Subject: DNV KEMA Selection of tests on SIA-C Overcurrent & Earth Fault Protection Relay
Dear Maitane San Martn,
KEMA Nederland B.V. Utrechtseweg 310, 6812 AR Arnhem P.O. Box 9035, 6800 ET Arnhem The Netherlands
T +31 26 356 9111 F +31 26 442 8388 [email protected] www.dnvkema.com Registered Arnhem 09080262
With this letter DNV KEMA declares that a selection of tests has been performed on the SIA-C
Overcurrent & Earth Fault Protection Relay according to IEC 60255-26, IEC 610000-4 series for
EMC, insulation tests according to IEC 60255-27 and IEC 60255-5, mechanical tests according to
IEC 60255-21 series and climatic tests according to IEC 60068-2 series at the DNV KEMA
laboratories in Arnhem, the Netherlands.
Test program SIA-C Overcurrent & Earth Fault Protection Relay
test standard level result
insulation tests
dielectric power frequency test IEC 60255-27
IEC 60255-5
2,0 kV 50 Hz 1 min pass
impulse voltage IEC 60255-1
IEC 60255-27
5 kV pass
insulation resistance IEC 60255-1
IEC 60255-27
500 V dc pass
EMC immunity
electrostatic discharges IEC 60255-1
IEC 60255-26
IEC 61000-4-2
6 kV contact
8 kV air
pass
radiated EM field IEC 60255-1
IEC 60255-26
IEC 61000-4-3
20 V/m pass
fast transient burst IEC 60255-1
IEC 60255-26
IEC 61000-4-4
4 kV CM pass
surge IEC 60255-1
IEC 60255-26
IEC 61000-4-5
4 kV L-G
2 kV L-L
pass
DNV KEMA Energy & Sustainability
2014-001
-2-
test standard level result
conducted RF interference IEC 60255-1
IEC 60255-26
IEC 61000-4-6
10 V pass
power frequency magnetic field IEC 60255-1
IEC 60255-26
IEC 61000-4-8
30 A/m continuous
300 A/m 2 s
pass
1 MHz damped oscillatory magnetic
field
IEC 61000-4-10 100 A/m pass
100 kHz damped oscillatory magnetic
field
IEC 61000-4-10 100 A/m pass
pulsed H-field IEC 61000-4-9 1000 A/m pass
conducted CM 50 Hz voltage IEC 60834-1
IEC 61000-6-2
IEC 61000-4-16
30 V continuous
300 V 1 s
pass
1 MHz damped oscillatory waves IEC 60255-1
IEC 60255-26
IEC 61000-4-18
2,5 kV CM
1,0 kV DM
pass
EMC emission
radiated emission CISPR 11
CISPR22
class A pass
mechanical tests
vibration response IEC 60255-1
IEC 60255-21-1
class1 pass
vibration endurance IEC 60255-1
IEC 60255-21-1
class1 pass
shock response IEC 60255-1
IEC 60255-21-2
class1 pass
shock withstand IEC 60255-1
IEC 60255-21-2
class1 pass
bump IEC 60255-1
IEC 60255-21-2
class1 pass
seismic IEC 60255-1
IEC 60255-21-3
class1 pass
climatic tests
cold test operation IEC 60255-1
IEC 60068-2-1
-25C pass
cold test storage IEC 60255-1
IEC 60068-2-1
-40C pass
dry heat test operation IEC 60255-1
IEC 60068-2-2
+70C pass
dry heat test storage IEC 60255-1
IEC 60068-2-2
+85C pass
damp heat cyclic IEC 60255-1
IEC 60068-2-30
+40C / 93% _ +25C / 97% pass
damp heat steady IEC 60255-1
IEC 60068-2-78
+40C / 93% pass
DNV KEMA Energy & Sustainability
2014-001
-3-
test standard level result
change of temperature IEC 60255-1
IEC 60068-2-78
-25C / +70C pass
The KEMA reference number is 72121106. The tests are scheduled to be finished February 7th 2014.
We trust to have informed you satisfactory with this information.
Yours sincerely,
KEMA Nederland B.V.
Marc Achterkamp
Manager Operations testing Metering, Protection & Substation Automation