................................................................................... 96 Configuring the SMTP Settings.................................................................................................. 97 Configuring the SNMP Settings................................................................................................. 98 Resetting the Dominion PX......................................................................................................... 99 Updating the Firmware............................................................................................................. 100

Outlet Grouping .................................................................................................................................... 102 Identifying Other Dominion PX Units .................................................................................... 102 Grouping Outlets Together....................................................................................................... 103 Controlling Outlet Groups........................................................................................................ 105 Editing or Deleting Outlet Groups .......................................................................................... 106

Page 8: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Contents

viii

Deleting Outlet Group Devices ................................................................................................ 106

Chapter 6 Integration 107

Dominion KX ......................................................................................................................................... 108 KX Manager Application (Dominion KX‐I only)................................................................... 108 Associate Outlets with a Target ............................................................................................... 108 Control a Targetʹs Power........................................................................................................... 110 Dominion KX‐II .......................................................................................................................... 111

Paragon II ............................................................................................................................................... 111 Paragon Manager Application ................................................................................................. 112 Add a Dominion PX Unit in Paragon II .................................................................................. 112 Associate Outlets with a Target ............................................................................................... 113 Control a Targetʹs Power........................................................................................................... 113 Control an Outletʹs Power......................................................................................................... 114

Dominion SX .......................................................................................................................................... 114 Configure a Dominion PX Power Unit on Dominion SX...................................................... 114 Power Control............................................................................................................................. 115 Check Power Strip Status.......................................................................................................... 116

Dominion KSX ....................................................................................................................................... 116 CommandCenter ................................................................................................................................... 117

Appendix A Dominion PX Models 118

Hardware Specification ........................................................................................................................ 119 Environmental Specifications .............................................................................................................. 120

Appendix B Equipment Setup Worksheet 121

Appendix C Using the CLP Interface 125

About the CLP Interface ....................................................................................................................... 125 Logging into the CLP interface............................................................................................................ 126

Using HyperTerminal................................................................................................................ 126 Using SSH or Telnet................................................................................................................... 127

Showing Outlet Information................................................................................................................ 127 Syntax........................................................................................................................................... 128 Attributes..................................................................................................................................... 128 Examples ..................................................................................................................................... 129

Turning an Outlet On or Off ................................................................................................................ 130 Syntax........................................................................................................................................... 130

Page 9: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Contents

ix

Querying an Outlet Sensor................................................................................................................... 130

Appendix D Using SNMP 131

Enabling SNMP ..................................................................................................................................... 132 Configuring Users for Encrypted SNMP v3........................................................................... 134

Configuring SNMP Traps..................................................................................................................... 135 SNMP Gets and Sets.............................................................................................................................. 136

The Dominion PX MIB .............................................................................................................. 137

Appendix E Using the IPMI Tool Set 139

Channel Commands.............................................................................................................................. 139 authcap <channel number> <max priv>.................................................................................. 139 info [channel number] ............................................................................................................... 140 getaccess <channel number> [userid] ...................................................................................... 140 setaccess <channel number> <userid>[callin=on|off] [ipmi=on|off] [link=on|off] [privilege=level].......................................................................................................................... 140 getciphers <all | supported> <ipmi | sol> [channel] ............................................................. 141

Event Commands .................................................................................................................................. 141 <predefined event number>...................................................................................................... 141 file <filename>............................................................................................................................. 142

LAN Commands.................................................................................................................................... 142 print <channel> ........................................................................................................................... 142 set <channel> <parameter>........................................................................................................ 143

Sensor Commands................................................................................................................................. 144 list ................................................................................................................................................. 144 get <id> ... [<id>] ......................................................................................................................... 144 thresh <id> <threshold> <setting> ............................................................................................ 145

OEM Commands ................................................................................................................................... 145 Set Power Set Delay Command................................................................................................ 146 Get Power On Delay Command .............................................................................................. 146 Set Receptacle State Command ................................................................................................ 146 Get Receptacle State Command ............................................................................................... 147 Set Group State Command ....................................................................................................... 147 Set Group Membership Command.......................................................................................... 148 Get Group Membership Command......................................................................................... 148 Set Group Power On Delay Command................................................................................... 149 Get Group Power On Delay Command.................................................................................. 149 Set Receptacle ACL .................................................................................................................... 150 Get Receptacle ACL ................................................................................................................... 150 Set Sensor Calibration................................................................................................................ 151 Test Actors................................................................................................................................... 151 Test Sensors................................................................................................................................. 151 Set Power Cycle Delay Command........................................................................................... 151

Page 10: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Contents

x

Get Power Cycle Delay Command .......................................................................................... 152 IPMI Privilege Levels............................................................................................................................ 152

Appendix F Event Types 153

Appendix G Specifications 155

Index 157

Page 11: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

1

The Dominion PX unit is an intelligent power distribution unit that allows you to reboot remote servers and other network devices, and monitor power in the data center, through Raritanʹs KVM switches and Secure Console Servers. From the office or from anywhere, the Dominion PX unit will power on, power off, or reboot remote equipment, as well as monitor current, voltage, power, and temperature.  

The Dominion PX offers the ability to recover systems remotely in the event of system failure and/or system lockup. It eliminates the need to perform manual intervention or dispatch field personnel, reduces downtime and mean time to repair, and increases productivity. 

In This Chapter Product Models..................................................................................................1 Product Photos ...................................................................................................1 Product Features ................................................................................................3 Package Contents...............................................................................................4 

Product Models

The Dominion PX comes in several models that are built to stock and can be obtained almost immediately. Raritan also offers custom models that are built to order and can only be obtained on request.  

Refer to Appendix A (see ʺDominion PX Modelsʺ on page 118) for a list of Dominion PX models. 

Product Photos

The Dominion PX comes in Zero U, 1U, and 2U sizes. 

Chapter 1 Introduction

Page 12: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Product Photos

2

Zero U Size

  

1U Size

  

 

Page 13: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 1: Introduction

3

2U Size

   

  

Product Features

All models and sizes of the Dominion PX provide the following features: 

• The ability to control outlets collectively and individually 

• The ability to power on, power off and reboot the devices connected to each outlet 

• The ability to group outlets from multiple Dominion PX as virtual outlets accessible from a single session 

• The ability to monitor the following at the outlet level: 

RMS Current 

Power Factor 

Maximum RMS Current 

RMS Voltage 

Active Power 

Apparent Power 

Page 14: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Package Contents

4

• The ability to monitor the internal, CPU temperature of the Dominion PX 

• The ability to monitor environmental factors such as external temperature and humidity 

• An audible alarm (beeper) and a visual alarm (blinking LED) to indicate current overload 

• Configurable alarm thresholds 

• Support for SNMP v1, v2 and V3. 

• The ability to send traps using SNMP protocol. 

• The ability to retrieve outlet specific data using SNMP, including outlet state, current, voltage and power. 

• The ability to configure and set values through SNMP, including unit and outlet threshold levels. 

• Fully shrouded local branch circuit breakers on products rated over 20A to protect connected equipment against overload and short circuits 

• Integration with Raritanʹs Paragon, CommandCenter Secure Gateway (CC‐SG), and Dominion solutions 

Package Contents

The following describes the equipment and other material included in each product package. 

Zero U Products

• Dominion PX unit including power cord 1.80m (6 feet)  

• Bracket for Zero U and screws 

• Tool‐less mounting bracket for Zero U units 

• Null‐modem cable with RJ‐45 and DB9F connectors on either end 

1U Products

• Dominion PX unit including power cord 1.80m (6 feet)  

• 1U bracket pack and screws 

• Null‐modem cable with RJ‐45 and DB9F connectors on either end 

Page 15: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 1: Introduction

5

2U Products

• Dominion PX unit including power cord 1.80m (6 feet)  

• 2U bracket pack and screws 

• Null‐modem cable with RJ‐45 and DB9F connectors on either end 

Page 16: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

6

In This Chapter Rack Mount Safety Guidelines.........................................................................6 Tool‐less Mounting Instructions......................................................................8 

Rack Mount Safety Guidelines

In Raritan products which require Rack Mounting, please follow these precautions: 

Operation temperature in a closed rack environment may be greater than room temperature. Do not exceed the rated maximum ambient temperature of the appliances (see Appendix A: Specifications). 

Ensure sufficient airflow through the rack environment.  

Mount equipment in the rack carefully to avoid uneven mechanical loading. 

Connect equipment to the supply circuit carefully to avoid overloading circuits.  

Ground all equipment properly, especially supply connections, to the branch circuit. 

 

 

The Zero U units are provided with high grade engineering polycarbonate isolation hardware to allow fixing in a variety of positions within the rack. 

 

For panel/flush mount, pull out fixing brackets are available on each end cap to allow mounting on suitable rails. 

 

See other options shown below. 

Chapter 2 Rack-Mounting the Dominion PX

Page 17: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 2: Rack-Mounting the Dominion PX

7

Side Fixing 

 

 

 

End Fixing 

 

 

 

Blind Fixing   

 

 

Page 18: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Tool-less Mounting Instructions

8

Tool-less Mounting Instructions

The Zero U units also ship with a tool‐less mounting kit consisting of a claw feet with a silver button on one side. These work by attaching to the back side of a Zero U Dominion PX (the side opposite of the outlets) and fitting the button into the mounting holes of the cabinet. Note that not all racks may allow the option of securing the Dominion PX in this way. 

 

Before Beginning:

• Ensure that you have sufficient space in the cabinet to mount the Dominion PX. Approximately one inch of clearance is required at each end (top and bottom) of the unit. 

• It may help to mark the back of the Dominion PX through the mounting holes you intend to use. You can then use this mark to assist in aligning the silver buttons properly when attaching the claw‐feet. 

Page 19: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 2: Rack-Mounting the Dominion PX

9

To Mount:

• Snap fit the claw feet mounts onto the back of the Dominion PX unit. Leave at least 24 inches between the buttons for stability.  Once the claw feet are mounted on the Dominion PX rail, they will not readily move‐a flat‐head screwdriver can be used to remove the feet if they need to be repositioned. 

• Align the silver buttons with the mounting holes in the cabinet, and ensure that both buttons can engage their mounting holes simultaneously. 

• Press the Dominion PX forward, pushing the silver buttons through the mounting holes, then letting the Dominion PX drop about 5/8ths of an inch. This will secure the Dominion PX in place and complete the installation. 

The picture shows how firm pressure is applied to snap fit the claw feet to the Dominion PX Zero‐U unit. Hook one side of the product body into one side of a claw foot first, and then apply pressure to snap in the second side. 

 

 

Page 20: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

10

This chapter explains how to install a Dominion PX unit and configure it for network connectivity. 

In This Chapter Before You Begin..............................................................................................10 Connect the Dominion PX to a Computer....................................................11 Connect the Dominion PX to Your Network ...............................................12 Configure the Dominion PX for Network Connectivity ............................12 Resetting to Factory Defaults .........................................................................16 

Before You Begin

Before beginning the installation, perform the activities listed below: 

Unpack the Dominion PX and Components

1. Remove the Dominion PX unit and other equipment from the box in which they were shipped. Refer to “Package Contents” section for a complete list of the contents of the box. 

2. Compare the unit and serial number of the equipment with the number on the packing slip located on the outside of the box and make sure they match. 

3. Inspect the equipment carefully. If any of the equipment is damaged or missing, contact Raritanʹs Technical Support Department for assistance. 

Prepare the Installation Site

1. Make sure the installation area is clean and free of extreme temperatures and humidity. 

2. Allow sufficient space around the Dominion PX for cabling and outlet connections. 

3. Review the Safety Instructions listed in the beginning of this user guide. 

Chapter 3 Installation and Configuration

Page 21: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 3: Installation and Configuration

11

Fill Out the Equipment Setup Worksheet

An Equipment Setup Worksheet is provided in Appendix B (see ʺEquipment Setup Worksheetʺ on page 121). Use this worksheet to record the model, serial number, and use of each device connected to the Dominion PX. 

As you add and remove devices, keep the worksheet up to date. 

Connect the Dominion PX to a Computer

You must connect the Dominion PX to a computer to configure it. This is done by means of a serial connection between the Dominion PX and the computer. If you plan to use this connection to log into the CLP command line interface, leave the cable connected after the configuration is complete. 

The computer must have a communications program such as HyperTerminal or PuTTY. You will also need the null‐modem cable and connectors that were shipped with the Dominion PX. 

1. Take the null‐modem cable and connect the end with the RJ‐45 connector to the port labeled Serial on the front of the Dominion PX. (Refer to the following pictures for the location of this port on your Dominion PX.) 

 

Page 22: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Connect the Dominion PX to Your Network

12

  

 

  

2. Plug the other end of the null‐modem cable (containing the DB9 connector) into the serial port (COM) of the computer. 

Connect the Dominion PX to Your Network

To use the Web interface to administer the Dominion PX, you must connect the Dominion PX to your local area network (LAN). 

1. Take a standard Category 5e UTP cable and connect one end to the LAN port on the front of the Dominion PX. (Refer to the pictures shown in Connect the Dominion PX to a Computer (on page 11) for the location of this port on your size Dominion PX.) 

2. Connect the other end of the cable to your LAN. 

Configure the Dominion PX for Network Connectivity

Once the Dominion PX is connected to your network, you must provide it with an IP address and some additional networking information. 

1. Go to the computer that you connected to the Dominion PX and open a communications program such as HyperTerminal or PuTTY. Make sure its port settings are configured as follows: 

Page 23: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 3: Installation and Configuration

13

Bits per second = 9600 

Data bits = 8 

Stop bits = 1 

Parity = None 

Flow control = None 

Note: The “Flow control” parameter must be set to “None” for the communications program to work correctly with the Dominion PX. 

2. Point the communications program at the serial port connecting the Dominion PX and open a terminal window.  

3. Press Enter to display the opening configuration prompt. 

 

4. Type config and press Enter to begin the configuration process. You are prompted to select an IP configuration method. 

 

5. You must assign the Dominion PX an IP address. There are two ways to do this: 

Auto configuration  Select an autoconfiguration method such as dhcp or bootp and let the DHCP or BOOTP server provide the IP address. 

Static IP address    Select None and assign the Dominion PX a static IP address. You will be prompted for the address, network mask, and gateway. 

Page 24: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Configure the Dominion PX for Network Connectivity

14

Note:  The Dominion PXʹs IP address is automatically displayed in the system prompt. The default IP address is 192.168.0.192. The default IP configuration method is DHCP, and the default IP address will be replaced by the address assigned by DHCP or BOOTP, or the static IP address you entered, as soon as the configuration process is complete. To use the factory default IP address, please type in none as the IP autoconfiguration command, and accept the default value. The default IP address for static (none) configuration is 192.168.0.192. 

Type your selection and press Enter. You are prompted to enable IP access control. 

 

6. By default, IP access control is NOT enabled. This disables the Dominion PX firewall. Leave the firewall disabled for now. Later on, you can enable the firewall from the Web interface and create firewall rules (refer to “Configuring the Firewall (on page 50)” section for details). 

Note:  If you ever accidentally create a rule that locks you out of the Dominion PX, you can rerun the configuration program and reset this parameter to disabled to allow you to access the Dominion PX. 

7. For now, press Enter. You are prompted to set the LAN interface speed. 

 

Page 25: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 3: Installation and Configuration

15

8. By default, the LAN interface speed is set to Auto, which allows the system to select the optimum speed. To keep the default, press Enter. To set the speed to 10 or 100 Mbps, type the speed you want and press Enter. You are prompted to select the duplex mode for the LAN interface. 

 

9. By default, the LAN interface duplex mode is set to Auto, which allows the system to pick the optimum mode. Half duplex allows data to be transmitted to and from the Dominion PX, but not at the same time. Full duplex allows data to be transmitted in both directions at the same time. 

To keep the default, press Enter. To specify half or full duplex, type half or full and press Enter. You are prompted to confirm the information you just entered. 

 

10. All the configuration parameters have now been entered. All the prompts are still displayed, so you can check the information you entered. Do one of the following: 

If the information is correct, type y and press Enter. The system completes the configuration and displays a message when the configuration is done. 

If one or more parameters are not correct, type n and press Enter. You are returned to the IP configuration prompt as shown in the screenshot of Step 4, and given the opportunity to correct each piece of information. When the information is correct, type y and press Enter to complete the configuration and return to the opening prompt as shown in the screenshot of Step 3. 

Page 26: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Resetting to Factory Defaults

16

If you want to terminate the configuration process, type c and press Enter. The configuration is cancelled and you are returned to the opening prompt as shown in the screenshot of Step 3. 

11. If you entered y to confirm the configuration, a message is displayed telling you when the configuration is complete. You are then returned to the opening prompt as shown in the screenshot of Step 3. You are now ready to begin using your Dominion PX. 

 

Note:  The IP address configured takes about 15 seconds to take effect for the device connected via serial line, or even longer if configured over DHCP. 

Resetting to Factory Defaults

Important:  Exercise caution before resetting a DPX to its factory defaults. This wipes out any information you have entered, including user profiles, user groups, thresholds, alert policies, etc. 

For security reasons, the Dominion PX may only be reset to factory defaults at the local serial console. To do this: 

1. Connect a computer to the serial port of the Dominion PX. 

2. Using a terminal emulation program such as HyperTerminal, Kermit or PuTTY (at a speed of 9600 bps), open a window on the DPX. Make sure serial port settings are configured as followed: 

Page 27: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 3: Installation and Configuration

17

• Baud rate (bits per second) = 9600 

• Data bits = 8 

• Stop bits = 1 

• Parity = None 

• Flow control = None 

1. Press (and release) the Reset button of DPX while pressing the Esc key several times in rapid succession. A prompt (=>) should appear after about one second. 

2. Execute the defaults command to reset the DPX to its factory defaults. 

Page 28: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Resetting to Factory Defaults

18

Note: Enter ʺhelpʺ to show a list of available command and a short description of each one. HyperTerminal is available on many Windows OS. But HyperTerminal is not available on Windows Vista. PuTTY is a free program you can download from the internet. Please refer to PuTTYʹs documentation for details on configuration. 

The picture below shows the location of the reset hole. 

     

 

Page 29: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

19

This chapter explains how to use the Dominion PX unit. It describes the LEDs and ports on the front and back panels of the Dominion PX, and explains how to use the display panel. It also explains how the circuit breaker works and when the beeper goes off. 

In This Chapter Front Panel........................................................................................................19 Back Panel.........................................................................................................20 Circuit Breaker .................................................................................................24 Beeper................................................................................................................25 Measurement Accuracy ..................................................................................25 

Front Panel

The front panel of the 1U and 2U Dominion PX units consists of a blue LED to the right and three connection ports to the left, while that of the Zero U model consists of power outlets to connect devices to Dominion PX, a display panel, and three connection ports. 

Connection Ports

The three ports, from left to right, are labeled as Serial (RJ‐45), Feature (RJ‐12), and LAN (Ethernet, RJ‐45). The table below explains what each port is used for. 

Port Used for... Serial  Establishing a serial connection between a computer and the Dominion PX 

Take the null‐modem cable that was shipped with the Dominion PX unit, connect the end with the RJ‐45 connector to the port labeled Serial on the front of the Dominion PX, and connect the end with the DB9F connector to the serial (COM) port on the computer. 

The serial port is also used to interface with some Raritan access products (such as the Dominion KX) through the use of a power CIM. 

Feature  For use with Raritan provided environmental sensors. 

Chapter 4 Using the Dominion PX

Page 30: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Back Panel

20

LAN  Connecting the Dominion PX to your companyʹs network 

Connect a standard Category 5e UTP cable to this port and connect the other end to your network. This connection is necessary to administer the Dominion PX remotely using the Web interface. 

There are two small LEDs under the LAN port. Green indicates a physical link and activity, and yellow indicates communication at 10/100 BaseT speeds. 

 

Note: Connecting any power CIM except the for the D2CIM‐PWR (e.g. P2CIM‐PWR) to the serial port of the Dominion PX will switch all the outlets to the ON state, even if they were previously OFF 

Blue LED

Only 1U and 2U models consist of a blue LED on the front panel. The blue LED on the right side of the front panel is lit solid as soon as the Dominion PX unit is plugged in. 

Back Panel

The back panel of the 1U and 2U Dominion PX units consists of, from left to right, a power cord, power outlets to connect devices to the Dominion PX, and a display panel, while the Zero U models consist of no back panel. 

Power Cord

The power cord that connects the Dominion PX to a power source is located on the far left of the back panel or on the end of the unit if the unit is a Zero U type. All devices can not be rewired by the user. 

Note:  Each Dominion PX model should be plugged into an appropriately rated outlet for its type. 

There is no power switch on the Dominion PX. On products rated at over 20A there are branch circuit breakers that are fully shrouded to prevent accidental operation. To power cycle the unit, remove the power cord from the power source and then re‐connect it. 

Page 31: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 4: Using the Dominion PX

21

Outlets

The number of outlets on the back panel depends upon the Dominion PX model. To the upper left of each outlet is a small LED. The units are shipped from the factory with all outlets powered ON. The table below explains how to interpret the different LED states. 

LED State Outlet Status What it Means

Not lit (Light grey)  Unit OFF The outlet is not connected to power or the control circuitryʹs power supply is broken. 

Red  ON and LIVE The outlet is ON (relay closed) and LIVE (voltage present). 

Red flashing  ON and LIVE The outlet is ON and LIVE, but there is overload and the current has crossed the non‐critical threshold. 

Green  OFF and LIVE  The outlet is OFF (relay open) and LIVE. 

Green flashing  OFF and NOT LIVE  The outlet is OFF and Circuit Breaker is OFF 

Yellow flashing  ON and NOT LIVE  The outlet is ON but NOT LIVE (circuit breaker open or other high voltage rail error). 

Cycling through Red, Green and Yellow 

n/a 

The Dominion PX has just been plugged in and its management software is loading. 

OR 

A firmware upgrade is being performed on the unit 

 

Note: When a Dominion PX unit is powered on, the power‐on self‐test and software loading takes a few moments. As the unit boots up, the outlet LEDs will cycle through red, green and yellow.  When the software has completed loading, the outlet LEDs will display a steady color and the meter will illuminate. 

 

Page 32: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Back Panel

22

LED Display

The LED display is located adjacent to the outlets on the Zero U model, and on the back right of the 1U and 2U models. The following picture shows the LED display. 

   

Page 33: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 4: Using the Dominion PX

23

The LED display consists of these components: 

• A lower row displaying two digits 

• An upper row displaying three digits 

• Up and Down buttons 

Note:  The small hole between the lower row and the Down button is the reset hole. The Dominion PX unit can be reset to its factory default values through this hole when connected to the serial port. Refer to Resetting to Factory Defaults (on page 16) section for additional details. Simply pressing on this Reset hole will ONLY restart the unit. 

Lower Row

The lower row shows the outlet number. 

Upper Row

The upper row shows the current, voltage, and power readings for the outlet indicated in the lower row. During the firmware upgrade process, the upper row displays “FuP” to indicate that a Firmware Upgrade is being performed on the unit. 

How to Operate the LED Display

1. Use the Up and Down buttons to select an outlet. Pressing the Up button once moves up one outlet number. Pressing the Down button once moves down one outlet number. 

2. When an outlet is selected, the outlet number is displayed in the lower row and the current in the upper row. Current is displayed in the format:  XX.X (A) 

3. To display the voltage for the selected outlet, press the Up and Down buttons simultaneously. The voltage reading will replace the current for about 5 seconds, after which the current will return. 

4. To display the active power for the selected outlet, first press the Up and Down button simultaneously to display the voltage, and then again to display the active power. Active Power is displayed in the format: X.XX in volt‐amps (VA).  

Page 34: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Circuit Breaker

24

Tip: A quick way to distinguish between voltage, current, and power is the placement of the decimal point in the display. Voltage has no decimal point, current has a decimal point between the first and second digits, and power has a decimal point between the second and third digits. 

You can view the current and voltage for the entire Dominion PX unit by using the Up and Down buttons to select the outlet number 00. The LEDs do not show the active power for the unit and display ‐‐‐ instead. 

Circuit Breaker

The Dominion PX includes branch circuit breakers that automatically trip when a power overload is detected. The Dominion PX uses circuit breakers with Type C Trip Characteristic. If the circuit breaker switches off the voltage rail, the lower row of the display panel will jump to the lowest outlet number affected by the circuit breaker error, and the upper row will display these three letters, which mean circuit breaker error: 

CbE 

Note: Dominion PX models that are embedded with circuit breakers are those units rated over 20 Amp, including DPCS12‐30L, DPCS20‐30L, DPCS20A‐32, DPCS20A‐30L6, DPCR20‐30L, and DPCR20A‐32. 

You will still be able to switch between outlets on the Dominion PXʹs display panel. Outlets affected by the error will show CbE. Unaffected outlets will show the current and voltage readings as described above. 

To reset the breakers in the event of an overload: 

• On the 1U and 2U products unclip, the front molding to access the breaker(s). 

• On the Zero U product, access the breaker(s) by lifting the hinged cover over the breaker element. 

Page 35: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 4: Using the Dominion PX

25

Beeper

The Dominion PX includes a beeper. It will ring if any of the circuit breakers is tripped or if the control board temperature sensor exceeds 80 degrees Celsius (or 176 degrees Fahrenheit). 

The beeper will cease ringing when the broken circuit breaker conditions disappear or the control board temperature sensor drops below 70 degrees Celsius (or 158 degrees Fahrenheit). 

The temperature thresholds are factory defaults, and can be user‐configurable. 

It takes a maximum of three seconds for the beeper to start ringing right after the circuit breaker is tripped. 

Measurement Accuracy

• Voltage (per outlet):  Range 0‐255V, +/‐5%, 3 digits, resolution 1V 

• Current (per outlet):  Range 0‐25A, +/‐5%, 3 digits, resolution 0.1A 

 

 

 

Page 36: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

26

This chapter explains how to use the Web interface to administer a Dominion PX. 

In This Chapter Logging into the Web Interface .....................................................................26 Using the Web Interface..................................................................................30 Using the Home Window...............................................................................36 Setting Up User Profiles..................................................................................39 Setting Up User Groups..................................................................................43 Setting Up Access Controls ............................................................................49 Setting Up a Digital Certificate ......................................................................59 Setting Up External User Authentication.....................................................62 Setting Up Outlets and Power Thresholds...................................................65 Environmental Sensors ...................................................................................72 Setting Up Alerts..............................................................................................76 Setting Up Event Logging ..............................................................................82 Managing the Dominion PX...........................................................................89 Outlet Grouping.............................................................................................102 

Logging into the Web Interface

To log into the Web interface, you must enter a user name and password. The first time you log in, use the default user name (admin) and password (raritan). You will then be prompted to change the password for security purposes. 

Once you have logged in, you can create user profiles for your other users. These profiles define their login names and passwords. (Refer to “Creating a User Profile (on page 39)” section for instructions on creating a user profile.) 

Logging In

To log into the Web interface: 

1. Open a browser such as Microsoft Internet Explorer or Mozilla Firefox and point it at this URL: 

https://<ip address> 

Chapter 5 Using the Web Interface

Page 37: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

27

where <ip address>  is the IP address of the Dominion PX. A Login dialog appears. 

   

2. Type your user name and password in the Username and Password fields. Both the user name and password are case sensitive, so make sure you capitalize the letters correctly. 

Page 38: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Logging into the Web Interface

28

3. Click Login. The Home window appears. 

   

Page 39: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

29

Note: The Home window shown above shows 8 outlets. If your Dominion PX has 20 outlets, the Home window will show all 20. 

Java script must be enabled in the web browser for proper operation. If Java Script is not enabled, features such as the Status Panel on the left side of the interface will not display correctly. 

 

Page 40: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Using the Web Interface

30

Changing Your Password

To change your password: 

1. Choose User Management ‐‐> Change Password. The Change Password window appears. 

 

2. Type your existing password in the Old Password field. 

3. Type your new password in the New Password and Confirm New Password fields. Passwords are case sensitive, so be sure to capitalize the same letters each time. 

4. Click Apply. Your password is changed. 

Using the Web Interface

Every window in the Web interface provides menus and a navigation path across the top, and a Status panel to the left. 

Page 41: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

31

Menus

There are several menus in the Web interface: 

• Power Outlets 

• Alerts 

• User Management 

• Device Settings 

• Maintenance 

• Outlet Groups 

Options

The following figure shows a complete list of the options available from each menu. 

 

Page 42: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Using the Web Interface

32

How to Select an Option

There are two ways to select an option from a menu: 

• Click the menu name to display a window listing each option, and then click the option you want to select it. 

• Position the cursor on the menu name. A list of options drops down from the menu. Slide the cursor to the option you want and click it to select it. 

Navigation Path

When you select an option from a menu and navigate to a specific window, the system displays a navigation path across the top that shows the menu and option you selected to get there. 

For example, if you choose User Management ‐‐> User/Group System Permissions, the navigation path looks like the one shown below. 

  

To return to a previous window, click the window name in the navigation path. Every navigation path begins at the Home window, so a single click always takes you back to the Home window from anywhere in the interface. 

Status Panel

The Status panel appears on the left of every window in the interface. It shows: 

• Current date and time 

• Information about the user, including: 

User name 

Userʹs current state (active, idle, etc.) 

IP address of the userʹs computer 

Date and time of the userʹs last login 

Page 43: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

33

• Information about the Dominion PX, including: 

Model name and number 

IP address 

Firmware version 

• Information about all the users currently connected, including user name, IP address, and current state. Your current session is included in this list. 

• A link to the User Guide on the Raritan Website. 

 

The State field in the user information section considers a user to be ʺidleʺ 30 seconds after the last keyboard or mouse action. It then updates the idle time every 10 seconds until another keyboard or mouse action is detected. 

If you exceed the idle time limit, you will be logged out, and re‐directed to the main login window automatically. 

Page 44: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Using the Web Interface

34

Status Messages

When you perform an operation from the Web interface, such as creating a user profile or changing a network setting, a message appears at the top of the window that indicates whether or not the operation was successful. Be sure to check this message to confirm that an operation was successful. 

Successful messages

The following are examples of status messages after an operation has completed successfully: 

 

   

Unsuccessful messages

The following are examples of status messages after an operation has completed unsuccessfully: 

 

 

Page 45: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

35

Unavailable Options

At times, certain actions will be unavailable. When this occurs, the appropriate buttons will be non‐functional, though different browsers may display this differently. For example: if you select the  Admin User Group in Internet Explorer, the buttons for Copy, Modify and Delete will be grayed‐out since you cannot Copy, Modify or Delete the Admin user group. In Firefox, however, these buttons will appear normal and simply be unclickable. 

 

Reset to Defaults

Many windows provide a Reset to Defaults button that returns all fields to their default values. If you use this button, you must click the Apply button afterward. This saves the defaults. If you neglect to do this, the next time you return to the window, you will still see the non‐default values. 

Default Asterisk

If a field has an asterisk after it, as shown below, 

 

then this field is currently set to its default value. If you change the default, the asterisk disappears. If you reset it to the default, the asterisk returns. 

Refresh

Many windows provide a Refresh button. If a window is open for a while, the information displayed may become ʺstaleʺ. Click this button periodically to reload the window and update the information displayed. 

Page 46: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Using the Home Window

36

Using the Home Window

The Home window is the first window to appear after a successful login. It consists of a Global Status, an Outlets list, and an All Outlets Control panel. The home window also contains an environmental sensors panel, and a time stamp in the top right corner, noting when the data on the screen was last refreshed. 

You can return to the Home window from any other window in the Web interface by clicking: 

• The Home link in the navigation path 

• The Raritan logo in the upper left of the window 

• Device Model Name under the logo 

Global Status Panel

The Global Status panel provides an overview of the Dominion PXʹs power consumption and temperature. It shows: 

• Unit Voltage 

• RMS Current (in Amps) 

• Active Power (in Watts) 

• CPU Temperature (in degrees Celsius) 

 

Page 47: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

37

Outlets List

The Outlets List displays each outlet on the Dominion PX as a table row with a view of the power status, the RMS current and the RMS Power through the individual outlet. 

 

Turn an Outlet On, Off, or Cycle the Power

To turn an outlet ON, OFF or cycle the power to it, click the On, Off, or Cycle in the outlet row. You will be asked to confirm your action, click OK and the outlet will then switch ON, OFF or will cycle its power. You can also turn an outlet on or off from the Outlet Details window (refer to Figure 49 for a picture of the window). 

 

Page 48: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Using the Home Window

38

Display Additional Details

To display additional details about an outlet, click the outlet name. This displays the Outlet Details window (refer to Figure 49 for a picture of the window). This window gives the name and status of the outlet, as well as: 

• RMS Current  

• Power Factor 

• Maximum RMS Current  

• RMS Voltage  

• Active Power 

• Apparent Power 

Note:  RMS refers to Root Mean Square, a statistical method for measuring certain types of variables. In this context, it gives the value of current or voltage that is equivalent to a comparable DC value. 

 

All Outlets Control

The All Outlets Control panel at the bottom of the Home Window allows you to turn all outlets ON and OFF. Click On to turn all outlets ON, click Off to turn all outlets OFF. As with individual outlets, you must confirm the selection before it takes effect. 

 

Note: Users must have permission to access all outlets in order to use All Outlets Control. 

Page 49: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

39

Setting Up User Profiles

The Dominion PX is shipped with one user profile built in. This is the Admin profile, which was used for the original login. This profile has full system and outlet permissions, and should be reserved for the system administrator. This profile cannot be modified or deleted. 

All users must have a user profile. The profile specifies a login name and password, and contains additional (optional) information about the user. It also assigns the user to a User Group, and the User Group determines the userʹs system and outlet permissions. 

If you choose, you can refrain from assigning some or all users to a User Group, and instead assign their system and outlets permissions on an individual basis. 

Note: By default, multiple users can log in at the same time using the login name from the same profile. You can change this so only one user at a time can use a specific login. This is done by choosing Device Settings ‐‐> Security and checking the checkbox labeled Enable Single Login Limitation. 

Creating a User Profile

To create a user profile: 

1. Choose User Management ‐‐> Users & Groups. The User/Group Management window appears. It is divided into a User Management panel and a Group Management panel. 

Page 50: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up User Profiles

40

  

Note: Before entering any information in the user profile, please make sure the User Group is created and available for selection. 

2. In the User Management panel, type the following information about the user in the corresponding fields: 

Field Type this... New user name    The name the user will enter to log into the Web interface 

Full Name    The userʹs first and last names 

Password  

Confirm Password  

The password the user will enter to log in. Type it first in the  

Password field and then again in the Confirm Password 

field.  

The password must be at least four characters long, and spaces are not permitted. The password is case sensitive, so be sure to capitalize the same letters each time. 

Email address   An email address where the user can be reached 

Mobile Number    A cell phone number where the user can be reached 

 

Page 51: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

41

Note:  New user name, Password, and Confirm Password are the only required fields. 

3. Select a User Group from the drop‐down list in the User Group field. The User Group determines the system functions and outlets this user can access. 

4. If you select None, the user is not assigned to a User Group. This means you have to set the userʹs permissions individually. Until you do this, the user is effectively blocked from accessing any system functions and outlets. (For instructions on setting permissions individually, refer to “Setting User Permissions Individually (on page 42)” section for details.) 

5. If you would like this user to set his or her own password, click the checkbox labeled Enforce user to change password on next login. The user logs in the first time using the password you entered above, and then is forced to change it to one of his or her choice. 

6. Click Create. The user profile is created. 

Note: The Use Password as Encryption Phrase, SNMP v3 Encryption Phrase and Confirm SNMP Encryption Phrase apply only when using secure SNMP v3 communication. Refer to the Using SNMP appendix for more details. 

Copying a User Profile

You can create a new user profile with the exact same settings as an existing profile by using the copy function. You can then modify the profile so that it differs as necessary from the original. This is a quick and easy way to create user profiles. 

To copy a user profile: 

1. Choose User Management ‐‐> Users & Groups. The User/Group Management window appears. 

2. Select the existing user profile from the drop‐down list in the Existing Users field. 

3. Type the name of the new user profile in the New User Name field. 

4. Click Copy. A new user profile is created with the same settings as the existing profile. The new profile can be seen by clicking the drop‐down list in the Existing Users field. 

Page 52: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up User Profiles

42

Modifying a User Profile

Every user with user management permissions can modify a user profile. (Refer to “Setting the System Permissions (on page 44)” section for information about setting user permissions.) 

To modify a user profile: 

1. Choose User Management ‐‐> Users & Groups. The User/Group Management window appears. 

2. Select the user profile you want to modify from the drop‐down list in the Existing Users field. All the information in the user profile is displayed except the password. 

3. Make all necessary changes to the information shown. To change the password, type a new password in the Password and Confirm Password fields. If the password field is left blank, the password is not changed. 

4. Click Modify. The user profile is modified. 

Deleting a User Profile

To delete a user profile: 

1. Choose User Management ‐‐> Users & Groups. The User/Group Management window appears. 

2. Select the user profile you want to delete from the drop‐down list in the Existing Users field. 

3. Click Delete. The user profile is deleted. 

Setting User Permissions Individually

If you selected None for User Group when creating a user profile, you must set the userʹs permissions individually. Until you do this, the user is effectively blocked from all system functions and outlets. 

System Permissions

To set the system permissions: 

1. Choose User Management ‐‐> User/Group System Permissions. The User/Group System Permissions window appears (refer to  the figure shown in Setting the System Permissions (on page 44) section). 

Page 53: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

43

2. Select the user from the drop‐down list in the User (not in group) field. The drop‐down list shows all user profiles that have NOT been assigned to a User Group. 

3. Set the permissions as necessary. Click this icon   in a field and choose either Yes or No. 

4. When you are finished, click Apply. The permissions are applied to the user. 

Outlet Permissions

To set the outlet permissions: 

1. Choose User Management ‐‐> User/Group Outlet Permissions. The User/Group Outlet Permissions window appears (refer to the figure shown in Setting the Outlet Permissions (on page 47) section). 

2. Select the user from the drop‐down list in the User field. 

3. Set the permissions as necessary. Click this icon   in a field and choose either Yes or No. 

4. When you are finished, click Apply. The permissions are applied to the user. 

Note:  At least IPMI privilege level ʺuserʺ is required to switch outlets over IPMI, which causes no effect on web front‐end use. However, privilege level has nothing to do with outlet permissions. 

Setting Up User Groups

The Dominion PX is shipped with one User Group built in. This is the Admin User Group. This User Group provides full system and outlet permissions. It can be neither modified nor deleted. 

When creating user profiles, the User Group field defaults to the Admin User Group. This means that if you do not change the entry in this field, the user will enjoy full system and outlet permissions. To restrict the userʹs permissions, create a User Group with limited system and/or outlet permissions, and assign the user to that group. 

Page 54: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up User Groups

44

Creating a User Group

To create a User Group: 

1. Choose User Management ‐‐> Users & Groups. The User/Group Management window appears. This window is divided into a User Management panel and a Group Management panel. 

 

2. In the Group Management panel, type the name of the group in the New Group Name field. 

3. Click Create. The User Group is created. 

Setting the System Permissions

System permissions include all the major functional areas of the Web interface. When you first create a User Group, all system permissions are set to NO. 

To set the system permissions for a User Group: 

1. Choose User Management ‐‐> Users/Group System Permissions. The User/Group System Permissions window appears. 

Page 55: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

45

  

2. Select the User Group from the drop‐down list in the Group field. The permissions that apply to this group are displayed. If this is the first time you are setting the permissions for this group, all permissions are set to No. 

3. Set the permissions as necessary. Click this icon   in a field and select either Yes or No. 

Page 56: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up User Groups

46

4. When you are finished, click Apply. The permissions are applied to the User Group. 

Note:  The User (not in group) field on this window is used to set individual user permissions. If you are setting group permissions, you may ignore this field. 

Page 57: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

47

Setting the Outlet Permissions

Setting outlet permissions allows you to specify which outlets members of a User Group are permitted to access. When you first create a User Group, all outlet permissions are set to NO. 

To set the outlet permissions for a User Group: 

1. Choose User Management ‐‐> Users/Group Outlet Permissions. The User/Group Outlet Permissions window appears. 

 

2. Select the User Group from the drop‐down list in the Group field. The permissions that apply to this group are displayed. If this is the first time you are setting the permissions for this group, all permissions are set to No. 

Page 58: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up User Groups

48

3. Set the permissions as necessary. Click this icon   in a field and select either Yes or No. 

4. When you are finished, click Apply. The permissions are applied to the User Group. 

Note:  The User field on this window is used to set individual user permissions. If you are setting group permissions, you may ignore this field. 

Copying a User Group

You can create a new User Group with the exact same permissions as an existing User Group by using the copy function. You can then modify the group so that its permissions differ as necessary from the original. This is a quick and easy way to create User Groups. 

To copy a User Group: 

1. Choose User Management ‐‐> Users & Groups. The User/Group Management window appears. 

2. Select the existing User Group from the drop‐down list in the Existing Groups field. 

3. Type the name of the new User Group in the New Group Name field. 

4. Click Copy. A new User Group is created with the same permissions as the existing group. The new User Group can be seen by clicking the drop‐down list in the Existing Groups field. 

Modifying a User Group

The only attribute of a User Group that can be modified is the group name. To do this: 

1. Choose User Management ‐‐> Users & Groups. The User/Group Management window appears. 

2. Select the User Group you want to modify from the drop‐down list in the Existing groups field. The name appears in the New group name field. 

3. Make any necessary changes to the name. 

4. Click Modify. The User Group is modified. 

Page 59: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

49

Note:  To modify a User Groupʹs system or outlet permissions, repeat the procedure for setting the system or outlet permissions described above and make any necessary changes. 

Deleting a User Group

To delete a User Group: 

1. Choose User Management ‐‐> Users & Groups. The User/Group Management window appears. 

2. Select the User Group you want to delete from the drop‐down list in the Existing groups field. 

3. Click Delete. The User Group is deleted. 

Setting Up Access Controls

The Dominion PX provides a number of tools to control access to the unit. You can require HTTPS encryption, enable the internal firewall and create firewall rules, and create login limitations. 

Forcing HTTPS Encryption

HTTPS is a more secure protocol than HTTP because it uses Secure Sockets Layer (SSL) technology to encrypt all traffic to and from the Dominion PX. To require users to use HTTPS instead of HTTP when accessing the Dominion PX through the Web interface: 

1. Choose Device Settings ‐‐> Security. The Security Settings window appears.  The panel at the upper left is labeled HTTP Encryption. 

   

2. Click the checkbox labeled Force HTTPS for web access. 

3. Click Apply. HTTPS is now required for browser access. 

Note:  Attempts using HTTP will be redirected back to HTTPS automatically, only if the option “Force HTTPS for web access” is checked. 

Page 60: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Access Controls

50

Configuring the Firewall

The Dominion PX has a firewall that can be configured to prevent specific IP addresses and ranges of IP addresses from accessing the Dominion PX. When the Dominion PX was initially configured, you were prompted to enable or disable IP access control. If you selected Disable (the default), the Dominion PX firewall was not enabled. 

To configure the firewall, you have to enable the firewall, and then you have to set the default policy and create rules specifying which addresses to accept and which addresses to drop. Changes made to firewall rules will take effect immediately. Any unauthorized IP activities will cease instantly. 

Note:  The purpose of disabling the firewall by default is to prevent users from accidentally locking themselves out of the unit. Refer to Installation and Configuration (on page 10) chapter for details. 

Enable the Firewall

To enable the Dominion PX firewall: 

1. Choose Device Settings ‐‐> Security. The Security Settings window appears.  The panel at the upper right is labeled IP Access Control. This controls the firewall. 

  

2. Click the checkbox labeled Enable IP Access Control. This enables the firewall. 

3. Click Apply. The firewall is enabled. 

Page 61: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

51

Change the Default Policy

Once enabled, the firewall has a default policy built in that accepts traffic from all IP addresses. This means any IP addresses not dropped by a specific rule will be permitted to access the Dominion PX. You can change the default policy to DROP, in which case traffic from all IP addresses will be dropped except traffic allowed by a specific ACCEPT rule. 

To change the default policy: 

1. Choose Device Settings ‐‐> Security. The Security Settings window appears.  The panel at the upper right is labeled IP Access Control. This controls the firewall. 

2. Make sure the checkbox labeled Enable IP Access Control is checked. 

3. The default policy is shown in the Default Policy field (refer to the figure shown above ). To change it, select the policy you want from the drop‐down list in the field. 

4. Click Apply. The new default policy is applied. 

Create Firewall Rules

Firewall rules accept or drop traffic intended for the Dominion PX, based on the IP address of the host sending the traffic. When creating firewall rules, keep the following in mind: 

• Rule order  The order of the rules is important. When traffic reaches the Dominion PX, the rules are executed in numerical order. The first rule that matches the IP address determines whether the traffic is accepted or dropped. Any subsequent rules matching the IP address have no effect on the traffic 

• Subnet mask  When typing the IP address, you MUST specify both the address and a subnet mask. For example, to specify a single address in a Class C network, use this format: 

x.x.x.x/24 

where /24 = a subnet mask of 255.255.255.0.To specify an entire subnet or range of addresses, change the subnet mask accordingly. 

To create firewall rules: 

1. Choose Device Settings ‐‐> Security. The Security Settings window appears.  The panel at the upper right is labeled IP Access Control. This controls the firewall. 

Page 62: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Access Controls

52

2. Make sure the checkbox labeled Enable IP Access Control is checked. 

Create specific rules. The following explains how:

Action Do this... Add a rule  to the end of the rules list 

• Type an IP address and subnet mask in the IP/Mask field. 

• Select ACCEPT or DROP in the Policy field. 

• Click Append. 

Do NOT enter a rule number. The system automatically numbers the rule. 

Insert a rule between two existing rules 

• Type a rule number where you want to insert a new rule above in the Rule # field. For example, to insert a rule between rules #5 and #6, type 6. 

• Type an IP address and subnet mask in the IP/Mask field. 

• Select ACCEPT or DROP from the drop‐down list in the Policy field. 

• Click Insert. 

The system inserts the rule and automatically renumbers the rules. 

Replace an existing rule   • Type the number of the rule to be replaced in the Rule # field. 

• Type an IP address and subnet mask in the IP/Mask field. 

• Select ACCEPT or DROP from the drop‐down list in the Policy field. 

• Click Replace. 

This system replaces the existing rule with the one you just created. 

 

1. When you are finished, the rules are displayed in the IP Access Control panel, as shown below. 

 

Page 63: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

53

2. Click Apply. The rules are applied. 

Delete Firewall Rules

To delete a firewall rule: 

1. Choose Device Settings ‐‐> Security. The Security Settings window appears. 

2. Make sure the checkbox labeled Enable IP Access Control is checked. 

3. Type the number of the rule to be deleted in the Rule # field. 

4. Click Delete. The rule is removed from the IP Access Control panel. 

5. Click Apply. The rule is deleted. 

Creating Group Based Access Control Rules

Group based access control rules are similar to firewall rules, except they can be applied to members of specific User Groups. In effect, this enables you to give entire User Groups system and outlet permissions based on their IP addresses or subnets. 

To create group based access control rules, you first have to enable the feature. Then, you have to set the default action, specify an IP address range, and associate the rule with a specific User group. Finally, you have to indicate whether the rule will accept or drop traffic. However, changes made will not affect users currently logged in until the next login. 

Enable the feature

To enable group based access control rules: 

1. Choose Device Settings ‐‐> Security. The Security Settings window appears. The panel labeled Group based System Access Control controls this feature. 

 

Page 64: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Access Controls

54

2. Click the checkbox labeled Enable Group based System Access Control. This enables the feature. 

3. Click Apply. Group based access control rules are enabled. 

Change the Default Action

The default action is shown in the Group based System Access Control panel on the Security Settings window. To change the default action: 

1. Choose Device Settings ‐‐> Security. The Security Settings window appears. The panel labeled Group based System Access Control controls this feature. 

2. Make sure the checkbox labeled Enable Group based System Access Control is checked. 

3. Select the action you want from the drop‐down list in the Default Action field (refer to the figure above). 

4. Click Apply. The default action is applied. 

Create Group Based Access Control Rules

Group based access control rules accept or drop traffic intended for the Dominion PX, based on the userʹs group membership. Like firewall rules, the order of the rule is important, since the rules are executed in numerical order. 

To create group based access control rules: 

1. Choose Device Settings ‐‐> Security. The Security Settings window appears. The panel labeled Group based System Access Control controls this feature. 

2. Make sure the checkbox labeled Enable Group based System Access Control is checked. 

3. Create or delete specific rules. The following explains how: 

Page 65: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

55

Action Do this... Add a rule  to the end of the rules list 

• Type a starting IP address in the Starting IP field. 

• Type an ending IP address in the Ending IP field. 

• Select a User Group from the drop‐down list in the Group field. This rule applies to members of this group only. 

• Select ACCEPT or DROP from the drop‐down list in the Policy field. 

• Click Append. 

Do NOT enter a rule number. This system automatically numbers the rule. 

Insert a rule between two existing rules 

• Type the higher of the two rule numbers in the Rule # field. For example, to insert a rule between rules #5 and #6, type 6. 

• Type a starting IP address in the Starting IP field. 

• Type an ending IP address in the Ending IP field. 

• Select ACCEPT or DROP from the drop‐down list in the Action field. 

• Click Insert. 

The system inserts the rule and automatically renumbers the rules. 

Replace an existing rule  

• Type the number of the rule to be replaced in the Rule # field. 

• Type an IP address and subnet mask in the IP/Mask field. 

• Select ACCEPT or DROP from the drop‐down list in the Action field. 

• Click Replace. 

This system replaces the existing rule with the one you just created. 

 

1. When you are finished, click Apply. The rules are applied. 

Delete Group Based Access Control Rules

To delete a firewall rule: 

1. Choose Device Settings ‐‐> Security. The Security Settings window appears. 

Page 66: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Access Controls

56

2. Make sure the checkbox labeled Enable Group based System Access Control is checked. 

3. Type the number of the rule to be deleted in the Rule # field. 

4. Click Delete. The rule is removed from the Group based System Access Control panel. 

5. Click Apply. The rule is deleted. 

Setting Up User Login Controls

You can set up login controls to make it more difficult for hackers to access the Dominion PX and the devices connected to it. You can arrange to lock persons out after a specified number of failed logins, limit the number of persons who can log in at the same time using the same login, and force users to create strong passwords. 

Enable User Blocking

User blocking allows you to determine how many times a user can attempt to log into the Dominion PX and fail authentication before the userʹs login is blocked. To set it up: 

1. Choose Device Settings ‐‐> Security. The Security Settings window appears. The User Blocking panel controls this feature. 

 

2. Type a number in the Max. number of failed logins field. This is the maximum number of failed logins the user is permitted before the userʹs login is blocked from accessing the Dominion PX. If no number is entered, there is no limit on failed logins. 

3. Type a number in the Block time field.  This is the length of time in minutes the login is blocked. 

4. Click Apply. The user blocking limits are applied. 

Page 67: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

57

Enable Login Limitations

Login limitations allow you to determine whether more than one person can use the same login at the same time, and whether or not users will be required to change passwords at regularly scheduled intervals. 

To enable login limitations: 

1. Choose Device Settings ‐‐> Security. The Security Settings window appears. The Login Limitations panel controls this feature. 

  

2. To prevent more than one person from using the same login at the same time, click the checkbox labeled Enable Single Login Limitation. 

3. To force users to change their passwords regularly, click the checkbox labeled Enable Password Aging, and then enter a number of days in the Password Aging Interval field. Users will be required to change their password every time that number of days has passed. 

4. Click Apply. The controls are applied. 

Page 68: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Access Controls

58

Enable Strong Passwords

Forcing users to create strong passwords makes it more difficult for intruders to crack user passwords and access the Dominion PX unit. Strong passwords should be at least eight characters long and should contain upper and lowercase letters, numbers, and special characters (such as @ or &). 

To force users to create strong passwords: 

1. Choose Device Settings ‐‐> Security. The Security Settings window appears. The Strong Passwords panel appears at the bottom of the window. 

 

2. Click the checkbox labeled Enable Strong Passwords to activate the strong password feature. The following are the default settings: 

 

Minimum length  = 8 characters 

Maximum length  = 16 characters 

At least one lowercase character  = Required 

At least one uppercase character  = Required 

At least one numeric character  = Required 

At least one printable special character  = Required 

Number of restricted passwords  = 5 

 

Page 69: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

59

3. Make any necessary changes to the default settings. 

4. When you are finished, click Apply. The changes are applied. 

Setting Up a Digital Certificate

The purpose of an X.509 digital certificate is to ensure that both parties in an SSL connection are who they say they are. To obtain a certificate for the Dominion PX, you must create a Certificate Signing Request (CSR) and submit it to a certificate authority (CA). 

Once the CA has processed the information in the CSR, it will provide you with a certificate, which you must install on the Dominion PX. 

Note:  Refer to “Forcing HTTPS Encryption (on page 49)” for instructions on forcing users to employ SSL when connecting to the Dominion PX. 

Page 70: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up a Digital Certificate

60

Creating a Certificate Signing Request

To create a CSR: 

1. Choose Device Setting ‐‐> Certificate. The first page of the SSL Server Certificate Management window appears. 

 

2. Provide the information requested. Type the following in the appropriate fields: 

Field Type this... Common name   The name of your company 

Organization unit   The name of your department 

Organization  The name of your organization within the department 

Locality/City   The city where your company is located 

Page 71: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

61

State/Province   The state or province where your company is located 

Country (ISO code)   The country where your company is located. Use the standard ISO code.  

For a list of ISO codes, go to this Web site: 

http://www.iso.org/iso/en/prods‐services/iso3166ma/ 02iso‐3166‐code‐lists/list‐en1.ht 

Email  An email address where you or another administrative user can be reached 

Challenge Password 

Confirm Challenge  Password  

The password that will be required to access the Dominion PX. Type it first in the Challenge Password field and then again in the Confirm Challenge password field.  

The password is case sensitive, so be sure to capitalize the same letters each time. 

3. Select the key length from the drop‐down list in the Key Length (bits) field. Default is 1024, but you can also select 2048. 

4. Click Create. The CSR is created and the second page of the SSL Server Certificate Management window appears. This window shows the information you entered when creating the CSR. 

 

5. To download the newly‐created CSR to your computer, click Download. You will be prompted to open or save the file. The file is called csr.txt. 

6. Once the file is stored on your computer, submit it to a CA to obtain the digital certificate. 

Installing a Certificate

Once the CA has provided you with a digital certificate, you must install it on the Dominion PX. To do this: 

1. Make sure a certificate has been created prior to any further configuration. Next, choose Device Settings ‐‐> Certificate. The second page of the Server Certificate Management window appears. 

Page 72: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up External User Authentication

62

2. Type the path and name of the certificate file in the SSL Certificate File field, or click Browse and select the file. 

3. Click Upload. The certificate is installed on the Dominion PX. 

Setting Up External User Authentication

For security purposes, users attempting to log into the Dominion PX must be authenticated. You can use the local database of user profiles in the Dominion PX, or you can use the Lightweight Directory Access Protocol (LDAP) or the Remote Access Dial‐In User Service (RADIUS) protocol. 

By default, the Dominion PX is configured for local authentication. If you stay with this method, you do not have to do anything other than create user profiles for each authorized user. If you prefer to use an external LDAP or RADIUS server, you have to provide the system with information about the server. 

Keep in mind that you still need to create user profiles for users who are authenticated externally. This is because the user profile determines the User Group to which the user belongs, and the User Group determines the userʹs system and outlet permissions. 

Page 73: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

63

Settings Up LDAP Authentication

To set up LDAP authentication: 

1. Choose Device Settings ‐‐> Authentication. The Authentication Settings window appears. The LDAP parameters appear on the left side of the window. 

   

2. Click the radio button labeled LDAP. 

3. Type the IP address of the LDAP server in the User LDAP Server field. 

4. To encrypt traffic to and from the LDAP server, click the checkbox labeled SSL Enabled. 

5. By default, the Dominion PX uses the standard ports 389 for LDAP and 636 for secure LDAP (SSL). If you prefer to use non‐standard ports, change the ports. 

Note:  The SSL port is only enabled if you click the check box in Step 3. 

Page 74: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up External User Authentication

64

6. Type the base DN in the Base DN of user LDAP server field. The base distinguished name (DN) is the top level of the LDAP directory tree. It indicates where in the LDAP directory you want to begin searching for user credentials. 

7. Select the type of LDAP server from the drop‐down list in the Type of external LDAP server field. Your choices are: 

Generic LDAP Server 

Novell Directory Service 

Microsoft Active Directory 

8. Type the following information in the corresponding fields. LDAP needs this information to verify user names and passwords. 

Login name attribute (also called as “AuthorizationString”) 

User entry object class 

User search subfilter (also called as “BaseSearch”) 

9. If you selected Microsoft Active Directory in Step 6, enter the domain name in the Active Directory Domain field. 

10. Click Apply. LDAP authentication is now in place. 

Setting Up RADIUS Authentication

To set up RADIUS authentication: 

1. Choose Device Settings ‐‐> Authentication. The Authentication Settings window appears. The RADIUS parameters appear on the right side of the window. 

  

2. Click the radio button labeled RADIUS. 

3. Type the IP address of the RADIUS server in the Server field. 

4. Type the shared secret in Shared Secret field. The shared secret is necessary to protect communication with the RADIUS server. 

Page 75: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

65

5. By default, the Dominion PX uses the standard RADIUS port 1812 (authentication) and 1813 (accounting). If you prefer to use non‐standard ports, change the ports. 

6. Type the timeout period in seconds in the Timeout field. This sets the maximum amount of time to establish contact with the RADIUS server before timing out. Default is 1 second. 

7. Type the number of retries permitted in the Retries field. Default is 3. 

8. If you have additional RADIUS servers, click the More Entries button. Fields for four additional servers appear. Enter the same information in Steps 2 ─ 7 for each additional server. 

9. Select an authentication protocol from the drop‐down list in the Global Authentication Type field. Your choices are: 

PAP (Password Authentication Protocol) 

CHAP (Challenge Handshake Authentication Protocol) 

CHAP is generally considered more secure because the user name and password are encrypted, while in PAP they are transmitted in the clear. 

10. Click Apply. RADIUS authentication is now in place. 

Setting Up Outlets and Power Thresholds

The Dominion PX is shipped with certain Dominion PX and outlet power thresholds already defined. You can change the default Dominion PX thresholds, and you can give each outlet a name and change its default thresholds. 

When setting the thresholds, keep in mind that you can set up alerts that are triggered whenever any of these thresholds are crossed. Refer to “Setting Up Alerts (on page 76)” section for details. 

Page 76: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Outlets and Power Thresholds

66

Setting the Default Outlet State

Sets a global default for the power state of the outlets when the Dominion PX unit is powered on. Setting an individual outletʹs startup state to something other than Device Default (refer to Naming the Outlets) will override this default state for that outlet. To set this default: 

1. Select Device Settings, and then select Unit Setup. The Unit Setup window appears. 

 

2. Select the default state from the drop‐down list in the Default outlet state on device startup field. 

3. When you are finished, click Apply. The default state setting is applied 

Setting the Dominion PX Thresholds

To set the Dominion PX thresholds: 

Choose Device Settings then Unit Setup. The Unit Setup window appears. 

1. Type a number in the field labeled Power off period during outlet power cycling. When the outlets on the Dominion PX are power cycled, they are turned off and then back on. The number you enter here determines the length of time (in seconds) it takes for the outlets to turn back on after they are shut down during the power cycle. The default is 10 seconds. The cycling delay can be set from 0 to 3600 seconds (one hour). 

Page 77: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

67

Note:  The number you enter here applies to all outlets on the Dominion PX. However, you can override this number for specific outlets, if you wish. refer to “Setting the Outlet Thresholds (on page 70)” section for more information. You can power cycle an outlet from the Outlet Details window. Refer to “Power Cycling an Outlet (on page 72)”  section for instructions. 

2. Type a number of seconds in the field labeled Sequence Delay in ms. The default is 200 milliseconds. 

3. Set the RMS voltage, current and temperature thresholds for the unit in the Thresholds panel. Enter critical or non‐critical threshold for each setting. 

4. When you are finished, click Apply. The delays and thresholds are applied. 

Note: When a large number of outlets are present, especially when dealing with outlets grouped from other Dominion PX Units, you may want to set both the Power off period and the Sequence Delays to lower numbers in order to avoid a long wait before all the outlets are available again. 

Setting the Outlet Power-Up Sequence

You can set the order in which the unitʹs outlets power up. This is useful when devices have multiple power supplies that should be powered‐on together. To do this: 

1. Select Device Settings, and then select Unit Setup. The Unit Setup window appears. 

 

2. The current outlet power‐up sequence appears in the list under Outlet Sequencing. To change the priority of an outlet, select it from the list and click one of four options: 

Page 78: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Outlets and Power Thresholds

68

• First moves the outlet to the top of the list and makes it the first outlet to receive power. 

• Up moves the outlet up one position in the list. 

• Down moves the outlet down one position in the list. 

• Last moves the outlet to the bottom of the list and makes it the last outlet to receive power. 

1. Click Apply. The new sequence is saved. 

Note: If you use Outlet Grouping to group outlets together, you should adjust the Outlet Sequencing to ensure that all outlets from this Dominion PX, that are part of the same group, power up consecutively. 

 

Page 79: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

69

Naming the Outlets

You can give each outlet a name to help you identify the device connected to it. To do this: 

1. Choose Power Outlets ‐‐> Outlet Setup. The Outlet Setup window appears. 

 

2. Select the outlet from the drop‐down list in the Show setup of outlet field. 

3. Type a name for the outlet in the Outlet Name field. It is a good idea to give the outlet an easily recognizable name that helps you identify the device connected to it. You can always change names if the device is replaced. 

4. Select an outlet state from the drop‐down list in the Outlet state on device startup. This will determine if the outlet is ON or OFF when the Dominion PX powers up. If set to Device Default, the state for this outlet will be determined by the Default Outlet State in the Unit Setup page. 

Page 80: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Outlets and Power Thresholds

70

5. Click Apply. The new name is applied. 

Setting the Outlet Thresholds

To set the current thresholds of an outlet: 

1. Choose Power Outlets ‐‐> Outlet Setup. The Outlet Setup window appears. 

2. Select an outlet from the drop‐down list in the Show setup of outlet field. 

3. Type a number in the field labeled Power off period during outlet power cycling. When an outlet is power cycled, it is turned off and then back on. The number you enter here determines the length of time (in seconds) it takes for the outlet to turn back on after it is shut down during the power cycle. If left blank, this outlet will use the value set in the Unit Setup page as a default. 

Note: You can power cycle an outlet from the Outlet Details window. Refer to “Power Cycling an Outlet (on page 72)” section for instructions. 

4. Set the RMS current thresholds for the outlet in the Thresholds panel. 

5. When you are finished, click Apply. The setup details are applied. 

Page 81: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

71

Viewing Outlet Details

To display details about a particular outlet: 

1. Choose Power Outlets ‐‐> Outlet Details. The Outlet Details window appears. 

 

2. Select an outlet from the drop‐down list in the Show details of outlet field. The window shows these details about the outlet: 

Outlet name 

Outlet status 

RMS current, voltage and power readings, including: 

RMS current 

Power Factor 

Maximum RMS Current 

RMS Voltage 

Active Power 

Apparent Power 

Page 82: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Environmental Sensors

72

Note:  To display the Outlet Setup window, click the [Setup] link. Refer to Naming the Outlets (on page 69) section for a picture of the Outlet Setup Window. 

Power Cycling an Outlet

To turn an outlet off and on: 

1. Choose Power Outlets ‐‐> Outlet Details. The Outlet Details window appears. 

2. Select an outlet from the drop‐down list in the Show details of outlet field. The outlet must be ON. 

3. Click Cycle. The outlet turns OFF and then back ON. 

Note:  You can also power cycle an outlet from the Home window. 

The length of time between the off and on states in a power cycle can be set on the Dominion PX as a whole, and for individual outlets. Refer to ”Setting the Dominion PX Thresholds (on page 66)” and ”Setting the Outlet Thresholds (on page 70)” sections for details. 

Turning an Outlet On or Off

To turn an outlet on or off: 

1. Choose Power Outlets ‐‐> Outlet Details. The Outlet Details window appears. 

2. Select an outlet from the drop‐down list in the Show details of outlet field. 

3. Click On to turn the outlet ON. Click Off to turn the outlet OFF. 

Note: You can also turn an outlet on or off from the Home window. 

Environmental Sensors

In addition to monitoring its own internal temperature, Dominion PX can monitor the environment where environmental sensors are placed. 

Connecting the Environmental Sensors

To enable Dominion PX to measure environmental factors, connect the cable of the environmental sensors to the Feature port of the unit. 

 

Page 83: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

73

Mapping the Environmental Sensors

Once the sensors have been physically connected to the Dominion PX, they must be mapped to the unitʹs logical sensors before Dominion PX will recognize (and display) the readings from them. To do this:s 

1. Select Device Settings, and then select Environmental Sensors. The Environmental Sensors window appears. The page will list the logical Temperature and Humidity sensors first. 

 

2. When physical sensors are attached to the Dominion PX, they will appear listed below the logical sensors. Temperature senors will be listed in the Environmental Temperature Sensors table, humidity sensors in the Environmental Humidity Sensors table. If the sensors are not attached properly, the page will state that ʺNo sensors were detectedʺ. 

3. For each physical sensor (shown as a row) in the table, click a radio select under the logical sensor (shown as columns) you want to map it to. Dominion PX will now track this sensors readings and will display them on the home page when configuration is finished. 

If you do not want to track the readings of a particular sensor, leave that row blank. 

Page 84: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Environmental Sensors

74

4. To unmap a logical sensor from any physical sensor, clilck clear at the bottom of the column. That logical sensor will no longer be associated with any of the physical sensors. 

Note: It is possible (but not advisable) to map more than one logical sensor to a single physical sensor. You cannot map multiple physical sensors to a single logical one. 

 

Configuring Environmental Sensors and Thresholds

To make sensors more useful, you should rename the logical sensors that are in use and configure their threshold settings. Configuring thresholds for these sensors allows Dominion PX to generate an alert whenever environmental factors at those sensors move outside of your idea values. 

1. From the Environmental Sensors page, locate the logical sensors that have been mapped to physical sensors as described above. 

 

2. In the Name field, type a new name for each mapped sensor that will help you identify the sensor and its purpose. 

3. Configure the upper and lower thresholds for each sensor in use.  

• The Upper Critical and Lower Critical values are points at which the Dominion PX considers the operating environment is critical, and outside the range of the acceptable threshold. 

• Once critical, the temperature or humidity must drop below the Upper Non‐Critical (or raise above the Lower Non‐Critical) value before the Dominion PX considers the environment to be acceptable again. 

1. Click Apply. The sensor name and threshold settings are saved. 

Page 85: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

75

When the configuration changes have been applied, the sensor readings will be displayed on the Home Page next to the outlets list and the sensor names will be updated. This updated name will also display in the physical sensors table at the bottom of the Environmental Sensors page. This can be useful for ensuring that the physical and logical sensors are correctly mapped together. 

 

 Note: The recommended maximum ambient operating temperature for the Dominion PX is 40 degrees Celsius. 

Viewing Sensor Readings

Mapped sensor readings appear beside the outlets list any time the Home page is displayed. To view the readings from any other page, click Home in the navigation path at the top of the window. 

 

Page 86: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Alerts

76

Setting Up Alerts

The Dominion PX can be configured to issue an alert whenever a threshold is crossed, either for the Dominion PX unit as a whole or for a specific outlet. The alert can be programmed to send an administrator an email message, or it can be programmed to send a Simple Network Management Protocol (SNMP) trap to a specific IP address. 

Note:  Refer to “Setting Up Outlets and Power Thresholds (on page 65)”  section for instructions on setting power thresholds. 

Configuring Alert Events

Alert events consist of an outlet, an associated threshold, and an associated policy. To configure an alert event: 

1. Choose Alerts ‐‐> Alert Configuration. The Alert Configuration window appears. It shows all existing policies. 

 

2. Go to the Event field and select the outlet from the first (left) drop‐down list. You can select the Dominion PX unit as a whole or you can select a specific outlet. You can also select an individual relay board, the Environmental Temperature Sensors or the Environmental Humidity Sensors. 

Page 87: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

77

3. Select the threshold from the second drop‐down list in the Event field as shown below. The list of thresholds will vary depending on what was selected in the first drop‐down list. 

 

4. Select an Event Direction from the third drop‐down list. 

• If set to Assert, this alert will only trigger when a measured value moves past a critical threshold (either above an upper critical threshold, or below a lower critical one). 

• If set to Deassert, this alert will only trigger when a measured value returns to normal from a critical state (either below an upper non‐critical threshold, or above a lower non‐critical one). 

• If set to Assert & Deassert, this alert will trigger when a measured value crosses any threshold state. 

1. Select a policy from the drop‐down list in the Policy field. 

2. Click Add. The alert is added to the system. 

Note:  No policies appear in this drop‐down list until you create them. Refer to “Creating Alert Policies (on page 78)”  section for instructions. 

If an Environmental Temperature or Humidity sensor is selected, an event will be created for each logical Temperature or Humidity sensor. These event alerts can be deleted so that only the ones you want are present. 

Page 88: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Alerts

78

Creating Alert Policies

Alert policies allow you to associate events with destinations. Policies determine whether specific events trigger an entry in the event log, an email message to an administrator, an SNMP trap, a selected outlet to be switched on/off/cycled, or any combination of the four. 

About Policies

The diagram below illustrates the way policies associate events with destinations. In this example, five events and two policies are defined.  

• Events 1 and 2 are associated with the Red policy. This means they trigger an email message to an administrator and an SNMP trap. 

• Events 3, 4, and 5 are associated with the Syslog policy. They trigger entries in the event log and selected outlets to be switched, but do not send email messages or traps. 

 

Display Existing Policies

To display a list of existing policies: 

1. Choose Alerts ‐‐> Alert Policies. The Alert Policies window appears. It lists each policy and shows their destinations. 

 

Page 89: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

79

2. You can modify or delete a policy by clicking the corresponding button next to the policy. You can add a new policy and configure alerts and destinations by clicking the appropriate link. 

Create a Policy

To create a policy: 

1. Choose Alerts ‐‐> Alert Policy Editor. The Alert Policy Editor appears. 

 

2. Type a name for the policy in the New policy Name field. 

Page 90: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Alerts

80

3. Select the destinations associated with the policy in the Destinations panel. Your choices are System (event log), Switch Outlet, eMail, and SNMP. 

4. Click Create. The policy is created. 

Modify a Policy

To modify a policy: 

1. Choose Alerts ‐‐> Alert Policy Editor. The Alert Policy Editor appears. 

2. Select the policy to be modified from the drop‐down list in the Existing Policies field. 

3. Make any necessary changes to the policyʹs name or destinations. 

4. Click Modify. The policy is modified. 

Delete a Policy

To delete a policy: 

1. Choose Alerts ‐‐> Alert Policy Editor. The Alert Policy Editor appears. 

2. Select the policy to be deleted from the drop‐down list in the Existing Policies field. 

3. Click Delete. The policy is deleted. 

Note: The default alert policy ‐ System Event Log cannot be deleted. 

Page 91: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

81

Specifying the Alert Destination

The alert destination can be an email address or an SNMP trap. To specify the destination: 

1. Choose Alerts ‐‐> Alert Destinations. The Alert Destinations window appears. 

 

Note:  If you have not configured the Dominion PXʹs SMTP, a note will appear on this page prompting you to do so now. You cannot enter an email address until you have configured the SMTP server. Either click the SMTP server here link that appears this page, or select Devices Settings ‐‐> SMTP Settings. Refer to Configuring the SMTP Settings (on page 97) section for details. 

2. Select the destination from the drop‐down list in the Destination type field. Your choices are Event Log, Switch Outlets, eMail and SNMP. 

3. Do one of the following: 

Event Log  This is one of the default options for Alert Destination. If you selected this option, event entries are recorded in the event log. This destination is built in by default, and can be neither added nor deleted. 

Switch Outlets  This is one of the default options for Alert Destinations. If you selected this option, configured outlet is switched on, off, or cycled. This destination is built in by default, and can be neither added nor deleted. 

Page 92: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Event Logging

82

Email  If you selected email, type the receiverʹs email address. 

SNMP  If you selected SNMP, enter the IP address of the trap and the community string. 

4. Click Add. The destination is added. 

Note:  To delete an alert destination, click the appropriate Delete button. 

 

Note: The Dominion PX is capable of sending out two types of SNMP traps, including: (1) PX‐specific traps, which are sent if configured in Event Log setting, while the PDU‐MIBs should be self‐explanatory. (2) IPMI PET (Platform Event Traps) traps, which are generated in alert configuration and sent out in IPMI‐specific formats, containing raw data. Details of such traps can be referenced at: http://www.intel.com/design/servers/ipmi/pdf/IPMIv2_0_rev1_0_E3_markup.pdf (http://www.intel.com/design/servers/ipmi/pdf/ipmiv2_0_rev1_0_e3_markup.pdf) (Chapter 17.16) and http://download.intel.com/design/servers/ipmi/PET100.pdf (http://download.intel.com/design/servers/ipmi/pet100.pdf). 

Setting Up Event Logging

By default, the Dominion PX captures certain system events and saves them in a local (internal) event log. You can expand the scope of the logging to also capture events in the NFS, SMTP, and SNMP logs. 

Page 93: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

83

Configuring the Local Event Log

To configure the local event log: 

1. Choose Device Settings ‐‐> Event Log. The Event Log Settings window appears. The Local Logging panel appears first. This panel controls the local event log. 

 

2. The local event log is enabled by default. To turn it off, uncheck the checkbox labeled Local Logging Enabled. 

3. By default, 20 log entries appear on each page of the local event log when it is displayed on your screen. To change this, type a different number in the Entries shown per page field. 

4. To clear all events from the local event log: 

a. Click the Clear button. The button changes to Really Clear and you are prompted to click it only if you really want to clear the log. 

b. Click Really Clear to complete the clear operation, or click Cancel to terminate it. 

Page 94: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Event Logging

84

5. By default, when the local event log is enabled, seven event types appear in the Event Log Assignments panel to the right. All are enabled by default. To disable any of these event types, clear the appropriate check boxes. 

 

 Note:  Refer to the Event Types appendix for a more detailed explanation of these event types. 

6. When you are finished, click Apply. Local logging is configured. 

Page 95: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

85

Viewing the Internal Event Log

To display the internal event log, select Maintenance and then select View Event Log. 

 

Entries

For each entry, the event log shows: 

• The date and time of the event 

• The type of event (board message, security, host control, or authentication) 

• A brief description of the event. For example, for an authentication event, the entry in the log shows the userʹs login name and the IP address of the userʹs computer. 

Note:  By default, the internal event log displays 20 events per page. Refer to “Configuring the Local Event Log (on page 83)”  section for instructions on changing this number. 

Page 96: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Event Logging

86

Configuring NFS Logging

To configure Network File System (NFS) logging: 

1. Choose Device Settings ‐‐> Event Log. The Event Log Settings window appears. The NFS Logging panel controls NFS logging. 

 

2. Click the checkbox labeled NFS Logging Enabled. 

3. Type the IP address of the NFS server in the NFS Server field. 

4. Type the name of the shared NFS directory in the NFS Share field. 

5. Type the name of the NFS log file in the NFS Log File field. Default is evtlog. 

6. By default, when NFS logging is enabled, seven event types appear in the Event Log Assignments panel to the right. All are disabled by default. To enable any of these event types, check the corresponding checkboxes. 

 

7. Click Apply. NFS logging is configured. 

Page 97: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

87

Configuring SMTP Logging

To configure Simple Mail Transfer Protocol (SMTP) logging: 

1. Choose Device Settings ‐‐> Event Log. The Event Log Settings window appears. The SMTP Logging panel controls SMTP logging. 

 

2. Click the checkbox labeled SMTP Logging Enabled. 

3. Type the receiverʹs email address in the Receiver Email Address field. 

4. By default, when SMTP logging is enabled, seven event types appear in the Event Log Assignments panel to the right. All are disabled by default. To enable any of these event types, check the appropriate checkboxes. 

 

5. Click Apply. SMTP logging is configured. 

Important: If you have not configured the Dominion PXʹs SMTP settings, you must do so for SMTP logging to work. Click the here link at the bottom of the panel. Refer to “Configuring the SMTP settings (on page 97)” section for instructions. 

Page 98: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Setting Up Event Logging

88

Configuring SNMP Logging

Event logging can be performed by sending SNMP traps to a third‐party SNMP manager. Refer to the Using SNMP appendix for instructions on enabling SNMP Event Logging on Dominion PX. 

Configuring Syslog Forwarding

To configure Syslog Forwarding: 

1. Choose Device Settings ‐‐> Event Log. The Event Log Settings window appears. The Syslog Forwarding panel controls forwarding of system logs. 

 

2. Click the checkbox labeled Enable Syslog Forwarding. 

3. Type an IP address in the IP Address field. This is the address to which syslog will be forwarded. 

4. By default, when Syslog Forwarding is enabled, seven event types appear in the Event Log Assignments panel to the right. All are disabled by default. To enable any of these event types, check the appropriate checkboxes. 

  

5. Click Apply. Syslog Forwarding is configured.  

Page 99: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

89

Managing the Dominion PX

You can display basic device information about the Dominion PX, give the Dominion PX a new device name, and modify any of the network settings that were entered during the initial configuration process. You can also set the unitʹs date and time and configure its SMTP settings so it can send email messages when alerts are issued. 

Displaying Basic Device Information

1. To display basic information about a Dominion PX unit, choose Maintenance ‐‐> Device Information. The Device Information window appears. 

Page 100: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Managing the Dominion PX

90

   

2. This Device Information panel displays the product name, serial number, and IP and MAC addresses of the Dominion PX, as well as detailed information about the firmware running in the unit. 

3. To open or save an XML file providing details for Raritan Technical Support, click the link entitled View the datafile for support. 

Page 101: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

91

Displaying Model Configuration Information

To display information about the specific model of the Dominion PX that you are using, choose Maintenance ‐‐> Device Information. The Device Information window appears. Information about your model is shown in the Model Configuration Panel below the Device Information panel. See Figure 64 for details. 

This panel shows: 

• The unitʹs and boardʹs maximum RMS current 

• The outlet maximum RMS current and current thresholds sum restriction 

• The number of outlets mapped to the board 

Displaying Connected Users

To display a list of users currently connected to the Dominion PX, choose Maintenance ‐‐> Device Information. The Device Information window appears. A list of connected users is shown in the Connected Users Panel. See the figure shown in Displaying Basic Device Information (on page 89) section for details. 

The panel shows the username and IP address of each user, and indicates whether or not the connection is active. 

Page 102: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Managing the Dominion PX

92

Naming the Dominion PX

By default, the Dominion PX has a device name of pdu. You may want to give the Dominion PX a more easily recognizable name to help identify it. To do this: 

1. Choose Device Settings ‐‐> Network. The Network Settings window appears. The left side of the window consists of the Basic Network Settings panel, which contains the device name. 

 

2. Type a new name in the Device Name field. 

3. If DHCP is selected for IP configuration, the name entered in the field of Preferred Host Name (DHCP only) will be registered with DNS and used on the assigned IPs by DHCP. 

4. Click Apply. The Dominion PX is renamed. 

Page 103: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

93

Modifying the Network Settings

The Dominion PX was configured for network connectivity during the installation and configuration process (refer to Installation and Configuration (on page 10) chapter for details). If necessary, you can modify any of these settings. To do this: 

1. Choose Device Settings ‐‐> Network. The Network Settings window appears. The left side of the window consists of the Basic Network Settings panel, which shows the current network settings. Refer to the figure shown in Naming the Dominion PX (on page 92) section for details about this panel. 

2. Do one of the following: 

Auto configuration  To auto configure the Dominion PX, select DHCP or BOOTP from the drop‐down list in the IP Auto Configuration field. If you select DHCP, you can also enter a preferred host name (this is optional). 

Static IP    To enter a static IP address, select none from the drop‐down list in the IP Auto Configuration field, and then enter: 

IP address 

Subnet mask 

Gateway address 

Primary and (optional) secondary DNS server addresses 

3. When you are finished, click Apply. The network settings are modified. 

Page 104: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Managing the Dominion PX

94

Modifying the Communications, Port and Bandwidth Settings

You can use Telnet or SSH to log into the Dominion PXʹs CLP interface. However, by default SSH is enabled and Telnet is not (because it communicates in the clear and is therefore not secure). You can change this and enable or disable either application. 

You can also set a bandwidth limit, and change any of the default port settings. Finally, you can enable or disable the Raritan Setup Protocol. 

To do all this: 

1. Choose Device Settings ‐‐> Network. The Network Settings window appears. The Miscellaneous Network Settings panel on the top right contains the communications, port, and bandwidth settings. 

 

2. By default, CLP‐Telnet is disabled and CLP‐SSH is enabled. To change this, click either check box. 

3. To set an upper limit on the amount of bandwidth Telnet or SSH will be allowed to use, type the number of kilobits per second in the Bandwidth Limit field. 

4. By default, the HTTP, HTTPS, Telnet, and SSH ports are set to the standard ports for these communications protocols. If you prefer to use different ports, you can change the port assignments here. 

5. Click the check box labeled Disable Setup Protocol to disable it. 

Page 105: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

95

Note:  No programs are currently available to use the Setup Protocol with Dominion PX. It is safe to leave this disabled. 

6. When you are finished, click Apply. The settings are modified. 

Modifying the LAN Interface Settings

The LAN interface speed and duplex mode were set during the installation and configuration process (refer to  for details). To modify either setting: 

1. Choose Device Settings ‐‐> Network. The Network Settings window appears. The LAN Interface Settings panel on the bottom right shows the interface speed and duplex mode. 

  

2. To change the interface speed, select the speed you want from the drop‐down list in the LAN Interface Speed field. Your choices are: 

Autodetect (system selects optimum speed) 

10 Mbps 

100 Mbps 

3. To change the duplex mode, select the mode you want from the drop‐down list in the LAN Interface Duplex Mode field. Your choices are: 

Autodetect (system selects optimum mode) 

Half duplex 

Full duplex 

4. Half duplex allows data to be transmitted to and from the Dominion PX, but not at the same time. Full duplex allows data to be transmitted in both directions at the same time. 

5. When you are finished, click Apply. The settings are modified. 

Page 106: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Managing the Dominion PX

96

Setting the Date and Time

You can set the internal clock on the Dominion PX manually, or you can link to a Network Time Protocol (NTP) server and let it set the date and time. 

1. Choose Device Settings ‐‐> Date/Time. The Date/Time Settings window appears. 

  

2. Enter a time zone by selecting the appropriate Coordinated Universal Time (UTC) offset from the drop‐down list in the UTC Offset field (e.g. US Eastern Standard Time = UTC‐5). 

3. To set the date and time manually, click the radio button labeled User specified time then enter the date and time in the Date and Time fields. Use the yyyy/mm/dd format for the date and the hh:mm:ss format for the time. 

4. To let an NTP server set the date and time, click the radio button labeled Synchronize with NTP server and enter the IP addresses of primary and secondary NTP servers in the corresponding fields. But if PXʹs IP address is assigned through DHCP, the NTP server addresses will be automatically discovered, then users will not be able to enter any data in the fields of primary and secondary time server. 

5. Click Apply. The date and time settings are applied. 

Page 107: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

97

Configuring the SMTP Settings

The Dominion PX allows you to configure alerts to send an email message to a specific administrator. To do this, you have to configure the Dominion PXʹs SMTP settings and enter an IP address for your SMTP server and a senderʹs email address. 

Note:  Refer to “Setting Up Alerts (on page 76)”  section for instructions on configuring alerts to send emails. 

 

1. Choose Device Settings ‐‐> SMTP Settings. The SMTP Settings window appears. 

  

2. Type the IP address of the mail server in the SMTP Server field. 

3. Type an email address for the sender in the Sender Email Address field. 

4. If your SMTP server requires password authentication, type a user name and password in the User Account and Password fields. 

5. Click Apply. Email is configured. 

6. Now that you have applied the SMTP settings, you can test them to ensue they work correctly. To do this, type the receiverʹs email address in the Receiver Address field and click Send. 

Important: Do not test the SMTP settings until you have first applied them. If you do, you will lose the settings and be forced to re‐enter them. 

Page 108: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Managing the Dominion PX

98

Configuring the SNMP Settings

The SNMP Settings window allows you to enable and disable SNMP communication between an SNMP manager and the PX unit. Enabling SNMP communication will allow the PX to send SNMP trap events to the manager, as well as allow the manager to retrieve and control the power status of each outlet. 

To configure SNMP communication (necessary for passing SNMP traps as well as individual outlet control): 

1. Select Device Settings, and then select SNMP Settings. The SNMP Settings window appears. 

 

2. Check the box for Enable SNMP Agent to enable the Dominion PX to communicate with external SNMP managers. A number of options will then become available. 

3. Check Enable SNMP v1 / v2c Protocol to enable communication with an SNMP manager using SNMP v2c protocol. Then type the SNMP read‐only community string in the Read Community field and the read/write community string in the Write Community field.  

Page 109: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

99

4. Check Enable SNMP v3 Protocol to enable communication with an SNMP manager using SNMP v3 protocol.  

5. Type the System Location in the System Location field. 

6. Type the System Contact in the System Contact field. 

7. Click on the link at the bottom of the window to download an SNMP MIB for your Dominion PX to use with your SNMP manager. 

8. Click Apply. The SNMP configuration is set. 

Resetting the Dominion PX

You can use Unit Reset function to reboot the Dominion PX from the Web interface. To do this: 

1. Choose Maintenance ‐‐> Unit Reset. The Reset Operations window appears. 

  

2. Click Reset. A Reset Confirmation window appears. 

  

3. By clicking Really Reset button, the Dominion PX unit will reboot. If you change your mind, click Cancel to terminate the reset operation. If you choose to proceed with the reset, the window shown below appears and the reset takes place. The reset takes about one minute to complete. 

Page 110: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Managing the Dominion PX

100

  

4. When the reset is complete, the Dominion PX unit restarts and the Login window is displayed. Then, you can log back into the Dominion PX. 

Updating the Firmware

Raritan will notify customers when new firmware is available to update the Dominion PX. Customers will be given instructions where to go to download the new firmware. Once the firmware is downloaded onto a PC, you can install it on the Dominion PX from the Web interface. 

 

To perform a firmware update: 

1. Choose Maintenance ‐‐> Update Firmware. The Firmware Upload window appears. 

  

2. Type the complete path to the firmware file in the Firmware File field, or click Browse and select the file. 

3. Or in the Firmware URL field, type in an URL link where the firmware file is network‐retrievable. 

Page 111: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

101

4. Click Upload. The Firmware Update window appears. It shows the current firmware version and the new firmware version, and gives you a last chance to terminate the update. 

 

5. To proceed with the update, click Update. To terminate the update, click Discard. The update may take several minutes. The Status panel on the left tracks the progress of the upgrade.  

Note: Do NOT power the Dominion PX off during the update. To indicate at the rack that an update is in progress, the outlet LEDs will flash and the unitʹs three‐digit display panel will also show “FuP”. 

6. When the update is complete, a message appears similar to the one shown below indicating the update was successful. The Dominion PX will be reset, and the Login window will re‐appear. You can now log in and resume managing the Dominion PX. 

 

Note: If you are using Dominion PX with an SNMP manager, you should re‐download the Dominion PX MIB after updating the unitʹs firmware. This will ensure your SNMP manager has the correct MIB for the release you are using. Refer to the Using SNMP appendix for more information. 

Page 112: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Outlet Grouping

102

Outlet Grouping

Using the Outlet Grouping feature, users can combine outlets from separate Dominion PX Units into a single, logical group, allowing control from a single Dominion PX.  Outlets that are grouped together power on (and power off) together in unison, making outlet grouping ideal for servers with power supplies plugged into multiple Dominion PX units. 

Users, or the group they belong to must have the Outlet Group Configuration permission under User/Group System Permissions in order to manage or access an Outlet Group. 

Note: Outlet Grouping supports adding outlets from up to four other Dominion PX units. All units must be accessible over IP and must be running firmware version 1.1 or higher. 

 

Identifying Other Dominion PX Units

To add outlets from other Dominion PX units, you must first identify which Dominion PX units will be sharing their outlets. To do this: 

1. Select Outlet Groups, and then select Outlet Group Devices. The Outlet Group Devices window appears. 

 

2. Type a name to identify the Dominion PX unit you want to add in the Name field. 

3. Type the IP Address of the Dominion PX unit you want to add in the IP Address field. 

4. Optionally, type a Username and Password used to authenticate on the Dominion PX unit being added. You can leave these fields blank to use the same username and password as the Dominion PX currently being accessed. 

Page 113: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

103

5. Click Add/Modify. The new Dominion PX is now available for outlet grouping. 

To modify the name, or the Username and Password used to access a participating Dominion PX, simply retype the information for the same Dominion PX unit and click Add/Modify again. 

Note: You can re‐add the Dominion PX unit you are accessing (if you deleted it from the list) or modify its details by using the IP address 127.0.0.1. 

Grouping Outlets Together

Once the participating Dominion PX units have been added to list of outlet group devices, their individual outlets can be grouped together. Outlets that are grouped together will power on and power off together, in unison, using a control panel from the Dominion PX where the outlet group was created. 

To group outlets together: 

1. Select Outlet Groups, and then select Outlet Group Editor. The Outlet Group Editor window appears. 

 

Page 114: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Outlet Grouping

104

2. Type a name for the outlet group in the Name field. It is a good idea to give the outlet group a recognizable name that helps identify the device(s) connected to it. 

3. Type a comment for the outlet group in the Comment field. This can be used to further identify device(s) powered by the group. 

4. Under the Capabilities field, check the boxes of the Power Control abilities you want available for this outlet. 

5. A list of available Dominion PX units and their outlets appears under Collection of Real Outlets. Check the box representing the desired physical outlet to make it part of the outlet group. All outlets that are checked will be grouped together when you click Create. 

Note: You should not add a physical outlet to more than one outlet group. 

6. Click Create. The outlet group is created and added to the Outlet Groups list.  

Grouped outlets are designed to be controlled together. Avoid doing anything to affect these outlets individually, such as turning one of the outlets ON or OFF, or unplugging one of the participating Dominion PX units. Once grouped, power control to those outlets should be managed from the Outlet Groups List. 

Page 115: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 5: Using the Web Interface

105

Controlling Outlet Groups

Any outlet groups created from this Dominion PX will appear in the Outlet Groups List. From this list, you can power ON, Power OFF or cycle power to the outlet group (if the capability is available). To control the power to an outlet group: 

1. Select Outlet Groups, then Outlet Group Details. The Outlet Groups List appears. 

 

Note: Only outlet groups created through this specific Dominion PX will appear in this Outlet Groups list. Outlet groups created through another Dominion PX will not appear here, even if they contain outlets from this unit. 

2. To turn an outlet group on, off, or cycle the power to it, click On, Off or Cycle in the row for the outlet group. 

3. You will be prompted to confirm your choice. Click OK to proceed. 

4. The page will refresh once to indicate that the desired command was performed, and again a few seconds later to update the status of the outlet group. 

Page 116: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Outlet Grouping

106

Note: The page must finish loading or refreshing before selecting an action. If you select an action before the page has finished updating the status of all outlet groups, the command will be ignored. 

If you want to view or edit the composition of an outlet group, clicking on the name of the outlet group in the list will take you to the Outlet Group Editor for the selected outlet group. 

 

Editing or Deleting Outlet Groups

1. Select Outlet Groups, and then select Outlet Group Editor. The Outlet Group Editor window appears. 

2. Select the desired outlet group from the drop‐down list in the Outlet Groups field. 

3. The details for the outlet group appear. Change the name, comment, capabilities or any of the included Real Outlets if you are modifying the group. 

4. Click Modify to save any changes if you are modifying the outlet group, or click Delete to remote the group from the outlet groups list. 

Deleting Outlet Group Devices

To delete a Dominion PX from outlet grouping when it is no longer available or in use: 

1. Select Outlet Groups, and then select Outlet Group Devices. The Outlet Group Devices window appears with a list of known Dominion PX units. 

2. Click Delete for the Dominion PX you want to remove from outlet grouping. 

Note: If you delete a Dominion PX that still has outlets in a group, it will remove the associated outlets from that group, but the group will still exist. Remove the group itself using the Outlet Group Editor. 

You should not delete the host device (the Dominion PX you are currently accessing) from the Outlet Group Devices list. If you do, you can add it back to the list using the IP address 127.0.0.1. 

Page 117: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

107

 

Direct Access Interfaces

Access thru CC Interfaces Product

Association  Control  Association   Control  Connectivity

Max # of PX units supported

Dominion SX  >= 3.1 SX GUI 

<3.1 None 

RSC into PX serial port 

CC GUI  CC GUI  CSCSPCS‐1 or CSCSPCS‐10 

Max = number of serial ports 

P2CIM‐PWR Dominion KX KX‐I KX Manager  

KX‐II KX GUI 

RRC/MPC JAC for KX‐II Only 

CC GUI  CC GUI 

D2CIM‐PWR 

(Increased to 8 in KX1.3) 

UST  • Paragon Manager 

• OSD 

OSD  IPR + OSD  IPR + OSD  P2CIM‐PWR  Max = number of channel ports 

Paragon II

USTIP  • Paragon Manager 

• OSD 

• RRC  

• OSD PIISC + Paragon Manager 

CC GUI  P2CIM‐PWR  Max = number of channel ports 

 

Association: Associate the target with power outlet 

Control: Power On/Off, and Power Recycle the device 

CSCSPCS‐1: An adapter which still needs a Cat5 straight through cable to connect 

Chapter 6 Integration

Page 118: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Dominion KX

108

NOTE: Connecting any power CIM except the for the D2CIM‐PWR (e.g. P2CIM‐PWR) to the serial port of the Dominion PX will switch all the outlets to the ON state, even if they were previously OFF. 

In This Chapter Dominion KX..................................................................................................108 Paragon II........................................................................................................111 Dominion SX ..................................................................................................114 Dominion KSX................................................................................................116 CommandCenter ...........................................................................................117 

Dominion KX

Dominion KX (with the latest firmware) supports up to eight Dominion PX units, and requires P2CIM‐PWR and straight CAT5 cable. You can associate up to four outlets to a target; all four outlets can be from separate Dominion PX Units, if needed. 

KX Manager Application (Dominion KX-I only)

Use Raritanʹs KX Manager application to configure associations. To do this: 

1. Select the target. 

2. Edit the Properties and choose the outlets to associate. The outlets are automatically renamed to the associated targetʹs name. 

3. RRC for control. 

4. Select the target. 

5. Select On, Off, or Recycle power from pop‐up menu. 

6. Refer to KX user guide for details. 

Associate Outlets with a Target

1. Select target; select Properties from pop‐up menu. 

Page 119: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 6: Integration

109

2. Select up to eight Dominion PX units from drop‐down list. 

 

3. Select up to a total of four outlets from the PX units. 

 

Page 120: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Dominion KX

110

4. Notice the target icon change to indicate power. 

 

5. Notice the outlet icon change to indicate association. 

6. Notice the outlet name automatically changes to the targetʹs name. 

 

Control a Target's Power

1. Select target associated with outlets. 

Page 121: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 6: Integration

111

2. Select from Power On, Power Off, or Cycle Power options. 

 

Dominion KX-II

To use the Dominion KX II power control feature: 

1. Connect the Dominion PX to your target server. 

2. Name the Dominion PX unit. 

3. Associate outlet(s) in the Dominion PX to the target server. 

4. Utilize remote power management of the target server from the Port Access Page. 

Refer to Dominion KX‐II user guide for more details. 

Paragon II

Paragon II use requires P2CIM‐PWR and straight CAT5 cable. You can associate up to four outlets to a target; all four outlets can be from separate Dominion PX units,if necessary. 

Page 122: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Paragon II

112

Paragon Manager Application

Use Raritanʹs Paragon Manager application to configure associations: 

1. In Paragon Manager, select the target. 

2. Click the target icon and drag‐and‐drop it on the desired outlets. 

3. The outlets will be renamed to the associated targetʹs name automatically. 

4. To turn on, turn off, or recycle power to the target, click on the target and press the F3 key; select On, Off, or Recycle power from the drop‐down menu. 

Add a Dominion PX Unit in Paragon II

Add a Dominion PX unit exactly as you would add any second‐tier device. Your Paragon II unit auto‐detects the Dominion PX and changes the device type to PCR8, PCS12, or PCS20. On the OSD screen, press F5 to enter the Channel Configuration page. Select the channel and change the channel name from the default name to an identifying name for the Dominion PX unit. 

 

 

Page 123: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 6: Integration

113

Associate Outlets with a Target

On the OSD screen, press F5 to enter the Channel Configuration page and select the channel. Press G to enter the special second‐tier screen (Outlet Configuration page). 

 

Control a Target's Power

To control a targetʹs power: 

1. From either “Channel Selection by Name” OR “Channel Selection” menus, press F3 to control power. The message, “X‐Power Off; O‐Power On; R‐Recycle Power” appears on the scrolling help line. 

2. If no outlets associated with the server, “No power outlets” displayed 

3. If no permission to outlets associated with the server, “Permission denied.” displayed 

4. Else, Paragon automatically switches to the channel, so that the server is displayed in the background. If switch fails, “Switch fail.” displays 

5. If switch successful, all outlets associated with the server are displayed as shown on the left. 

6. User selects Outlet and Presses X, O, or R: 

7. If O, execute on command. 

8. If X or R, “Are you sure (yes/no)?” displayed. User must type “yes” (case insensitive) in order for command to execute. Type the full word for command to execute. 

Page 124: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Dominion SX

114

Control an Outlet's Power

When in “Channel Selection” Menus (NOT in “Channel Selection by Name”), users can navigate to individual Dominion PX ports and control power. 

User Selects Outlet and Presses X, O, or R: 

•  If no permission to the outlet, “Permission denied.” displayed 

•  If O, executes on command 

If X or R, “Are you sure (yes/no)?” displayed. User must type “yes” (case insensitive) in order for command to execute. Typing “Y” or “y” or “ye”, etc. is not acceptable. The full word, “yes” must be typed in order for command to execute. 

Pressing <ENTER> does nothing. 

The message, “X‐Power Off; O‐Power On; R‐Recycle Power” should appear on the scrolling help line. 

 

Dominion SX

By connecting to a Dominion SX, youʹre allowed to associate one or more outlets on a Dominion PX unit to specific DSX ports. 

 

Configure a Dominion PX Power Unit on Dominion SX

1. Choose Setup ‐‐> Power Strip Configuration.  

2. Click Add. The Power Strip Configuration screen appears. 

 

Page 125: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 6: Integration

115

3. Type a name and description in the Name and Description fields. 

4. Select the number of outlets from the drop‐down menu in the Number of Outlets field. 

5. Type the port number in the Port field. 

6. Click OK. 

Power Control

1. Choose Power Control ‐‐> Power Strip Power Control. 

2. The Outlet Control screen appears. 

 

3. Check the box of outlet number you wish to control, and click On/Off buttons to power on/off the selected outlet(s). 

Page 126: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Dominion KSX

116

4. A confirmation message will appear to indicate the successful operation. 

 Figure 1: Outlet Confirmation Screen 

Check Power Strip Status

1. Choose Power Control ‐‐> Power Strip Status. 

 

2. A status box appears to display details of the controlled Dominion PX, including power state of each outlet on the unit. 

Dominion KSX

Support of KSX G1 for Dominion PX is currently not available at this stage. However, Dominion PX can be managed as a serial target on one of KSXʹs serial ports, interacting through CLP interface. 

Page 127: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Chapter 6: Integration

117

CommandCenter

You can manage a Dominion PX from a CommandCenter if it is connected through any of the following Raritan products: 

• Dominion SX 

• Dominion KX 

• Paragon II 

• Refer to CC‐SG user guide for more details. 

NOTE: If you have to reboot or power OFF the Dominion PX while it is integrated with a Raritan product under CC‐SG management you should PAUSE MANAGEMENT of the integrated product until the Dominion PX fully powers ON again. Failure to do so may result in the outlets being deleted from CC‐SGʹs view and your power associations becoming lost when the Dominion PX is back online. 

Page 128: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

118

Model Rack V Current

Outlet Type

# of Outlets

Plug Type # of Circuit

# of Circuit Breaker

DPCR8‐15  1U  120  15  Nema 5‐15R  8  Nema 5‐15P  1  None 

DPCR8A‐16  1U  230  16  IEC320 C13  8  IEC60309 16A  1  None 

DPCR8A‐20L6  1U  208  20  IEC320 C13  8  Nema L6‐20P  1  None 

DPCS12‐20  0U  120  20  Nema 5‐15R  12  Nema 5‐20P  1  None 

DPCS12A‐16  0U  230  16  IEC320 C13  12  IEC60309 16A  1  None 

DPCS20‐20  0U  120  20  Nema 5‐15R  20  Nema 5‐20P  1  None 

DPCS20‐20L  0U  120  20  Nema 5‐15R  20  Nema L5‐20P  1  None 

DPCS20‐30L  0U  120  30  Nema 5‐15R  20  Nema L5‐30P  1  2 (dual) 

DPCS20A‐16  0U  230  16  IEC320 C13  20  IEC60309 16A  1  None 

DPCS20A‐32  0U  230  32  IEC320 C13  20  IEC60309 32A  1  2 

DPCS20A‐20L6  0U  208  20  IEC320 C13  20  Nema L6‐20P  1  None 

DPCS20A‐30L6  0U  208  30  IEC320 C13  20  Nema L6‐30P  1  2 (dual) 

DPCR20‐20  2U  120  20  Nema 5‐15R  20  Nema 5‐20P  1  None 

DPCR20‐30L  2U  120  20  Nema 5‐15R  20  Nema L5‐30P  1  2 (dual) 

DPCR20A‐32  2U  230  32  IEC320 C13  20  IEC60309 32A  1  2 

DPCR20A‐30L6  2U  208  30  IEC320 C13  20  Nema L6‐30P  1  2 

Appendix A Dominion PX Models

Page 129: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Appendix A: Dominion PX Models

119

 

Note: Per NEC rules, North American units should be de‐rated by 20%. For example, a Dominion PX rated at 30A can provide 24A of current in North America. 

Regardless of Dominion PX model, the maximum current load is 10A per outlet. 

In This Chapter Hardware Specification.................................................................................119 Environmental Specifications.......................................................................120 

Hardware Specification

Model weights (lb / kg) dimensions DPCR8‐15  8.02 / 3.64  17.32ʺ x 6.57” x 1.69ʺ; 440 x 167 x 43mm 

DPCR8A‐16  8.02 / 3.64  17.32ʺ x 6.57” x 1.69ʺ; 440 x 167 x 43mm 

DPCR8A‐20L6  8.02 / 3.64  17.32ʺ x 6.57” x 1.69ʺ; 440 x 167 x 43mm 

DPCS12‐20  7.67 / 3.48  2.24ʺ x 1.95ʺ x 49.33ʺ; 57 x 49.5 x 1,253mm 

DPCS12A‐16  7.67 / 3.48  2.24ʺ x 1.95ʺ x 49.33ʺ; 57 x 49.5 x 1,253mm 

DPCS20‐20  11.20 / 5.08  2.24ʺ x 1.95ʺ x 70.71ʺ; 57 x 43 x 1,796mm 

DPCS20‐20L  11.20 / 5.08  2.24ʺ x 1.95ʺ x 70.71ʺ; 57 x 43 x 1,796mm 

DPCS20‐30L  11.81 / 5.36  2.24ʺ x 1.95ʺ x 70.71ʺ; 57 x 43 x 1,796mm 

DPCS20A‐16  11.20 / 5.08  2.24ʺ x 1.95ʺ x 70.79ʺ; 57 x 43 x 1,798mm 

PCS20A‐32  11.81 / 5.36  2.24ʺ x 1.95ʺ x 70.79ʺ; 57 x 43 x 1,798mm 

DPCS20A‐20L6  11.20 / 5.08  2.24ʺ x 1.95ʺ x 70.79ʺ; 57 x 43 x 1,798mm 

DPCS20A‐30L6  11.81 / 5.36  2.24ʺ x 1.95ʺ x 70.79ʺ; 57 x 43 x 1,798mm 

DPCR20‐20  12.78 / 5.80  17.32ʺ x 3.46” x 10.79ʺ; 440 x 88 x 274mm 

DPCR20‐30L  13.40 / 6.08  17.32ʺ x 3.46” x 10.79ʺ; 440 x 88 x 274mm 

DPCR20A‐32  13.40 / 6.08  17.32ʺ x 3.46” x 10.79ʺ; 440 x 88 x 274mm 

DPCR20A‐30L6  13.40 / 6.08  17.32ʺ x 3.46” x 10.79ʺ; 440 x 88 x 274mm 

 

Page 130: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Environmental Specifications

120

Environmental Specifications

Environmental Factor Threshold Max Ambient Temperature  40 degrees Celsius 

 

Page 131: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

121

Dominion PX Series Unit Model                    ____________ 

 

Dominion PX Series Unit Serial Number      ____________ 

Appendix B Equipment Setup Worksheet

Page 132: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Environmental Specifications

122

OUTLET 1 

OUTLET 2  OUTLET3 

MODEL 

 

MODEL  MODEL 

SERIAL NUMBER 

 

SERIAL NUMBER  SERIAL NUMBER 

USE 

 

USE  USE 

OUTLET 4 

OUTLET 5  OUTLET 6 

MODEL 

 

MODEL  MODEL 

SERIAL NUMBER 

 

SERIAL NUMBER  SERIAL NUMBER 

USE 

 

USE  USE 

OUTLET 7 

OUTLET 8  OUTLET 9 

MODEL 

 

MODEL  MODEL 

SERIAL NUMBER 

 

SERIAL NUMBER  SERIAL NUMBER 

USE 

 

USE  USE 

OUTLET 10 

OUTLET 11  OUTLET 12 

Page 133: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Appendix B: Equipment Setup Worksheet

123

MODEL 

 

MODEL  MODEL 

SERIAL NUMBER 

 

SERIAL NUMBER  SERIAL NUMBER 

USE 

 

USE  USE 

OUTLET 13 

OUTLET 14  OUTLET 15 

MODEL 

 

MODEL  MODEL 

SERIAL NUMBER 

 

SERIAL NUMBER  SERIAL NUMBER 

USE 

 

USE  USE 

OUTLET 16 

OUTLET 17  OUTLET 18 

MODEL 

 

MODEL  MODEL 

SERIAL NUMBER 

 

SERIAL NUMBER  SERIAL NUMBER 

USE 

 

USE  USE 

OUTLET 19 

OUTLET 20   

MODEL 

 

MODEL   

Page 134: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Environmental Specifications

124

SERIAL NUMBER 

 

SERIAL NUMBER   

USE 

 

USE   

 

Types of adapters _____________________________________________________________ 

 

Types of cables ________________________________________________________________ 

 

Name of software program ______________________________________________________ 

 

 

 

 

Page 135: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

125

This section explains how to use the Command Line Protocol (CLP) interface to administer a Dominion PX. 

In This Chapter About the CLP Interface ...............................................................................125 Logging into the CLP interface ....................................................................126 Showing Outlet Information ........................................................................127 Turning an Outlet On or Off ........................................................................130 Querying an Outlet Sensor ...........................................................................130 

About the CLP Interface

The Dominion PX provides a command line interface that enables data center administrators to perform certain basic management tasks. You can access the interface over a serial connection using a terminal emulation program such as HyperTerminal, or via a Telnet or SSH client such as PuTTY. 

Note:  Telnet access to the Dominion PX is disabled by default because Telnet transmits in the clear and is insecure. To enable Telnet, select Device Settings ‐‐> Network and click the check box labeled Enable CLP‐Telnet Access. 

 

Note: About Terminal Emulation Programs ‐ HyperTerminal is available on many Windows OS. But HyperTerminal is not available on Windows Vista. PuTTY is a free program you can download from the internet. Please refer to PuTTYʹs documentation for details on configuration. 

 

The command line interface is based on the Systems Management Architecture for Server Hardware (SMASH) Command Line Protocol (CLP). Using this interface, you can do the following: 

• Display the name, power state (on or off), and sensors associated with each Dominion PX outlet 

• Turn each outlet on or off 

• Display the status of the sensors associated with each outlet 

Appendix C Using the CLP Interface

Page 136: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Logging into the CLP interface

126

Logging into the CLP interface

Logging in via HyperTerminal and a serial connection is a little different than logging in using SSH or Telnet. 

Using HyperTerminal

To log in using HyperTerminal: 

1. Connect your PC to the Dominion PX serial port via a serial cable, launch HyperTerminal and open a console window. When the window first appears, it is blank. 

2. Press Enter to display a Command prompt. 

  

3. At the Command prompt, type clp and press Enter. You are prompted to enter a login name. The login name is case‐sensitive, so make sure you capitalize the correct letters. 

 

4. Type a login name and press Enter. You are prompted to enter a password. 

  

5. Type a password and press Enter. The password is case‐sensitive, so make sure you capitalize the correct letters. Once the password is accepted, the clp:/‐> system prompt appears. 

Page 137: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Appendix C: Using the CLP Interface

127

  

6. You are now logged into the CLP interface and can begin using the interface to administer the Dominion PX. 

Using SSH or Telnet

To log in using SSH or Telnet: 

1. Launch an SSH or Telnet client such as PuTTY and open a console window. A Login prompt appears. 

  

2. Type a login name and press Enter. You are prompted to enter a password. 

  

3. Type a password and press Enter. The password is case‐sensitive, so make sure you capitalize the correct letters. Once the password is accepted, the clp:/‐> system prompt appears. 

  

4. You are now logged into the CLP interface and can begin using the interface to administer the Dominion PX. 

Showing Outlet Information

The show command displays the name, power state (on or off), and associated sensors for one outlet or for all outlets. 

Page 138: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Showing Outlet Information

128

Syntax

The following is the syntax for the show command: 

 

clp:/->  show /system1/outlet<outlet number> 

 

where <outlet number> is the number of the outlet. To display information for all outlets, type the wildcard asterisk (*) instead of a number. 

Attributes

You can use the name and powerState attributes to filter the output of the show command. The name attribute displays only the name of the outlet, and the powerState attribute displays only the power state (on or off). 

The following shows the syntax for both attributes: 

 

clp:/->  show -d properties=name /system1/outlet<outlet number> 

 

clp:/->  show -d properties=powerState /system1/outlet<outlet number

 

where <outlet number> is the number of the outlet. In both cases, the outlet number can also be a wildcard asterisk (*). 

Page 139: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Appendix C: Using the CLP Interface

129

Examples

The following are examples of the show command. 

Example 1 -- No Attributes

The following shows the output of the show command with no attributes entered. 

  

Example 2 -- Name Attribute

The following shows the output of the show command with the name attribute. 

  

Example 3 -- powerState Attribute

The following shows the output of the show command with the powerState attribute. 

 

Page 140: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Turning an Outlet On or Off

130

Turning an Outlet On or Off

The set command turns an outlet on or off. 

Syntax

The following is the syntax for the set command: 

 

clp:/->  set /system1/<outlet number> powerState=on|off 

 

where the keyword on turns the outlet on and the keyword off turns the outlet off. 

Querying an Outlet Sensor

The show command with the Antecedent key word queries an outletʹs sensors 

 

clp:/->  Show -d properties=Antecedent/system1/outlet<outlet number>=>AssociatedSensor 

 

where <outlet number> is the number of the outlet. 

 

 

 

 

 

Page 141: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

131

This Appendix will help you set up Dominion PX for use with an SNMP manager. The Dominion PX can be configured to send traps to an SNMP manager, as well as receive GET and SET commands in order to retrieve status and configure some basic settings. 

 

In This Chapter Enabling SNMP..............................................................................................132 Configuring SNMP Traps.............................................................................135 SNMP Gets and Sets......................................................................................136 

Appendix D Using SNMP

Page 142: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Enabling SNMP

132

Enabling SNMP

To communicate with an SNMP manager, you must first enable the SNMP agent on Dominion PX. This can be done from the SNMP Settings window: 

1. Select Device Settings, and then select SNMP Settings. The SNMP Settings window appears. 

 

2. Check the box for Enable SNMP Agent to enable the Dominion PX to communicate with external SNMP managers. A number of options will then become available. 

3. Check Enable SNMP v1 / v2c Protocol to enable communication with an SNMP manager using SNMP v1 or v2c protocol. Then type the SNMP read‐only community string in the Read Community field and the read/write community string in the Write Community field.  

4. Check Enable SNMP v3 Protocol to enable communication with an SNMP manager using SNMP v3 protocol.  

Page 143: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Appendix D: Using SNMP

133

• Additionally, check Force Encryption to force using encrypted SNMP communication. 

1. Type the SNMP MIBII sysLocation value in the System Location field. 

2. Type the SNMP MIBII sysContact value in the System Contact field. 

3. Click on the link at the bottom of the window to download an SNMP MIB for your Dominion PX to use with your SNMP manager. 

4. Click Apply. The SNMP configuration is set. 

 

Page 144: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Enabling SNMP

134

Configuring Users for Encrypted SNMP v3

The SNMP v3 protocol allows for encrypted communication. To take advantage of this, users will need to have a Encryption Phrase,which acts as a shared secret between them and the Dominion PX. This encryption phrase can be set in the User Management page. 

1. Choose User Management, then Users & Groups. The User/Group Management window appears. 

 

2. Select the user profile you want to modify from the drop‐down list in the Existing Users field. 

3. If you want to use the userʹs password as their Encryption Phrase leave the box marked Use Password as Encryption Phrase checked (or check the box if it is unchecked). 

Page 145: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Appendix D: Using SNMP

135

4. If you want to specify a different encryption phrase, uncheck this box, type the new phrase in the SNMP v3 Encryption Phrase field, then type it again in the Confirm SNMP v3 Encryption Phrase field. 

5. Click Modify. The user is now setup for encrypted SNMP v3 communication. 

Configuring SNMP Traps

Dominion PX automatically keeps an internal log of events that occur (refer to Setting Up Event Logging under the Using the Web interface chapter). These events can also be used to send SNMP traps to a third party manager. 

To configure Dominion PX to send SNMP traps: 

1. Choose Device Settings ‐‐> Event Log. The Event Log Settings window appears. The SNMP Logging panel controls the use of SNMP traps. 

 

2. Click the checkbox labeled SNMP Logging Enabled. 

3. Type an IP address in the Destination IP field. This is the address to which traps are sent by the SNMP system agent. 

4. Type the name of the SNMP community in the Community field. The community is the group representing the Dominion PX and all SNMP management stations. 

5. To take a look at the Management Information Base (MIB), click the link labeled Click here to view the (<device name>) SNMP MIB. It is located under the Community field. 

Page 146: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

SNMP Gets and Sets

136

6. When SNMP logging is enabled, seven event types appear in the Event Log Assignments panel to the right. All are disabled by default. To enable any of these event types, check the appropriate checkboxes. 

 

7.  Click Apply. SNMP logging is configured. 

Note: You should re‐download the Dominion PX MIB after updating the unitʹs firmware. This will ensure your SNMP manager has the correct MIB for the release you are using. 

SNMP Gets and Sets

In addition to sending traps, Dominion PX is able to receive SNMP get and set requests from third‐party SNMP managers. Get requests can be used to retrieve information about the Dominion PX (such as the system location, or the current on a specific outlet). Set requests can be used to configure a subset of this information (such as the SNMP system name). 

Valid objects for these requests are limited to those found in the SNMP MIBII System Group and the custom Dominion PX MIB.  

 

 

Page 147: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Appendix D: Using SNMP

137

The Dominion PX MIB

This MIB is available from the SNMP Settings page, the Event Logging page, or by pointing your browser to http://<ip-address>/MIB.txt, where <ip-address> is the IP address of your Dominion PX. 

Layout

Opening the MIB will reveal the custom objects that describe the Dominion PX system at the unit‐level as well as at the individual‐outlet‐level. As standard, these objects are first presented at the beginning of the file, listed under their parent group. The objects then appear again individually, defined and described in detail. 

 

Page 148: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

SNMP Gets and Sets

138

For example, the unitSensorsGroup group contains objects for sensor readings of the Dominion PX as a whole. One object listed under this group, unitCurrent, is described later in the MIB as ʺThe value for the unitʹs current sensor in millampsʺ‐‐the measure of the current drawn by Dominion PX.  outletCurrent, part of the outletsGroup group describes the current passing through a specific outlet. 

NOTE: When performing an SNMP get, all current values are measured in milliamps (ma). HOWEVER: when performing an SNMP set, all are measured in amps (A). 

SNMP Sets and Thresholds

Several of these objects can be configured from the SNMP manager using SNMP set commands. Objects that can be written to will have a MAX‐ACCESS level of ʺread‐writeʺ in the MIB. These objects include threshold objects, cause Dominion PX to provide a warning (and send an SNMP trap) when certain parameters are exceeded. Refer to the Setting up Outlets and Power Thresholds section in the Using the Web Interface chapter for a description of how thresholds work. 

 

Page 149: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

139

The IPMI tool set is command‐line that allows users to display channel information, print sensor data, and set LAN configuration parameters. The following explains the available IPMI commands. 

Note: The open source IPMI tool can be downloaded from sourceforge, and compiled on Linux system .Then users can interact with Dominion PX via IPMI protocol through this tool. An example at the Linux command shell is given as: $ ipmitool ‐I lan ‐H 192.168.51.58 ‐U admin ‐a channel info 

In This Chapter Channel Commands......................................................................................139 Event Commands ..........................................................................................141 LAN Commands............................................................................................142 Sensor Commands.........................................................................................144 OEM Commands ...........................................................................................145 IPMI Privilege Levels ....................................................................................152 

Channel Commands

authcap <channel number> <max priv>

Displays information about the authentication capabilities of the selected channel at the specified privilege level. Possible privilege levels are: 

1. Callback level 

2. User level 

3. Operator level 

4. Administrator level 

5. OEM Proprietary level 

Appendix E Using the IPMI Tool Set

Page 150: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Channel Commands

140

Example

$ ipmitool -I lan -H 192.168.51.58 -U admin -a channel authcap 14 5 

 Refer to the IPMI Privileges Levels section for additional information about IPMI privileges. 

 

info [channel number]

Displays information about the selected channel. If no channel is given it will display information about the currently used channel: 

Example

$ ipmitool -I lan -H 192.168.51.58 -U admin -a channel info 

 

getaccess <channel number> [userid]

Configures the given userid as the default on the given channel number. When the given channel is subsequently used, the user is identified implicitly by the given userid. 

Example

$ ipmitool -I lan -H allen-dpxpcr20-20 -U admin -P raritan1 channel getaccess 14 63 

 

setaccess <channel number> <userid>[callin=on|off] [ipmi=on|off] [link=on|off] [privilege=level]

Configures user access information on the given channel for the given userid. 

Example

$ ipmitool -I lan -H allen-dpxpcr20-20 -U admin -P raritan1 channel setaccess 14 63 privilege=5 

 

Page 151: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Appendix E: Using the IPMI Tool Set

141

getciphers <all | supported> <ipmi | sol> [channel]

Displays the list of cipher suites supported for the given application (ipmi or sol) on the given channel. 

Example

$ ipmitool -I lan -H allen-dpxpcr20-20 -U admin -P raritan1 channel getciphers ipmi 14 

 

Event Commands

The Event commands allow you to send pre‐defined events to a Management Controller. 

<predefined event number>

Sends a pre‐defined event to the System Event Log.  The Currently supported values for are: 

• Temperature: Upper Critical: Going High 

• Voltage Threshold: Lower Critical: Going Low 

• Memory: Correctable ECC Error Detected 

Note: These pre‐defined events will likely not produce ʺaccurateʺ SEL records for a particular system because they will not be correctly tied to a valid sensor number, but they are sufficient to verify correct operation of the SEL. 

Example

$ ipmitool -I lan -H allen-dpxpcr20-20 -U admin -P raritan1 event 1 

Page 152: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

LAN Commands

142

file <filename>

Event log records specified in filename will be added to the System Event Log. The format of each line in the file is as follows: 

<{EvM Revision} {Sensor Type} {Sensor Num} {Event Dir/Type} {Event Data 0} {Event Data 1} {Event Data 2}>[# COMMENT] 

Note: The Event Dir/Type field is encoded with the event direction as the high bit (bit 7) and the event type as the low 7 bits. 

Example

0x4 0x2 0x60 0x1 0x52 0x0 0x0 # Voltage threshold: Lower Critical: Going Low 

 

LAN Commands

The LAN commands allow you to configure the LAN channels. 

print <channel>

Prints the current configuration for the given channel. 

Page 153: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Appendix E: Using the IPMI Tool Set

143

set <channel> <parameter>

Sets the given parameter on the given channel. Valid parameters are: 

• ipaddr <x.x.x.x>   Sets the IP address for this channel. 

• netmask <x.x.x.x>    Sets the netmask for this channel. 

• macaddr <xx:xx:xx:xx:xx:xx>   Sets the MAC address for this channel. 

• defgw ipaddr <x.x.x.x>   Sets the default gateway IP address. 

• defgw macaddr <xx:xx:xx:xx:xx:xx>   Sets the default gateway MAC address. 

• bakgw ipaddr <x.x.x.x>   Sets the backup gateway IP address. 

• bakgw macaddr <xx:xx:xx:xx:xx:xx>   Sets the backup gateway MAC address. 

• password <pass>   Sets the null user password. 

• snmp <community string>   Sets the SNMP community string. 

• user   Enables user access mode for userid 1 (issue the `userʹ command to display information about userids for a given channel). 

• access <on|off>   Set LAN channel access mode. 

• ipsrc   Ses the IP address source: 

none    unspecified 

static   manually configured static IP address 

dhcp   address obtained by DHCP 

bios   address loaded by BIOS or system software 

• arp respond <on|off>   Sets generated ARP responses. 

• arp generate <on|off>   Sets  generated gratuitous ARPs. 

• arp interval <seconds>   Sets generated gratuitous ARP interval. 

• auth <level,...> <type,...>   Sets the valid authtypes for a given auth level. 

Levels: callback, user, operator, admin 

Types: none, md2, md5, password, oem 

• cipher_privs <privlist>   Correlates cipher suite numbers with the maximum privilege level that is allowed to use it. In this way, cipher suites can restricted to users with a given privilege level, so that, for example, administrators are required to use a stronger cipher suite than normal users. 

 

Page 154: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Sensor Commands

144

The format of privlist is as follows. Each character represents a privilege level and the character position identifies the cipher suite number. For example, the first character represents cipher suite 1 (cipher suite 0 is reserved), the second represents cipher suite 2, and so on. privlist must be 15 characters in length. 

Characters used in privlist and their associated privilege levels are: 

• X   Cipher Suite Unused 

• c  CALLBACK 

• u  USER 

• O  OPERATOR 

• a  ADMIN 

• O  OEM 

Sensor Commands

The Sensor commands allow you to display detailed sensor information. 

list

Lists sensors and thresholds in a wide table format. 

Example

$ ipmitool -I lan -H allen-dpxpcr20-20 -U admin -a sensor list 

 

get <id> ... [<id>]

Prints information for sensors specified by name. 

Example

$ ipmitool -I lan -H allen-dpxpcr20-20 -U admin -P raritan1 sensor get "R.14 Current" 

 

Page 155: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Appendix E: Using the IPMI Tool Set

145

thresh <id> <threshold> <setting>

This allows you to set a particular sensor threshold value. The sensor is specified by name. Valid thresholds are: 

• unr    Upper Non‐Recoverable 

• ucr    Upper Critical 

• unc    Upper Non‐Critical 

• lnc    Lower Non‐Critical 

• lcr    Lower Critical 

• lnr    Lower Non‐Recoverable 

Example

$ ipmitool -I lan -H allen-dpxpcr20-20 -U admin -P raritan1 sensor thresh "R.14 Current" unr 10.5 

OEM Commands

You can use the OEM commands to manage and control the operation of the Dominion PX. 

OEM Net‐Fn is as defined below: 

#define IPMI_NETFN_OEM_PP 0x3C

 

The table below lists each OEM command and gives its ID. The sections that follow explain each command in greater detail. 

Command Name Id Set Power On Delay Command  0x10 

Get Power On Delay Command  0x11 

Set Receptacle State Command  0x12 

Get Receptacle State Command  0x13 

Set Group State Command  0x14 

Set Group Membership Command  0x15 

Get Group Membership Command  0x16 

Set Group Power On Delay Command  0x17 

Get Group Power On Delay Command  0x18 

Page 156: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

OEM Commands

146

Command Name Id Set Receptacle ACL  0x19 

Get Receptacle ACL  0x1A 

Set Sensor Calibration  0x1B 

Test Actors  0x1C 

Test Sensors  0x1D 

Set Power Cycle Delay Command  0x1E 

Get Power Cycle Delay Command  0x1F 

 

Set Power Set Delay Command

The global power on delay defines how much time has to pass between two power on actions. 

Request Data  1  delay in 1/10 seconds 

the delay is the minimum time after which a receptacle will be  switched on after a previous receptacle has been switched on. 

Response Data  1  Completion Code 

 

Get Power On Delay Command

Request Data  ‐  ‐ 

Response Data  1  Completion Code 

2  delay in 1/10 seconds 

 

Set Receptacle State Command

This command is used to switch on/off individual receptacles. 

Request Data  1  # of receptacle 

[7 ‐ 5] reserved 

[4 ‐ 0] # of receptacle, 0 based, highest valid # depends on device model 

Page 157: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Appendix E: Using the IPMI Tool Set

147

Request Data  1  # of receptacle 

[7 ‐ 5] reserved 

[4 ‐ 0] # of receptacle, 0 based, highest valid # depends on device model 

2  new state 

[7 ‐ 1] reserved 

[0]  1b = power on, 0b = power off  

Response Data  1  Completion Code 

 

Get Receptacle State Command

Request Data  1  # of receptacle 

[7 ‐ 5] reserved 

[4 ‐ 0] # of receptacle, 0 based, highest valid # depends on device model 

Response Data  1  Completion Code 

2  current receptacle state and visual state 

[7] reserved 

[6]  1b = blinking, 0b = steady 

[5]  1b = LED green on, 0b = off 

[4]  1b = LED red on, 0b = off 

[3]  1b = enqueued to be switched on, 0b = not enqueued 

[2]  1b = in power cycle delay phase, 0b = not delayed 

[1]  1b = released because of soft breaker, 0b = norm 

[0]  1b = power on, 0b = power off  

 

 

Set Group State Command

This command is used to switch on/off all receptacles belonging to a group. There is no Get Group State Command. Getting the state of a receptacle has to be carried out with Get Receptacle State Command. 

Page 158: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

OEM Commands

148

Request Data  1  # of group 

[7 ‐ 5] reserved 

[4 ‐ 0] group #, valid numbers: 0 ‐ 23 

2  new state 

[7 ‐ 1] reserved 

[0]  1b = power on, 0b = power off 

Response Data  1  Completion Code 

 

Set Group Membership Command

Request Data  1  # of group 

[7 ‐ 5] reserved 

[4 ‐ 0] group #, valid numbers: 0 ‐ 23 

2  [7 ‐ 1] reserved 

[0]  1b = enable group, 0b = disable group 

3  [7]  1b = receptacle 7 belongs to group 

... 

[0]  1b = receptacle 0 belongs to group 

4  [7]  1b = receptacle 15 belongs to group 

... 

[0]  1b = receptacle 8 belongs to group 

5  [7]  1b = receptacle 23 belongs to group 

... 

[0]  1b = receptacle 16 belongs to group 

Response Data  1  Completion Code 

 

Get Group Membership Command

Request Data  1  # of group 

[7 ‐ 5] reserved 

[4 ‐ 0] group #, valid numbers: 0 ‐ 23 

Response Data  1  Completion Code 

Page 159: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Appendix E: Using the IPMI Tool Set

149

Request Data  1  # of group 

[7 ‐ 5] reserved 

[4 ‐ 0] group #, valid numbers: 0 ‐ 23 

2  [7 ‐ 1] reserved 

[0]  1b = group is enabled, 0b = group is disabled 

3  [7]  1b = receptacle 7 belongs to group 

... 

[0]  1b = receptacle 0 belongs to group 

4  [7]  1b = receptacle 15 belongs to group 

... 

[0]  1b = receptacle 8 belongs to group 

5  [7]  1b = receptacle 23 belongs to group 

... 

[0]  1b = receptacle 16 belongs to group 

 

Set Group Power On Delay Command

Request  

 

Data 

1  # of group 

[7 ‐ 5] reserved 

[4 ‐ 0] group #, valid numbers: 0 ‐ 23 

2  delay in 1/10 seconds 

This delay overwrites the global delay for all receptacles in that group. The delay will apply not only when using the Set Group State Command but also when using Set Receptacle State Command. 

Response Data  1  Completion Code 

 

 

 

 

Get Group Power On Delay Command

Page 160: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

OEM Commands

150

Request Data  1  # of group 

[7 ‐ 5] reserved 

[4 ‐ 0] group #, valid numbers: 0 ‐ 23 

Response Data  1  Completion Code 

2  delay in 1/10 seconds 

 

Set Receptacle ACL

ACLs define who is authorized to change the state of a receptacle. ACLs will be stored for each individual outlet. A single ACL entry defines whether a certain user id or privilege level is allowed or denied to issue control commands for the outlet. ACL will be evaluated top to bottom, hence order of ACL entries is important. If there is no ACL entry at all, receptacle ACLs are disabled, i.e. any user id has access. 

Request Data  1  # of receptacle 

2  number of ACL entries to follow 

+N 

ACL entry 

[7] 0b = deny, 1b = allow 

[6] 0b = user id, 1b = privilege level 

[5 ‐ 0] user id or privilege level depending on [6] 

Response Data  1  Completion Code 

 

Get Receptacle ACL

Request Data  1  # of receptacle 

Response Data  1  Completion Code 

2  number of ACL entries to follow 

+N 

ACL entry 

[7] 0b = deny, 1b = allow 

[6] 0b = user id, 1b = privilege level 

[5 ‐ 0] user id or privilege level depending on [6] 

 

Page 161: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Appendix E: Using the IPMI Tool Set

151

Set Sensor Calibration

Sensor calibration is only allowed for threshold based sensors that return a sensor reading byte with the Get Sensor Reading Command. Also not all threshold based sensors have capability to be calibrated. 

Request Data  1  Sensor number (ffh = reserved) 

2  Actual sensor reading value 

Assumes, that at the time this command is executed a calibrated measurement is applied to this sensor. 

Response Data  1  Completion Code 

00h ‐ If calibration ok 

CDh ‐ if sensor canʹt be calibrated 

 

Test Actors

Used for hardware testing during production 

Request Data  1  [7 ‐ 2] reserved 

[1] Beeper test, 0b ‐ disable, 1b ‐ enable 

[0] 7 segment display test, 0b ‐ disable, 1b ‐ enable 

Response Data  1  Completion Code 

 

Test Sensors

Used for hardware testing during production 

Request Data  1  ‐ 

Response Data  1  Completion Code 

2  [7 ‐ 2] reserved 

[1] down button, 0b ‐ not pressed, 1b ‐ pressed 

[0] up button, 0b ‐ not pressed, 1b ‐ pressed 

 

Set Power Cycle Delay Command

Request Data  1  # of receptacle (0xFF for global unit delay) 

Page 162: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

IPMI Privilege Levels

152

Request Data  1  # of receptacle (0xFF for global unit delay) 

2  Delay (seconds), 1‐255 for unit and receptacle, 0 fallback to unit delay (receptacle only) 

Response Data  1  Completion Code 

 

Get Power Cycle Delay Command

Request Data  1  # of receptacle (0xFF for global unit delay) 

Response Data  1  Completion Code 

2  Delay (seconds), 1‐255, 0 if not set (receptacle only) 

Note: Values greater than 255 cannot be sent to the Dominion PX via IPMI. In order to set the Power Cycle Delay to longer than 255 seconds, you must use the web interface. 

IPMI Privilege Levels

The IPMI privilege level that you select determines: 

 Figure 2: IPMI Privilege Level 

Page 163: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

153

Event Type Examples Outlet Control  Outlet(#) switched on by user 

Outlet(#) switched off by user 

Outlet(#) cycled by user 

Outlet/Unit/Environmental Sensors 

Assertion: Environmental Temperature (#) above upper non‐critical threshold 

Deassertion: Environmental Temperature (#) above upper critical threshold 

User/Group Administration  User added successfully 

User successfully changed 

User successfully deleted 

User password successfully changed 

Group added successfully 

Group successfully changed 

Group successfully deleted 

Security Relevant  User login failed 

User Activity  User logged in successfully 

User logged out 

User session timeout 

Note:  The user activity entries in the event log always show the IP address of the computer that logged in or out. Entries with an IP address of 127.0.0.1 (the loopback IP address) represent a serial connection and a CLP session. 

Device Operation  Device successfully started 

Device Management  The Device update has started 

Virtual Device Management  Master PDU lost connectivity with SlaveIPAddress : 

Appendix F Event Types

Page 164: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

IPMI Privilege Levels

154

 

 

 

 

 

Page 165: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

155

This appendix contains information describing: 

• DPX Serial RJ‐45 pinouts  

RJ-45 Pin/signal definition Pin No. Signal  Direction  Description 

1  DTR  Output  Reserved 

2  GND  ―  Signal Ground 

3  +5V  ―  Power for CIM 

(200mA, fuse protected) 

4  TxD  Output  Transmit Data (Data out) 

5  RxD  Input  Receive Data (Data in) 

6  N/C  N/C  No Connection 

7  GND  ―  Signal Ground 

8  DCD  Input  Reserved 

 

• DPX Feature RJ‐11 pinouts  

RJ-11 Pin/signal definition Pin No. Signal  Direction  Description 

1  +12V  ―  Power  

(500mA, fuse protected) 

2  GND  ―  Signal Ground 

3  RS485 (Data +) 

bi‐directional 

Data Line + 

4  RS485  

(Data ‐) 

bi‐directional 

Data Line ‐ 

5  GND  ―  Signal Ground 

6  1‐wire   

 

Appendix G Specifications

Page 166: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...
Page 167: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

157

<

<predefined event number> • 141 

1

1U Products • 4 1U Size • 2 

2

2U Products • 5 2U Size • 3 

A

About the CLP Interface • 125 Add a Dominion PX Unit in Paragon II • 112 All Outlets Control • 38 Associate Outlets with a Target • 108, 113 Attributes • 128 authcap <channel number> <max priv> • 139 

B

Back Panel • 20 Beeper • 25 Before Beginning: • 8 Before You Begin • 10 Blue LED • 20 

C

Changing Your Password • 30 Channel Commands • 139 Check Power Strip Status • 116 Circuit Breaker • 24 CommandCenter • 117 Configure a Dominion PX Power Unit on Dominion SX • 114 

Configure the Dominion PX for Network Connectivity • 12 

Configuring Alert Events • 76 Configuring Environmental Sensors and Thresholds • 74 

Configuring NFS Logging • 86 Configuring SMTP Logging • 87 

Configuring SNMP Logging • 88 Configuring SNMP Traps • 135 Configuring Syslog Forwarding • 88 Configuring the Firewall • 14, 50 Configuring the Local Event Log • 83, 85 Configuring the SMTP Settings • 81, 87, 97 Configuring the SNMP Settings • 98 Configuring Users for Encrypted SNMP v3 • 134 

Connect the Dominion PX to a Computer • 11, 12 

Connect the Dominion PX to Your Network • 12 

Connecting the Environmental Sensors • 72 Connection Ports • 19 Control a Targetʹs Power • 110, 113 Control an Outletʹs Power • 114 Controlling Outlet Groups • 105 Copying a User Group • 48 Copying a User Profile • 41 Creating a Certificate Signing Request • 60 Creating a User Group • 44 Creating a User Profile • 26, 39 Creating Alert Policies • 77, 78 Creating Group Based Access Control Rules • 53 

D

Deleting a User Group • 49 Deleting a User Profile • 42 Deleting Outlet Group Devices • 106 Displaying Basic Device Information • 89, 91 Displaying Connected Users • 91 Displaying Model Configuration Information • 91 

Dominion KSX • 116 Dominion KX • 108 Dominion KX‐II • 111 Dominion PX Models • 1, 118 Dominion SX • 114 

E

Editing or Deleting Outlet Groups • 106 

Index

Page 168: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Index

158

Enabling SNMP • 132 Environmental Sensors • 72 Environmental Specifications • 120 Equipment Setup Worksheet • 11, 121 Event Commands • 141 Event Types • 153 Examples • 129 

F

file <filename> • 142 Fill Out the Equipment Setup Worksheet • 11 Forcing HTTPS Encryption • 49, 59 Front Panel • 19 

G

get <id> ... [<id>] • 144 Get Group Membership Command • 148 Get Group Power On Delay Command • 149 Get Power Cycle Delay Command • 152 Get Power On Delay Command • 146 Get Receptacle ACL • 150 Get Receptacle State Command • 147 getaccess <channel number> [userid] • 140 getciphers <all | supported> <ipmi | sol> [channel] • 141 

Global Status Panel • 36 Grouping Outlets Together • 103 

H

Hardware Specification • 119 

I Identifying Other Dominion PX Units • 102 info [channel number] • 140 Installation and Configuration • 10, 50, 93 Installing a Certificate • 61 Integration • 107 Introduction • 1 IPMI Privilege Levels • 152 

K

KX Manager Application (Dominion KX‐I only) • 108 

L

LAN Commands • 142 LED Display • 22 list • 144 Logging In • 26 Logging into the CLP interface • 126 Logging into the Web Interface • 26 

M

Managing the Dominion PX • 89 Mapping the Environmental Sensors • 73 Measurement Accuracy • 25 Menus • 31 Modifying a User Group • 48 Modifying a User Profile • 42 Modifying the Communications, Port and Bandwidth Settings • 94 

Modifying the LAN Interface Settings • 95 Modifying the Network Settings • 93 

N

Naming the Dominion PX • 92, 93 Naming the Outlets • 69, 72 Navigation Path • 32 

O

OEM Commands • 145 Outlet Grouping • 102 Outlets • 21 Outlets List • 37 

P

Package Contents • 4 Paragon II • 111 Paragon Manager Application • 112 Power Control • 115 Power Cord • 20 Power Cycling an Outlet • 67, 70, 72 Prepare the Installation Site • 10 print <channel> • 142 Product Features • 3 Product Models • 1 Product Photos • 1 

Page 169: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

Index

159

Q

Querying an Outlet Sensor • 130 

R

Rack Mount Safety Guidelines • 6 Rack‐Mounting the Dominion PX • 6 Refresh • 35 Reset to Defaults • 35 Resetting the Dominion PX • 99 Resetting to Factory Defaults • 16, 23 

S

Safety Guidelines • iii Sensor Commands • 144 set <channel> <parameter> • 143 Set Group Membership Command • 148 Set Group Power On Delay Command • 149 Set Group State Command • 147 Set Power Cycle Delay Command • 151 Set Power Set Delay Command • 146 Set Receptacle ACL • 150 Set Receptacle State Command • 146 Set Sensor Calibration • 151 setaccess <channel number> <userid>[callin=on|off] [ipmi=on|off] [link=on|off] [privilege=level] • 140 

Setting the Date and Time • 96 Setting the Default Outlet State • 66 Setting the Dominion PX Thresholds • 66, 72 Setting the Outlet Permissions • 43, 47 Setting the Outlet Power‐Up Sequence • 67 Setting the Outlet Thresholds • 67, 70, 72 Setting the System Permissions • 42, 44 Setting Up a Digital Certificate • 59 Setting Up Access Controls • 49 Setting Up Alerts • 65, 76, 97 Setting Up Event Logging • 82 Setting Up External User Authentication • 62 Setting Up Outlets and Power Thresholds • 65, 76 

Setting Up RADIUS Authentication • 64 Setting Up User Groups • 43 Setting Up User Login Controls • 56 Setting Up User Profiles • 39 

Setting User Permissions Individually • 41, 42 Settings Up LDAP Authentication • 63 Showing Outlet Information • 127 SNMP Gets and Sets • 136 Specifications • 155 Specifying the Alert Destination • 81 Status Messages • 34 Status Panel • 32 Syntax • 128, 130 

T

Test Actors • 151 Test Sensors • 151 The Dominion PX MIB • 137 thresh <id> <threshold> <setting> • 145 To Mount: • 9 Tool‐less Mounting Instructions • 8 Turning an Outlet On or Off • 72, 130 

U

Unavailable Options • 35 Unpack the Dominion PX and Components • 10 

Updating the Firmware • 100 Using HyperTerminal • 126 Using SNMP • 131 Using SSH or Telnet • 127 Using the CLP Interface • 125 Using the Dominion PX • 19 Using the Home Window • 36 Using the IPMI Tool Set • 139 Using the Web Interface • 26, 30 

V

Viewing Outlet Details • 71 Viewing Sensor Readings • 75 Viewing the Internal Event Log • 85 

Z

Zero U Products • 4 Zero U Size • 2 

Page 170: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...
Page 171: Dominion® PX - Raritan Inc.support.raritan.com/PX/version-1.1/user-guides/dominionpx-1-1-0... · Chapter 2 Rack-Mounting the Dominion PX 6 Rack Mount Safety Guidelines ...

 

 

 

U.S./Canada/Latin America Monday ‐ Friday  8 a.m. ‐ 8 p.m. ET  Phone: 800‐724‐8090 or 732‐764‐8886 For CommandCenter NOC: Press 6, then Press 1 For CommandCenter Secure Gateway: Press 6, then Press 2 Fax: 732‐764‐8887 Email for CommandCenter NOC: tech‐[email protected] Email for all other products: [email protected] 

China

Beijing Monday ‐ Friday  9 a.m. ‐ 6 p.m. local time  Phone: +86‐10‐88091890 

Shanghai Monday ‐ Friday  9 a.m. ‐ 6 p.m. local time  Phone: +86‐21‐5425‐2499  

GuangZhou Monday ‐ Friday  9 a.m. ‐ 6 p.m. local time  Phone: +86‐20‐8755‐5561  

India Monday ‐ Friday  9 a.m. ‐ 6 p.m. local time Phone: +91‐124‐410‐7881  

Japan Monday ‐ Friday  9:30 a.m. ‐ 5:30 p.m. local time  Phone: +81‐3‐3523‐5994 Email: [email protected] 

Europe

Europe Monday ‐ Friday 8:30 a.m. ‐ 5 p.m. GMT+1 CET  Phone: +31‐10‐2844040  Email: [email protected] 

United Kingdom Monday ‐ Friday  8:30 a.m. to 5 p.m. GMT+1 CET  Phone +44‐20‐7614‐77‐00  France  Monday ‐ Friday  8:30 a.m. ‐ 5 p.m. GMT+1 CET  Phone: +33‐1‐47‐56‐20‐39 