Distance Protection and Dynamic Loading of Transmission Lines

download Distance Protection and Dynamic Loading of Transmission Lines

of 6

Transcript of Distance Protection and Dynamic Loading of Transmission Lines

  • 5/21/2018 Distance Protection and Dynamic Loading of Transmission Lines

    1/6

    AbstractDynamic loading of transmission lines is becoming

    one of the tools that allows system operators to increase the

    loading of the transmission line when required by the system or

    the energy market. The paper discusses in detail the effect of

    dynamic loading on different types of distance relays. Advanced

    microprocessor based relays offer a variety of different

    characteristics and functions that provide sufficient resistive

    reach to cover the expected range of fault arc resistances, while at

    the same time are not affected by encroachment of the load

    impedance in the distance characteristic.

    Index TermsProtective relaying, Dynamic loading,

    Impedance characteristic.

    I. INTRODUCTION

    Distance relays have been successfully used for many

    years as the most common type of protection of transmission

    lines. The development of electromechanical and solid state

    relays with mho characteristics can be considered as an

    important factor in the wide spread acceptance of this type of

    protection at different voltage levels all over the world.

    Zone 1 of distance relays is used to provide primary high-

    speed protection of a significant portion of the transmission

    line. Zone 2 is used to cover the rest of the protected line and

    provide some backup for the remote end bus. Zone 3 is the

    backup protection for all the lines connected to the remote

    end bus.

    The implementation of distance relays requires

    understanding of its operating principles, as well as the factors

    that affect the performance of the device under different

    abnormal conditions.

    The setting of distance relays should ensure that the relay

    is not going to operate when not required and will operate

    when necessary.

    The behavior of distance relays during several recent majorblackouts combined with the significant pressure on utilities

    to increase the loading of their transmission systems are the

    reasons to look at dynamic loading of transmission lines and

    A. P. Apostolov is with ALSTOM T&D Energy Automation & Information, Los

    Angeles, CA 90064 USA (e-mail: [email protected]).

    D. Tholomier is with ALSTOM T&D Energy Automation & Information,

    Levallois, France (e-mail: [email protected])

    S. Richards is with ALSTOM T&D Energy Automation & Information,

    Stafford, UK (e-mail: [email protected])

    the effects that it has on the commonly used distance relays.

    At the same time the characteristics of modern distanc

    relays are analyzed in order to demonstrate that they can

    provide better protection and at the same time are not affecte

    by dynamic loading conditions.

    II. DYNAMIC LOADING AND DISTANCE PROTECTION

    REQUIREMENTS

    The requirements for increase of the loading of man

    transmission lines due to changing system or marke

    conditions have to be considered when analyzing th

    performance of distance relays, selecting protection device

    with distance functions and calculating their settings.

    Since the dynamic stability is a function of the loading o

    the line and the duration of the fault, the operating time of th

    distance relay will affect the level of loading of the protecte

    line. As can be seen from Fig. 1 [3], shorter fault clearin

    times allow increased power transfer.

    Fig. 1. Typical power/time relationship for various fault types

    The detection of a fault and a decision to trip is made by

    modern distance relays in less than one cycle. However, th

    operating time of the relay is not the only factor to b

    considered while selecting a distance protection for

    transmission line that requires dynamic loading.

    The loading of transmission lines is typically limited b

    their rating. The thermal rating is usually based on

    conservative assumption of weather conditions. Since weathe

    conditions are continuously changing, most of the time th

    actual rating of the line can be significantly increased

    especially if specialized monitoring equipment is being used

    Distance Protection and Dynamic Loading of

    Transmission LinesA. P. Apostolov, Senior Member, IEEE,D. Tholomier, S. H. Richards,Member, IEE

  • 5/21/2018 Distance Protection and Dynamic Loading of Transmission Lines

    2/6

    Many utilities are experimenting with dynamic thermal line

    rating. Reports [5] indicate that real-time rating allows 40 to

    80 percent more power transfer compared to the static rating

    that is usually used.

    Figure 2 shows a comparison between the monitored line

    loading and the static, emergency and dynamic rating [5] over

    a period of time.

    Fig. 2. Dynamic rating profile of a transmission line

    The current interest in increase of the rating of

    transmission lines however lacks enough attention to the

    effect on the protection system.

    The distance elements of protective relays have to beselected and configured in such a way that they will provide

    sufficient resistive reach to ensure correct operation when a

    fault is inside of the designed zone of protection. The

    resistance of the arc has to be taken into consideration. It is

    affected by many factors, such as the distance between the

    phases and the extension of the arc by wind. The calculation

    of the arc resistance will never be completely accurate, but

    still there are formulas that can help in estimating the required

    resistive coverage. For example, the protection engineer may

    use the empirical formula derived by A. R. van C. Warrington

    [4] to calculate the resistance of the arc:

    Ra= 28710 L / I1.4

    (1)

    Where:

    Ra = arc resistance (ohms)

    L = length of arc (meters)

    I = arc current (Amps)

    Figure 3 below shows the protected transmission line in the

    impedance plane with the area of arc resistance that has to be

    covered by the protection element. Obviously, the

    characteristic needs to have a shape and be wide enough to

    provide this coverage.

    At the same time the characteristic should have a shape

    and be narrow enough so that the dynamically changing load

    impedance does not enter inside the characteristic, that wil

    result in undesired tripping of the protected line at the tim

    when it is needed the most.

    Fig. 3. Arc and Load impedance regions in the impedance plane

    The effect of load on the operation of distance relays i

    well known and studied for example [1, 2]. It may lead t

    under or over-reaching of the distance characteristic. Th

    apparent impedance seen by the relays under very heavy load

    may lead to relay tripping. This is especially true in the cas

    of long transmission lines or Zone 3 elements that have t

    provide backup protection for lines outgoing from substationwith significant infeed. This is quite dangerous during wid

    area disturbances and may result in quick deterioration of th

    system and a blackout.

    The analysis of recent blackouts in the Western and North

    Eastern United States [6] clearly demonstrate this problem

    with typical distance protection applications. Operation o

    distance relays with Mho characteristics under increased loa

    conditions resulted in tripping of transmission lines an

    worsening of the overall system stability.

    Utilities and regional industry coordinating bodies, such a

    the WSCC , are analyzing their practices related especially t

    the application of Zone 3 of distance protection relays. Load

    encroachment has to be considered during the selection o

    distance relays to be used and while calculating the setting

    for each specific location.

    From Figure 3 above it is clear that the distanc

    characteristics for each zone of a multifunctional transmissio

    line protection relay should lie between the fault + ar

    impedance area and the load impedance area. The shaded par

    of the load impedance region corresponds to the normal an

    emergency rating of the line, while the white area is the loa

    based on the dynamic rating.

    X

    R

    ZLoad

    Fault + arc impedanceregion

    ZLine

    Load impedance

    region

  • 5/21/2018 Distance Protection and Dynamic Loading of Transmission Lines

    3/6

    The analysis so far has been simplified, as in reality all

    lines have two or three terminals, and if sources are present at

    the remote terminals, they will infeed and contribute towards

    any internal fault current. Figure 4 shows how for a fixed

    amount of fault arc resistance, the apparent resistance as

    measured by the distance relay at the local terminal appears to

    magnify with increasing distance to the fault. This is because

    the remote end current contribution increases proportionally

    more, as the local current contribution decreases. For thisreason, it is common that the arc resistance reach of distance

    zones might be four times that from the van Warrington

    calculation.

    The gray shaded region shows the possible fault

    resistances measured when the load flow was forwards prior

    to the fault (load export), and the solid lined region adds the

    possible fault area when load import was the scenario. The

    angular tilt of the resistance is an issue for the zone reactance

    reaches of distance relays, and is not related to line

    loadability. This is not addressed further in the paper,

    reference [7] discusses in more detail.

    X

    R

    ZLoad

    Arc impedance with

    Remote end infeed

    ZLine

    Load impedance

    region

    load export

    load import

    Fig. 4. Arc and Load impedance regions in the impedance plane

    The electromechanical or solid state relays with Mho

    characteristics have some problems with the above mentionedareas. They usually can not cover the arc impedance for faults

    at the end of the protected zone, while at the same time are

    subject to load encroachment, especially if the load is

    dynamically changing above the static rating of the

    transmission line.

    Figure 5 shows a typical case of the Mho characteristics of

    a transmission line protection relay with three forward looking

    zones in the R X plane.

    Zone 1 is not affected by the dynamic loading of the

    protected line. Zone 2 may operate in the case of the highest

    level of dynamic loading, while Zone 3 will operate during

    dynamic or even emergency loading conditions.

    Fig. 5. Arc and Load impedance regions and distance protection zones in th

    impedance plane

    Because of the significant problems with the application o

    Zone 3 distance elements with Mho characteristic, som

    utilities have disabled them in order to avoid potential lin

    tripping during emergency system conditions. In other case

    the reach settings are changed to reduce the probability fo

    tripping under load conditions. However, this reduces theffectiveness of Zone 3 as a remote backup protection

    element.

    All of the above has been taken into consideration in th

    design of modern microprocessor based transmission lin

    protection relays with distance characteristics.

    III. DISTANCE CHARACTERISTICS OF TRANSMISSION LINE

    PROTECTION RELAYS

    A. Lenticular Distance Characteristics

    To avoid the operation of a Zone 3 distance element with

    Mho characteristic one can select to use instead a lenticular

    (lens-shaped) characteristic.From Figure 6 it is clear that the resistive coverage of thi

    characteristic is restricted. The aspect ratio of the lens a/bi

    adjustable. By selecting the configuration parameter a/b th

    user can provide the maximum fault resistance coverage an

    at the same time avoid the operation under maximum loa

    transfer conditions. However, it is clear that the resistiv

    coverage is not consistent along the length of the line an

    varies with the location of the fault. Faults at the end of Zone

    2 will probably be cleared by Zone 3 in the cases when ther

    is arc resistance.

    R

    X

    ZLoad

    ZArc

    ZLine

    Zone 2

    Zone 3

  • 5/21/2018 Distance Protection and Dynamic Loading of Transmission Lines

    4/6

    This tripped zone indication can be confusing to system

    operators and technicians, most of whom will not be distance

    protection experts. There is thus the risk that the fault location

    might be falsely presumed to be on a line downstream of the

    actual faulted line.

    Fig. 6. Zone 2 element with Lenticular characteristic

    B. Distance Characteristics with Load Blinders

    If we would still like to have a Mho distance characteristic

    that provides sufficient arc resistance coverage but at thesame time eliminates the possibility for tripping under

    maximum load condition, we can select to use a transmission

    line protection relay that combines a Mho element with a load

    blinder.

    Figure 7 shows the characteristics of a distance relay with

    load blinders for Zone 2 and Zone 3. The blinder restrains the

    operation of the distance element for load impedance that

    appears to the right of the blinder.

    If the impedance seen by the relay is within the Mho

    characteristic and to the left of the blinder, it is allowed to

    operate and trip the breaker.

    The setting of the resistive reach of the load blinder shouldtake into consideration the requirements for maximum arc

    resistance coverage and at the same time elimination of the

    possibility for operation of the distance element under

    maximum load conditions. This means that the protection

    engineer needs to know what is the maximum dynamic rating

    of the protected transmission line.

    Another option for combining Mho characteristics and load

    blinders is by reducing the size of the Zone 3 element and

    using at the same time forward offset in order to ensure

    appropriate coverage of the outgoing lines at the remote end

    substation. In this case a load blinder is required only for th

    Zone 2 element. An advantage is that the non-blinded Zone

    can better cope with the magnified fault resistance as wa

    seen in Figure 4.

    Fig. 7. Zone 2 and Zone 3 elements with Mho characteristics and load blinders

    Fig. 8 Zone 2 with reverse offset Mho characteristic and load blinder an

    forward offset Zone 3 Mho characteristic

    A more advanced load blinder is designed to provide bette

    resistive reach coverage. The blinder is basically formed from

    an underimpedance circle, with radius set by the user and tw

    blinder lines crossing through the origin of the impedanc

    plane. It cuts the area of the impedance characteristic tha

    may result in an operation under maximum dynamic load

    X

    R

    ZLoad

    ZArc

    ZLine

    Zone 2

    Zone 3

    ba

    X

    R

    ZLoad

    ZArc

    ZLine

    Zone 2

    Zone 3

    X

    Zone 2

    Zone 3

    R

    ZLoad

  • 5/21/2018 Distance Protection and Dynamic Loading of Transmission Lines

    5/6

    conditions.

    The radius of the circle should be less than the maximum

    dynamic load impedance. The blinder angle should be set half

    way between the worst case power factor angle, and the line

    impedance angle.

    In the case of a fault on the line it is no longer necessary to

    avoid load. So, for that phase, the blinder can be bypassed,

    allowing the full mho characteristic to measure. The resistive

    reach during the fault condition is thus improved, as theblinder no-longer acts as a constraint.

    Phase undervoltage detectors are the chosen elements to

    govern switching of the blinders.

    Figure 9 shows an example of such a load blinder

    characteristic. Again it is possible to make use of a broader

    Zone 2 and Zone 3 characteristic to cater for the fault

    resistance magnifying effect in Figure 4.

    Fig. 9. Advanced load blinder characteristic

    C. Quadrilateral Characteristics

    This form of impedance characteristic is shown in Figure

    10.

    Fig. 10 Zone 2 with quadrilateral characteristic and reverse offset Zone 3

    quadrilateral characteristic

    The characteristic is provided with forward reach and

    resistive reach settings that are independently adjustable. I

    therefore provides better resistive coverage than Mho typ

    characteristic and is not affected by the load encroachment.

    Quadrilateral impedance characteristics are highly flexibl

    in terms of fault impedance coverage for both phase and

    ground faults. For this reason, most digital and numerica

    distance relays now offer this form of characteristic.

    With this type characteristic, the resistive reach settings fo

    each zone can be set independently of the impedance reachsettings.

    The resistive reach setting represents the maximum

    amount of additional fault resistance (in excess of the lin

    impedance) for which a zone will trip.

    Two constraints are imposed upon the settings, as follows:

    The resistive reach must be greater than the maximum

    expected phase-phase or phase-ground fault resistanc

    (basically that of the fault arc)

    It must be less than the apparent resistance measured

    due to the heaviest dynamic load on the line

    Figure 10 shows the Zone 2 and Zone 3 quadrilatera

    characteristics of a transmission line protection relay. Zone is forward looking based on the reactive reach line, th

    resistive reach blinders and a directional line.

    It is clear from the figure that this characteristic provide

    sufficient arc resistance coverage, and at the same time is no

    affected by the maximum dynamic loading of the protected

    line.

    D. Polygon Characteristic

    A polygon characteristic can be built from several blinder

    and a directional element. An example of such characteristi

    is shown on Figure 11.

    Fig. 11 Polygon characteristic

    RestrainRestrain Operate

    X

    R

    ZLoad

    ZArc

    ZLine Zone 2

    Zone 3

    X

    R

    ZLoad

    ZArc

    ZLine

    X1

    R1PP

  • 5/21/2018 Distance Protection and Dynamic Loading of Transmission Lines

    6/6

    This type of characteristic can provide (depending on the

    settings) resistive coverage similar to the advanced load

    blinder described earlier.

    Setting the resistive reach and the slope angle allows the

    definition of an optimal characteristic positioned between the

    arc resistance and the load impedance areas.

    IV. CONCLUSIONS

    The requirements for increase of power transfer over

    existing transmission lines based on system stability or energy

    markets requirements is forcing utilities to find solutions that

    will allow them to load the lines based on their dynamic

    rating.

    Successful pilot projects demonstrate that it is possible to

    increase by more than 50 percent the loading of the lines.

    On the other hand, experience with recent blackouts shows

    that the dynamic changes of load may result in undesired

    operation of distance elements due to the load impedance

    entering the distance characteristic.

    The different types of distance characteristics analyzed in

    the paper demonstrate that by properly selecting and settingthe distance characteristics, the user can define an optimal

    protection element that will provide sufficient arc resistance

    coverage and at the same time eliminate the possibility for

    tripping under maximum dynamic load conditions. It is

    concluded that distance relays should not constrain the

    loadability of transmission lines. The distance relay is

    designed according to the power system needs not vice

    versa.

    Any loadability limit should be determined by the dynamic

    rating of the transmission line.

    V. REFERENCES[1] R. J. Marttila, "Performance of Distance Relay Mho Elements on MOV-

    Protected Series-Compensated Transmission Lines," IEEE Trans. Power

    Delivery, vol. 7, pp. 1167-1178, Apr. 1988.

    [2] R. J. Marttila, "Effect of Transmission Line Loading on the Performance

    Characteristics of Polyphase Distance Relay Elements," IEEE Trans.

    Power Delivery, vol. 3, pp. 1466-1474, Oct. 1988.

    [3] ALSTOM, Network Protection & Automation Guide, 2002

    [4] A. R. van C. Warrington, "Protective Relays their Theory and Practice"

    Chapman and Hall, 1962

    [5] PIER, "Dynamic Circuit Thermal Line Rating," California Energy

    Commission, Los Angeles, CA, Tech. Rep. TR-0200 (4230-46)-3, Oct.

    1999.

    [6] U.S.-Canada Power System Outage Task Force, Interim Report: Causes

    of the August 14th Blackout in the United States and Canada, Nov. 2003

    [Online]. Available: http://www.nerc.com/

    [7] IEEE Std C37.113-1999 IEEE Guide for Protective Relay Applications to

    Transmission. Lines.

    VI. BIOGRAPHIES

    Alexander Apostolovreceived MS degree in Electrical

    Engineering, MS in Applied Mathematics and Ph.D.

    from the Technical University in Sofia, Bulgaria. He has

    worked for fourteen years in the Protection &Control

    Section of Energoproject Research and Design Institute,

    Sofia, Bulgaria.

    From 1990-94 he was Lead Engineer in the Protection

    Engineering Group, New York State Electric & Gas

    where he worked on the protection of the six-phase line, application o

    microprocessor relays, programmable logic and artificial intelligence in protection

    1994-95 he was Manager of Relay Applications Engineering at Rochester

    Integrated Systems Division. 1995-96 he was Principal Engineer at Tasnet.

    He is presently Principal Engineer for AREVA (formerly ALSTOM) T&D EAI i

    Los Angeles, CA. He is a Senior Member of IEEE and Member of the Powe

    Systems Relaying Committee and Substations C0 Subcommittee. He is Vic

    Chairman of the Relay Communications Subcommittee, serves on several IEEE PE

    Working Groups and is Chairman of Working Group C3: New Technology Relate

    to Power Systems Protection and Working Group C9: Guide for Abnorma

    Frequency Load Shedding and Restoration.He is member of IEC TC57 and CIGRE WG 34.01.He is Chairman of the Technica

    Publications Subcommittee of the UCA International Users Group. He holds thre

    patents and has authored and presented more than 140 technical papers.

    Damien Tholomier received a BEng in Electrical an

    Automation Engineering in 1992 from the University o

    Marseilles, France (Ecole Polytechnique Universitair

    de Marseille). Damien joined ALSTOM T&D GmbH i

    Stuttgart, Germany where he worked for 5 years in th

    Protection & Control department as Power System

    Application Engineer.

    In 1997 Damien moved as Marketing Manager Hig

    Voltage Protection Business Unit with Alstom T&D

    Protection & Control in Lattes, France where he worke

    on full scheme distance protection algorithms.

    From 1999-2001 he was Sales & Service Director for Mediterranean Countrieand Africa.

    Since 2002 he is Marketing Protection Relays Director for ALSTOM T&D EA

    where he worked on new busbar relay (application of universal topology and CT

    saturation detection algorithms).

    Simon Richardsis the UK-based Marketing Directo

    for Protection Products from AREVA. AREVA ha

    recently acquired the Transmission and Distributio

    businesses of ALSTOM. Protection Products are

    part of AREVAs Energy Automation and Informatio

    activity, and the author is based in Stafford, UK. H

    has a B.Eng (Hons) in Electrical and Electroni

    Engineering from the University of Bath, and is

    Chartered Engineer, and MIEE. Previously a 25kV

    electrification Distribution Engineer for the 500km

    West Coast Main Line railway between London and Scotland, Simon also held number of protection applications engineering positions within ALSTOM prio

    to his current role. The Marketing function provides technical support to Sale

    and Service teams worldwide, and investigates opportunities for new produc

    developments.