Disturbance Recorder_Standardisation of Channels
-
Upload
brijendra-singh -
Category
Documents
-
view
216 -
download
2
description
Transcript of Disturbance Recorder_Standardisation of Channels
Standardization of the signals for the disturbance recordersThe numerical relays now come with 32 Digital Channels in DR.Sl NoAnalog SignalDigital SignalRemark
1R-Phase CurrentR-Phase Main CB Open
2Y-Phase CurrentY-Phase Main CB Open
3B-Phase CurrentB-Phase Main CB Open
4Neutral CurrentR-Phase Tie CB OpenFor One and Half Bus
5R-Phase VoltageY-Phase Tie CB OpenFor One and Half Bus
6Y-Phase VoltageB-Phase Tie CB OpenFor One and Half Bus
7B-Phase VoltageZ1 Start
8Neutral VoltageMain-I /II Carrier Received
9Z2 Start
10T2
11Z3 Start
12T3
13Z4 Start
14T4
15Distance Trip
16Stub Enable
17SOTF Trip
18DEF Start
19DEF Trip
20DT received Channel I/II
21Bus Bar Protection TripShall ensure that the currents of all the feeders is recorded in case of Bus Bar Tripping
22Line Reactor protection tripTo get the disturbance record for a reactor tripping
23Over Voltage Stage-I startShall be helpful to verify the cases of OV tripping.
24Over Voltage Stage-I Trip
25Over Voltage Stage-II Start
26Over Voltage Stage-II Trip
27LBB Initiation R-phaseShall be instrumental in analyzing bus-bar maltrippings
28LBB Initiation Y-phase
29LBB Initiation B-phase
30Main Bay LBB operated
31Tie Bay LBB operated
32Main-I Trip