Direct Emission Measurements on Cast Iron Pipe

21
Direct Emission Measurements on Cast Iron Pipe Lillian L. Woolley, P.E. DTE Energy October 25, 2007

Transcript of Direct Emission Measurements on Cast Iron Pipe

Page 1: Direct Emission Measurements on Cast Iron Pipe

Direct Emission Measurements on Cast Iron Pipe

Lillian L. Woolley, P.E. DTE Energy

October 25, 2007

Page 2: Direct Emission Measurements on Cast Iron Pipe

OVERVIEW

• Background • Use of Hi-Flow Gas

Sampler • Second Study • Going Forward

2

Page 3: Direct Emission Measurements on Cast Iron Pipe

DTE Energy - MichCon

• DTE Energy is one of the nation’s largest diversified energy companies.

• Its largest operating units are Detroit Edison, an electric utility serving 2.2 million customers in SE Michigan, and MichCon, a natural gas utility serving 1.3 million customers in Michigan.

• MichCon, founded in 1849, is the fifth largest natural gas utility.

• MichCon is able to store 130 billion cubic feet of gas in naturally occurring underground rock formations.

3

Page 4: Direct Emission Measurements on Cast Iron Pipe

What is the issue?

• Cast Iron Pipe Replacement Program – 2500 Miles in 50 Years

• Increased Focus on GHG – Should we use emissions to help us prioritize?

• Little Emissions Data is available on Underground Pipe

• GRI/EPA study dated June, 1996 • MichCon Needs Better Quality Data!

4

Page 5: Direct Emission Measurements on Cast Iron Pipe

Why does cast iron pipe leak?

• Bell-and-spigot joints that connect pipe sections together tend to leak as pipe ages.

• Corrosion of pipe may also be an issue.

5

Page 6: Direct Emission Measurements on Cast Iron Pipe

Factors Affecting Leak Rate -GRI/EPA Study

• Stratifying variables were identified as:– Pipe use (service versus mains) – Pipe materials – Pipe age

6

Page 7: Direct Emission Measurements on Cast Iron Pipe

Factors Affecting Leak Rate -GRI/EPA Study

• Additional Factors: – System leak detection and repair programs – Pipe operating pressures – Distribution soil characteristics – Pipe diameter

7

Page 8: Direct Emission Measurements on Cast Iron Pipe

•EPA/GRI Test Procedure

• Leak was identified • Segment to be tested was capped off at the service-to-main

connection • A short segment of main (20 feet long) with a detectable leak

was isolated or • A longer segment with multiple leaks was isolated • Cast iron pipe was slightly different as many sections have

undetected leaks • Gas was metered to the section and the gas flow rate required to

maintain pressure was recorded • Separate work was completed on the oxidation of methane in

soil

8

Page 9: Direct Emission Measurements on Cast Iron Pipe

MichCon Emissions Study

• MichCon worked with Heath Consultants to establish a protocol for measuring leaks in underground pipe using a high-flow sampler.

• The study included: – Selection of several sites with different

characteristics (similar to the GRI/EPA study)

– Use of three different methods of enclosing leaks

9

Page 10: Direct Emission Measurements on Cast Iron Pipe

Funnel Method

10

Page 11: Direct Emission Measurements on Cast Iron Pipe

Issues associated with sampling

Funnel Method – • Many did not produce any measured sample

• May have been issues with the seal to the ground

• May have been venting over a wider range – even at the curb

• Cannot be used on city streets • Sampling could be improved with a much

larger funnel

11

Page 12: Direct Emission Measurements on Cast Iron Pipe

3-Hole Sampling Method

12

Page 13: Direct Emission Measurements on Cast Iron Pipe

Issued associated with sampling

Direct Measurement – 3-Hose Sampling Method

• Produced results – but still not sure entire leak was captured

• Even with this method, not sure steady-state was reached and pooled gas was not being measured

• MichCon employees felt maybe gas was being pulled out of pipe

13

Page 14: Direct Emission Measurements on Cast Iron Pipe

Tarp Enclosure Method

14

Page 15: Direct Emission Measurements on Cast Iron Pipe

Issues Associated with Sampling

Tarp Enclosure Method – • Need to test outside of tarp area to ensure all gas was

captured • Problems in areas between the curb and sidewalk • Issues with seal to the ground • Need a larger sample to adequately determine

effectiveness

15

Page 16: Direct Emission Measurements on Cast Iron Pipe

Leak Rate from Funnel Measurements

Leak Rate (cf/hr)

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

Leak

Rat

e (c

f/hr)

16

Page 17: Direct Emission Measurements on Cast Iron Pipe

Cast Iron Pipe Emissions Data

• GRI/EPA – 238 Mcf/mile

• DTE – 21,595 Mcf/mile

17

Page 18: Direct Emission Measurements on Cast Iron Pipe

Emissions Study

• As main services were renewed, service was transferred to the new main

• Meter was installed between the soon-to-be abandoned main and the existing system

• Gas to the isolated system was measured for 1.5 weeks to determine the leak rate

• One system – 0 gas leaks (580 feet)

• Second system – 16.7 cf/hr (1150 feet)

• Similar repair histories, etc.

18

Page 19: Direct Emission Measurements on Cast Iron Pipe

Going Forward

• Additional main renewal emissions collection

• Better Repair HistoryTracking

• Additional Information on Leaks Collected

• Newer Technologies?

19

Page 20: Direct Emission Measurements on Cast Iron Pipe

Any Questions?

20

Page 21: Direct Emission Measurements on Cast Iron Pipe

21