Doble Solutions for IEC 61850
Jun VerzosaJay GosaliaNestor CasillaDoble Engineering Company
Topics Covered
Doble
Protection Diagnostics
Brief Introduction of IEC61850
IEC 61850 9-2 LE Requirements
F6150 Process Bus Implementation
Data Interpretation
Testing Demonstration
10th India Doble Power Forum Conference 3
Doble E
ngineering
Company
-
Doble Engineering
Doble Engineering Company is the worldleader in diagnostic test instruments andknowledge services to the electric powerindustry.
Now in 110 countries, Doble Engineering hasbeen helping clients in the electric powerindustry improve operations and optimizesystem performance for more than 85 years.
Doble Engineering
Doble offers diagnostic instruments, services,and the worlds premier library of statisticallysignificant apparatus test results for thebenefit of energy generation and deliverycompanies and industrial power usersworldwide.
10th India Doble Power Forum Conference 4
Doble E
ngineering
Company
-
Doble Engineering
Doble was acquired by ESCO TechnologiesInc. (NYSE: ESE) in 2007. Doble continues tobe operated as a stand-alone company.
Doble Engineering
Doble has established products in the following areas:
Circuit Breaker Diagnostics
Continuous On-Line Diagnostics
Insulation Analysis
Oil/Materials Analysis/DOMINO
10th India Doble Power Forum Conference 5
Doble E
ngineering
Company
-
Doble Engineering
Partial Discharge Detection
Protection Diagnostics
Surge Arresters Monitoring
Sweep Frequency Response Analysis
Transformer Diagnostics
Protection Diagnostics
Doble protection diagnostic instruments arecompact, rugged, field-portable devices usedworldwide by test engineers to diagnose andcalibrate electromechanical and numericalschemes. The instruments are designed toprovide fully automated steady-state, dynamic,and transient testing capability, in the field aswell as in a laboratory.
10th India Doble Power Forum Conference 6
Doble E
ngineering
Company
-
Protection Diagnostics
Doble offers the following protection diagnostic instruments and software: F6150SV and F6150 Power System Simulator
Protection Diagnostics
F6350 Real Time Power System Simulation Interface
Low Level Sources
10th India Doble Power Forum Conference 7
Doble E
ngineering
Company
-
Protection Diagnostics
F6300 High-Power Current Amplifier
Protection Diagnostics
ProTesT
F6Test
Transwin
Protection Suite
10th India Doble Power Forum Conference 8
Doble E
ngineering
Company
-
IEC61850 SolutionsVoltage and Current
Analog or SV
1. Fault SimulationIED 1
BREAKER
IED 2
ProtectionFunction
Reclose/Synch
2. Trip
3. New Position
4. Reclose Command
5. New Position
GOOSE Message: Trip
GOOSE Message: Position
GOOSE Message: Reclose
IEC61850 NETWORKS
Voltage
What Is IEC 61850?
Borrowed from
Siemens
International Standard More than a Protocol A Framework for Substation Automation
SubstationLAN
Network
HMI
10th India Doble Power Forum Conference 9
Doble E
ngineering
Company
-
What Is IEC 61850?
Proc
ess
Leve
lBa
y Le
vel
Stat
ion
Leve
l HMI
Station Bus
Process Bus (sampled analog
values)Conventional CTs and VTs
with hard wiring are used today
Borrowed from
Siemens
What Is IEC 61850?
The core idea is a description language,that completely describes the datastructure and functionality of asubstation information system in astandardized manner.
10th India Doble Power Forum Conference 10
Doble E
ngineering
Company
-
What Is IEC 61850?
The core idea is a description language, that completely describes the data structure and functionality of a substation information system in a standardized manner.
IEC61850 Documents
Basic principles Part 1
Glossary Part 2
General Requirements Part 3
System and project management Part 4
Communication requirements Part 5
Substation Automation System Configuration Part 6
Basic Communication Structure Part 7
Part 9Sampled Measured Values
Part 8
Conformance testing Part 10
Mapping to Ethernet
Mapping to MMS and Ethernet
10th India Doble Power Forum Conference 11
Doble E
ngineering
Company
-
This standardized language can be understood by devices from different manufacturers ensuring one of the key goals of IEC 61850, Multi-Vendor Inter-Operability.
Borrowed from
Siemens
IEC 61850
What Is IEC 61850?
What Is IEC 61850?
Borrowed from
Siemens
IEC 61850
This standardized language can be understood by devices from different manufacturers ensuring one of the key goals of IEC 61850, Multi-Vendor Inter-Operability.
10th India Doble Power Forum Conference 12
Doble E
ngineering
Company
-
IEC61850 : Defining Devices
CB1
IED1
PTOC
RREC
XCBR
XSWI
MMXU
MMTR Metering
CSWI
CSWI
Borrowed from
Siemens
Measurement Unit
Disconnect SwitchIndication & Control
Circuit BreakerIndication & Control
Auto Reclosing
Time Over Current
IEC61850 : Defining Devices
CB1
IED1
PTOC
RREC
XCBR
XSWI
MMXU
MMTR
CSWI
CSWI
Borrowed from
Siemens
10th India Doble Power Forum Conference 13
Doble E
ngineering
Company
-
IEC61850 : Defining Devices
CB1
IED1
PTOC
RREC
XCBR
XSWI
MMXU
MMTR
IED1Logical Device
CSWI
CSWI
The description of the logical device
(i.e. the IED) is what you will find in
a device description file. (called
ICD)
Borrowed from
Siemens
Accessing Data :Think Windows Explorer
PTOC (Time Over Current LN )RREC (Autorecloser LN )XCBR (Switchgear Circuit Breaker)CSWI (Control - Circuit Breaker)XSWI (Switchgear Disconnect)CSWI (Control - Disconnect)MMXU (Measurement Unit)MMTR (Metering)
+
+
+
+
+
+
IED1
IED1
+
+
Borrowed from
Siemens
IED1/XCBR
10th India Doble Power Forum Conference 14
Doble E
ngineering
Company
-
Accessing Data :Tree view
Mode (Mode)Beh (Behavior )Health (Health)Name (Name plate)Loc (Local operation)EEHealth (External equipment)EEName (External equipment name plate)OperCnt (Operation counter)Pos (Switch position)BlkOpen (Block opening)BlkClos (Block closing)ChMotEna (Charger motor enabled)CBOpCap (Circuit breaker operating capability)POWCap (Point On Wave switching capability)
+
+
+
+
+
+
+
+
+
+
++
+
+
XCBR
PTOCRREC
+
+
-
IED1/XCBRIED1
Borrowed from
Siemens
IED1/XCBR.Pos
Accessing Data :Tree view
Mode (Mode)Beh (Behavior )Health (Health)Name (Name plate)Loc (Local operation)EEHealth (External equipment)EEName (External equipment name plate)OperCnt (Operation counter)Pos (Switch position)
+
+
+
+
+
+
+
+
-
XCBR
PTOCRREC
+
+
-
ctlValstValpulseConfigoperTimqmore
intermediate-state (0)off (1)on (2)bad-state (3)
IED1/XCBR.Pos
IED1
Borrowed from
Siemens
IED1/XCBR.Pos.stVal
10th India Doble Power Forum Conference 15
Doble E
ngineering
Company
-
Logical Groupings Devices, Nodes, Classes & Data
Physical Device(network address)
Physical Device - server(network address)
Logical Device(IED1)
LN2(PDIS)
LN1(XCBR)
Logical Groupings Devices, Nodes, Classes & Data
Pos Op
gen. qstVal q
Physical Device
Logical Device(1 to n)
Logical Node(1 to n)
Data Class
Data
Borrowed from
Siemens
10th India Doble Power Forum Conference 16
Doble E
ngineering
Company
-
IEC61850 Primary Parts
Part 6-1: Substation Configuration Language (SCL) Part 7-2: Abstract Communications Service Interface
(ACSI) and base types Part 7-3: Common Data Classes (CDC) Part 7-4: Logical Nodes Part 8-1: Specific Communications Service Mappings
(SCSM) - MMS & Ethernet Part 9-2: SCSM - Sampled Values over Ethernet Part 10-1: Conformance Testing
UCA : 9-2 LE Guide line Document
10th India Doble Power Forum Conference 17
Doble E
ngineering
Company
-
9-2 LE Implementation Guideline
Purpose of implementation guideline Support fast market introduction of the standard Define a subset to facilitate first implementations
Logical device merging unit name: xxxxMUnnyy xxxx : alphanumeric name MU : fixed, stands for merging unit nn : merging unit number yy : 01 for protection (80 samples/cy), 02 for metering (256
samples/cy)
Examples: DOBLMU1201, A1Z9MU0401 Fixed dataset : 4 currents & 4 voltages (Phases A,
B, C & Neutral)
Data Structure : Sample Value Packet
Preamble : 8 BytesStart of the Frame : 1 Byte
Destination Address: 010CCD04
Source Address: MAC Address : F6
Priority Tagged : 4 BytesProtocol Data Unit : PDUData type :88BAApp ID : 0400Data Length :Reserved Bytes : 2 Bytes : 0000, 0000A,B,C,N : V & I Data : Quality and Value
10th India Doble Power Forum Conference 18
Doble E
ngineering
Company
-
F6TesT : SV Source Configuration
Destination Address: 010CCD04
Priority Tagged VLAN ID = 0VLAN Priority=4
Process Bus : Data Capture
10th India Doble Power Forum Conference 19
Doble E
ngineering
Company
-
Process Bus : Data Capture
Process Bus : Sampled values Data
10th India Doble Power Forum Conference 20
Doble E
ngineering
Company
-
Process Bus : Sampled Values
svID : last two digit 01 : 80 samples/cy.smpCnt :829 : 0-4799 for 60Hz & rolls OversmpSynch : 1 : samples are synchronized
Value is 32 bit integer. One bit is for sign.31 bit provides very wide dynamic rangeThis is expressed as peak value in mA(10-3) and cV (10-2)
SV Packet : Quality Bits
10th India Doble Power Forum Conference 21
Doble E
ngineering
Company
-
Process Bus : 9-2 LE Requirements
Protection sampled value should be sampled at 80 samples/Cycle & metering sampled value should be sampled at 256 Samples/Cycle Last two digit on svid indicates 01 (for 80 samples) & 02 (for 256
Samples)
Physical layer requirements : Fiber optic 100 Base FX Full Duplex with ST connector Electrical connection : 100 Base TX Full Duplex
In the test mode : MU should flag the data as Test with a bit in quality bit
MU should be synchronized with external 1 PPS signal with an accuracy of 1 microsecond to the absolute time
Process Bus : 9-2 LE Requirements
If the synchronization signal is lost SmpSynch in the SV packet should be set to false
If Neutral current or voltage is not measured, MU should calculate and flag the value as calculated in quality field.
Up to 8 ASDUs can be transmitted in one PDU packet
No SV messages are sent until Merging Unit is fully operational.
10th India Doble Power Forum Conference 22
Doble E
ngineering
Company
-
IED Communications
Ethernet Ports for GOOSE and Setting
Copper port
F.O. port
IRIB-BTime sync
Copper port
F.O. port
Ethernet Ports for IEC61850 9-2 LE Sampled Values
IED Communications
Ethernet Ports for GOOSE and Setting
IRIB-BTime sync
F.O. Ports for IEC61850 9-2 LE Sampled Values
10th India Doble Power Forum Conference 23
Doble E
ngineering
Company
-
Configuring F6150 Sampled Values
Configuring F6150 Sampled Values
10th India Doble Power Forum Conference 24
Doble E
ngineering
Company
-
F6150SV Communications
F.O. port Sampled Values
Copper port
Sampled Values
USB portF6 control & configuration
2-port switchGSE messages
F6 control & configuration
F6150SV Communications
10th India Doble Power Forum Conference 25
Doble E
ngineering
Company
-
Testing the IED with F6150SV
HUB
SAMPLE VALUES
GE UR Relay SEL 421 Relay
IP 192.168.5.193
IP 192.168.5.192
IP 192.168.5.194
GOOSE Messages
IP 192.168.5.191
Testing the IED with F6150SV
GOOSE messages
sampled values
P444 IEDF6150SV
F6TesT 3GSEIED swother sw
10th India Doble Power Forum Conference 26
Doble E
ngineering
Company
-
Testing the IED with F6150SV
F6TesT 3GSEIED swother sw
Configuring F6150 Sampled Values
10th India Doble Power Forum Conference 27
Doble E
ngineering
Company
-
Metering Test of SV
Metering Test of SV
10th India Doble Power Forum Conference 28
Doble E
ngineering
Company
-
State Simulation Test using SV
Waveforms recorded by IED from SV
10th India Doble Power Forum Conference 29
Doble E
ngineering
Company
-
Doble IEC 61850 GSE Configurator
Create, import or discover GSE messages. Configures the F6150 Power System Simulator
for GSE Message Subscription (Input or Reception) Publishing (Output or
Simulation/Transmission). Supports GOOSE and GSSE messages.
Doble IEC 61850 GSE Configurator
Define GSE Messages and their payload (Dataset items) Discover, import SCL files, or manually create them.
Select Dataset items from messages that will be used for testing
Assign data items to F6150 Inputs and Outputs Download the Data Items and I/O mappings to
the F6150 (Configure the instrument) Observe Live Data Status while testing
10th India Doble Power Forum Conference 30
Doble E
ngineering
Company
-
Doble IEC 61850 GSE Configurator
Doble IEC 61850 GSE Configurator
10th India Doble Power Forum Conference 31
Doble E
ngineering
Company
-
Doble IEC 61850 GSE Configurator
Doble IEC 61850 GSE Configurator
10th India Doble Power Forum Conference 32
Doble E
ngineering
Company
-
Doble IEC 61850 GSE Configurator
Doble IEC 61850 GSE Configurator
10th India Doble Power Forum Conference 33
Doble E
ngineering
Company
-
Doble IEC 61850 GSE Configurator
Doble IEC 61850 GSE Configurator
10th India Doble Power Forum Conference 34
Doble E
ngineering
Company
-
Doble IEC 61850 GSE Configurator
Doble IEC 61850 GSE Configurator
10th India Doble Power Forum Conference 35
Doble E
ngineering
Company
-
Doble IEC 61850 GSE Configurator
Doble IEC 61850 GSE Configurator
10th India Doble Power Forum Conference 36
Doble E
ngineering
Company
-
Doble IEC 61850 GSE Configurator