CODE OPTIONS CSD-1 UTC Lockout/Reset Control Manual Reset LWCO Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment. 2. Dimensions are subject to change without notice. DOMINATOR 300 Category I or Category III Appliance (see Installation and Operation Manual for venting information) SDOM-300-7 The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009. 15 3/8 in [39.1 cm] 15 in [38.1 cm] 4 1/4 in [10.8 cm] 26 9/16 in [67.5 cm] 37 7/8 in [96.2 cm] 4 7/8 in [12.4 cm] 29 5/16 in [74.4 cm] 4 7/16 [11.3 5 3/16 [13.2 c 2 1/2" WATER (2 PLCS.) Ø3/4" NAT & LP 5 in [12.6 cm] 27 3/16 in [69.1 cm] 35 3/16 in [89.4 cm] 12 15/16 in [32.9 cm] 19 1/16 in [48.4 cm] 11 1/16 in [28.1 cm] 22 1/8 in [56.2 cm] 4 7/16 in [11.3 cm] 31 7/8 in [81.0 cm] 7 1/2 in [19.1 cm] Ø6" 5 3/16 in [13.2 cm] ATER CS.) 6 in [15.2 cm] 33 1/16 in [84.0 cm] REAR FLUE OUTLET (OPTIONAL) AIR INTAKE 2 3/4 in [7.0 cm] 10 7/8 in [27.6 cm] CENTER OF GRAVITY RSUB-27-D

Transcript of DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… ·...

Page 1: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

CODE OPTIONS

CSD-1UTC Lockout/Reset Control Manual Reset LWCO

Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.

DOMINATOR 300Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

SDOM-300-7The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

15 3/8 in [39.1 cm]

15 in [38.1 cm]

4 1/4 in [10.8 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

4 7/8 in [12.4 cm]

29 5/16 in [74.4 cm]

11 1/16 in [28.1 cm]

22 1/8 in [56.2 cm]

4 7/16 in [11.3 cm]

31 7/8 in [81.0 cm]

7 1/2 in [19.1 cm]

Ø6"

5 3/16 in [13.2 cm]

2 1/2" WATER(2 PLCS.)

Ø3/4"NAT & LP

5 in [12.6 cm] 6 in

[15.2 cm]

33 1/16 in [84.0 cm]

REAR FLUE OUTLET(OPTIONAL)

AIR INTAKE

27 3/16 in [69.1 cm]

35 3/16 in [89.4 cm]

2 3/4 in [7.0 cm]

12 15/16 in [32.9 cm]

19 1/16 in [48.4 cm]

10 7/8 in [27.6 cm]

CENTER OFGRAVITY

15 3/8 in [39.1 cm]

15 in [38.1 cm]

4 1/4 in [10.8 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

4 7/8 in [12.4 cm]

29 5/16 in [74.4 cm]

11 1/16 in [28.1 cm]

22 1/8 in [56.2 cm]

4 7/16 in [11.3 cm]

31 7/8 in [81.0 cm]

7 1/2 in [19.1 cm]

Ø6"

5 3/16 in [13.2 cm]

2 1/2" WATER(2 PLCS.)

Ø3/4"NAT & LP

5 in [12.6 cm] 6 in

[15.2 cm]

33 1/16 in [84.0 cm]

REAR FLUE OUTLET(OPTIONAL)

AIR INTAKE

27 3/16 in [69.1 cm]

35 3/16 in [89.4 cm]

2 3/4 in [7.0 cm]

12 15/16 in [32.9 cm]

19 1/16 in [48.4 cm]

10 7/8 in [27.6 cm]

CENTER OFGRAVITY

RSUB-27-D

Page 2: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

DOMINATOR 300Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 3.8*

Input BTU/hr. 300,000 / 88 kW Min. Gas Pressure Required 7" WC**

Output BTU/hr. 250,500 / 73 kW Max. Gas Pressure Allowed 14" WC

Electrical Requirements 120VAC/ 1 ph/ 60 hz Operating Weight 416 lbs. / 189 kg.

BOILER / WATER HEATER TRIM & CONTROLSMain Gas Valve Honeywell VR8304 3/4" Pilot Valve Honeywell VR8304

Firing Valve Honeywell B200T1025 3/4" Air Switch Cleveland RSS-495

Ignition Control UTC 1003-61A Blower Motor 1/5 hp - FLA 3.0

High Limit Honeywell L4008E Relief Valve - DW 3/4" x 3/4" set @ 125 psi

Relief Valve - DB 3/4" x 3/4" set @ 50 psi

Flow Switch TACO

A.S.M.E.ASME Sect IV Htg Surface 38.0 Sq. Ft. / 3.53 Sq. M. Design Data Max. 160 psig & 250˚F

Water Volume 3.5 gal / 13.2 Liters

BOILER TEMPERATURE RISE / PRESSURE DROP15°F / 8.3°C 20°F / 11.1°C 25°F / 13.9°C

Flow Rate Pressure Drop Flow Rate Pressure Drop Flow Rate Pressure Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

33.4 2.1 0.21 0.6 25.1 1.6 0.12 0.4 20.0 1.3 0.08 0.2

* Add circulator amps.** For incoming gas pressures lower than 7” WC natural or 11” WC propane, consult factory.

SDOM-300-7

WATER HEATER HOURLY RECOVERY CAPACITY (GPH & LPH)40°F 22°C 60°F 33°C 80°F 44°C 100°F 56°C 120°F 67°C 140°F 78°C

723 2733 482 1822 361 1366 289 1093 241 911 207 781

The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

Page 3: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

CODE OPTIONS

CSD-1UTC Lockout/Reset Control Manual Reset LWCO

Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.

DOMINATOR 400Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

SDOM-400-7The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

RSUB-28-D

15 3/8 in [39.1 cm]

15 in [38.1 cm]

3 13/16 in [9.7 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

4 7/8 in [12.4 cm]

5 in [12.6 cm]

29 5/16 in [74.4 cm]

14 5/16 in [36.4 cm]

28 5/8 in [72.7 cm]

4 7/16 in [11.3 cm]

29 5/8 in [75.2 cm]

7 1/2 in [19.1 cm]

Ø6"

5 3/16 in [13.2 cm]

Ø3/4"NAT & LP

6 in [15.2 cm]

33 1/16 in [84.0 cm]

REAR FLUE OUTLET(OPTIONAL)

AIR INTAKE

33 11/16 in [85.6 cm]

35 3/16 in [89.4 cm]

2 3/4 in [7.0 cm]

19 1/16 in [48.4 cm]

14 1/16 in [35.7 cm]

CENTER OFGRAVITY

15 3/8 in [39.1 cm]

15 in [38.1 cm]

3 13/16 in [9.7 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

4 7/8 in [12.4 cm]

5 in [12.6 cm]

29 5/16 in [74.4 cm]

14 5/16 in [36.4 cm]

28 5/8 in [72.7 cm]

4 7/16 in [11.3 cm]

29 5/8 in [75.2 cm]

7 1/2 in [19.1 cm]

Ø6"

5 3/16 in [13.2 cm]

Ø3/4"NAT & LP

6 in [15.2 cm]

33 1/16 in [84.0 cm]

REAR FLUE OUTLET(OPTIONAL)

AIR INTAKE

33 11/16 in [85.6 cm]

35 3/16 in [89.4 cm]

2 3/4 in [7.0 cm]

19 1/16 in [48.4 cm]

14 1/16 in [35.7 cm]

CENTER OFGRAVITY

Dominator 400 model water heater not available for sale in the U.S. market due to DOE regulations.

Page 4: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

DOMINATOR 400Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 3.8*

Input BTU/hr. 399,000 / 117 kW Min. Gas Pressure Required 7" WC**

Output BTU/hr. 339,150 / 99 kW Max. Gas Pressure Allowed 14" WC

Electrical Requirements 120VAC/ 1 ph/ 60 hz Operating Weight 490 lbs. / 222 kg.

BOILER / WATER HEATER TRIM & CONTROLSMain Gas Valve Honeywell VR8305 3/4" Pilot Valve Honeywell VR8205

Firing Valve Honeywell B200T1025 3/4" Air Switch Cleveland RSS-495

Ignition Control UTC 1003-61A Blower Motor 1/5 hp - FLA 3.0

Operating Control Tekmar BTC-2PA Relief Valve - DW 3/4" x 3/4" set @ 125 psi

High Limit Honeywell L4008E Relief Valve - DB 3/4" x 3/4" set @ 50 psi

Flow Switch TACO

A.S.M.E.ASME Sect IV Htg Surface 50.0 Sq. Ft. / 4.65 Sq. M. Design Data Max. 160 psig & 250˚F

Water Volume 3.6 gal / 13.6 Liters

BOILER TEMPERATURE RISE / PRESSURE DROP15°F / 8.3°C 20°F / 11.1°C 25°F / 13.9°C

Flow Rate Pressure Drop Flow Rate Pressure Drop Flow Rate Pressure Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

45.3 2.9 0.49 1.5 34.0 2.1 0.29 0.9 27.2 1.7 0.19 0.6

* Add circulator amps.** For incoming gas pressures lower than 7” WC natural or 11” WC propane, consult factory.

SDOM-400-7

WATER HEATER HOURLY RECOVERY CAPACITY (GPH & LPH)40°F 22°C 60°F 33°C 80°F 44°C 100°F 56°C 120°F 67°C 140°F 78°C

1018 3853 679 2569 509 1927 407 1541 339 1284 291 1101

The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

Dominator 400 model water heater not available for sale in the U.S. market due to DOE regulations.

Page 5: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

CODE OPTIONS

CSD-1UTC Lockout/Reset Control Manual Reset LWCO

Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.

DOMINATOR 600Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

SDOM-600-7The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

RSUB-29-D

15 3/8 in [39.1 cm]

15 in [38.1 cm]

4 1/4 in [10.8 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

4 7/8 in [12.4 cm]

5 in [12.6 cm]

29 5/16 in [74.4 cm]

17 9/16 in [44.6 cm]

35 1/8 in [89.2 cm]

4 7/16 in [11.3 cm]

29 5/8 in [75.2 cm]

7 1/2 in [19.1 cm]

Ø8"

5 3/16 in [13.2 cm]

Ø2 1/2" WATER(2 PLCS.)

Ø1"NAT & LP

7 in [17.8 cm]

33 1/16 in [84.0 cm]

REAR FLUE OUTLET(OPTIONAL)

AIR INTAKE

40 3/16 in [102.1 cm]

35 3/16 in [89.4 cm]

2 3/4 in [7.0 cm]

12 15/16 in [32.9 cm]

19 1/16 in [48.4 cm]

17 1/4 in [43.9 cm]

CENTER OFGRAVITY

15 3/8 in [39.1 cm]

15 in [38.1 cm]

4 1/4 in [10.8 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

4 7/8 in [12.4 cm]

5 in [12.6 cm]

29 5/16 in [74.4 cm]

17 9/16 in [44.6 cm]

35 1/8 in [89.2 cm]

4 7/16 in [11.3 cm]

29 5/8 in [75.2 cm]

7 1/2 in [19.1 cm]

Ø8"

5 3/16 in [13.2 cm]

Ø2 1/2" WATER(2 PLCS.)

Ø1"NAT & LP

7 in [17.8 cm]

33 1/16 in [84.0 cm]

REAR FLUE OUTLET(OPTIONAL)

AIR INTAKE

40 3/16 in [102.1 cm]

35 3/16 in [89.4 cm]

2 3/4 in [7.0 cm]

12 15/16 in [32.9 cm]

19 1/16 in [48.4 cm]

17 1/4 in [43.9 cm]

CENTER OFGRAVITY

Page 6: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

DOMINATOR 600Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 3.8*

Input BTU/hr. 600,000 / 176 kW Min. Gas Pressure Required 7" WC**

Output BTU/hr. 510,000 / 149 kW Max. Gas Pressure Allowed 14" WC

Electrical Requirements 120VAC/ 1 ph/ 60 hz Operating Weight 532 lbs. / 242 kg.

BOILER / WATER HEATER TRIM & CONTROLSMain Gas Valve Honeywell V8944 1" Pilot Valve Honeywell VR8205

Firing Valve Honeywell B200T1033 1" Air Switch Cleveland RSS-495

Safety Valve ASCO L8214G 1" Blower Motor 1/5 hp - FLA 3.0

Ignition Control UTC 1003-61A Relief Valve - DW 3/4" x 3/4" set @ 125 psi

Operating Control Tekmar BTC-2PA Relief Valve - DB 3/4" x 3/4" set @ 50 psi

High Limit Honeywell L4008E Flow Switch TACO

A.S.M.E.ASME Sect IV Htg Surface 64.0 Sq. Ft. / 5.95 Sq. M. Design Data Max. 160 psig & 250˚F

Water Volume 3.8 gal / 14.5 Liters

BOILER TEMPERATURE RISE / PRESSURE DROP15°F / 8.3°C 20°F / 11.1°C 25°F / 13.9°C 30°F / 16.7°C

Flow Rate Pressure Drop Flow Rate Pressure Drop Flow Rate Pressure Drop Flow Rate Pressure Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

68.0 4.3 1.30 3.8 51.0 3.2 0.76 2.2 40.8 2.6 0.50 1.5 34.0 2.1 0.36 1.1

* Add circulator amps.** For incoming gas pressures lower than 7” WC natural or 11” WC propane, consult factory.

SDOM-600-7

WATER HEATER HOURLY RECOVERY CAPACITY (GPH & LPH)40°F 22°C 60°F 33°C 80°F 44°C 100°F 56°C 120°F 67°C 140°F 78°C

1486 5616 990 3744 743 2808 594 2246 495 1872 424 1604

The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

Page 7: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

CODE OPTIONS

CSD-1UTC Lockout/Reset Control Manual Reset LWCO

Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.

DOMINATOR 750Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

SDOM-750-7The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

RSUB-30-D

15 3/8 in [39.1 cm]

15 in [38.1 cm]

4 1/4 in [10.8 cm]

Ø2 1/2" WATER(2 PLCS.)

29 5/8 in [75.2 cm]

7 1/2 in [19.1 cm]

Ø8"[20.32 cm]

4 7/16 in [11.3 cm]

41 5/8 in [105.7 cm]

20 13/16 in [52.9 cm]

5 3/16 in [13.2 cm]

8 in [20.3 cm] REAR FLUE OUTLET

(OPTIONAL)

AIR INTAKE(REAR MOUNTOPTIONAL)

6 1/4 in [15.9 cm]

Ø1"NAT & LP

29 5/16 in [74.4 cm]

37 7/8 in [96.1 cm]

26 9/16 in [67.5 cm]

5 in [12.7 cm]

15 15/16 in [40.5 cm]

11 in [28.0 cm]

46 11/16 in [118.7 cm]

35 3/16 in [89.4 cm] 31 7/8 in

[80.9 cm]

2 3/4 in [7.0 cm]

19 in [48.3 cm]

12 15/16 in [32.9 cm]

20 5/16 in [51.5 cm]

CENTER OFGRAVITY

15 3/8 in [39.1 cm]

15 in [38.1 cm]

4 1/4 in [10.8 cm]

Ø2 1/2" WATER(2 PLCS.)

29 5/8 in [75.2 cm]

7 1/2 in [19.1 cm]

Ø8"[20.32 cm]

4 7/16 in [11.3 cm]

41 5/8 in [105.7 cm]

20 13/16 in [52.9 cm]

5 3/16 in [13.2 cm]

8 in [20.3 cm] REAR FLUE OUTLET

(OPTIONAL)

AIR INTAKE(REAR MOUNTOPTIONAL)

6 1/4 in [15.9 cm]

Ø1"NAT & LP

29 5/16 in [74.4 cm]

37 7/8 in [96.1 cm]

26 9/16 in [67.5 cm]

5 in [12.7 cm]

15 15/16 in [40.5 cm]

11 in [28.0 cm]

46 11/16 in [118.7 cm]

35 3/16 in [89.4 cm] 31 7/8 in

[80.9 cm]

2 3/4 in [7.0 cm]

19 in [48.3 cm]

12 15/16 in [32.9 cm]

20 5/16 in [51.5 cm]

CENTER OFGRAVITY

Page 8: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

DOMINATOR 750Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 5.9*

Input BTU/hr. 750,000 / 220 kW Min. Gas Pressure Required 7" WC**

Output BTU/hr. 637,500 / 187 kW Max. Gas Pressure Allowed 14" WC

Electrical Requirements 120VAC/ 1 ph/ 60 hz Operating Weight 573 lbs. / 260 kg.

BOILER / WATER HEATER TRIM & CONTROLSMain Gas Valve Honeywell V8944 1" Pilot Valve Honeywell VR8205

Firing Valve Honeywell B200T1033 1" Air Switch Cleveland RSS-495

Safety Valve ASCO L8214G 1" Blower Motor 1/4 hp - FLA 5.1

Ignition Control UTC 1003-61A Relief Valve - DW 3/4" x 3/4" set @ 125 psi

Operating Control Tekmar BTC-2PA Relief Valve - DB 3/4" x 3/4" set @ 50 psi

High Limit Honeywell L4008E Flow Switch TACO

A.S.M.E.ASME Sect IV Htg Surface 77.0 Sq. Ft. / 7.15 Sq. M. Design Data Max. 160 psig & 250˚F

Water Volume 3.9 gal / 14.9 Liters

BOILER TEMPERATURE RISE / PRESSURE DROP20°F / 11.1°C 25°F / 13.9°C 30°F / 16.7°C 35°F / 19.4°C

Flow Rate Pressure Drop Flow Rate Pressure Drop Flow Rate Pressure Drop Flow Rate Pressure Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

63.8 4.0 1.38 4.1 51.0 3.2 0.91 2.7 42.5 2.7 0.65 1.9 36.4 2.3 0.49 1.4

* Add circulator amps.** For incoming gas pressures lower than 7” WC natural or 11” WC propane, consult factory.

SDOM-750-7

WATER HEATER HOURLY RECOVERY CAPACITY (GPH & LPH)40°F 22°C 60°F 33°C 80°F 44°C 100°F 56°C 120°F 67°C 140°F 78°C

1857 7019 1238 4680 928 3510 743 2808 619 2340 531 2006

The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

Page 9: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

CODE OPTIONS

CSD-1UTC Lockout/Reset Control Manual Reset LWCO

Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.

DOMINATOR 900Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

SDOM-900-7The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

RSUB-31-D

15 3/8 in [39.1 cm]

15 in [38.1 cm]

4 1/4 in [10.8 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

5 in [12.6 cm]

6 5/16 in [16.1 cm]

29 5/16 in [74.4 cm]

24 1/16 in [61.1 cm]

48 1/8 in [122.2 cm]

6 7/16 in [16.4 cm]

29 5/8 in [75.2 cm]

7 1/2 in [19.1 cm]

Ø10"

5 3/16 in [13.2 cm]

Ø2 1/2" WATER(2 PLCS.)

Ø1"NAT & LP

10 in [25.4 cm]

31 5/8 in [80.3 cm]

REAR FLUE OUTLET(OPTIONAL)

AIR INTAKE(REAR MOUNTOPTIONAL)

53 3/16 in [135.2 cm] 18 15/16 in

[48.1 cm]

11 in [28.0 cm]

35 3/16 in [89.4 cm]

2 3/4 in [7.0 cm]

19 1/16 in [48.4 cm]

23 5/8 in [60.1 cm]

12 15/16 in [32.9 cm]

CENTER OFGRAVITY

15 3/8 in [39.1 cm]

15 in [38.1 cm]

4 1/4 in [10.8 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

5 in [12.6 cm]

6 5/16 in [16.1 cm]

29 5/16 in [74.4 cm]

24 1/16 in [61.1 cm]

48 1/8 in [122.2 cm]

6 7/16 in [16.4 cm]

29 5/8 in [75.2 cm]

7 1/2 in [19.1 cm]

Ø10"

5 3/16 in [13.2 cm]

Ø2 1/2" WATER(2 PLCS.)

Ø1"NAT & LP

10 in [25.4 cm]

31 5/8 in [80.3 cm]

REAR FLUE OUTLET(OPTIONAL)

AIR INTAKE(REAR MOUNTOPTIONAL)

53 3/16 in [135.2 cm] 18 15/16 in

[48.1 cm]

11 in [28.0 cm]

35 3/16 in [89.4 cm]

2 3/4 in [7.0 cm]

19 1/16 in [48.4 cm]

23 5/8 in [60.1 cm]

12 15/16 in [32.9 cm]

CENTER OFGRAVITY

Page 10: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

DOMINATOR 900Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 5.9*

Input BTU/hr. 900,000 / 264 kW Min. Gas Pressure Required 7" WC**

Output BTU/hr. 765,000 / 224 kW Max. Gas Pressure Allowed 14" WC

Electrical Requirements 120VAC/ 1 ph/ 60 hz Operating Weight 664 lbs. / 301 kg.

BOILER / WATER HEATER TRIM & CONTROLSMain Gas Valve Honeywell V8944 1" Pilot Valve Honeywell VR8205

Firing Valve Honeywell B200T1033 1" Air Switch Cleveland RSS-495

Safety Valve ASCO L8214G 1" Blower Motor 1/4 hp - FLA 5.1

Ignition Control UTC 1003-61A Relief Valve - DW 3/4" x 3/4" set @ 125 psi

Operating Control Tekmar BTC-2PA Relief Valve - DB 3/4" x 3/4" set @ 50 psi

High Limit Honeywell L4008E Flow Switch TACO

A.S.M.E.ASME Sect IV Htg Surface 90.0 Sq. Ft. / 8.36 Sq. M. Design Data Max. 160 psig & 250˚F

Water Volume 4.1 gal / 15.4 Liters

BOILER TEMPERATURE RISE / PRESSURE DROP20°F / 11.1°C 25°F / 13.9°C 30°F / 16.7°C 35°F / 19.4°C

Flow Rate Pressure Drop Flow Rate Pressure Drop Flow Rate Pressure Drop Flow Rate Pressure Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

76.5 4.8 2.25 6.6 61.2 3.9 1.49 4.4 51.0 3.2 1.06 3.1 43.7 2.8 0.80 2.4

* Add circulator amps.** For incoming gas pressures lower than 7” WC natural or 11” WC propane, consult factory.

SDOM-900-7

WATER HEATER HOURLY RECOVERY CAPACITY (GPH & LPH)40°F 22°C 60°F 33°C 80°F 44°C 100°F 56°C 120°F 67°C 140°F 78°C

2228 8423 1486 5616 1114 4212 891 3369 743 2808 637 2407

The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

Page 11: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

CODE OPTIONS

CSD-1UTC Lockout/Reset Control Manual Reset LWCO

Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.

DOMINATOR 1050Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

SDOM-1050-7The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

RSUB-32-D

15 3/8 in [39.1 cm]

15 in [38.1 cm]

3 13/16 in [9.7 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

5 in [12.6 cm]

6 5/16 in [16.1 cm]

29 5/16 in [74.4 cm]

29 3/16 in [74.1 cm]

58 3/8 in [148.3 cm]

4 3/16 in [10.7 cm]

8 7/8 in [22.5 cm]

29 5/8 in [75.2 cm]

7 1/2 in [19.1 cm]

Ø10"

5 3/16 in [13.2 cm]

Ø2 1/2" WATER(2 PLCS.)

Ø1 1/4"NAT & LP

10 in [25.4 cm]

31 5/8 in [80.3 cm]

REAR FLUE OUTLET(OPTIONAL)

AIR INTAKE(REAR MOUNTOPTIONAL)

63 7/16 in [161.2 cm]

20 7/8 in [53.1 cm]

11 in [28.0 cm]

35 3/16 in [89.4 cm]

2 3/4 in [7.0 cm]

12 15/16 in [32.9 cm]

28 11/16 in [72.9 cm]

19 1/16 in [48.4 cm]

CENTER OFGRAVITY

15 3/8 in [39.1 cm]

15 in [38.1 cm]

3 13/16 in [9.7 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

5 in [12.6 cm]

6 5/16 in [16.1 cm]

29 5/16 in [74.4 cm]

29 3/16 in [74.1 cm]

58 3/8 in [148.3 cm]

4 3/16 in [10.7 cm]

8 7/8 in [22.5 cm]

29 5/8 in [75.2 cm]

7 1/2 in [19.1 cm]

Ø10"

5 3/16 in [13.2 cm]

Ø2 1/2" WATER(2 PLCS.)

Ø1 1/4"NAT & LP

10 in [25.4 cm]

31 5/8 in [80.3 cm]

REAR FLUE OUTLET(OPTIONAL)

AIR INTAKE(REAR MOUNTOPTIONAL)

63 7/16 in [161.2 cm]

20 7/8 in [53.1 cm]

11 in [28.0 cm]

35 3/16 in [89.4 cm]

2 3/4 in [7.0 cm]

12 15/16 in [32.9 cm]

28 11/16 in [72.9 cm]

19 1/16 in [48.4 cm]

CENTER OFGRAVITY

Page 12: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

DOMINATOR 1050Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 11.0*

Input BTU/hr. 1,050,000 / 308 kW Min. Gas Pressure Required 7" WC**

Output BTU/hr. 892,500 / 262 kW Max. Gas Pressure Allowed 14" WC

Electrical Requirements 120VAC/ 1 ph/ 60 hz Operating Weight 772 lbs. / 350 kg.

BOILER / WATER HEATER TRIM & CONTROLSMain Gas Valve Honeywell (2) V8944 1" Pilot Valve Honeywell VR8205

Firing Valve Honeywell (2) B200T1033 1" Air Switch Cleveland RSS-495

Safety Valve ASCO L8214G 1-1/4" Blower Motor (2) 1/4 hp - FLA 10.2

Ignition Control UTC 1003-61A Relief Valve - DW 3/4" x 3/4" set @ 125 psi

Operating Control Tekmar BTC-2PA Relief Valve - DB 3/4" x 3/4" set @ 50 psi

Operating Control Tekmar BTC-4PA Flow Switch TACO

High Limit Honeywell L4008E

A.S.M.E.ASME Sect IV Htg Surface 110.0 Sq. Ft. / 10.22 Sq. M. Design Data Max. 160 psig & 250˚F

Water Volume 4.4 gal / 16.8 Liters

BOILER TEMPERATURE RISE / PRESSURE DROP20°F / 11.1°C 25°F / 13.9°C 30°F / 16.7°C 35°F / 19.4°C

Flow Rate Pressure Drop Flow Rate Pressure Drop Flow Rate Pressure Drop Flow Rate Pressure Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

89.3 5.6 3.65 10.7 71.4 4.5 2.41 7.1 59.5 3.8 1.72 5.1 51.0 3.2 1.29 3.8

* Add circulator amps.** For incoming gas pressures lower than 7” WC natural or 11” WC propane, consult factory.

SDOM-1050-7

WATER HEATER HOURLY RECOVERY CAPACITY (GPH & LPH)40°F 22°C 60°F 33°C 80°F 44°C 100°F 56°C 120°F 67°C 140°F 78°C

2597 9815 1731 6544 1298 4908 1039 3926 866 3272 742 2804

The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

Page 13: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

CODE OPTIONS

CSD-1UTC Lockout/Reset Control Manual Reset LWCO

Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.

DOMINATOR 1350Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

SDOM-1350-7The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

RSUB-33-E

15 3/8 in [39.1 cm]

15 in [38.1 cm]

4 1/4 in [10.8 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

5 in [12.6 cm]

7 13/16 in [19.8 cm]

29 5/16 in [74.4 cm]

35 11/16 in [90.6 cm]

71 3/8 in [181.3 cm]

4 3/16 in [10.7 cm]

13 3/8 in [34.0 cm]

29 5/8 in [75.2 cm]

7 1/2 in [19.1 cm]

2 3/4 in [7.0 cm]

5 3/16 in [13.2 cm]

Ø1 1/4"NAT & LP Ø12"

12 in [30.5 cm]

30 in [76.3 cm]

AIR INTAKE(REAR MOUNTOPTIONAL)

27 3/8 in [69.6 cm]

11 in [28.0 cm]

76 7/16 in [194.2 cm]

35 3/16 in [89.4 cm]

12 15/16 in [32.9 cm]

19 1/16 in [48.4 cm]

35 13/16 in [91.0 cm]

CENTER OFGRAVITY

15 3/8 in [39.1 cm]

15 in [38.1 cm]

4 1/4 in [10.8 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

5 in [12.6 cm]

7 13/16 in [19.8 cm]

29 5/16 in [74.4 cm]

35 11/16 in [90.6 cm]

71 3/8 in [181.3 cm]

4 3/16 in [10.7 cm]

13 3/8 in [34.0 cm]

29 5/8 in [75.2 cm]

7 1/2 in [19.1 cm]

2 3/4 in [7.0 cm]

5 3/16 in [13.2 cm]

Ø1 1/4"NAT & LP Ø12"

12 in [30.5 cm]

30 in [76.3 cm]

AIR INTAKE(REAR MOUNTOPTIONAL)

27 3/8 in [69.6 cm]

11 in [28.0 cm]

76 7/16 in [194.2 cm]

35 3/16 in [89.4 cm]

12 15/16 in [32.9 cm]

19 1/16 in [48.4 cm]

35 13/16 in [91.0 cm]

CENTER OFGRAVITY

Page 14: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

DOMINATOR 1350Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 11.0*

Input BTU/hr. 1,350,000 / 396 kW Min. Gas Pressure Required 7" WC**

Output BTU/hr. 1,147,500 / 336 kW Max. Gas Pressure Allowed 14" WC

Electrical Requirements 120VAC/ 1 ph/ 60 hz Operating Weight 805 lbs. / 365 kg.

BOILER / WATER HEATER TRIM & CONTROLSMain Gas Valve Honeywell (2) V8944 1" Pilot Valve Honeywell VR8205

Firing Valve Honeywell (2) B200T1033 1" Air Switch Cleveland RSS-495

Safety Valve ASCO L8214G 1-1/4" Blower Motor (2) 1/4 hp - FLA 10.2

Ignition Control UTC 1003-61A Relief Valve - DW 3/4" x 3/4" set @ 125 psi

Operating Control Tekmar BTC-2PA Relief Valve - DB 3/4" x 1" set @ 50 psi

Operating Control Tekmar BTC-4PA Flow Switch TACO

High Limit Honeywell L4008E

A.S.M.E.ASME Sect IV Htg Surface 136.0 Sq. Ft. / 12.63 Sq. M. Design Data Max. 160 psig & 250˚F

Water Volume 4.8 gal / 18.2 Liters

BOILER TEMPERATURE RISE / PRESSURE DROP20°F / 11.1°C 25°F / 13.9°C 30°F / 16.7°C 35°F / 19.4°C

Flow Rate Pressure Drop Flow Rate Pressure Drop Flow Rate Pressure Drop Flow Rate Pressure Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

114.8† 7.2† 7.15 21.1 91.8 5.8 4.73 13.9 76.5 4.8 3.38 9.9 65.6 4.1 2.54 7.5

* Add circulator amps.** For incoming gas pressures lower than 7” WC natural or 11” WC propane, consult factory.

† Flow exceeds recommended maximum use a greater temperature rise or consult manufacturer. Cupronickel heat exchanger should be considered.

SDOM-1350-7

WATER HEATER HOURLY RECOVERY CAPACITY (GPH & LPH)40°F 22°C 60°F 33°C 80°F 44°C 100°F 56°C 120°F 67°C 140°F 78°C

3339 12620 2226 8413 1669 6310 1335 5048 1113 4207 954 3606

The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

Page 15: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

CODE OPTIONS

CSD-1UTC Lockout/Reset Control Manual Reset LWCO

Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.

DOMINATOR 1500Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

SDOM-1500-8The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

RSUB-34-F

Page 16: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

DOMINATOR 1500Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 11.0*

Input BTU/hr. 1,500,000 / 440 kW Min. Gas Pressure Required 7" WC**

Output BTU/hr. 1,275,000 / 374 kW Max. Gas Pressure Allowed 14" WC

Electrical Requirements 120VAC/ 1 ph/ 60 hz Operating Weight 846 lbs. / 384 kg.

BOILER / WATER HEATER TRIM & CONTROLSMain Gas Valve Honeywell (2) V8944 1" Pilot Valve Honeywell VR8205

Firing Valve Honeywell (2) B200T1033 1" Air Switch Cleveland RSS-495

Safety Valve ASCO L8214G 1-1/4" Blower Motor (2) 1/4 hp - FLA 10.2

Ignition Control UTC 1003-61A Relief Valve - DW 3/4" x 3/4" set @ 125 psi

Operating Control Tekmar BTC-2PA Relief Valve - DB 3/4" x 1" set @ 50 psi

Operating Control Tekmar BTC-4PA Flow Switch TACO

High Limit Honeywell L4008E

A.S.M.E.ASME Sect IV Htg Surface 149.0 Sq. Ft. / 13.84 Sq. M. Design Data Max. 160 psig & 250˚F

Water Volume 4.9 gal / 18.6 Liters

BOILER TEMPERATURE RISE / PRESSURE DROP25°F / 13.9°C 30°F / 16.7°C 35°F / 19.4°C

Flow Rate Pressure Drop Flow Rate Pressure Drop Flow Rate Pressure Drop

GPM L/s Ft kPa GPM L/s Ft kPa GPM L/s Ft kPa

102.0 6.4 6.29 18.5 85.0 5.4 4.49 13.2 72.9 4.6 3.37 9.9

* Add circulator amps.** For incoming gas pressures lower than 7” WC natural or 11” WC propane, consult factory.

SDOM-1500-8

WATER HEATER HOURLY RECOVERY CAPACITY (GPH & LPH)40°F 22°C 60°F 33°C 80°F 44°C 100°F 56°C 120°F 67°C 140°F 78°C

3709 14022 2473 9348 1855 7011 1484 5609 1236 4674 1060 4006

The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

Page 17: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

CODE OPTIONS

CSD-1UTC Lockout/Reset Control Manual Reset LWCO

Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.

DOMINATOR 1950Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

SDOM-1950-8The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

RSUB-35-F

15 3/8 in [39.1 cm]

15 in [38.1 cm]

4 1/4 in [10.8 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

5 in [12.6 cm]

7 13/16 in [19.8 cm]

29 5/16 in [74.4 cm]

48 11/16 in [123.7 cm]

97 3/8 in [247.3 cm]

4 3/16 in [10.7 cm]

26 3/8 in [67.0 cm]

5 3/16 in [13.2 cm]

Ø2"NAT & LP

Ø2 1/2" WATER(2 PLCS.)

Ø12"

7 1/2 in [19.1 cm]

29 5/8 in [75.2 cm]

30 in [76.3 cm]

REAR FLUEOUTLET(OPTIONAL)

AIR INTAKE(REAR MOUNTOPTIONAL)

102 7/16 in [260.3 cm]

40 3/8 in [102.6 cm]

11 in [28.0 cm]

35 3/16 in [89.4 cm]

14 in [35.6 cm]41 11/16 in

[105.9 cm]

2 3/4 in [7.0 cm]

47 7/8 in [47.9 cm]

19 1/16 in [19.1 cm]

12 15/16 in [12.9 cm]

50 9/32 in [50.3 cm]

15 3/8 in [39.1 cm]

15 in [38.1 cm]

4 1/4 in [10.8 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

5 in [12.6 cm]

7 13/16 in [19.8 cm]

29 5/16 in [74.4 cm]

48 11/16 in [123.7 cm]

97 3/8 in [247.3 cm]

4 3/16 in [10.7 cm]

26 3/8 in [67.0 cm]

5 3/16 in [13.2 cm]

Ø2"NAT & LP

Ø2 1/2" WATER(2 PLCS.)

Ø12"

7 1/2 in [19.1 cm]

29 5/8 in [75.2 cm]

30 in [76.3 cm]

REAR FLUEOUTLET(OPTIONAL)

AIR INTAKE(REAR MOUNTOPTIONAL)

102 7/16 in [260.3 cm]

40 3/8 in [102.6 cm]

11 in [28.0 cm]

35 3/16 in [89.4 cm]

14 in [35.6 cm]41 11/16 in

[105.9 cm]

2 3/4 in [7.0 cm]

47 7/8 in [47.9 cm]

19 1/16 in [19.1 cm]

12 15/16 in [12.9 cm]

50 9/32 in [50.3 cm]

Page 18: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

DOMINATOR 1950Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 11.0*

Input BTU/hr. 1,950,000 / 572 kW Min. Gas Pressure Required 7" WC**

Output BTU/hr. 1,657,500 / 486 kW Max. Gas Pressure Allowed 14" WC

Electrical Requirements 120VAC/ 1 ph/ 60 hz Operating Weight 1088 lbs. / 494 kg.

BOILER / WATER HEATER TRIM & CONTROLSMain Gas Valve Honeywell (2) V8944 1" Pilot Valve Honeywell VR8205

Firing Valve Honeywell (2) B200T1033 1" Air Switch Cleveland RSS-495

Safety Valve ASCO L8214G 1-1/2" Blower Motor (2) 1/4 hp - FLA 10.2

Ignition Control UTC 1003-61A Relief Valve - DW 3/4" x 3/4" set @ 125 psi

Operating Control Tekmar BTC-2PA Relief Valve - DB 3/4" x 1-1/4" set @ 50 psi

Operating Control Tekmar BTC-4PA Flow Switch TACO

High Limit Honeywell L4008E

A.S.M.E.ASME Sect IV Htg Surface 189.0 Sq. Ft. / 17.56 Sq. M. Design Data Max. 160 psig & 250˚F

Water Volume 5.4 gal / 20.4 Liters

BOILER TEMPERATURE RISE / PRESSURE DROP30°F / 16.7°C 35°F / 19.4°C

Flow Rate Pressure Drop Flow Rate Pressure Drop

GPM L/s Ft kPa GPM L/s Ft kPa

110.5† 7.0† 9.18 27.0 94.7 6.0 6.90 20.3

* Add circulator amps.** For incoming gas pressures lower than 7” WC natural or 11” WC propane, consult factory.

SDOM-1950-8

WATER HEATER HOURLY RECOVERY CAPACITY (GPH & LPH)40°F 22°C 60°F 33°C 80°F 44°C 100°F 56°C 120°F 67°C 140°F 78°C

4816 18206 3211 12138 2408 9103 1927 7283 1605 6069 1376 5202

The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

† Flow exceeds recommended maximum use a greater temperature rise or consult manufacturer. Cupronickel heat exchanger should be considered.

Page 19: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

CODE OPTIONS

CSD-1UTC Lockout/Reset Control Manual Reset LWCO

Notes: 1. Dimensions are approximate and should not be used to "rough-in" equipment.2. Dimensions are subject to change without notice.

DOMINATOR 2100Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

SDOM-2100-8The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

RSUB-36-F

15 3/8 in [39.1 cm]

15 in [38.1 cm]

4 1/4 in [10.8 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

5 in [12.6 cm]

7 13/16 in [19.8 cm]

29 5/16 in [74.4 cm]

51 15/16 in [131.9 cm]

103 7/8 in [263.8 cm]

4 3/16 in [10.7 cm]

29 7/8 in [75.9 cm]

5 3/16 in [13.2 cm]

Ø2"NAT & LP

Ø2 1/2" WATER(2 PLCS.)

Ø12"

7 1/2 in [19.1 cm]

29 5/8 in [75.2 cm]

REAR FLUEOUTLET(OPTIONAL)

30 in [76.3 cm]

AIR INTAKE(REAR MOUNTOPTIONAL)

43 5/8 in [110.9 cm]

11 in [28.0 cm]

108 15/16 in [276.8 cm]

35 3/16 in [89.4 cm]

14 in [35.6 cm]

44 15/16 in [114.1 cm]

2 3/4 in [7.0 cm]

12 15/16 in [32.9 cm]

19 1/16 in [48.4 cm]

51 1/16 in [129.7 cm]

15 3/8 in [39.1 cm]

15 in [38.1 cm]

4 1/4 in [10.8 cm]

26 9/16 in [67.5 cm]

37 7/8 in [96.2 cm]

5 in [12.6 cm]

7 13/16 in [19.8 cm]

29 5/16 in [74.4 cm]

51 15/16 in [131.9 cm]

103 7/8 in [263.8 cm]

4 3/16 in [10.7 cm]

29 7/8 in [75.9 cm]

5 3/16 in [13.2 cm]

Ø2"NAT & LP

Ø2 1/2" WATER(2 PLCS.)

Ø12"

7 1/2 in [19.1 cm]

29 5/8 in [75.2 cm]

REAR FLUEOUTLET(OPTIONAL)

30 in [76.3 cm]

AIR INTAKE(REAR MOUNTOPTIONAL)

43 5/8 in [110.9 cm]

11 in [28.0 cm]

108 15/16 in [276.8 cm]

35 3/16 in [89.4 cm]

14 in [35.6 cm]

44 15/16 in [114.1 cm]

2 3/4 in [7.0 cm]

12 15/16 in [32.9 cm]

19 1/16 in [48.4 cm]

51 1/16 in [129.7 cm]

Page 20: DOMINATOR 300 - mesteksa.commesteksa.com/fileuploads/Literature/RBI Water Heaters/Dominator S… · [27.6 cm] CENTER OF GRAVITY: RSUB-27-D: REP FIRM: SUBMITTED BY JOB NAME: ARCHITECT

REP FIRM

SUBMITTED BY

JOB NAME

ARCHITECT

ENGINEER

CONTRACTOR

DATE

DOMINATOR 2100Category I or Category III Appliance

(see Installation and Operation Manual for venting information)

A Division of Mestek, Inc.Westfield, MA 01085(413) 564-5515

BOILER CERTIFIED RATINGS & CAPACITIESFuel Type Natural/Propane Gas Boiler FLA 11.0*

Input BTU/hr. 2,100,000 / 616 kW Min. Gas Pressure Required 7" WC**

Output BTU/hr. 1,785,000 / 523 kW Max. Gas Pressure Allowed 14" WC

Electrical Requirements 120VAC/ 1 ph/ 60 hz Operating Weight 1105 lbs. / 502 kg.

BOILER / WATER HEATER TRIM & CONTROLSMain Gas Valve Honeywell (2) V8944 1-1/4" Pilot Valve Honeywell VR8205

Firing Valve Honeywell (2) B200T1041 1-1/4" Air Switch Cleveland RSS-495

Safety Valve ASCO L8214G 1-1/2" Blower Motor (2) 1/4 hp - FLA 10.2

Ignition Control UTC 1003-61A Relief Valve - DW 3/4" x 3/4" set @ 125 psi

Operating Control Tekmar BTC-2PA Relief Valve - DB 3/4" x 1-1/4" set @ 50 psi

Operating Control Tekmar BTC-4PA Flow Switch TACO

High Limit Honeywell L4008E

A.S.M.E.ASME Sect IV Htg Surface 202.0 Sq. Ft. / 18.77 Sq. M. Design Data Max. 160 psig & 250˚F

Water Volume 5.6 gal / 21.4 Liters

BOILER TEMPERATURE RISE / PRESSURE DROP30°F / 16.7°C 35°F / 19.4°C

Flow Rate Pressure Drop Flow Rate Pressure Drop

GPM L/s Ft kPa GPM L/s Ft kPa

119.0† 7.5† 11.24 33.1 102.0 6.4 8.45 24.9

* Add circulator amps.** For incoming gas pressures lower than 7” WC natural or 11” WC propane, consult factory.

SDOM-2100-8

WATER HEATER HOURLY RECOVERY CAPACITY (GPH & LPH)40°F 22°C 60°F 33°C 80°F 44°C 100°F 56°C 120°F 67°C 140°F 78°C

5187 19607 3458 13071 2593 9803 2075 7843 1729 6536 1482 5602

The Dominator Boiler Series will no longer be available for sale in the Canadian Province of Ontario due to the Ontario Regulation 404/12, Green Energy Act 2009.

† Flow exceeds recommended maximum use a greater temperature rise or consult manufacturer. Cupronickel heat exchanger should be considered.