TILLAMOOK PEOPLE’S UTILITY DISTRICT DISTRIBUTION FEEDER FAULT ANALYSIS

Transcript of DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at...

Page 1: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

T I L L A M O O K P E O P L E ’ S U T I L I T Y D I S T R I C T

DISTRIBUTION FEEDER FAULT ANALYSIS

Page 2: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

SCADA TO DG SITES

Page 3: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

DIGESTER MW AND MVAR

Page 4: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

INSTANTANEOUS READINGSFROM SEL 751 RELAY

Page 5: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

TRASK SUBSTATION LOADINGDO NOT WANT TO FEED INTO 115 KV

Page 6: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

FAULT LOCATOR TOOL DEVELOPED BY GIS SPECIALIST

Page 7: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

CAR HIT POLE EVENT ANALYSIS

W I L S O N R I V E R S U B S T A T I O N E V E N T O N 9 - 2 - 1 3

Page 8: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

WILSON RIVER SUBSTATION, CIRCUIT 63

Car Pole Accident

Olsen Rd.Recloser

Misty MeadowsGeneration

Page 9: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

SCADA ALARMS DURING EVENTNOTE: DEVICE TIMES ARE NOT

SYNCHED

DG on adjacent circTripped Open

Olsen Rd. RecloserOperations

Ckt 63 RecloserLocks Out

Page 10: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

SOE FROM SUBSTATION RECLOSER

Page 11: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

OLSEN RD. RECLOSER OPERATIONS

Page 12: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

NEXUS 1500 METER ON SUBSTATION BUS

Page 13: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

A PHASE CURRENT – 2 OPERATIONS OF RECLOSER

Page 14: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

3RD INTERRUPTION – MUCH HIGHER FAULT CURRENT

Page 15: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

SEL 751 AT MISTY MEADOWS GENERATION 480 VOLT BUS

Page 16: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

MAX FLT I = 3078 AMPS AT ACCIDENT SITE

Page 17: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

SO HOW DID WE GET 4178 AMPS ON THE CIRCUIT 63 SEQUENCE OF EVENTS FILE?

Page 18: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

SYNERGI PREDICTS A FAULT OF THIS MAGNITUDE SHOULD BE CLOSER IN TO

THE SUBSTATION

Page 19: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

THIS IS SECTION OF LINE THAT SYNERGIPREDICTED THE FAULT SHOULD BE IN

Page 20: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

A SHARP EYED OPS SUPV. FOUND BURN MARKS IN THIS VICINITY. LONG SPANS

DUE TO 115 KV UNDERBUILD

Page 21: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

ELBOW FAILURE ON UG

Page 22: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

SCADA ALARM AT 17:10 INDICATES FAULT ON NESTUCCA FEEDER 39

Page 23: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

FIRST STEP IS TO CONNECT TO FORM 6 RELAY OVER ETHERNET – SEQ COORD. MEANS ANOTHER DEVICE OPERATED

Page 24: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

OSCILLOGRAPHIC FILE FROM THE FORM 6 RELAY – PEAK CURRENT =1737 A

1737 X .707=1228 A RMS

Page 25: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

FAULT LOCATION TOOL THAT GIS SPECIALIST MADE – FLT I FROM SYNERGI PROTECTION STUDY

Page 26: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

FAULT WAS ON SINGLE PHASE UG IN SUBDIVISION – ELBOW FAILED

Page 27: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

EXTENT OF FEEDERPOSSIBLE LOCATIONS ON MULTIPLE BRANCHES

Page 28: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

FIRST RAIN AFTER DRY SUMMER

T I LLAMOOK PEOPLE’S UT I L I TY D ISTR ICT

Page 29: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

FIRST INDICATION OF PROBLEMSCADA SHOWS FAULT ON CKT. 64

Page 30: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

NEXUS 1500 ON SUB BUS

Page 31: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

ZOOM IN ON PHASE A AND B CURRENTS

Page 32: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

THE 3 PHASE CURRENTS ON CIRCUIT 64

Page 33: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

COMPARE WAVEFORMS TO FORM 62ND PHASE GETS INVOLVED

Page 34: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

OUTAGE REPORT SHOWS INSULATOR FLASHED OVER

Page 35: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

PROBLEMS AT TCCA BOILERTCCA=T I LLAMOOK CHEESE FACTORY

Page 36: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

FORM 6 OSCILLOGRAPHPEAK CURRENT = 3820 AMPSRMS CURRENT = 2700 AMPS

Page 37: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

NEXUS 1500 ON SUB BUS

Page 38: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

NEXUS FAULT CURRENT IS CLOSE TO FORM 6 VALUE = 3900A X .707=2757 A,

NOTE DROP IN LOAD

Page 39: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

FROM SYNERGI, FAULT CURRENT AT BOILER MATCHES MEASURED FAULT I

Page 40: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

FAULT LOCATOR TOOL PRETTY CLOSE

Page 41: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

TREE THROUGH LINEMOHLER CIRCUIT 91

Page 42: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

RECLOSER AT SUB SHOWS 428 A FAULT CURRENT ON C PHASE

Page 43: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

OSCILLOGRAPH FROM FORM 6 SHOWS FOUR CYCLES OF FAULT CURRENT

4 CYCLES = .066 SEC.

Page 44: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

FAULT BLEW A 15 A FUSE AT FISH HATCHERY

Page 45: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

TCC CURVE SHOWS THAT 15 A FUSE SHOULD BLOW IN .06 SEC. AT 425 AMPS

Page 46: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

FAULT LOCATOR TOOL TURNED OUT TO BE FAIRLY ACCURATE

Fuse Blew Here

Tree throughLine Here

Page 47: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

SYNERGI PREDICTS 411 AMPS FAULT CURRENT AT THIS LOCATION

Page 48: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

F A U L T E V E N T O N 1 1 - 9 - 1 5

STARLING BRINGS DOWN BLUE HERON

Page 49: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

TUESDAY MORNING AT 8:20 AM

• Public Relations called Operations to find out if a breaker operated at Wilson River Substation• The Mill in town called to report a power dip

• SCADA showed that Circuit 61 had operated and Circuit 62 (Mill Feeder) saw current above Min Trip

Page 50: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

ENGINEERING CONNECTED TO FORM 6 RECLOSER CONTROLS AT SUBSTATION VIA ETHERNET

• The Sequence of Events report from Ckt 61showed that the recloser tripped on Overcurrent, then reclosed and reset

Page 51: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

ALSO DOWNLOADED OSCILLGRAPHYFILES FROM THE RECLOSERS

• Confirmed fault on Ckt 62

Page 52: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

CONTINUATION OF WAVEFORM ON PRIOR SLIDE

• Note that second phase gets involved in fault in the last couple cycles before interruption

Page 53: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

AFTER THE RECLOSER RECLOSED THE TRANSFORMER MAGNETIZING CURRENT WAS PRESENT

• After a few cycles, the magnetizing current decayed to below the minimum pickup value

Page 54: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

NEXUS 1500 METER MONITORING THE TRANSFORMER BUS GIVES A BETTER PICTURE OF THE EVENT

• Note that 2nd phase gets involved before breaker opens. And transformer inrush currents can be seen

Page 55: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

ZOOMING IN TO PHASE B

• The recloser was open for 2010 ms (2 sec.)

Page 56: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

PLUGGED FAULT CURRENTS INTO FAULT LOCATOR TOOL TO PREDICT LOCATION OF FAULT

• Area highlighted in red is most likely fault location

Page 57: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

BLUE HERON RESTAURANT REPORTED HEARING A LOUD BANG – DEAD STARLING WAS FOUND AT

THE BASE OF A POLE NEAR THEM

Blue Heron

Dead Starling

Predicted Fault Location

Page 58: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

IT IS QUESTIONABLE THAT THE STARLING CAUSED THIS FAULT

• Usually takes a bigger bird to cause a phase-to-phase fault

• Phase-to-phase fault current at location where starling was found did not match calculated fault current

• No burn marks from arcing were observed on the pole

Page 59: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

A 10-15-15 FAULT WAS SIMILAR TO THIS ONE AND NO CAUSE WAS FOUND

(COMPARE TO SLIDE 36)

Page 60: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

UG CABLE FAILUREL O C A T I O N P R E D I C T I O N G O O D

F L T I C O N T R I B U T I O N F R O M M I L L M O T O R S

Page 61: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

SCADA ALARMS

Page 62: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

INTERROGATE FEEDER BREAKERS

• Form 6 Recloser Controls did not show anything in Sequence of Events Files

• But they did capture Oscillographic waveforms• The fault was on Circuit 63. The Form 6 on Ckt 63

showed two Oscillographic events• First Event:

Page 63: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

CIRCUIT 63 – SECOND EVENTLINEMAN REFUSED THE RISER POLE

Page 64: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

CIRCUIT 62 CONTRIBUTED FAULT CURRENT DUE TO LARGE MOTOR LOAD

• Note that current is going in the opposite direction as the current in Ckt 63

Page 65: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

FROM PQ METER ON SUB BUSRMS VALUE OF FAULT CURRENT IS CLOSE TO WHAT THE FORM

6 SHOWS: 2165 A ON FORM 6, 2072 A ON NEXUSFAULT LASTED FOR 1.5 CYCLES = .0025 SEC

Page 66: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

FAULT LOCATION PREDICTION NOT FAR OFF

Fault on UG Cable

Page 67: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

SYNERGI PROTECTION STUDY PREDICTS MAX SLG FAULT CURRENT TO BE 2292 A AT

THIS LOCATION

Page 68: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

30 A FUSE SHOULD BLOW IN .019 SEC. AT 2165 AMPS. 1.5 CYCLES = .025 SEC.

Page 69: DISTRIBUTION FEEDER FAULT ANALYSIS...due to 115 kv underbuild. elbow failure on ug. scada alarm at 17:10 indicates fault on nestucca feeder 39. first step is to connect to form 6 relay

QUESTIONS?G A I L S H A W

G S H A W @ T P U D . O R G