Read carefully the instructions published in this manual before the first use of the level meter. Keep the manual at a safe place. The manufacturer reserves the right to implement changes without prior notice.
INSTRUCTION MANUALprůmyslová elektronika
RadaR level meteRs with guided wave gRlm – 70
valid for firmware version 2.X
Table of conTenTs
1 . Measuring principle .................................................................................................................3
2 . Range of applications ..............................................................................................................3
3 . Features of variants .................................................................................................................4
4 . Dimensional drawings .............................................................................................................4
5 . Installation and putting into operation ...................................................................................6
6. Installation instructions ..........................................................................................................6
7. Electrical connection ...............................................................................................................12
8 . Set-up elements .......................................................................................................................13
9. Status signalization ..................................................................................................................13
10. Setting .....................................................................................................................................14
10.1 . Basicsettings ...................................................................................................................14
10.2 . Servicesettings ...............................................................................................................17
10.3 . Additionalfunctions ..........................................................................................................19
11. HART® communication protocol ...........................................................................................21
12. The installation of the custom measuring electrode,
exchange or shortening of the electrode ..............................................................................22
13. Order code ..............................................................................................................................24
14. Accessories ............................................................................................................................24
15. Safety, protection and compatibility ....................................................................................24
16. Use, manipulation and maintenance ....................................................................................25
17. Marking of labels ....................................................................................................................25
18. Menu structure........................................................................................................................27
19 . Specifications .........................................................................................................................28
GRLM–70 © Dinel, s.r.o.3
1 . Measuring principleThe GRLM® radar level meters arecompactmeasurementdevicesincludingantransmitterofmicrowavepulses,centralprocessorunitanddisplaymodule.Theelectronicstransmitsveryshortelectricalpulses(0.5ns),whicharelinkedtoaone-wiretransmissionline(measuringelectrode).Measuringelectrodecanbecreatedofrodorrope.Thepulsepropagatesalongtheelectrodeintheformofelectromagneticwavetowardthelevelsurface,whereitispartlyreflectedandthereflectedcomponent is returned to thereceivingmoduleof theelectronics.Theelectronicsmeasures thetimeofflightofelectromagneticwaveand theinstantdistancetothesurfaceleveliscalculated.Accordingtothelevelheight,thelevelmeteroutputissetandthemeasuredvalueisdisplayedonthedisplay.
2 . range of applicaTionsRadar levelmeters with guidedwave are suited to continuous levelmesurement of variousliquid,mushandbulk-solidmaterials.Levelmetersareresistantagainstchangesintheatmos-phere(pressure,temperature,dust,steam)andtochangesinmediumparameters(changeindi-electricconstant,conductivity).
All operations described in this instruction manual have to be carried out only by trained personnel or an accredited person. Warranty and post warranty service must be exclusively carried out by the manufacturer.
Improper use, installation or set-up of the level meter can result in crashes in the application (overfilling of the tank or damage of system components).
The manufacturer is not responsible for improper use, losses of work caused by either direct or indirect damage, and for expenses incurred during installation or use of the level meter.
safeTy
Alert, warning, danger
Thissymbolinformsyouaboutparticularlyimportantinstructionsforinstallationandoperationofequipmentordangeroussituationsthatmayoccurduringtheinstalla-tionandoperation.Notobservingtheseinstructionsmaycausedisturbance,dam-ageordestructionofequipmentormaycauseinjury
Information
Thissymbolindicatesparticularlyimportantcharacteristicsofthedevice.
Note
Thissymbolindicateshelpfuladditionalinformation.
Valid for:
IntheborderarethetypesGRLM,forwhichisintendedthechapter.all types
used syMbols
Toensuremaximumsafetyofcontrolprocesses,wehavedefinedthefollowingsafetyinstructionsandinformation.Eachinstructionislabeledwiththeappropriatepictogram.
4© Dinel, s.r.o. GRLM–70
3 . VarianTs of sensors
4 . diMensional drawings
GRLM –70_–00 without electrode,theelectrodeismadebycustomer(onlyvariant10or30)andconnectedtotheelectrodejunctionbyM8thread.
GRLM –70_–10 Uncoated stainless steel rod electrode, forlevelmeasurementliquidsandbulksolidmaterials(water,watersolutions,emulsion,oils,diesel,flour,sand,granulates,etc.).Maximumelectrodelength8m.
GRLM –70_–11 Fully coated stainless steel rod electrode (PFA Teflon®), forlevelmeasurementofaggressiveliquidsandverypureliquids. Maximumelectrodelength2m.
GRLM –70_–12 Fully coated stainless steel rod electrode (FEP Teflon®), forlevelmeasurementofaggressiveliquidsanddrinks. Maximumelectrodelength2m.
GRLM –70_–20 Uncoated stainless steel rod electrode with reference tube, foraccuratelevelmeasurementofliquidsincrampedspaces.Maximumelectrodelength3m.
GRLM –70_–30 Uncoated stainless steel rope electrode and weight, forlevelmeasurementofliquidsandbulksolidmaterials(water,grains,sand,flour,cement,etc.)inhighersilos,vessels,reservoirs.Maximumelectrodelength40m.
GRLM –70_–32 Fully coated stainless steel rope electrode (FEP Teflon®) and coated weight (PTFE), forlevelmeasurementofaggressiveliquidsandverypureliquids.Maximumelectrodelength12m.
GRLM –70_–33 Uncoated stainless steel rope electrode with anchorage, forlevelmeasurementofbulksolidmaterials(grains,flour,cement,etc.)inhighersilos,vessels.Maximumelectrodelength40m.
GRLM –70_–34 Coated stainless steel rope electrode (Polyamid) and uncoated weight, forlevelmeasurementofliquidsandadhesivebulksolids (flour,cement,etc.).Maximumelectrodelength40m.
GRLM –70_–35 Coated stainless steel rope electrode (Polyamid) with uncoated anchorage, forlevelmeasurementofadhesivebulksolids (flour,cement,etc.).Maximumelectrodelength40m.
GRLM–70_–00variant GRLM-70 with protective
conductor
GRLM–70 © Dinel, s.r.o.5
GRLM
–70_–10(11,12)
GRLM
–70_–20
GRLM
–70_–30(33)
High temperature perform
ance
GRLM
–70_T
GRLM
–70_–32
Ancho
ring eye for
varia
nt G
RLM
-70_-33
electr
ode
holde
r
electr
ode
4x h
ole
6© Dinel, s.r.o. GRLM–70
BASIC INFORMATIONS
• Install the levelmeter into the upper lid of thetankorreservoirusingawelding flange orfas-tering nut.
• Themin.distancetoinstallthelevelmeterintoalidoraceilingofatankfromthetankwall isgivenintableright.
• Otherwise, the levelmeter installas faraspo-ssiblefromthewalls,tothemiddlebetweenthewallandtheverticalinlet,seeFig.1.a2.
type of wall d(without ref. tube)
d(with ref. tube)
metal ≥ 300 mm any distance
non-metal ≥ 500 mm any distance
Pleasefollownext3steps:
• insTallaTion
• elecTrical connecTion
• seTTing
5 . insTallaTion and puTTing inTo operaTion
6 . insTallaTion insTrucTions
E = m + t + k E = m + t + zall types
Fig. 1: Level meter installation with the rod electrode
Fig. 2: Level meter installation with the rope electrode
E – The length of rope electrodet – Measuring rangem – Dead zone on the beginning of electrodek – Dead zone on the end of electrodez – The lengt of weight (110 mm)d – The distance from the tank wall (min. 300 mm)
GRLM–70 © Dinel, s.r.o.7
DEAD ZONE
• Inconnectionwith themeasurementprinciple, thesignals reflected in thearea justunder thelevelmetercannotbeevaluated.The zone(Fig.3and4)determinesthemin.distancepossiblebetweenthelevelmeterandthehighestsurfacelevel. Itisnecessarytoinstallthelevelmetersothatthebinlevelcannotinterferewiththedeadzonewhenfilleduptothemaximumordepletetotheminimum.Ifthemeasuredlevelinterfereswiththedeadzone,thelevelmeterwillnotworkproperly.
• Thesizeofthedeadzoneisaffectedbythesetmeasurementsensitivity.Theminimumdistan-cestothemedium(deadzones)arepresentedinthetablesbelow.
Fig. 3: Level meter dead zone with rod electrode
Fig. 4: Level meter dead zone with rope electrode
measurement sensitivity m k
(rod electrode)k
(rope electrode)low, medium, user (1 - 4) 100 mm 0 mm 110 mm
high, user (5) 150 mm 50 mm 110 mm
user (6, 7) 200 mm 50 mm 110 mm
user (8) 250 mm 50 mm 110 mm
INPUT NECK
• Forcorrectmeasurement it is important toavoid in-stallation in thehighneck.Forshortneckarereco-mmendednextconditions:a<b,b>50mm,whereaistheNeckheightandbistheNeckwidth a ≤ b
b ≥ 50 mma – neck heightb – neck width
Fig. 5: Level meter installation in the input neck
If you can not eliminate all interference, which could affect the measurement of level, it is recommended to use the procedure "TEACHING" (see chap. 10.2 Service settings). This procedure sets the level meter to mode, which suppresses false reflections.
all types
all types
except GRLM-70_-20
8© Dinel, s.r.o. GRLM–70
• The end of the socket or the welding flangemust not have an extension into the tankinFig.6.
CONCTRETE SILO
• Forinstallationofthelevelmeteronaconcreteroofthediameterboftheholemustbegreaterthanthethicknessaoftheconcrete,seeFig.8.
• Ifthethicknessaoftheconcreteisgreaterthanthediameterbofthehole,installthelevelmeterinarecess,see.Fig.9.
a < b
NON-METAL TANK
• Forlevelmeterinstallationinnon-conductive tanksitisnecessarytouseametalsheet(dia-metralgreaterthan200mm)beneaththepro-cessfittingwhenscrewingitin.Makesurethatthe plate has direct contact with the processfitting.
Fig. 6: Incorrect welding flange mounting to the tank
Fig. 7: Incorrect welding flange mounting to the tank
Fig. 8: Level meter installation on the roof of the concrete silo
Fig. 9: Level meter installation on the roof of the concrete silo
all types
except GRLM-70_-20
all types
except GRLM-70_-20
Fig. 10: Solar radiation shielding cover
all typesLEVEL METER PROTECTION
• Thelevelmetermustnotbeinstalledinplaceswithdirectsolar radiationandmustbeprotectedagainstweathereffects.
• Iftheinstallationinplaceswithdirectsolarradiationisinevitable,itisnecessarytomountashielding cover abovethelevelmeter.
GRLM-70_-30, 32, 33
GRLM–70 © Dinel, s.r.o.9
OUTSIDE THE INFLUENCE OF FILLING
• Donotinstallthelevelmeterinorabovethefillingstream.Theinflowingproductcaninfluencethemeasurementofthelevelmeter.
s -Radius of protec tive zone along the electrode level meter
• If still these objects intervene into the protective zoneofthelevelmeter,itisne-cessarytocreateamapoffalsereflectionsbyactivatingthe"TEACHING"mode(p.16).Incaseofinstalledmixers,itisnecessary topositionthemixersnearthelevelmeter(turningthemixerbladetotheproximityoftheelectrode).fortocreateamapfalsere-flections. Items inside the tank must not be from the electrode distance of less than 100 mm, because a interference ofelectromagnetic field is very strong in thiszone and "TEACHING" mode can not beused.
s = 300 mm
n = 100 mm
n - minimal distance of objects from the electrode from level meter
OBSTACLES IN THE TANK
• The level meter generates electromagne-tic guidedwave,which creates an electro-magneticfieldalong theelectrode.Objectsplaced close to the electrode disturb theelectromagneticfieldandthusaffecttheme-asurement.Therefore,itisdeterminedpro-tective zone along theelectrodeof radius300 mm.The levelmeter is recommendedto install the tank so that the items placedinside the tank (ladders, various partitions,mixers,etc.)doesnotinterveneintothepro-tectivezone,seeFig.12.
Fig. 11: Level meter installation outside the influence of filling
Fig. 12: Level meter installation outside obstacles in the tank
Fig. 13: Incorrect level meter installation close to obstacles
all types
except GRLM-70_-20
all types
10© Dinel, s.r.o. GRLM–70
CRAMPED SPACES
• Forthetypeoflevelmeterwith referen-ce tube electromagnetic guided wavepropagates inside the reference tube.Thiswaveisnotaffectedbytheambientenvironment. So for this type of radaris not intended protective zone aroundthe electrodes and the levelmeter canbeusedformeasurements incramped spaces.
DEEP TANKS AND SILOS
• Forinstallationofthelevelmeterwithropeelectrode into deep tanks and silos thelengthof theelectrodemustbeselectedsothatthe weightwillbebelowthemini-mummeasuredlevel,seeFig.16.
• The distance the electrode from the tank wallmustbeatleast300mm.Other-wise,thelevelmeterinstallasfaraspossi-blefromthewalls,tothemiddlebetweenthewallandtheverticalinlet,seeFig.16.Itmustbeensuredthattheropeelectrodecouldnottouchthevesselwallcausedbythemotionofthemedium.
• Takecaredoesnotexceedthemaximumtensileloadoftheropeelectrode.Theva-lueofthemax.tensilestrengthisspecifiedinchapter"Technicalspecifications".Highloadscanbreaktherope.Tensileloadde-pendsontheheightandshapeofthetank,thedensityandadhesionof themediumandtherateatwhichthetankisemptied.
E = m + t + z
HUMIDITY
• Itissuitabletorunthecableunderacablebushing(obliquelydowninslack)accord-ing to Fig. 15 to preventpenetration of humidity.Then therainandcondensingwatercanflowofffreely.
• Thecablebushingandconnectorhavetobesufficiently tightenedtopreventpen-etrationofhumidity.
Fig. 14: Level meter installation with reference tube in cramped spaces
Fig. 15: Prevention to avoid intrusion of humidity through cable gland
Fig. 16: Level meter installation with the rope electrode
GRLM-70_-20
GRLM-70_-30, 32, 33
all types
E – The length of rope electrodet – Measuring rangem – Dead zone on the beginning of electrodez – The lengt of weight (110 mm)d – The distance from the tank wall (min. 300 mm)
GRLM–70 © Dinel, s.r.o.11
Rope electrode level meter must untangle and then can be inserted into the tank.
ROPE ELECTRODE WITH ANCHORAGE
• Forinstallationofthelevelmeterwith ropeelectrodewith ancho-rage into deep tanks and silosit is recommended to place theanchorage closer to axis of thesilo than is the position of levelmeter. See Fig. 17. This moun-tingwill lower theThis installati-onwillreducethesideforcesofthemediaontheropeelectrode.
• In case of anchoring we re-commend to preload the ropeelectrode by tension force ofabout100N.
Fig. 17: Recommended Level meter installation with anchorage
GRLM-70_-33
VARIANT WITHOUT ELECTRODE
• Type of level meter withoutelectrode issuppliedwithoutanelectrode. It is therefore nece-ssarytoacustomertomounthisownmademeasuringelectrode.The diameter of the electrodemustbebetween8-10mm.Foraconnectionitisnecessarythaton the electrode is made M8thread.Theconnectionprocedu-reisgiveninSec.12page22.
Fig. 18: Level meter witout electrode
GRLM-70_-00
For the type of level GRLM-70_-00 manufactu-rer is not responsible for failures related to the mounted measuring electrode.
12© Dinel, s.r.o. GRLM–70
Electrical connection must be done in de-energized state!
With regard to possible occurrence of electrostatic charge on non-conductive parts of the level meter for explosive areas (GRLM–70Xi(XiT)), level meters must be grounded with ground terminal! It will be done using a screw placed on the head of the level meter under the cable bushing.
7 . elecTrical connecTionThelevelmeter isconnectedtoconsequential (evaluating)devicewithasuitablecablewith theouterdiameterof6to8mmusingscrewterminalslocatedunderthedisplaymodule.Therecom-mendedcrosssectionofcoresforthecurrentversion2x0,5÷0,75mm2andfortheversionwithModbuscommunication2x2x0,25mm2 (twistedpair,shielded).Pluspole(+U)isconnectedtotheterminal(+),minuspole(0V)totheterminal(-)andtheshielding(onlyforshieldedcables)totheterminal( ).Commu-nicationwiresAandBofthelineRS-485(forversion"M"-Modbus)areconnectedtotheterminalsAandB.Procedure to connect the cable to the level meter:
1. Unscrewthenutoftheuppertransparentlid.
2. Take the upper edge of the displaymodule andtakeitoutcarefullybymildswingingup.
3. If you cannot grasp the module, you can useasmallscrewdriver. Insert itas faras theseamandusefromseveralsidestoslightlyliftthemod-ule.
4. Releasethecableoutletandthreadthestrippedsupplycablein.
5. Connectthecabletothescrewterminalsaccord-ingtothediagraminFig.19or21.Firmlytightentheterminalsandthecableoutlet.
6. If the level meter with Modbus is involved as aterminalforRS-485,werecommend(toavoidre-flectionsontheline)toconnect120Ωterminationresistor.This isdonebymovingasmall leveroftheswitchmarked120Ω to theONposition.OnthelevelmetersconnectedtothelineRS-485asan intermediatedevice, the termination resistorsarenotconnected(switchremainsoff).
7. Insert thedisplaymoduleback into theheadsothattheconnectorisproperlyconnected.
8. Slidesiliconesealonthethreadofthelevelmeterbody, then tighten thenutof theupper lid.Con-nectthecabletoconsequentialdevice.
display unit connector
Terminal block
metal clip
Fig. 20: Inside view of screw terminals of the level meter with current output GRLM-70_-_-_-I
Fig. 19: Wiring diagram of the level meter with current output GRLM-70 _-_-_- I
+ A B ISGND
ON
120
display unit connector
Terminal block
metal clip
120Ω switch
Fig. 21: Wiring diagram of the level meter with Modbus GRLM-70_-_-_-M
Fig. 22: Inside view of screw terminals of the level meter with Modbus GRLM-70_-_-_-M
GRLM–70 © Dinel, s.r.o.13
button
• Set-upmodeaccess• Confirmationofselectediteminthemenu• Movethecursorintheline• Savingofset-updata
button
• Moveinthemenu• Changeofvalues
button
• Cancellingofcarriedoutchanges• Shiftonelevelup
9 . sTaTus signalizaTion
1) symbol appears in the lower left corner of the display
8 . seT-up eleMenTs
displej funkce
„NO ECHO“ Lighting intermittently – the level meter is not able to receive echo for a long time. Incorrect installation of the level meter.
„NO PASSWORD“ It will appear in the item "MENU" – the level meter is protected using a password against unauthorised setting. Enter the correct password.
„LOW POWER“ Low supply voltage level meter
Symbol „T“ 1) Lighting permanently – "TEACHING" mode activation.
Symbol „E“ 1) Lighting intermittently – correct echo receiving (of the reflected signal) from the measured surface level.
Symbol
ESC OK
www.dinel.cz
Ultrasonic Level Meter ULM-70
ESC OK
1745T E mm 1) Lighting permanently – level meter is locked against unauthorized set-
tings by a password. You must enter the correct password to unlock it.
Setthelevelmeterusing3buttonsplacedonthedisplaymodule.AllsettingsareaccessibleintheGRLM-70set-upmodeaccess.
* Slow flashing while the reflected signal (echo) is received from the measured level.
The type of level meter GRLM-70_ _-_-_-I-B is supplied without a display module DM-70. To set the level meter it is required to join the display module. Once set, the display module can be disconnected and the level meter can measure without him.
The voltage source should be preferably realized as a stabilized power supply unit with safe voltage from 18 to 36 V DC, which can be a part of the evaluation or display device.
In case of strong electromagnetic interferences (EMI), parallel cable ducting with power lines, or when cable length exceeds 30 m we recommended to use shielded cable.
ESC OK
www.dinel.cz
Ultrasonic Level Meter ULM-70
ESC OK
1745T E mm
ESC OK
www.dinel.cz
Ultrasonic Level Meter ULM-70
ESC OK
1745T E mm
Teachingmode activation Units
Displayof measured values
Set-up elements
Echo receiving
Warning signs
Lock of level meter
14© Dinel, s.r.o. GRLM–70
MIN LEVELMAX LEVELUN ITSDAMP INGSENS IT IV ITYTEACH ING
MIN ACTUAL LEVEL0 2 8 7 0 mm
OUTPUT : 0 4 . 0 0 mA
LEVEL : 0 6 0 0 0 mm
DISPLAY: 0 0 0 0 0 %
MAX ACTUAL LEVEL0 2 8 7 0 mm
OUTPUT : 2 0 . 0 0 mA
LEVEL : 0 0 2 5 0 mm
DISPLAY: 0 0 1 0 0 %
START ING
Dinel®
10 . seTTingSetthelevelmeterusing3buttonsplacedonthedisplaymodule(seeChapterSet-upelements).After5min.ofinactivity,thelevelmeterautomaticallyreturnsbacktothemeasurementmode.Ifthepassword isactive, the levelmeterwill bealso locked.Theval-uesthathavenotbeenconfirmedusingthebutton willnotbesaved!After themeter is locked,youcannotchange thesetting!Whenyouattempttoedit,thewords"NOPASSWORD"willappearonthedisplay.Howtounlockthelevelmeterisgivenonpage21.Afterconnectionofthesupplyvoltagetothelevelmeterthedisplayshowsthelogo"Dinel"andthetext"Starting"(approx.30s).Then,thelevelmetergoestothemeasuringmodeandthedisplayshowsthecurrentmeasuredvalue.
10 .1 . basic seTTings
MIN LEVEL and MAX LEVEL
Youcanfreelydefinetheminimum / maximum distance fromthefrontsurfaceofthelevelmeter(item"LEVEL"forcurrents4/20mA).The"DISPLAY"isintendedtosetthevalueshowedonthedisplay.Settingtheunitsisdoneinthe"UNITS".
ACTUAL LEVEL: Actual distance to levelOUTPUT: current 4 mA / 20 mALEVEL: Definition of the min / max levelDISPLAY: The value showed on the display
BAS IC SETT INGSSERV ICED IAGNOST ICCLONE SETT INGSPASSWORDLANGUAGEINFO
MIN LEVELMAX LEVELUN ITSDAMP INGSENS IT IV ITYTEACH ING
UN ITS
LEVEL : mm
DISPLAY: %
SAVED
Ifinthebottomofthedisplayappears(whenenteringthevalues)theinscription"OUTOFLIMITS",thevaluespecifiedfortheitem"LEVEL"isoutsidethemeasuringrangeofthelevelmeter.Iftheinscription"SPANTOOSMALL"isshown,itmustbespecifiedalargerspanbetweenMinandMaxvalues.Formoreinformation,seechapter"Specifications".Thedecimalpointpositionoftheitem'LEVEL'isfirmlyset(accordingtotheselectedunits),intheitem"DISPLAY"itisfreelyadjustable.
After the first start of the levelmeter it is necessary to performthebasicconfiguration(settingofthemeasuringrange,choiceofunits,possiblydamping,sensitivityandteaching).Thesettingsareaccessible in the basicmenu by pressing the "BASICSET-TINGS".
GRLM–70 © Dinel, s.r.o.15
UNITS
LEVEL : mm
DISPLAY: %
DAMP ING
05
UNITS
Levelmetercanprocessandconvertalargenumberofdifferentphysical values.Thesettingisdoneintheitem"UNITS".
MIN LEVELMAX LEVELUN ITSDAMP INGSENS IT IV ITYTEACH ING
LEVEL: Unit selection (mm, cm, m, in, ft)DISPLAY: The unit showed on the display (%, mm, cm, m, in, ft, l, hl, m3, gal, bbl, mA)
DAMPING
Settingthe response timeofthemeasurements.Thefunctionisusefulforsuppressinglevelfluc-tuations,wavesandrapidchangesofthelevel.Thereactiontimewilldependontheexponentialfunction.Dampingwithadefineddelayinsecondsrepresentsthetimewhenexponentialreaches2/3ofitsmaximumvalue.
The damping time can be set in the interval from 0 to 99 s.
1. Toentertothemenupress thesamebuttontoselect"BASICSETTINGS".Then,usingand select"UNITS".
2. Nowthemenuitem"UNITS"isshown. Bypressingthe and buttonmakethesettingsofindividualitems.
3. Bypressing buttonsave thedata.Bynextpressesof thebutton leave themenu.Thelevelmeterreturnstomeasurementmode.
MIN LEVELMAX LEVELUN ITSDAMP INGSENS IT IV ITYTEACH ING
1. Toentertothemenupress thesamebuttontoselect"BASICSETTINGS".Then,usingand select"DAMPING".
2. Nowthemenuitem"DAMPING"isshown. Bypressingthe and buttonmakethesettingsofindividualitems.
3. Bypressing buttonsave thedata.Bynextpressesof thebutton leave themenu.Thelevelmeterreturnstomeasurementmode.
1. Toentertothemenupress thesamebuttontoselect"BASICSETTINGS". Then,usingand select "MINLEVEL"or"MAXLEVEL".
2. Nowitisshowntheitem"MINLEVEL"("MAXLEVEL").Bypressing and settheoutputcur-rent"OUTPUT",thedistanceforthedefinedcurrent"LEVEL"thevalueonthedisplay "DISPLAY".
3. Bypressing buttonsave thedata.Bynextpressesof thebutton leave themenu.Thelevelmeterreturnstomeasurementmode.
16© Dinel, s.r.o. GRLM–70
MIN LEVELMAX LEVELUN ITSDAMP INGSENS IT IV ITYTEACH ING
You can set the sensitivity in four degrees:LOW (1) – MEDIUM (3) – HIGH (5) – USER (1 - 8).
SENS IT IV ITY
SENSITIVITY
Thesettingisdoneusingtwoparameters.Atfirtsthesettingisdefinedinfourstepsofthelevelmetersensitivity.Threestepsarebasicsensitivityandfourthstepcontainsuseroptions.
STEP 1 - „LOW“ – Low sensitivity in case of surrounding interferences affecting the measurement. STEP 3 - „MEDIUM“ – Medium sensitivity (suitable for most applications).STEP 5 - „HIGH“ – Enhanced sensitivity for measured mediums partly absorbing the guided wave (foams)STEP 1 - 8 - „USER“ – user freely adjustable sensitivity in eight steps
Thenissetthethetypeofmaterial.Withthisfunction,youcanchoosefromtwotypesofmaterials.Ifthemeasuredmaterialliquid(water,aqueoussolutions,emulsions,oil,diesel,etc.)selectLIQUID.Ifthemediumissolid(grain,sand,flour,cement,granulates,etc.)selectSOLID.Selectingthetypeofmediatakesintoaccountthedifferentreflectivepropertiesofthemedium.
1. Pressingthebutton isforenterthemenu,pressthesamebuttontoselecttheitem"BASICSETTINGS".Thenbypressingthebuttons and isselectedtheitem"SENSITIVITY".
2. Usingthebuttons and setthepropersensitivity..
3. Afterswitchingthesensitivitytostep"USER",theusercanmovethroughdifferent(eight)levelsofsensitivitybypressing .Press toconfirmtheselection..
4. Nextusingthe and buttonsissetthetypeofmaterial.
5. Aftercompletionofsettingpressingofthe buttonsavesthesetting.Continuebypressingtoexitamenuandthelevelmeterreturnstothemeasuringmode.
You can set the material from two types:
LIQUID – SOLID.
SENS IT IV ITY : LOW
1 2 3 4 5 6 ! 7 ! 8 !
MATER IAL : L IQU ID
Table of recommended sensitivity according to rel. permittivity of the medium is given on page 32
Sensitivity steps 6-8 are highly sensitive, so use them only in exceptional cases for media with a low dielectric constant, or after consultation with the manufacturer.
SENS IT IV ITY
SENS IT IV ITY : USER
1 2 3 4 5 6 ! 7 ! 8 !
MATER IAL : L IQU ID
TEACHING
Themodeservesforsuppressing false reflectionsresultingfromreflectionoftheguidedwavefromroughnessesonwallsofthetank,variouspartitions,mixers,otherobstacles,orifdistanceelectrodefromthewalloftankislowerthan300mm.Thesensorstartingthismodedetectsfalsereflectionsandsavetheminthememory.Thenthesefalsereflectionswillnotaffectthesubse-quentmeasurement(theyaremasked).
TEACH ING
TANK MUST ME EMPTY
START
MIN LEVELMAX LEVELUN ITSDAMP INGSENS IT IV ITYTEACH ING
TEACH ING
TANK MUST ME EMPTY
ARE YOU SURE?
GRLM–70 © Dinel, s.r.o.17
Before starting the mode, it is necessary to com-pletely empty the tank!Incaseof installedmixers, it isnecessary toposi-tionthemixersnearthelevelmeter(turningthemixerbladetotheproximityoftheelectrode).Note: If therearesignificantobstacles in theupperhalfofthetank,multiple false reflectionscanoccurespeciallyinclosedtanks.
ELECTRODE
Settingofthelengthandtypeoftheelectrode.Thefunctionisusedwhenisneededtochangethelength(e.g.shorteningoftheelectrode),orthetypeofelectrodes(e.g.exchangeofrodandropetypeofelectrode).
First,choosethetypeofelectrode.
„ROD“ – for rod-electrodes of type 10„ROPE“ – for rope-electrodes type 30„ANCHORED ROPE“ – for anchored rope electrode type 33
Thensetthelengthoftheelectrode.Eitherselectthe"AUTODETECTION"andthelevelmeterwillmeasurethelengthoftheelectrodeitself,orselectthe"Manual"andthelengthoftheelectrodemustbeenteredmanuallyviathedisplaymodule.
Fig. 23: Turning the mixer blade to the proximity of the electrode before activation
"Teaching" mode10 .2 . serVice seTTings
In the supplemented configuration, you can set parameters ofsensitivity, mapping of false reflections, temperature differencecompensation, behaviour in case of fault conditions or HART® communication.Here,youcansetthesensorintotheinitialstateorresetitaswell.Thesettingsareaccessibleinthebasicmenuundertheitem"SERVICE".
Before setting of the length and type of the electrode it is first necessary to empty the tank in which the level meter is placed, since in this tank will be necessary to run the procedure "TEACHING".
1. Toentertothemenupress thesamebuttontoselect"BASICSETTINGS".Then,usingand select"TEACHING".
2. Nowthemenuitem"TEACHING"isshown. Afterpressingthebutton youareaskedifyouaresuretorunthe"TEACHING"procedure.Bypressing buttonthesystemstarts"teaching"(falsereflectionmapping).Duringthemapping,thedisplayshowsflashingsign"RUNNING".
3. Theprocedureiscompletelyfinishedwhenyoucanseetheinscription"DONE".Itisthenpos-sibletoexitthemenubyrepeatedpressingthebutton .
TEACH ING
TANK MUST BE EMPTY
RUNN ING
TEACH ING
TANK MUST BE EMPTY
DONEPRESS TO EX IT ESC
BAS IC SETT INGSSERV ICED IAGNOST ICCLONE SETT INGSPASSWORDLANGUAGEINFO
n = 100 mm
n - minimal distance of objects from the electrode from level meter
The function of Autodetection can only be used for electrodes longer than 500 mm.
ELECTRODE FA I LURE MODEHARTFACTORY DEFAULTRESET
ELECTRODE
TANK MUST BE EMPTY
T Y P E : R O D
LENGTH: MANUAL 05000 mm
You can choose type of electrode from three options: ROD – ROPE – ANCHORING ROPE
You can enter the length of electrode by two ways: MANUAL – AUTO DETECTION.
18© Dinel, s.r.o. GRLM–70
When the setting of the type and length of the electrodes is carried out outside the tank it is required to insert a metallic plate (with diameter greater than 200 mm) in the place of process connection (thread) before this setting - see Fig. 7. The metal plate must be in good electrical contact with the thread.
The procedure for replacing or shortening the electrode is given in chapter 12 on page 22.
HART
HART® mode(pointtopoint,multidrop)andmultidropmodeaddress setting.Upto15unitscanbeconnectedtoonetwo-wiredcableinthemultidropmode..
In case of the address "00", the point to point mode is enabled. The range from "01" to "15" is reserved for addresses in the multidrop mode.
After you press the button "RUNNING" will be displayed for about 3 sec. After the initial values are set, "DONE" will be appear on the display.
FACTORY DEFAULT
Toreset the initial values ofthelevelmetersetbythemanufacturer,pressthebutton (seetheFactorydefaulttable,p.32.
ELECTRODE FA I LURE MODEHARTFACTORY DEFAULTRESET
HART
00
FACTORY DEFAULT
ARE YOU SURE?
RUNN ING
ELECTRODE FA I LURE MODEHARTFACTORY DEFAULTRESET
POLL ING ADDRESS
FACTORY DEFAULT
NO ECHO: Current in case of echo lossThe values can be set in five steps: 3,75 mA – 4 mA – 20 mA – – 22 mA – LAST (last measured data).
FAILURE MODE
Itdefines the output currentofthelevelmeterincaseofecholoss("NOECHO").
ELECTRODE FA I LURE MODEHARTFACTORY DEFAULTRESET
FA ILURE MODE
NO ECHO: 4 .00 mA
FACTORY DEFAULT
DONEPRESS ESC TO EX IT
MODBUS
ThisitemispartofamenuwithModbusoutputlevelmeterGRLM-70_-_-_-M.ModbusmodeisintendedforthesettingsofthelevelModbusaddresses,baudrateandparitysettings.
MODBUS
ADDRESS : 001
BAUD RATE : 9600
FORMAT: 8N1
ADDRESS: 1 to 247 (default 1) BAUD RATE: 4800, 9600, 19200 (default 9600) FORMAT : 8N1, 8O1, 8E1, 8N2 (default 8N1)
data:
parita: N – non parityO – odd parityE – even parity
8 – number of bits
FORMAT: number of stop bits: 12
MEDIUM TEMPERATUREFA ILURE MODEMODBUSFACTORY DEFAULTRESET
GRLM–70 © Dinel, s.r.o.19
10 .3 . addiTional funcTions
Additionalfunctionsincludemodestodisplaytemperatureinthetankortofindouttheactualflowingcurrentintheloop.Besides,tolockmodificationsusingapassword,languageversionandinforma-tionaboutthelevelmeterversion.Allofthefunctionsareaccessiblefromthemainmenu.displeje).
BAS IC SETT INGSSERV ICED IAGNOST ICCLONE SETT INGSPASSWORDLANGUAGEINFO
DIAGNOSTIC
Itcontainsinformationsaboutactualvalueofdistancetolevelfromlevelmeter"DISTANCETOLEVEL"andaboutcurrentflowingthroughtheloop"CURRENT".Itcanbeusedforexampletochecktheset-tingsoftheconnectedevaluationdeviceordiagnoseanyproblemwiththemeasurementlevel.
D ISTANCE TO LEVEL
01220 mm
DISTANCE TO LEVELCURRENT
BAS IC SETT INGSSERV ICED IAGNOST ICCLONE SETT INGSPASSWORDLANGUAGEINFO
CLONE SETT INGS
NOW CLON ING
CLONE SETT INGS
SENSOR D ISPLAYMODULE
D ISPLAYMODULE
SENSOR
→→
1. Press toenterthemenuandselecttheitem"CLONESETTINGS".Copyingofthesettingsfromthebodyofthelevelmetertodisplaymoduleisdonebyselecting"SENSOR→ DISPLAYMODULE".TotransferthesettingsfromthedisplaymoduletoanotherlevelmeterselecttheitemDISPLAYMODULE→ SENSOR.
CLONE SETT INGS
SENSOR D ISPLAYMODULE
D ISPLAYMODULE
SENSOR
→→
ARE YOU SURE?
CLONE SETTINGS
Thismodeisintendedforcopyingofthelevelmeter(GRLM–70body) configuration into the display module (DM–70) andback.Thedisplaymodule can thenbe removed from the levelmeterbodyandputintoanotherlevelmeterandmaketherethesettingstransfer(cloning).The"CLONESETTINGS"modetransfersalldata,excludingset-tingofthe"Teaching"andHART®.
CUURENT
17 .30 mA
D ISTANCE TO LEVELCURRENT
RESET
Complete restartofthelevelmeter.Thesameeffecthasalsoashort-timeinterruptionofthesupplyvoltage.Toenabletheresetting,pressthebutton .
ELECTRODE FA I LURE MODEHARTFACTORY DEFAULTRESET
RESET
ARE YOU SURE?
During the restart process, "RUNNING" will be displayed. Then the level meter will be automatically turned off and on.
20© Dinel, s.r.o. GRLM–70
Incompatible type of level meter and length of electrode. Transfer of the settings can be realized only with the same type of level meter and with same length of electrode.
1. Usethebuttons and inthemenu"PASSWORD"toselectthemode"ENTER"forenteringthepasswordorthemode"CHANGE"forchangingthepassword(whenactivated,thewordsaredisplayedinversely).Pressthebutton onceagaintoconfirmtheselection.Youcanchangethepasswordonlywhenthelevelmeterisunlocked.Otherwise,thewords"NOPASSWORD"willbedisplayed.
2. Nowyoucaneditthepassword.Theactualediteditemisdisplayedinversely.Pressthebuttontomovetothenextposition(clockwisedirection),button servestochangethevalues(0...9).
3. Aftertheoperationiscompleted,confirmtheediteddatabypressingthebutton .
Display of status information to confirm data:"YES" – correctly edited password"NO" – incorrectly edited password"OK" – the password saved (only in case of "CHANGE")The password is automatically hidden after it is edited or changed ("00000" will appear). To deactivate the password, edit the nu-merical combination "00000" in the mode "CHANGE".
PASSWORD
ENTER
0 0 0 0 0
PASSWORD
CHANGE
0 0 0 0 0
BAS IC SETT INGSSERV ICED IAGNOST ICCLONE SETT INGSPASSWORDLANGUAGEINFO
The data set is not stored into the display module (DM–70). The transfer can not be done. It is necessary to repeat the procedure of the copying the settings in the mode "CLONE SETTINGS".
The level meter with activated password will be automatically locked after 5 minutes of inactivity or after 5 min. from switching to measuring mode. Locking of level meter is indicated in the lower left corner of the screen by the symbol
ESC OK
www.dinel.cz
Ultrasonic Level Meter ULM-70
ESC OK
1745T E mm .
If the password is lost, contact the manufacturer.
PASSWORD
Youcanlockthelevelmeterdataagainstunauthorized editing.Afteractivatingthepasswordthedatamayberead,butcannotbeedited.Ifyoutrytoeditthesettings(withouttruepassword)thedisplayshows"NOPASSWORD".Thepasswordcanbeany5-digitnumericcombination.Thecombinationofnumbers00000isre-servedfordisablingthepassword.
1.
2. Theselectedmodestartsbypressingbutton Duringtransmissionthedisplayshows"NOWCLONING".
3. Aftercompletingtheprocessinthemiddleofthescreendisplays"DONE".Itisthenpossibletoleavethemenuandthemodebypressingthebutton .
CLONE SETT INGS
WARN ING–CLON ING IS NOT POSS IBLE
WRONG SENSOR TYPE
PRESS ESC TO EX IT
CLONE SETT INGS
WARN ING–CLON ING IS NOT POSS IBLE
NO SETT INGS SAVED
PRESS ESC TO EX IT
GRLM–70 © Dinel, s.r.o.21
11 . HarT® coMMunicaTion proTokolUniversalcommunication interfacefordatacommunicationofperipheraldeviceswiththe levelmeter.Datatransmissionrunsthroughthesamelineasthe4÷20mAcurrentloopwithoutimpactonanalogcommunication.
SENSOR
GRLM-70N -10 - I HART
ELECTRODE : 1000 mm
SN: 140015 SW: 2 .1
D ISPLAY MODULE
DM-70
SN: 140085
SW: 4 .1
SENSORD ISPLAY MODULE
SENSORD ISPLAY MODULE
BAS IC SETT INGSSERV ICED IAGNOST ICCLONE SETT INGSPASSWORDLANGUAGEINFO
INFO
Informationaboutthetype,serialnumberandproductiondateofthelevelmeter(type,serialnumber–SNandfirmwareversion–SW).
LANGUAGE
Settingthelanguageofdisplaymenu.
BAS IC SETT INGSSERV ICED IAGNOST ICCLONE SETT INGSPASSWORDLANGUAGEINFO
LANGUAGE
ENGL ISH
You can set three kinds of language:ČESKY – ENGLISH – по русски
HART®
modem
USB / RS232HART®
communicator
GRLM–70
PC
≈ 250 R Power supply unit
HART Specifications
TheversionoftheHARTProtocolisrevision5. UniversalCommands:0,1,2,3,6,11,12,13,14,15,16,17,18,19andCommonsPracticeCommands:34,35,40,42,44,49.
Obr. 24: Typical hardware configuration with HART
22© Dinel, s.r.o. GRLM–70
12 . THe insTallaTion of THe cusToM Measuring elecTrode, excHange or sHorTening of THe elecTrode
1. CreateyourownelectrodeasshownonFig.26.Thelengthoftheelectrodemustbeabout7mmshorterthanthedimension"E"infigure25.Thematerialoftheelectrodeisrecommendedtobeusedstainlesssteeltype1.4571(AISI316Ti)orsimilardependingontheapplication.
2. Onthethreadofpreparedelectrode,applythreadglueforsecuringthreadedfasteners(gluequantityisspecifiedbythemanufactu-rer).Theadhesivemustmeettherequirementsdependonthespecificapplication,forexample:withstandinghightemperatures,corrosivechemicals,resp.contactwithfood.
3. Screwtheelectrodeusingsuitablepliersoraspanner(onthesideoftheelectrode)andaflatspanner10mm(onthesideoftheelectrodeholder)firmlyintotheelectrodeholder.
4. Letthegluedjunctiontoharden,asrecommendedbythegluemanufacturer,thenthelevelmeterisreadyforinstallation.
5. Afteran installation intoanempty tank,setanew levelmeterelectrodetypeandthelength-seeChap.10.2.ELECTRODE
6. Ifnecessary,enteranewrangeoflevelmeasurement-seeChap.10.1.MIN/MAXLEVEL.
Theprocedureofreplacementofthemeasuringelectrode-appliesonlytoversions10,30,33
1. Heatthejunctionplace(threadedconnection)oftheelectrodeandtheelectrodeholder(seeFigures27and28)usingaheatgunatabout120-150°C(or220-250°Cforhightempera-tureversion).
2. Unscrewtheelectrodeusingsuitablepliers(forrodelectrodes)orflatspanner7mm(incaseofropeelectrode)andaflatspanner10mm(onthesideoftheelectrodeholder)awayfromtheelectrodeholder.
3. Applytheglueforsecuringofthreadedfasteners(gluequantityspecifiedbythemanufacturer)tothethreadofthenewelectrode(madeacc.Fig.26.).Theusedgluemustmeettherequi-rementsdependonthespecificapplication, forexample:withstandinghightemperatures,corrosivechemicals,resp.contactwithfood.
Fig. 25: Drawing of the level meter with size "E"
Fig. 26: The drawing of the measuring electrode marked with the threaded connection and grooving
electrode holder
electrode
The installation of the custom measuring electrode, - applies to type 00
striations
dimension
GRLM–70 © Dinel, s.r.o.23
60
Fig. 29: Scheme of the weight for the rope electrode
1. If necessary, remove the rodor ropeelectrode from theelectrodeholder-seepoints1and2of"Theprocedureofreplacementofthemeasuringelectrode"
2. Rodelectrodesareadvisedtobeshortenedbyusingasuitablehacksawanddeburrtheendoftheelectrode.Fortheropeelectrodeisneededtoloosenthreefixingscrewsontheweightandpullouttheropeend,seeFigure29.Makesurethattheropelengthaftertrimmingiscorrect-thecableisembeddedinweighttoapprox.60mm.Shorteningtheropeisbestdonebymeansofsidecuttingpliers.Takecaretoavoidfrayingoftheropeend.
3. Inserttheendoftheropeintotheweightagainandsecurebytighteningofthethreescrews.
4. Ifyouunmountedtheelectrodefromtheelectrodeholder,re-assemblethem-seeparagraphs3to7of"Theprocedureofreplacementofthemeasuringelectrode"
Places to be heated, see "The procedure of replacement of
the measuring electrode"
Fig. 27: The threaded connection of the electrode holder with the rod electrode
Fig. 28: The threaded connection of the electrode holder with the rope electrode
1. 2. 3. 4. Screwtheelectrodeusingsuitablepliersoraspanner(onthesideoftheelectrode)andaflat
spanner10mm(onthesideoftheelectrodeholder)firmlyintotheelectrodeholder..5. Letthegluedjunctiontoharden,asrecommendedbythegluemanufacturer,thenthelevel
meterisreadyforinstallation.6. Afteraninstallationintoanemptytank,setanewlevelmeterelectrodetypeandthelength
-seeChap.10.2.ELECTRODE7. Ifnecessary,enteranewrangeoflevelmeasurement-seeChap.10.1.MIN/MAXLEVEL.
Shortening of the measuring electrode - applies only to versions 10, 30, 33
24© Dinel, s.r.o. GRLM–70
13 . order code
14 . accessories
15 . safeTy, proTecTion, coMpaTibiliTy and explosion proof
Standard – included in the price of the level meter
• 1xofseal(asbestosfree),• otherseals(PTFE,Al,etc.)
volitelné – za příplatek
• FixingsteinlesssteelnutsG1“
• SteelorSteinlesssteelwelding
flangeON-G1",NN-G1"
ThelevelmeterGRLM–70isequippedwithprotectionagainstreversepolarityandoutputcurrentoverload.ProtectionagainstdangerouscontactissecuredbylowsafetyvoltagethatcomplieswithEN332000-4-41.ElectromagneticcompatibilityaccordingtoEN55022/B,EN61326/Z1andEN61000-4-2to6.
The explosion proof of GRLM-70Xi (XiT) is ensured by compliance with the followingstandards: EN 60079-0: 2007; EN 60079-11: 2007 and BS EN 60079-26: 2007. ExplosionproofofGRLM-70Xi(XiT)isprovenbyFTZÚ-AO210Ostrava-Radvanice:certificateNo:FTZÚ13ATEX0212X
Performance:
Electrode performance: 0 – without electrode10 – Uncoated St. steel rod electrode11 – Fully coated St. steel rod electrode (PFA)12 – Fully coated St. steel rod electrode (FEP)20 – Uncoated St. steel rod electrode with reference tube30 – Uncoated St. steel rope electrode and weight32 – Fully coated rope electrode and weight (FEP + PTFE)33 – Uncoated St. stel rope electrode with anchorage34 – Coated rope electrode (Polyamid) and uncoated weight35 –Coated rope electrode (Polyamid) and uncoated anchorage
N –Normal - usable in non-explosive areas only Xi – Explosion proof - suitable for explosive areas (gas, vapor) Xd – Explosion proof - suitable for flammable dust areas NT, XiT, XdT – High temperature performance
GRLM – 70 –
Output type: I – currentM – RS-485 (Modbus RTU)
– –
Process connection: G – thread G1"
E Length electrode in mm– –
Electrical connection: B – short cable outletH – outlet for protective conductor
Set-up elements: D – basic version with displayL – without display, metal lid
GRLM–70 © Dinel, s.r.o.25
LevelmeterslabeldataGRLM–70N(T)
Symbolofproducer:logoDinel®
Internetaddress:www.dinel.czCountryoforigin:MadeinCzechRepublicLevelmetertype:GRLM–70N_–__–G–IE______Serialnumber:Ser.No.:______–(fromtheleft:productionyear,serialproductionnumber)Supplyvoltage:Ui= 18...36V=Outputcurrentrange:I =4...20mAAmbienttemperaturerange:ta=-30...+70°CProtectionclass:IP67Compliancemark: Electro-waste take-back system mark:
16 . use, ManipulaTion and MainTenance
Special conditions for safe use of variant GRLM-70XiLevelmetersGRLM-70Xi(XiT)aredesignedforconnectiontointrinsicallysafecircuitswithgalvanicisolation.Ifyouusethedevicewithoutgalvanicisolation(Zenerbarriers)itisnecessarytooffsetapotentialbetweenthesensorandthegroundingpointofthebarriers.Maximumoutputparametersofintrinsicallysafeunitsmustcorrespondwithlimitinputparametersofthelevelmeter.Intheevaluationofintrinsicsafetyofthecircuitmustbetakenintoaccounttheparametersoftheconnectedcable(especiallyitsinductanceandcapacitance).TheelectrodepartoftheGRLM-70Xi(XiT)canbeplacedinzone0,thebodywithelectronicscanbeplacedinzone1.Inzone20canbeplacedwholelevelmeter.
17 . Marking of labels
The levelmeterdoesnot requireanypersonnel for itsoperation.Follow-updisplayingdevice isusedtoinformthetechnologicalentityoperatingpersonnelonthemeasuredsubstancelevelheightduringtheoperation.
Maintenanceofthisequipmentconsistsinverificationofintegrityofthelevelmeterandofthesup-plycable.Incaseanyvisibledefectsarediscovered,themanufacturerorresellerofthisequipmentmustbecontactedimmediately.
It is forbidden to perform any modifications or interventions into the GRLM–70 level meter without manufacturer's approval. Potential repairs must be carried out by the manufacturer or by a manufacturer authorized service organization only.
Installation, commissioning, operation and maintenance of the GRLM–70 level meter has to be carried out in accordance with this instruction manual; the provisions of regulations in force regarding the installation of electrical equipment have to be adhered to.
The level meter must be installed to prevent tensile overload of the rope electrode.
0 – without electrode10 – Uncoated St. steel rod electrode11 – Fully coated St. steel rod electrode (PFA)12 – Fully coated St. steel rod electrode (FEP)20 – Uncoated St. steel rod electrode with reference tube30 – Uncoated St. steel rope electrode and weight32 – Fully coated rope electrode and weight (FEP + PTFE)33 – Uncoated St. stel rope electrode with anchorage34 – Coated rope electrode (Polyamid) and uncoated weight35 –Coated rope electrode (Polyamid) and uncoated anchorage
N –Normal - usable in non-explosive areas only Xi – Explosion proof - suitable for explosive areas (gas, vapor) Xd – Explosion proof - suitable for flammable dust areas NT, XiT, XdT – High temperature performance
26© Dinel, s.r.o. GRLM–70
LevelmeterslabeldataGRLM–70Xi (XiT):
Symbolofproducer:logoDinel®
Internetaddress:www.dinel.czCountryoforigin:MadeinCzechRepublicLevelmetertype:GRLM–70Xi_–__–G–IE______Serialnumber:Ser.No.:______–(fromtheleft:productionyear,serialproductionnumber)Supplyvoltage:Ui= 18...36V=Outputcurrentrange:I =4...20mALimitoperatingparameters:Ui= 30V=,Ii=132mA;Pi=0,99W;Ci=370nF;Li=0,9mHAmbienttemperaturerange:ta=-30...+70°CLabelofnon-explosivedevice:Performance:II1/2GExiaIIBT5Ga/GbNumberofcertificateofintrinsicallysafety:FTZÚ13ATEX0212XProtectionclass:IP67Compliancemark: ,No.ofauthorizedpersonexaminingcontrolofsystemquality:1026Electro-wastetake-backsystemmark:
Real label size is 70x20mm.
ÚdajenaštítkuhladinoměruGRLM–70Xd (XdT):
Symbolofproducer:logoDinel®
Internetaddress:www.dinel.czCountryoforigin:MadeinCzechRepublicLevelmetertype:GRLM–70Xd_–__–G–IE______,orGRLM–70Xd_–__–G–ME______Serialnumber:Ser.No.:______–(fromtheleft:productionyear,serialproductionnumber)Supplyvoltage:Ui= 18...36V=Outputcurrentrange:I =4...20mAorcommunication:RS-485(ModbusRTU)Ambienttemperaturerange:ta=-30...+70°CLabelofnon-explosivedevice: Performance:II1DExtaIIICT85°C...T300°CDa,neboII1DExtaIIICT100°C...T300°CDaNumberofcertificateofintrinsicallysafety:FTZÚ14ATEX____XProtectionclass:IP67Compliancemark: ,No.ofauthorizedpersonexaminingcontrolofsystemquality:1026Electro-wastetake-backsystemmark:
GRLM–70 © Dinel, s.r.o.27
18 .
Men
u s
Tru
cTu
reM
INM
AX
05
00
SE
NS
OR
GR
LM
-70
N-1
0-I
HA
RT
EL
EC
TR
OD
E:
10
00
mm
SN
: 1
40
01
5
SW
: 2
.1
DIS
PL
AY
MO
DU
LE
DM
-70
SN
: 1
40
08
5
SW
: 4
.1
SE
NS
OR
DIS
PL
AY
MO
DU
LE
BA
SIC
SE
TT
ING
SS
ER
VIC
ED
IAG
NO
ST
ICC
LO
NE
SE
TT
ING
SP
AS
SW
OR
DL
AN
GU
AG
EIN
FO
BA
SIC
SE
TT
ING
SS
ER
VIC
ED
IAG
NO
ST
ICC
LO
NE
SE
TT
ING
SP
AS
SW
OR
DL
AN
GU
AG
EIN
FO
BA
SIC
SE
TT
ING
SS
ER
VIC
ED
IAG
NO
ST
ICC
LO
NE
SE
TT
ING
SP
AS
SW
OR
DL
AN
GU
AG
EIN
FO
BA
SIC
SE
TT
ING
SS
ER
VIC
ED
IAG
NO
ST
ICC
LO
NE
SE
TT
ING
SP
AS
SW
OR
DL
AN
GU
AG
EIN
FO
BA
SIC
SE
TT
ING
SS
ER
VIC
ED
IAG
NO
ST
ICC
LO
NE
SE
TT
ING
SP
AS
SW
OR
DL
AN
GU
AG
EIN
FO
BA
SIC
SE
TT
ING
SS
ER
VIC
ED
IAG
NO
ST
ICC
LO
NE
SE
TT
ING
SP
AS
SW
OR
DL
AN
GU
AG
EIN
FO
BA
SIC
SE
TT
ING
SS
ER
VIC
ED
IAG
NO
ST
ICC
LO
NE
SE
TT
ING
SP
AS
SW
OR
DL
AN
GU
AG
EIN
FO
MIN
LE
VE
LM
AX
LE
VE
LU
NIT
SD
AM
PIN
GS
EN
SIT
IVIT
YT
EA
CH
ING
AC
TU
AL
02
87
0m
m
OU
TP
UT
:0
4.0
0m
A
LE
VE
L:
06
00
0m
m
DIS
PL
AY
:0
00
00
%
AC
TU
AL
02
87
0m
m
OU
TP
UT
:2
0.0
0m
A
LE
VE
L:
00
25
0m
m
DIS
PL
AY
:0
01
00
%
UN
ITS
LE
VE
L:
mm
DIS
PL
AY
:%
DA
MP
ING
EL
EC
TR
OD
E F
AIL
UR
E M
OD
EH
AR
TF
AC
TO
RY
DE
FA
UL
TR
ES
ET
TE
AC
HIN
G
TA
NK
MU
ST
BE
EM
PT
Y
ST
AR
T
EL
EC
TR
OD
E
TA
NK
MU
ST
BE
EM
PT
Y
TY
PE
: R
OD
LE
NG
TH
: M
AN
UA
L
05
00
0 m
m
FA
ILU
RE
MO
DE
NO
EC
HO
: 4
.00
mA
HA
RT
RE
SE
T AR
E Y
OU
SU
RE
?
FA
CT
OR
Y D
EF
AU
LT
AR
E Y
OU
SU
RE
?
DIS
TA
NC
E T
O L
EV
EL
01
22
0 m
m
DIS
TA
NC
E T
O L
EV
EL
CU
RR
EN
TC
UR
RE
NT 1
7.3
0 m
A
CL
ON
E S
ET
TIN
G
SE
NS
OR
DIS
PL
AY
MO
DU
LE
DIS
PL
AY
MO
DU
LE
SE
NS
OR
→ →
PA
SS
WO
RD
EN
TE
R
00
00
0
LA
NG
UA
GE
EN
GL
ISH
PO
LL
ING
AD
DR
ES
S
SE
NS
ITIV
ITY
SE
NS
ITIV
ITY
: M
ED
IUM
1 2
3
4 5
6!
7!
8!
MA
TE
RIA
L:
LIQ
UID
28© Dinel, s.r.o. GRLM–70
19 . specificaTions
TecHnical specificaTions– leVel MeTer
Supplyvoltage GRLM–70N–__GRLM–70Xi–__GRLM–70Xd–__
18...36VDC18...30VDC18...36VDC
Output GRLM–70_–__-_-IGRLM–70_–__-_-M
4...20mA,HART®
RS-485withModbusRTUCurrentconsumption GRLM–70_–__-_-IGRLM–70_–__-_-M
4...20mA/max.22mA30mA
Basicerror1)(forreferencereflector) -GRLM-70_-20inarea0,1–0,2m/0,2–2,0m/2,0 –40m-othertypesinarea0,1–0,2m/0,2–2,0m/2,0 –40m
± 5mm/±3mm/±2mm± 10mm/±4mm/±2mm
Resolution 1mmMaximallengthofmeasuringelectrode GRLM–70_–10GRLM–70_–11(12)GRLM–70_–20GRLM–70_–30(33)GRLM–70_–32
8m2m3m40m12m
Deadzone2)-formeasur.sensitivity-low,medium,user(1-4)-high,user(5)-user(6,7)-user(8)
100/0mm3)150/50mm3)200/50mm3)250/50mm3)
ElectricalparametersforvariantsXi(XiT) –max.internalvalues Ui=30VDC;Ii=132mA;Pi=0,99W;Ci=370nF;Li=0,9mH
Measurementsensitivity(8degrees) low(1)-medium(3)-high(5)-user(1-8)
Failureindication (echoloss,internal failure)Adjustableinmodes: 3,75mA,4mA,20mA,
22mA,LAST4)
Damping 1..99s
Warmuptime cca60sInternalresistance/Electricstrength(Electrode-Housing) 10kΩCouplingcapacity/Electricstrength(Housing-Supplyleads) 5nF/500VACMaximalcurrentoutputloadresistanceforU=24VDC U=22VDC U=20VDC
Rmax=270Ω5)Rmax=180ΩRmax=90Ω
Maximumtensilestrengthoftheropeelectrode 1400kgTighteningtorqueofcablegland GRLM–70N(NT,Xi,XiT)GRLM–70Xd(XdT)
3Nm(plastic)7Nm(steel)
Protectionclass IP67
Processconnection screwingwiththreadG1"
Recommendedcable GRLM–70_–_-_-IGRLM–70_–_-_-M
PVC2x0,75mm2
PVC2x2x0,25mm2
Weight(withoutelectrode) cca0,5kg (1kgvariantNT,XiT)
GRLM–70 © Dinel, s.r.o.29
0
2 mm
-2 mm
3 mm5 mm
-3 mm-5 mm
0,2 m0,1 m
2 m0,2 m
0,01 m
E (pro GRLM-70_-20)
6 mm
-6 mm
- hatched place shows dead zone1)
- hatched place shows dead zone6)
1) Error is larger at the beginning and end of the rod or rope electrode. More detailed informations can be found in Fig. 30 and 31.2) Dead zone = Blind zone = Blocking distance3) The length of dead zone at the beginnig / at the end of the electrode. (The length of dead zone is 110 mm at the end of rope electrode.)4) Level meter displays last measured value.5) Including 250R resistor in case of HART connection.6) hatched space applies for set measurement sensitivities: low (1), moderate (3) or user (1-4). When the sensitivity set to high (5), or custom (5-8), the dead zone at the beginning and at the end of the electrode extends, see "Table of sensitivity of the measurement" on page 28.
Fig. 30: The graph of the measurement errors along the rod electrode with reference tube
Fig. 31: The graph of the measurement errors along the rod and wire electrode
for
forfor
30© Dinel, s.r.o. GRLM–70
used MaTerials
Sensor part Variants Standard materialLid Alltypes aluminiumwithpowdercoating
Glass Alltypes polycarbonate
Body Alltypes aluminiumwithpowdercoating
Housingwiththread Alltypes St.SteelW.Nr.1.4571(AISI316Ti)
ElectrodeGRLM-70_-10(11,20)GRLM-70_-12GRLM-70_-30(32,33,34,35)
St.SteelW.Nr.1.4571(AISI316Ti)St.SteelW.Nr.1.4301(AISI304)St.SteelW.Nr.1.4404(AISI316L)
Electrodecoating
GRLM-70_-11GRLM-70_-12GRLM-70_-32GRLM-70_-34,35
PFAFEPFEPPA
Referencetube GRLM-70_-20 St.SteelW.Nr.1.4301(AISI304)
Weight GRLM-70_-30 St.SteelW.Nr.1.4301(AISI304)
Weightcoating GRLM-70_-32 PTFE
Anchorage GRLM-70_-33 St.SteelW.Nr.1.4301(AISI304)
Displaymodule Alltypes plasticmaterialPOM
TecHnical specificaTions – display Modul
Typeofdisplay matrixOLED
Resolution 128x64pixels
Heightofdigits/Numberofdisplaydigitsofmeasuredvalues 9mm/5digits
Colourofdisplay yellow
Typeofbuttons membrane
Ambienttemperaturerange -30...+70°C
Weight 46g
deVice classificaTion (according to EN 60079-10-1 and EN 60079-10-2)GRLM–70N Performancefornon-explosiveareas
GRLM–70NT Hightemperatureperformancefornon-Exareas(max.200°C)
GRLM–70Xi(XiT)Performanceforexplosiveareas(gasesorvapour) II1/2GExiaIIBT6Ga/GbwithISSU1)
electrodepartzone0,housingzone1
GRLM–70Xd(XdT)Performanceforflammabledustareas II1DExtaIIICT85°C…T300°CDa(current), II1DExtaIIICT100°C…T300°CDa
(Modbus),wholelevelmeterzone201) Intrinsically safe supply unit (for example: Dinel IRU–420).
GRLM–70 © Dinel, s.r.o.31
Themaximumallowabletemperatureofthemedium,processconnectionandambienttemperaturedependsinGRLM-70Xi(XiT)atthedesiredtemperatureclass(seetab.MaximumtemperaturesfortheperformanceXi(XiT)category1/2Gandtab.).Thetemperaturevaluecannotbeexceeded,be-causethehotsurfaceofthedevicecouldcauseignitionofanexplosiveorflammableatmosphere.Atthesametimecannotexceedthemaximumtemperatureforthedifferentvariantsoftheelectro-des(Tableoftemperaturedurability).
TeMperaTure and pressure resisTiViTy (performance N, Xi)
Variants / Performance temperature tp temperature tm temperature ta
Max. operation pressure for temp. tp
to 30°C to 85°CGRLM–70_–10(20) -40°C ... +85°C -40°C ... +300°C -30°C ... +70°C 15 MPa 10 MPaGRlM –70_–11(12) -40°C ... +85°C -40°C ... +200°C -30°C ... +70°C 4 MPa 2,5 MPaGRLM–70_–30(33) -40°C ... +85°C -40°C ... +200°C -30°C ... +70°C 15 MPa 10 MPaGRLM–70_–32 -40°C ... +85°C -40°C ... +130°C -30°C ... +70°C 1 MPa 0,5 MPaGRLM–70_–34(35) -40°C ... +85°C -40°C ... +95°C -30°C ... +70°C 15 MPa 10 MPa
tp – Temperature in process connection place
tm – Medium operating temperature
ta – Ambient temperature range(on housing)
TeMperaTure resisTiViTy (performance NT, XiT)
Variants / Performance temperature tp temperature tm temperature ta
GRLM–70_T–10(20) -40°C ... +200°C -40°C ... +300°C -30°C ... +70°CGRlM –70_T–11(12) -40°C ... +200°C -40°C ... +200°C -30°C ... +70°CGRLM–70_T–30(33) -40°C ... +130°C -40°C ... +200°C -30°C ... +70°CGRLM–70_T–32 -40°C ... +130°C -40°C ... +130°C -30°C ... +70°CGRLM–70_T–34(35) -40°C ... +130°C -40°C ... +95°C -30°C ... +70°C
Note: For correct function of the level meter must not be exceeded any of the temperature range (tp, tm or ta).
MaxiMal TeMperaTures for perforMance xi(xiT) caTegory 1/2gtemp. class temperature tp temperature tm temperature ta
T5 -40°C ... +90°C -40°C ... +98°C -30°C ... +70°CT4 -40°C ... +125°C -40°C ... +133°C -30°C ... +70°CT3 -40°C ... +190°C -40°C ... +198°C -30°C ... +70°CT2 -40°C ... +200°C -40°C ... +298°C -30°C ... +70°CT1 -40°C ... +200°C -40°C ... +300°C -30°C ... +70°C
deVice surface TeMperaTure for perforMance xd(xdT) caTegory 1d part of level meter device surface
temperatureelectrodeGRLM-70_-_-_-IGRLM-70_-_-_-M
medium temp. tm +5°Cmedium temp. tm +10°C
housing, electronic partGRLM-70_-_-_-I
GRLM-70_-_-_-M
temperature tp +15°Ctemperature ta +15°Ctemperature tp +30°Ctemperature ta +30°C
32© Dinel, s.r.o. GRLM–70
facTory defaulT
GRLM–70_-_ _
MINLEVEL(Distancetomin.level) accordingtothelengthoftherod(rope)electrode
MAXLEVEL(Distancetomax.level) 100mm
UNITS mm;%;°C
DAMPING 2
SENSITIVITY MEDIUM
MEDIUM LIQUID
FAILUREMODE–NOECHO 4,00mA
POOLINGADDRESS(HART®) 00
PASSWORD Nopassword
1) Dead zone = Blind zone = Blocking distance
pressure resisTiViTy (performance NT, XiT)
Variants / PerformanceMax. operation pressure for temp. tp
to 30°C to 85°C to 130°C to 160°C to 200°CGRLM–70_T–10(20) 15 MPa 10 MPa 3 MPa 2 MPa 1 MPaGRlM –70_T–11(12) 4 MPa 2,5 MPa 2 MPa 1,5 MPa 0,3 MPaGRLM–70_T–30(33) 15 MPa 10 MPa 3 MPa - -GRLM–70_T–32 1 MPa 0,5 MPa 0,1 MPa - -
recoMMended sensiTiViTy depending on THe dielecTric consTanT of THe MediuM
Degrees SensitivityDielectric constant of the medium
for length of electrode to 20 m for length of electrode over 20 m
8! USER (extreme) 1,8 .. 1,9 2 .. 3
7! USER (extreme) 1,9 .. 2 4 .. 6
6! USER (extreme) 2 .. 3 6 .. 8
5 HIGH 3 .. 4 8 .. 10
4 USER 4 .. 6 10 .. 13
3 MEDIUM 6 .. 8 13 .. 16
2 USER 8 .. 10 16 .. 20
1 LOW 10 and more 20 and more
GRLM–70 © Dinel, s.r.o.33
34© Dinel, s.r.o. GRLM–70
Dinel, s.r.o.U Tescomy 249
760 01 ZlínCzech Republic
Tel.: +420 577 002 003Fax: +420 577 002 007E-mail: [email protected]
www.dinel.cz
The lastest version of this instruction manual can be found at www.dinel.czVersion:
industrial electronics
9/2015