· division 26 - electrical specifications 2. where approved by the authorities having...
Transcript of · division 26 - electrical specifications 2. where approved by the authorities having...
![Page 1: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/1.jpg)
![Page 2: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/2.jpg)
![Page 3: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/3.jpg)
![Page 4: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/4.jpg)
![Page 5: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/5.jpg)
![Page 6: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/6.jpg)
![Page 7: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/7.jpg)
DIVISION 26 - ELECTRICAL SPECIFICATIONS
2. WHERE APPROVED BY THE AUTHORITIES HAVING JURISDICTION AND ENGINEER, "MC" CABLE MAY BE UTILIZED FOR
INTERIOR BRANCH CIRCUITS.
3. ALL MC CABLE SHALL HAVE A GREEN INSULATED GROUND WIRE IN ADDITION TO THE BONDING WIRE.
4. ALL 120 VOLT CIRCUIT HOMERUNS WHICH ARE OVER 100 LINEAR FEET SHALL BE #10 CONDUCTORS MINIMUM.
5. RUN MULTIPLE HOMERUNS TO ALTERNATELY NUMBERED PANELBOARD CIRCUITS (I.E., 1, 3, 5)
D. WIRING DEVICES AND TELEPHONE/DATA OUTLETS
1. THE LOCATION OF ALL WIRING DEVICES AND TELEPHONE/DATA OUTLETS SHALL BE VERIFIED BEFORE
INSTALLATION WITH THE ARCHITECT. THE ARCHITECT MAY, AT HIS OPTION, RELOCATE ANY DEVICE 5 FEET AT NO
CHARGE TO THE OWNER.
2. WHERE TWO OR MORE DEVICES ARE SHOWN TOGETHER ON THE PLANS, A MULTI-GANG BOX AND PLATE SHALL BE
USED. DEVICES OF DIFFERENT VOLTAGES SHALL BE SEPARATED BY PERMANENTLY INSTALLED BOX PARTITIONS.
3. ALL OUTLETS SHOWN ON A WALL BACK TO BACK SHALL BE OFFSET A MINIMUM OF 6" HORIZONTALLY.
4. WALL MOUNTED WIRING DEVICES SHALL BE WHITE COLOR, OR AS SELECTED BY THE ARCHITECT AND EQUAL TO
THE FOLLOWING
SINGLE POLE SWITCH HUBBELL 1221
TWO-POLE SWITCH HUBBELL 1222
THREE-WAY SWITCH HUBBELL 1223
FOUR-WAY SWITCH HUBBELL 1224
DIMMER SWITCH LUTRON NOVA SERIES
SWITCH WITH PILOT LIGHT (120V) HUBBELL 1221PL
DUPLEX RECEPTACLE HUBBELL 5352
DUPLEX RECEPTACLE WITH GFCI* HUBBELL GF5352
DUPLEX RECEPTACLE WITH
ISOLATED GROUND HUBBELL IG5362
COMBINATION OCUPANCY SENSOR SWITCH SENSORSWITCH WSD-PDT
*GFCI - GROUND FAULT CIRCUIT INTERRUPTER
5. DEVICE PLATES SHALL BE WHITE OVERSIZED STEEL.
6. COORDINATE LIGHT SWITCHES SHOWN ON DRAWINGS WITH DOOR SWINGS. LOCATE LIGHT SWITCH ON LOCK SIDE
OF DOOR.
7. COORDINATE WALL MOUNTED TELEPHONE/DATA OUTLET LOCATIONS WITH THE ARCHITECT. PROVIDE DEVICE
RING, 3/4"C AND PULLSTRING IN ALL WALL SPACES TO 6" ABOVE CEILING SPACE. TELEPHONE/DATA CONDUCTORS
WILL BE INSTALLED BY OTHERS.
8. PROVIDE FOR COMPLETE INSTALLATION OF FLOOR DEVICES INCLUDING ALL ACCESSORIES.
E. SUPPORTING DEVICES
1. INSTALL SUPPORTING DEVICES TO FASTEN ELECTRICAL COMPONENTS SECURELY AND PERMANENTLY IN
ACCORDANCE WITH NEC REQUIREMENTS AND ANY ADDITIONAL LOCAL CODES.
2. COORDINATE WITH THE BUILDING STRUCTURAL SYSTEM AND WITH OTHER ELECTRICAL INSTALLATIONS.
F. ELECTRICAL IDENTIFICATION
1. CONDUCTOR COLOR CODING: PROVIDE COLOR CODING FOR FEEDER AND BRANCH CIRCUIT CONDUCTOR
VOLTAGES AS FOLLOWS:
208/120 PHASE [480/277]460/265
BLACK A YELLOW
RED B BROWN
BLUE C ORANGE
WHITE NEUTRAL GRAY
GREEN GROUND GREEN
2. APPLY EQUIPMENT IDENTIFICATION LABELS (MINIMUM 1" HIGH LETTERS) OF ENGRAVED PLASTIC-LAMINATE ON
EACH MAJOR UNIT OF ELECTRICAL EQUIPMENT. APPLY LABELS FOR EACH UNIT OF THE FOLLOWING CATEGORIES
OF ELECTRICAL EQUIPMENT.
a. PANELBOARDS, ELECTRICAL CABINETS AND ENCLOSURES.
b. ACCESS DOORS AND PANELS FOR CONCEALED ELECTRICAL ITEMS.
c. ELECTRICAL SWITCHGEAR AND SWITCHBOARDS.
d. MOTOR CONTROL CENTERS.
e. MOTOR STARTERS.
f. PUSHBUTTON STATIONS.
g. POWER TRANSFER EQUIPMENT.
h. CONTACTORS.
i. REMOTE-CONTROLLED SWITCHES.
j. DIMMERS.
k. CONTROL DEVICES.
l. TRANSFORMERS.
m. POWER GENERATING UNITS.
n. FIRE ALARM MASTER STATION OR CONTROL PANEL.
3. APPLY CIRCUIT/CONTROL/ITEM DESIGNATION LABELS OF ENGRAVED PLASTIC LAMINATE FOR DISCONNECT
SWITCHES, BREAKERS, PUSHBUTTONS, PILOT LIGHTS, MOTOR CONTROL CENTERS, AND SIMILAR ITEMS FOR
POWER DISTRIBUTION AND CONTROL COMPONENTS ABOVE.
4. FOR PANELBOARDS: PROVIDE FRAMED, TYPED CIRCUIT SCHEDULES WITH EXPLICIT DESCRIPTION AND
IDENTIFICATION OF ITEMS CONTROLLED BY EACH INDIVIDUAL BREAKER.
5. FOR RECEPTACLES: PROVIDE LABEL TO INDICATE PANEL AND CIRCUIT BREAKER NO. SUPPLYING THE RECEPTACLE
OR OUTLET. PROVIDE PRESSURE SENSITIVE, LABEL WITH BLACK LETTERING ON CLEAR BACKGROUND. LETTERING
HEIGHT IS 1/8".
G. GROUNDING
1. GROUND ELECTRICAL SYSTEMS AND EQUIPMENT IN ACCORDANCE WITH NEC EXCEPT WHERE GROUNDING IN
EXCESS OF NEC REQUIREMENTS IS INDICATED.
2. ALL CIRCUITS SHALL CONTAIN AN INSULATED GROUNDING CONDUCTORS. ALL NEW RECEPTACLE CIRCUITS SHALL
CONTAIN A #12 INSULATED GROUNDING CONDUCTOR.
3. SEPARATELY DERIVED SYSTEMS REQUIRED BY NEC TO BE GROUNDED SHALL BE GROUNDED AS APPROVED BY
THE AUTHORITY HAVING JURISDICTION.
I. PANELBOARDS
1. IN PANELBOARDS, "EQUIPPED SPACE" OR "SPACE" IS DEFINED TO INCLUDE ALL NECESSARY BUS, DEVICE
SUPPORTS AND CONNECTIONS FOR INSERTION OF A FUTURE DEVICE.
2. ALL PANELBOARDS SHALL BE EQUIPPED WITH COMMON KEYED LOCKS. PROVIDE A MINIMUM OF TWO KEYS PER
PANEL. PANELBOARDS SHALL BE COMPLETE WITH DOOR IN DOOR TYPE COVERS AND TRIMS AND SHALL CONTAIN
A GROUND BUS.
3. PANELBOARD CIRCUITING SHALL MATCH THE DRAWINGS. CIRCUITING CHANGES MUST BE APPROVED BY THE
ENGINEER.
4. PANELBOARD BUS SHALL BE COPPER.
5. BEFORE ORDERING PANELBOARDS, COORDINATE ALL MOTOR CIRCUIT BREAKER TRIPS WITH MECHANICAL
EQUIPMENT MANUFACTURER'S REQUIREMENTS. COORDINATE CONDUCTOR SIZE WITH ACTUAL MOTORS AND
OTHER MECHANICAL AND ARCHITECTURAL EQUIPMENT FURNISHED BEFORE INSTALLING CIRCUITRY. ADJUSTABLE
TRIP CIRCUIT BREAKERS SHALL BE SET BY THE CONTRACTOR IN THE FIELD.
6. SURFACE MOUNTED PANELBOARD CABINETS SHALL BE INSTALLED ON AN APPROVED STEEL FRAMEWORK TO
DISTRIBUTE THE WEIGHT EVENLY TO THE WALL AND FLOOR AND TO PROVIDE A 1-INCH AIR SPACE BETWEEN WALL
AND CABINET. PAINT FRAMEWORK WITH TWO COATS OF GRAY ENAMEL AFTER FABRICATION.
7. FOR RECESSED PANELBOARDS, RUN ONE 3/4" CONDUIT FROM TOP OF PANEL 6" INTO CEILING SPACE FOR EVERY
SET OF 3 SPARE CIRCUIT BREAKERS OR SPACES.
8. PANELBOARD SHALL BE EQUAL TO SQUARE D TYPE NEHB, NQOD UNLESS OTHERWISE NOTED
J. FUSES
1. INSTALL FUSES IN FUSIBLE DEVICES AS INDICATED.
2. INSTALL TYPEWRITTEN LABELS ON THE INSIDE DOOR OF EACH FUSED SWITCH TO INDICATE FUSE REPLACEMENT
INFORMATION.
3. ALL FUSES SHALL BE CLASS RK-5 TIME DELAY TYPE, UNLESS OTHERWISE INDICATED.
4. SPARE FUSES: FURNISH QUANTITY EQUAL TO 20 PERCENT OF EACH FUSE TYPE AND SIZE INSTALLED, BUT NOT
LESS THAN 1 SET OF 3 OF EACH TYPE AND SIZE.
5. SPARE FUSE CABINET: WALL-MOUNTED, 18-GAUGE MINIMUM STEEL UNIT WITH FULL-LENGTH, RECESSED
PIANO-HINGED DOOR WITH KEY-CODED CAM LOCK AND PULL.
a. SIZE: ADEQUATE FOR ORDERLY STORAGE OF SPARE FUSES SPECIFIED WITH 15 PERCENT SPARE CAPACITY
MINIMUM.
b. FINISH: GRAY BAKED ENAMEL.
c. IDENTIFICATION: STENCIL LEGEND "SPARE FUSES" IN 1-1/2" (40 mm) LETTERS ON DOOR.
K. DISCONNECTS AND CIRCUIT BREAKERS
1. ENCLOSED NON-FUSIBLE SWITCH SHALL BE NEMA HEAVY-DUTY TYPE WITH ENCLOSURE CONSISTENT WITH
ENVIRONMENT WHERE LOCATED, HANDLE LOCKABLE WITH 2 PADLOCKS, AND INTERLOCKED WITH COVER IN
"CLOSED" POSITION.
2. ENCLOSED FUSIBLE SWITCHES SHALL BE NEMA HEAVY-DUTY TYPE WITH CLIPS TO ACCOMMODATE SPECIFIED
FUSES, ENCLOSURE CONSISTENT WITH ENVIRONMENT WHERE LOCATED, HANDLE LOCKABLE WITH 2 PADLOCKS
AND INTERLOCKED WITH COVER IN "CLOSED" POSITION. SWITCHES SHALL HAVE MINIMUM FAULT CURRENT
RATING OF 200,000 SYMMETRICAL RMS AMPERES.
A. GENERAL
1. THE CONTRACTOR SHALL COMPLY WITH ALL THE LAWS, ORDINANCES, RULES AND REGULATIONS OF ALL LOCAL AND STATE GOVERNMENTAL
AUTHORITIES, THE RULES OF THE NATIONAL FIRE PROTECTION ASSOCIATION AS INTERPRETED BY THE ENFORCING AUTHORITY HAVING
JURISDICTION AND OF THE PUBLIC UTILITIES HAVING CONNECTION WITH ANY OF THE SYSTEMS HEREIN SPECIFIED.
2. THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND INSPECTIONS REQUIRED BY ANY OF THE FOREGOING AUTHORITIES, AND
PAY FOR ALL OTHER COSTS IN CONNECTION WITH THE WORK. ALL CERTIFICATES SHALL BE IN DUPLICATE AND SHALL BE DELIVERED TO THE
OWNER.
3. THE SITE, LOCATION AND ROUTING OF SYSTEMS INDICATED TO HAVE NEW CONNECTIONS MADE TO THEM ARE SHOWN AS ACCURATELY AS
FIELD CONDITIONS WOULD PERMIT. BIDDERS SHALL VISIT THE SITE AND THOROUGHLY EXAMINE THE CONTRACT DRAWINGS. BIDDERS WHO
DO NOT VISIT THE SITE MAY BE UNILATERALLY NOT PERMITTED TO SUBMIT A BID IF THE OWNER SO DESIGNATES. ALL EXISTING CONDITIONS
SHALL BE EXAMINED AND THEIR EXACT LOCATIONS VERIFIED. THE CONTRACTOR SHALL REPORT TO THE ARCHITECT, ENGINEER AND OWNER
BEFORE SUBMITTING A BID, ANY CONDITIONS WHICH MIGHT MAKE INSTALLATION OF REQUIRED EQUIPMENT A PROBLEM. NO CONSIDERATION
OR ALLOWANCE WILL BE GRANTED FOR FAILURE TO INVESTIGATE CONDITIONS OR MISUNDERSTANDINGS OF THE CONTRACTUAL
REQUIREMENTS.
4. THE CONTRACTOR SHALL REMOVE ALL EQUIPMENT NOT INDICATED TO BE REUSED TO A DESIGNATED LOCATION AT THE PROJECT SITE.
AFTER THE EQUIPMENT HAS BEEN ASSEMBLED FOR THE OWNER'S INSPECTION AND POSSIBLE RETENTION, ALL EQUIPMENT NOT TO BE
RETAINED BY THE OWNER SHALL BE REMOVED FROM THE SITE BY THE CONTRACTOR. ALL BUILDING SYSTEMS SHALL REMAIN IN SERVICE
UNLESS INDICATED OTHERWISE. ALL OUTAGES OR INTERRUPTIONS SHALL BE KEPT TO MINIMUM DURATION. NOTIFY THE OWNER 48 HOURS
IN ADVANCE OF ANY OUTAGE OR INTERRUPTION.
5. THE CONTRACTOR SHALL INSTALL AND CONNECT ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH THE BEST ENGINEERING PRACTICE
AND, UNLESS OTHERWISE SHOWN OR SPECIFIED, FOLLOW THE MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS AND FURNISH
AND INSTALL ALL REQUIRED AUXILIARY ITEMS COMPLETE.
6. DRAWINGS SHALL BE CONSIDERED DIAGRAMMATIC AND FOR BIDDING PURPOSES ONLY. WHILE THE DRAWINGS ARE GENERALLY TO SCALE
AND ARE AS ACCURATE AS THE SCALE WILL PERMIT, ALL IMPORTANT DIMENSIONS SHALL BE DETERMINED IN THE FIELD.
7. COORDINATE WITH ALL TRADES TO AVOID INTERFERENCE AMONG MECHANICAL, ELECTRICAL, ARCHITECTURAL AND STRUCTURAL ITEMS.
PROVIDE ALL NECESSARY OFFSETS AND FITTINGS IN CIRCUITRY AND OTHER ITEMS REQUIRED TO INSTALL THE WORK WITHOUT
INTERFERENCES.
8. THE CONTRACTOR SHALL TEST ALL EQUIPMENT INSTALLED UNDER THIS CONTRACT AND DEMONSTRATE TO THE OWNER ITS PROPER
OPERATIONS. ALL NEW EQUIPMENT SHALL BE MOUNTED VIBRATION FREE.
9. ALL EQUIPMENT AND WORKMANSHIP SHALL BE GUARANTEED IN FULL FROM ALL DEFECTS FOR ONE (1) YEAR FROM THE DATE OF FINAL
ACCEPTANCE OF THIS WORK.
10. ALL EQUIPMENT INSTALLED SHALL BE NEW AND SHALL CONFORM IN ALL RESPECTS TO THE LATEST APPROVED STANDARDS OF IEEE, ANSI,
NEMA AND UNDERWRITERS LABORATORIES, INC., (UNLESS INDICATED OTHERWISE). SUBSTITUTIONS SHALL ONLY BE ACCOMPLISHED AT THE
DISCRETION OF THE ENGINEER. SHOP DRAWINGS ARE TO BE SUBMITTED AND APPROVED BEFORE THE EQUIPMENT IS ORDERED. SUBMIT
SIX (6) COPIES OF SHOP DRAWINGS TO THE ENGINEER OF THE FOLLOWING: LIGHTING FIXTURES, PANELBOARDS, TRANSFORMER,
DISCONNECT SWITCHES AND WIRING DEVICES.
11. THE CONTRACTOR SHALL REPAIR ALL WALL, CEILING, FLOOR, OR ROOF OPENINGS WHICH ARE CREATED BY DEMOLITION OR PENETRATION.
THE REPAIRS SHALL BE WITH MATERIALS AND FINISHES TO MATCH EXISTING. ALL FIRE RATED PENETRATIONS SHALL BE SEALED WITH
SUITABLE MATERIALS TO PRESERVE FIRE RATED INTEGRITY.
12. DEFINITIONS
a. "PROVIDE" UNDER THIS CONTRACT IS DEFINED AS FURNISH AND INSTALL.
b. "CONCEALED" UNDER THIS CONTRACT IS DEFINED AS HIDDEN BY ARCHITECTURAL WALLS AND CEILINGS.
c. "EXPOSED" UNDER THIS CONTRACT IS DEFINED AS VISIBLE TO VIEW.
d. "INDICATED" UNDER THIS CONTRACT IS DEFINED AS SHOWN IN THE CONTRACT DOCUMENTS.
13. UPON COMPLETION OF THE WORK, THE CONTRACTOR SHALL THOROUGHLY CLEAN THE CONTRACT AREA AND ALL OTHER AREAS USED FOR
STORAGE, STAGING, ETC.
14. THE CONTRACTOR SHALL NOTIFY THE OWNER WHEN THE PROJECT IS APPROXIMATELY 75% COMPLETED IN ORDER TO SCHEDULE A
PRE-FINAL REVIEW OF CONSTRUCTION. NO WORK SHALL BE CONCEALED BY CEILINGS, WALLS, ETC. FINAL REVIEW SHALL BE SCHEDULED AT
100% COMPLETION. ALL PUNCH LIST ITEMS MUST BE ACCOMPLISHED PRIOR TO FINAL ACCEPTANCE.
15. THE CONTRACTOR SHALL PREPARE A COMPREHENSIVE METHOD OF PROCEDURE AND SUBMIT IT TO THE OWNER WITH SHOP DRAWINGS FOR
REVIEW. THE SUBMITTAL SHALL ITEMIZE METHODS OF PROCEDURE FOR ALL POTENTIAL EMERGENCY SITUATIONS AND SHALL INCLUDE A
LIST OF PERSONS REPRESENTING THE OWNER AND THE CONTRACTOR ALONG WITH DAYTIME AND EMERGENCY PHONE NUMBERS AND
PAGER NUMBERS WHO SHALL BE CONTACTED IN THE EVENT OF AN EMERGENCY. THIS LIST SHALL BE DISTRIBUTED TO THE OWNER'S
REPRESENTATIVE AND THE CONTRACTORS SUPERINTENDENT OR FOREMAN AT THE SITE. EMERGENCY SITUATIONS SHALL INCLUDE BUT
NOT BE LIMITED TO POWER OUTAGES, CHILLED AND CONDENSER WATER SYSTEM RUPTURES, AUTOMATIC TEMPERATURE CONTROL
OUTAGES AND OWNER'S EQUIPMENT DAMAGE. THE COMPREHENSIVE METHOD OF PROCEDURE SHALL BE APPROVED BY THE OWNER PRIOR
TO COMMENCEMENT OF ANY WORK.
16. THE USE OF POWDER DRIVEN FASTENERS OR IMPACT TOOLS SHALL NOT BE PERMITTED.
17. ALL WORK SHALL BE PERFORMED DURING NORMAL WORKING HOURS MONDAY THROUGH FRIDAY - 7:00 A.M. TO 5:00 P.M. WORK PERFORMED
OUTSIDE OF NORMAL WORKING HOURS WILL BE REIMBURSED AT PREMIUM RATES AND SHALL BE NEGOTIATED WITH THE OWNER PRIOR TO
THE CONSTRUCTION PHASE.
18. PROVIDE TEMPORARY SERVICE FOR LIGHTING AND POWER EQUIPMENT (DRILLS, SAW, ETC.). VERIFY TEMPORARY REQUIREMENTS WITH
GENERAL CONTRACTOR. TEMPORARY LIGHTING AND POWER SHALL MEET OSHA REQUIREMENTS AND LOCAL CODE. TEMPORARY POWER
SHALL BE 120 VOLTS.
19. UNLESS SPECIFICALLY NOTED ON THE DEMOLITION PLANS, REMOVE ALL LIGHTING, SWITCHES, RECEPTACLES AND CLOCK OUTLETS AND
ASSOCIATED CIRCUITRY INDICATED. CIRCUITRY TO BE REMOVED SHALL BE ALL CONDUCTORS AND ANY EXPOSED RACEWAYS INCLUDING
WIREMOLD AND ALL RACEWAY THAT BECOMES EXPOSED UPON REMOVAL OF WALLS AND CEILINGS. NOT ALL DEVICES TO BE REMOVED ARE
SHOWN ON PLANS.
20. UNLESS SPECIFICALLY NOTED ON THE PLANS, ALL CIRCUITRY, EQUIPMENT, DEVICES, ETC., NOT NOTED AS EXISTING TO REMAIN OR TO BE
RELOCATED, SHALL BE NEW. THE CONTRACTOR MAY REUSE ALL EXISTING CIRCUITRY AS FIELD CONDITIONS PERMIT. REMOVE ALL DEVICES
AND CIRCUITRY NOT BEING REUSED. CIRCUITRY TO BE REMOVED SHALL BE REMOVED BACK TO THE SOURCE AND ALL HOLES SHALL BE
REPAIRED TO CONFORM TO FINISHED SURFACE. ALL CIRCUITS THAT ARE TO REMAIN IN SERVICE UPON COMPLETION OF THIS PROJECT
WHICH ARE COORDINATED WITH THE OWNER.
21. PROTECT ADJACENT MATERIALS INDICATED TO REMAIN. INSTALL AND MAINTAIN DUST AND NOISE BARRIERS TO KEEP DIRT, DUST, AND NOISE
FROM BEING TRANSMITTED TO ADJACENT AREAS. REMOVE PROTECTION AND BARRIERS AFTER DEMOLITION OPERATIONS ARE COMPLETE.
22. LOCATE, IDENTIFY AND PROTECT ELECTRICAL SERVICES PASSING THROUGH DEMOLITION AREA AND SERVING OTHER AREAS OUTSIDE THE
DEMOLITION LIMITS. MAINTAIN SERVICES TO AREAS OUTSIDE DEMOLITION LIMITS. WHEN SERVICES MUST BE INTERRUPTED, INSTALL
TEMPORARY SERVICES FOR AFFECTED AREAS.
23. FINAL TESTING: AT THE TIME OF FINAL INSPECTION AND TESTS, ALL CONNECTIONS AT PANELBOARDS, DEVICES AND EQUIPMENT AND ALL
SPLICES MUST BE COMPLETED. EACH BRANCH CIRCUIT AND ITS RESPECTIVE CONNECTED EQUIPMENT MUST TEST FREE OF SHORT
CIRCUITS. UPON COMPLETION OF THE WORK, CLEAN AND POLISH ALL EXPOSED SURFACES IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
B. RACEWAYS, BOXES, AND CONDUITS
1. OUTDOORS WIRING METHODS: USE THE FOLLOWING WIRING METHODS:
a. EXPOSED: RIGID OR INTERMEDIATE METAL CONDUIT.
b. CONCEALED: RIGID OR INTERMEDIATE METAL CONDUIT.
c. UNDERGROUND: RIGID NONMETALLIC CONDUIT (PVC SCHEDULE 40), UNLESS OTHERWISE NOTED.
d. CONNECTION TO VIBRATING EQUIPMENT: LIQUIDTIGHT FLEXIBLE METAL CONDUIT.
e. BOXES AND ENCLOSURES: NEMA TYPE 3R.
2. INDOORS WIRING METHODS: USE THE FOLLOWING METHODS:
a. CONNECTION TO VIBRATING EQUIPMENT: FLEXIBLE METAL CONDUIT, EXCEPT IN WET OR DAMP LOCATIONS USE LIQUIDTIGHT FLEXIBLE
METAL CONDUIT.
b. DAMP OR WET LOCATIONS: RIGID STEEL CONDUIT.
c. EXPOSED: ELECTRICAL METALLIC TUBING.
d. CONCEALED: ELECTRICAL METALLIC TUBING OR, AS APPROVED BY ENGINEER, MC TYPE ARMORED CABLE.
e. BOXES AND ENCLOSURES: NEMA TYPE 1, EXCEPT IN DAMP OR WET LOCATIONS AND KITCHENS USE NEMA TYPE STAINLESS STEEL.
3. ALL CIRCUITRY IN FINISHED AREAS SHALL BE RUN CONCEALED. MINIMUM SIZE CONDUIT SHALL BE 3/4".
4. EMT CONNECTORS AND COUPLINGS SHALL BE OF THE ALL-STEEL, COMPRESSION TYPE WITH INSULATED THROAT.
5. EXPOSED AND CONCEALED CIRCUITRY (WHETHER CONDUIT AND WIRE OR CABLE) SHALL BE RUN TIGHT TO CEILING SLAB (AS HIGH AS
POSSIBLE TO MAXIMIZE HEADROOM) IN A NEAT, WORKMANLIKE MANNER. ALL RUNS SHALL BE PARALLEL OR PERPENDICULAR TO BUILDING
WALLS.
6. ALL CIRCUITRY RUNS INDICATED ARE DIAGRAMMATIC. THE CONTRACTOR SHALL DETERMINE IN THE FIELD THE MOST SUITABLE ROUTES.
7. ALL EMPTY RACEWAYS SHALL CONTAIN A DRAG WIRE. EMPTY RACEWAYS 2" OR LARGER IN SIZE SHALL HAVE A MAXIMUM OF 3 - 90 DEGREE
BENDS. PROVIDE 3/4" EMT FROM EACH TELEPHONE OR COMMUNICATIONS OUTLET DEVICE TO CEILING SPACE FOR ALL INSULATED WALLS.
8. GROUND ACCESS RAISED FLOOR SYSTEM WITH #4 CONDUCTOR TO BUILDING STEEL OR BUILDING GROUNDING SYSTEM PER
MANUFACTURER'S REQUIREMENT. MINIMUM 1 LOCATION PER 1000 SQUARE FEET. TIE ALL GROUNDS TOGETHER.
9. UNDER COMPUTER FLOOR SEPARATE BRANCH CIRCUIT AND POWER FEEDS A MINIMUM OF 6" FROM COMMUNICATION OR COMPUTER CABLE
10. EXPOSED LOW VOLTAGE WIRING SHALL BE INSTALLED IN A RACEWAY, UNLESS OTHERWISE NOTED.
11. OUTLET BOXES SHALL BE A MINIMUM OF 4" SQUARE WITH THE APPROPRIATE PLASTER RING OR TILE COVER.
12. ALL CONDUIT FOR FEEDERS, AND WHERE INSTALLED FOR UNDERGROUND SERVICE ENTRANCE CONDUCTORS, AT THE EXTERIOR OF THE BUILDING SHALL
COMPLY WITH NEC 358.10 (C)FOR CORROSION PROTECTION. CONDUIT SHALL BE SEALED WHERE IT ENTERS THE BUILDING OR ENTERS REFRIGERATED
SPACES PER NEC 300.7. CIRCUIT CONDUCTORS SHALL BE SUITABLE FOR INSTALLATION IN WET LOCATION PER NEC 300.9.
C. WIRE AND CABLE
1. ALL CONDUCTORS SHALL BE COPPER, MINIMUM #12 (EXCEPT CONTROL CONDUCTORS AND LIGHTING TAPS AS PERMITTED BY NEC.
CONDUCTORS FOR SWITCHING LIGHTS SHALL NOT BE CONSIDERED CONTROL CONDUCTORS), WITH 600 VOLT TYPE "THHN-THWN"
INSULATION. CONDUCTORS #10 AND LARGER SHALL BE STRANDED.
3. LOCATE DISCONNECT SWITCH (AND MOTOR CONTROLLER) FOR MECHANICAL EQUIPMENT TO PERMIT SERVICING
OF EQUIPMENT. CHECK MOTORS FOR PROPER ROTATION. CONNECT CONDUCTORS AS REQUIRED BY
MANUFACTURER.
4. ENCLOSED MOLDED-CASE CIRCUIT BREAKER: FRAME SIZE, TRIP RATING, NUMBER OF POLES, AND AUXILIARY
DEVICES AS INDICATED; INTERRUPTING CAPACITY RATING TO MEET AVAILABLE FAULT CURRENT, 10,000
SYMMETRICAL RMS AMPERES MINIMUM; WITH APPROPRIATE APPLICATION LISTING WHEN USED FOR SWITCHING
FLUORESCENT LIGHTING LOADS OR HEATING, AIR CONDITIONING, AND REFRIGERATION EQUIPMENT.
5. ENCLOSURE: NEMA TYPE 1, UNLESS SPECIFIED OR REQUIRED OTHERWISE TO MEET ENVIRONMENTAL
CONDITIONS OF INSTALLED LOCATION.
a. OUTDOOR LOCATIONS: TYPE 12/3R.
b. KITCHEN AREAS: TYPE 4X, STAINLESS STEEL.
c. OTHER WET OR DAMP INDOOR LOCATIONS: TYPE 4.
d. HAZARDOUS AREAS INDICATED ON DRAWINGS: NEMA 7C.
6. PROPERLY SUPPORT DISCONNECT OR ENCLOSED CIRCUIT BREAKER ON WALL WITH METAL FRAMING AS
REQUIRED.
7. PROVIDE FUSES IF REQUIRED BY MANUFACTURER OF EQUIPMENT FOR UL APPROVAL OR HACR CIRCUIT
BREAKERS.
L. MOTOR CONTROLLERS
1. MOTOR CONTROLLER FEATURES: PROVIDE CONTROLLERS CONSISTENT WITH THE RATINGS AND
CHARACTERISTICS OF THE SUPPLY CIRCUIT, THE MOTOR, THE REQUIRED CONTROL SEQUENCE, THE DUTY
CYCLE OF THE MOTOR, DRIVE, AND LOAD, AND THE PILOT DEVICE, AND CONTROL CIRCUIT AFFECTING
CONTROLLER FUNCTIONS. CONTROLLERS SHALL BE HORSEPOWER RATED TO SUIT THE MOTOR CONTROLLED.
a. CONTACTS SHALL OPEN EACH UNGROUNDED CONNECTION TO THE MOTOR.
b. OVERLOAD RELAYS: FOR MOTORS 1/3 HP OR LARGER, PROVIDE IN EACH PHASE AMBIENT COMPENSATED
TYPE WITH INVERSE TIME-CURRENT CHARACTERISTIC, WITH HEATERS OR SENSORS IN EACH PHASE
MATCHED TO NAMEPLATE FULL-LOAD CURRENT OF THE SPECIFIC MOTOR TO WHICH CONNECTED, WITH
APPROPRIATE ADJUSTMENT FOR DUTY CYCLE.
c. ENCLOSURES FOR INDIVIDUALLY MOUNTED MOTOR CONTROLLERS AND CONTROL DEVICES: SUITABLE FOR
THE ENVIRONMENTAL CONDITIONS AT THE CONTROLLER LOCATION.
2. MANUAL MOTOR CONTROLLERS: QUICK-MAKE, QUICK-BREAK TOGGLE ACTION WITH RED PILOT LIGHT AND
HANDLE GUARD/LOCK OFF.
3. MAGNETIC MOTOR CONTROLLERS: PROVIDE FULL-VOLTAGE, NONREVERSING, ACROSS-THE-LINE, MAGNETIC
CONTROLLER, EXCEPT WHERE ANOTHER TYPE IS INDICATED. CONTROLLERS TO BE EQUIPPED WITH 2 N.O. AND
2 N.C. AUXILIARY CONTACTS, HAND-OFF-AUTO SELECTOR SWITCH, RED AND GREEN PILOT LIGHTS.
a. CONTROL CIRCUIT: MAXIMUM 120V CONTROL POWER. PROVIDE TRANSFORMER CONSISTENT WITH CONTROL
CONTRACTOR VOLTAGE AND SIZE REQUIREMENTS. PROVIDE CONTROL POWER TRANSFORMER WITH
ADEQUATE CAPACITY TO OPERATE CONNECTED PILOT, INDICATING AND CONTROL DEVICES, PLUS 100
PERCENT SPARE CAPACITY.
b. COMBINATION CONTROLLER: SWITCH TYPE; FUSED OR NONFUSED AS INDICATED; QUICK-MAKE,
QUICK-BREAK SWITCH FACTORY ASSEMBLED WITH CONTROLLER AND ARRANGED TO DISCONNECT IT. FOR
FUSED SWITCHES, PROVIDE REJECTION-TYPE FUSE CLIPS AND FUSES RATED AS INDICATED. INTERLOCK
SWITCH WITH UNIT COVER OR DOOR.
M. LIGHTING
1. COORDINATE RECESSED LIGHTING FIXTURES WITH MECHANICAL EQUIPMENT AND ARCHITECTURAL CEILING
PLAN. GRID LAYOUT ON PLANS IS APPROXIMATE. ADJUST LIGHTING FIXTURES IN FIELD PER ARCHITECT.
2. PROVIDE FINISHING FRAMES FOR ALL RECESSED LIGHTING FIXTURES, TYPE TO BE COMPATIBLE WITH CEILING.
COORDINATE ALL FIXTURE TYPES WITH CEILING SYSTEM BEFORE ORDERING FIXTURES. PROVIDE ALL
MOUNTING ATTACHMENTS FOR A COMPLETE INSTALLATION.
3. ALL NEW LIGHTING FIXTURES SHALL BE INSTALLED COMPLETE WITH LAMPS. SEE PLANS FOR SPECIFIC
REQUIREMENTS. RELAMP ALL EXISTING LIGHTING FIXTURES PER PLANS.
4. 2' X 2' FLUORESCENT FIXTURES IN ANY ROOM OR COMMON AREA SHALL HAVE ALL LAMPS ORIENTED IN THE
SAME DIRECTION.
5. COORDINATE LOW VOLTAGE DIMMERS WITH ELECTRONIC OR MAGNETIC LOW VOLTAGE LIGHTING PER
MANUFACTURER OF LIGHTING FIXTURES.
6. IN LOCATIONS WHERE NEW DUCTWORK OR CEILING IS INSTALLED UNDER THIS CONTRACT BUT LIGHTING
FIXTURES HAVE NOT BEEN REVISED, REMOVE EXISTING FIXTURES AS NECESSARY TO RUN THE NEW DUCTWORK
OR CEILING AND RE-HANG AFTER THE MECHANICAL OR ARCHITECTURAL WORK IS COMPLETED.
7. COLOR LIGHTING FIXTURES SHALL BE AS SELECTED BY THE ARCHITECT.
8. THE EXACT LOCATION OF LIGHTING FIXTURES IN MECHANICAL ROOM SHALL BE COORDINATED WITH THE
MECHANICAL EQUIPMENT TO PROVIDE LIGHT OVER SERVICE AREAS.
9. IF EXISTING LAMP BALLASTS ARE REPLACED, PROVIDE DISCONNECT FOR EXISTING FLUORESCENT FIXTURES TO
COMPLY WITH NEC 410.130(G)
N. EQUIPMENT CONNECTION
1. EXTEND WIRING TO ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS AND MAKE FINAL AND COMPLETE
CONNECTIONS TO ALL EQUIPMENT. BEFORE ROUGHING IN, THE LOCATION AND TYPE OF DEVICE SHALL BE
VERIFIED FROM SHOP DRAWINGS OF THE EQUIPMENT. STARTERS AND DISCONNECTS AND OTHER ELECTRICAL
CIRCUITRY AND DEVICES SHALL BE LOCATED TO ALLOW ACCESS TO DEVICES AND NOT INTERFERE WITH THE
OPERATION OF THE MECHANICAL OR ARCHITECTURAL DEVICES OR THEIR POSSIBLE MAINTENANCE OR
REMOVAL.
FIRE ALARM ANNUNCIATOR PANEL
FLA
HP
GFI
HOA
(ER)
FA
FACP
FAAP
EMER
ELEC
(E)
FULL LOAD AMPS
GROUND FAULT INTERRUPTER
HANDS OFF AUTOMATIC
HORSEPOWER
GROUND
EXISTING TO REMAIN
EQUIPMENT TO BE RELOCATED
FIRE ALARM CONTROL PANEL
FIRE ALARM
EMERGENCY
ELECTRIC
AFF
CKT
CT
CLG
C
AWG
CB
A
AIC
ABOVE FINISHED FLOOR
CURRENT TRANSFORMER
AMERICAN WIRE GAGE
CIRCUIT BREAKERS
CIRCUIT
CEILING
CONDUIT
AMPS INTERRUPTING CAPACITY
AMPS
KILOVOLT AMPERE
MAIN CIRCUIT BREAKER
MAIN LUGS ONLY
MAIN DISTRIBUTION PANEL
LIGHTING LTG
MLO
MCB
MIN
MDP
MINIMUM
KVA
KW KILOWATTS
NOTE: ALL SYMBOLS LISTED MAY NOT APPEAR ON THE DRAWINGS
DIVISION 26 - ELECTRICAL SYMBOLS
DIVISION 26 - ELECTRICAL ABBREVIATIONS
G
4'-0"
4'-0"
4'-0"
4'-0"
4'-0"
4'-0"
WIRING DEVICES
THREE WAY SWITCH
SINGLE POLE SWITCH
FOUR WAY SWITCH
DIMMER SWITCH
MANUAL MOTOR STARTER SWITCH WITH THERMAL OVERLOAD PROTECTION
SINGLE POLE SWITCH - LOWERCASE SUBSCRIPT INDICATES ITEM CONTROLLED
COORDINATE
IN FIELD
1'-6"
1'-6"
1'-6" UONDUPLEX RECEPTACLE - NEMA 5-20R
PROTECTION
OCCUPANCY SENSOR SWITCH
TWO DUPLEX RECEPTACLE - NEMA 5-20R
DUPLEX RECEPTACLE NEMA 5-20R WITH INTEGRAL GROUND FAULT
CEILING MOUNTED RECEPTACLE - NEMA 5-20R
30
SM
SOC
SD
S3
S4
Sa
S
NON-FUSED SAFETY DISCONNECT SWITCH - NUMERAL DENOTES SWITCH SIZE - 3 POLE, UON
TRANSFORMERT
SWITCH SIZE, LOWER NUMERAL DENOTES FUSE SIZE - 3 POLE, UON
FUSED SAFETY DISCONNECT SWITCH - UPPER NUMERAL DENOTES
EQUIPMENT
CB
MOTOR CONNECTION
PANELBOARD, BRANCH
COMBINATION MOTOR STARTER DISCONNECT W/ HOA SWITCH AND PILOT LIGHT
JUNCTION BOX
ENCLOSED CIRCUIT BREAKER
PANELBOARD, DISTRIBUTION
30/15
30/15
4'-0"
LP-10,12
HOMERUN TO PANELBOARD. NUMERALS AND LETTERS ADJACENT TO ARROW HEAD(S)
INDICATE ASSIGNED PANEL AND CIRCUIT(S) NUMBERS(S). SEE PANEL SCHEDULE(S) FOR
CIRCUIT WIRE AND CONDUIT SIZES/QUANTITIES.
NUMERAL SUBSCRIPT INDICATES CANDELA POWER
COMBINATION FIRE ALARM AUDIO/VISUAL APPLIANCE - CEILING MOUNTED UON,
INDICATES CANDELA POWER.
FIRE ALARM VISUAL APPLIANCE - CEILING MOUNTED UON, NUMERAL SUBSCRIPT
FIRE ALARM
FIRE ALARM MANUAL STATION
FIRE ALARM AUDIO ALARM - CEILING MOUNTED UON.
FIRE ALARM CONTROL PANEL (FACP)
SMOKE DETECTOR - CEILING MOUNTED UON
FIRE ALARM SPEAKER - CEILING MOUNTED UON
FIRE ALARM ANNUNCIATOR PANEL (FAAP)
HEAT DETECTOR - CEILING MOUNTED UON
V
AV
A
15
FACP
SP
15
FAAP
EXISTING TO REMAIN
EXISTING TO BE REMOVED
PLAN REFERENCE NOTE SYMBOL
NEW WORK
PLAN SYMBOLS
X
NOT TO SCALE
RELOCATED EQUIPMENT
WEATHERPROOF
UNLESS OTHERWISE NOTED
WP
W
V
UON
WATTS
VOLTS
T
SW
TELE
TYP
NTS
(R)
PBO
TRANSFORMER
SWITCH
TELEPHONE
TYPICAL
PROVIDED BY OTHERS
NATIONAL ELECTRIC CODENEC
(N) NEW
PH PHASE
DATA/TELEPHONE OUTLET
BRANCH CIRCUIT WIRING NOTES
CIRCUIT #
DESIGNATION
PANEL
HP-4
1. WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES OR SPECIAL CONDITIONS.
2. PROVIDE WIRING AND CONDUIT BETWEEN ALL OUTLETS/FIXTURES INDICATED WITH CIRCUIT NUMBERS
AND PANEL DESIGNATIONS.
3. ALL SWITCH CONTROLS SHALL BE PROVIDED WITH WIRING AND CONDUIT AS REQUIRED.
4. ALTHOUGH ALL BRANCH CIRCUIT WIRING AND CONDUIT IS NOT SHOWN, IT IS THE INTENT OF THESE
DOCUMENTS THAT A COMPLETE BRANCH CIRCUIT WIRING SYSTEM BE INSTALLED.
5. BRANCH CIRCUIT WIRING IS INDICATED ON THE DRAWINGS IN ACCORDANCE FOR BOTH LIGHTING AND
POWER.
6. LIGHT SWITCH CONTROLS LIGHTS IN THE SAME ROOM UON.
X
(X) REMOVE
G
66"
TV OUTLET - STUB 3/4" C 6" INTO CEILING SPACE - UON
1'-6"
1'-6"
CEILING MOUNTED OCCUPANCY SENSOR
CARD READER - STUB 3/4" C 6" INTO CEILING SPACE
4'-0"
PROVIDE A LABEL FOR EACH RECEPTACLE TO INDICATE
PANEL AND CIRCUIT BREAKER NO. SUPPLYING THE DEVICE.
PROVIDE PRESSURE SENSITIVE, LABEL WITH BLACK
LETTERING ON CLEAR BACKGROUND. LETTERING HEIGHT
IS 1/8".
1/8"RP-3
RECEPTACLE LABELING DETAIL
FAIR
FAX
CO
UN
TY
PU
BLI
C S
CH
OO
LS
![Page 8: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/8.jpg)
FAIR
FAX
CO
UN
TY
PU
BLI
C S
CH
OO
LS
![Page 9: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/9.jpg)
FAIR
FAX
CO
UN
TY
PU
BLI
C S
CH
OO
LS
![Page 10: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/10.jpg)
TEACHING WALL POWER COLUMN 1NO SCALE
NOTES:
1. THIS CONTRACTOR SHALL COORDINATE INSTALLATION WITH MARKERBOARDINSTALLATION.
2. LIGHTING CONTROL SIX BUTTON DIGITAL SWITCH NOT TYPICAL FOR ALL POWER POWERCOLUMN NO. 1 INSTALLATIONS. REFER TO FLOOR PLANS FOR EXACT LOCATIONS.
FINISHED FLOOR
CEILING
33"
NOTE NO. 1 - CATV, DATA AND MULTI-MEDIA OUTLET CONSISTING OF WIREMOLD/ORTRONICS MODEL NO'S:· TWO (2) V4050 DEVICE PLATES.· ONE (1) V4047C-1 DEVICE PLATE.· ONE (1) OR-TJ600-00 (CAT. 6) T568A/B TRACKJACK INSERTS WITH OR-40300200 FOR DATA.· ONE (1) OR-TJ600 (CAT. 6) T568A/B TRACKJACK INSERTS WITH OR-40309100 FOR VOICE.· ONE (1) OR-63700006 SINGLE "F" CONNECTOR TRACKJACK INSERT.· ONE (1) 5507-4TJ DATACOM INSERT.· ONE (1) OR-42100002 BLANK TRACKJACK INSERT.· ONE (1) 5507D DUPLEX RECEPTACLE FACEPLATE MODULE.· ONE (1) 5507R RECTANGLAR RECEPTACLE FACEPLATE MODULE.· ONE (1) NEMA 5-20R DUPLEX RECEPTACLE.· ONE (1) NEMA 5-20R DUPLEX RECEPTACLE WITH 2-USB CHARGING PORTS.· ONE (1) MULTI-MEDIA OUTLET WITH A SINGLE GANG ALUMINUM FACEPLATES.· TWO (2) C5507S RECTANGULAR SPACING MODULE.· ONE (1) 5507B BLANK FACEPLATE MODULE
NOTE NO. 4 - DIMMER SWITCH CONSISTING OF WIREMOLD/ORTRONICS CO. MODEL NO.'S:· ONE (1) V4047C-1 DEVICE PLATE.· ONE (1) DIMMER SWITCH (MARKERBOARD LIGHTING).
NOTE NO. 3 - DUPLEX/DATA ONLY OUTLET CONSISTING OF WIREMOLD/ORTRONICS MODEL NO'S:· ONE (1) V4050 DEVICE PLATES.· TWO (2) OR-TJ600-00 (CAT. 6) T568A/B TRACKJACK INSERTS WITH OR-40300200 FOR DATA.· TWO (2) OR-42100002 BLANK TRACKJACK INSERTS.· ONE (1) 5507-4TJ DATACOM INSERT.· ONE (1) 5507D DUPLEX RECEPTACLE FACEPLATE MODULE.· ONE (1) NEMA 5-20R DUPLEX RECEPTACLE.
NOTE NO. 2 - CALL BACK SWITCH CONSISTING OF WIREMOLD/ORTRONICS CO. MODEL NO.'S:· ONE (1) V4047C-1 DEVICE PLATE.· ONE (1) CALL BACK SWITCH WITH SINGLE GANG STAINLESS STEEL FACEPLATE.
WIREMOLD CAT. NO. V4000 BASE,COVER AND DIVIDER
1 1/4" BUSHED OPENING
WIREMOLD CAT. NO. 4010DFOENTRANCE END FITTING
WIREMOLD CAT. NO. V4010BBLANK END FITTING15"
MARKERBOARD LIGHTINGDIMMMER SWITCH (SD).SEE NOTE NO. 4.
CATV/TELECOMMUNICATIONS/MULTI-MEDIA OUTLET.SEE NOTE NO. 1.
DUPLEX/DATA ONLY OUTLET.SEE NOTE NO. 3. CENTERUNDER MARKERBOARD.
WIREMOLD CAT. NO.V4011FO FLAT ELBOW
CALLBACK SWITCH.SEE NOTE NO. 2.
BRANCH CIRCUIT RACEWAY -REFER TO FLOOR PLANS FOR
CONTINUATION (TYPICAL)
WHEN A DIGITAL SWITCH ISINSTALLED REVERSE THE
MOUNTING AND INSTALL INTHE LOW VOLTAGE SIDE OF
THE V4000
FAIR
FAX
CO
UN
TY
PU
BLI
C S
CH
OO
LS
![Page 11: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/11.jpg)
FAIR
FAX
CO
UN
TY
PU
BLI
C S
CH
OO
LS
![Page 12: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/12.jpg)
![Page 13: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/13.jpg)
![Page 14: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/14.jpg)
![Page 15: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/15.jpg)
![Page 16: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/16.jpg)
![Page 17: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/17.jpg)
![Page 18: · division 26 - electrical specifications 2. where approved by the authorities having jurisdiction and engineer, "mc" cable may be utilized for interior branch circuits.](https://reader033.fdocuments.in/reader033/viewer/2022042021/5e77f82c2c77c8274742dadf/html5/thumbnails/18.jpg)