DIGITAL VOLTAGE REGULATOR DIGITAL+VOLTAGE+REGULATOR+ … · StacoDVR-5 60kVA to 6000kVA StacoDVR)5+...

5
StacoDVR-5 60kVA to 6000kVA DIGITAL VOLTAGE REGULATOR DATASHEET April 2016 StacoDVR5: 3ph. Voltage Regulator Why choose a voltage regulator The availability of steady voltage supply is critical for a number of situations involving voltage sensitive equipment. Whether because of the unreliability of the energy distribution or the presence of electronically controlled machinery and systems, high quality voltage supply regardless of the incoming fluctuation is very often the key for ensuring efficiency and reliability to the final user. Disrupted production, loss of data security failure, machinery faults, inaccurate information and domestic inconvenience are only a few examples of possible problems caused by unstable supply. Of course, all this means increased costs. The voltage regulator has proved to be an efficient solution in order to prevent from potentially dangerous situation due to input voltage instability. A voltage regulator is a device able to respond to changes in the voltage level on the input line caused by sags (due to undersized distribution lines, connection of large loads to the network, ground faults, etc.) and surges (generated by disconnection of large loads, increased voltage at the generating plant, atmospheric events, etc.). The duration of such phenomena depends on their cause and is not easily predictable. Sags are generally more common especially where the distribution is not efficient. The result of the regulator operation is a steady output voltage for the load. Applications Voltage regulators are suitable for a wide range of applications. Characteristics The regulators are designed and built in compliance with the European Directives concerning CE marking 2006/95/EEC (Low Voltage Directive) and 2004/EEC (Electromagnetic Compatibility Directive) and can be used in A and B environments according to EN61439 1/2. StacoDVR5 regulators use columnar voltage regulators which and cover the range from 60kVA to 6000kVA , allowing for the choice of several input voltage variation percentages within a broad range (from +30% up to 45%). The regulation is performed independently on each phase and the presence of the neutral wire is required . The StacoDVR5 regulator is used when the main is unbalanced and it is suitable for supplying threephase loads, twophase loads and singlephase loads. Output voltage reduced and regulated to the desired value with ±0.5% accuracy High power availability High reliability and ruggedness use with asymmetrical input supply and singlephase loads or unbalanced threephase loads; StacoDVR

Transcript of DIGITAL VOLTAGE REGULATOR DIGITAL+VOLTAGE+REGULATOR+ … · StacoDVR-5 60kVA to 6000kVA StacoDVR)5+...

Page 1: DIGITAL VOLTAGE REGULATOR DIGITAL+VOLTAGE+REGULATOR+ … · StacoDVR-5 60kVA to 6000kVA StacoDVR)5+ DIGITAL VOLTAGE REGULATOR DATASHEET DIGITAL+VOLTAGE+REGULATOR+ April!2016! StacoDVR)5:3)ph.VoltageRegulator+

 

StacoDVR-5 60kVA to 6000kVA StacoDVR-­‐5  

DIGITAL VOLTAGE REGULATOR DATASHEET DIGITAL  VOLTAGE  REGULATOR  

 

April  2016  

StacoDVR-­‐5:  3-­‐ph.  Voltage  Regulator  Why choose a voltage regulator The  availability  of  steady  voltage  supply  is  critical  for  a  number  of  situations  involving  voltage  sensitive  equipment.  Whether  because  of  the  unreliability  of  the  energy  distribution  or  the  presence  of  electronically  controlled  machinery  and  systems,  high  quality  voltage  supply  regardless  of  the  incoming  fluctuation  is  very  often  the  key  for  ensuring  efficiency  and  reliability  to  the  final  user.  Disrupted  production,  loss  of  data  security  failure,  machinery  faults,  inaccurate  information  and  domestic  inconvenience  are  only  a  few  examples  of  possible  problems  caused  by  unstable  supply.  Of  course,  all  this  means  increased  costs.  The  voltage  regulator  has  proved  to  be  an  efficient  solution  in  order  to  prevent  from  potentially  dangerous  situation  due  to  input  voltage  instability.  A  voltage  regulator  is  a  device  able  to  respond  to  changes  in  the  voltage  level  on  the  input  line  caused  by  sags  (due  to  undersized  distribution  lines,  connection  of  large  loads  to  the  network,  ground  faults,  etc.)  and  surges  (generated  by  disconnection  of  large  loads,  increased  voltage  at  the  generating  plant,  atmospheric  events,  etc.).  The  duration  of  such  phenomena  depends  on  their  cause  and  is  not  easily  predictable.  Sags  are  generally  more  common  especially  where  the  distribution  is  not  efficient.  The  result  of  the  regulator  operation  is  a  steady  output  voltage  for  the  load.  

Applications Voltage  regulators  are  suitable  for  a  wide  range  of  applications.    

     

Characteristics The  regulators  are  designed  and  built  in  compliance  with  the  European  Directives  concerning  CE  marking  2006/95/EEC  (Low  Voltage  Directive)  and  2004/EEC  (Electromagnetic  Compatibility  Directive)  and  can  be  used  in  A  and  B  environments  according  to  EN61439-­‐1/-­‐2.  StacoDVR-­‐5  regulators  use  columnar  voltage  regulators  which  and  cover  the  range  from  60kVA  to  6000kVA,  allowing  for  the  choice  of  several  input  voltage  variation  percentages  within  a  broad  range  (from  +30%  up  to  -­‐45%).  The  regulation  is  performed  independently  on  each  phase  and  the  presence  of  the  neutral  wire   is  required.  The  StacoDVR-­‐5  regulator  is  used  when  the  main  is  unbalanced  and  it  is  suitable  for  supplying  three-­‐phase  loads,  two-­‐phase  loads  and  single-­‐phase  loads.   Output  voltage  reduced  and  regulated  to  the  desired  value  with  ±0.5%  accuracy   High  power  availability   High  reliability  and  ruggedness   use  with  asymmetrical  input  supply  and  single-­‐phase  loads  or  unbalanced  three-­‐phase  loads;  

StacoDVR  

Page 2: DIGITAL VOLTAGE REGULATOR DIGITAL+VOLTAGE+REGULATOR+ … · StacoDVR-5 60kVA to 6000kVA StacoDVR)5+ DIGITAL VOLTAGE REGULATOR DATASHEET DIGITAL+VOLTAGE+REGULATOR+ April!2016! StacoDVR)5:3)ph.VoltageRegulator+

 

StacoDVR-5 60kVA to 6000kVA StacoDVR-­‐5  

DIGITAL VOLTAGE REGULATOR DATASHEET DIGITAL  VOLTAGE  REGULATOR  

 

April  2016  

functionality  based  on  the  ‘rms  voltage’.  The  control  supplies  the  load  to  a  correctly  regulated  voltage  even  with  non-­‐sinusoidal  waves,  frequently  found  in  habitual  applications.  These  waveforms  are  caused  by  the  presence  of  (for  example)  converters,  transformers  with  saturated  core,  non-­‐linear  loads,  pulses,  connecting  or  disconnecting  transients,  etc.    

regulation  performed  independently  on  each  single  phase  (referring  to  the  neutral,  which  must  be  available  and  connected);   fully  functioning  with  load  charge  variable  from  0  to  100%  and  100%  phase  unbalance.   up  to  30%  harmonic  content  admitted  on  the  load  current.   insensitivity  to  the  load  power  factor   no  harmonic  distortions  generated  on  the  output  voltage   absence  of  batteries  and  consequent  easy  storage  and  handling   remote  monitoring  The  STACO  DVR-­‐5  regulator   is  provided  with  an  electronic  voltage  regulator  protection  system  which  act ivates  in  case  of  overload  on  the  voltage  regulator.   In  such  condit ion  the   load  supply   is  not   interrupted,  but  the  regulator  output  voltage   is  automatical ly  set  to  the   lower  between  the  mains  voltage  and  the  pre-­‐set  output  voltage.  The  service  continuity   is  guaranteed,  a lthough  the  voltage   is  not  regulated.  When  the  overload  condit ion  ceases  to  exist ,  the  regulator  switches  automatical ly  back  to  regular  functioning.  

Main components and working principle three-­‐phase  ‘buck/boost’  transformer   motorised  three-­‐phase  autotransformer  with  continuously  

variable  transformer  ratio   microprocessor-­‐based  control  system  The  control  system  refers  the  output  voltage  value  to  the  set  nominal  one.  If  the  voltage  is  outside  the  accuracy  range  (±0.5%),  the  control  drives  the  motorized  autotransformer  gear-­‐motor.  By  doing  so,  its  rollers  change  position  thus  varying  the  voltage  drawn  and  supplied  to  the  buck/boost  transformer  primary  winding.  Being  the  secondary  voltage  of  the  buck/boost  transformer  in  phase  or  in  opposition  to  the  supply,  the  voltage  drawn  from  the  motorized  autotransformer  is  added  or  subtracted  to  the  mains  voltage,  thus  compensating  its  variations.  

DSP microprocessor-based control board Totally  digitalised  control  via  DIGITAL  S IGNAL  PROCESSOR  (DSP)  microprocessors   control  CPU   measure  CPU  output  voltage  supervisor  CPU  (bodyguard)  

External control panel  Input  and  output  digital  multimeter  Keypad  to  surf  through  the  menus  available  on  the  local  display  Display  indicating  alarms,  setting  parameters  and  connecting  data.  USB  ports  to  update  the  base  board  software  and  download  the  stored  data  Phase  LEDs  Alarm  LEDs    

Protections Voltage  reset  to  the  minimum  value  in  case  of  black-­‐out   Motor  stop  in  case  of  motor  overload   Motor  stop  in  case  of  motor  short-­‐circuit   Overload  on  the  voltage  regulator   Roof  fans  activation  managed  by  the  control  system   Automatic  c ircuit  breaker  to  protect  the  

voltage  regulator  v ia  digital  control  e lectronic  protection    

Protection  of  voltmeter  lines  and  motor  supplying  circuits  (fuses)   Base  board  protection  (fuses)   Fan  relays  protection  (fuses)   Input  SPD  Surge  Arrestor  Class   I  protects  against  

l ightning   Output  SPD  Surge  Arrestor  Class   I I  protects  against  

transients  &  spikes  

 

INPUT OUTPUT

PVI: input digital multimetreTM: buck/boost transformerVT: motorized autotransformerM: DC gearmotorN1: base boardN2: signalling LED board

PVO: output digital multimetreCOM: remote communication board

M M M

COM

GPRSEthernet

N1 N2

USB

TM

TM

TM

VTVTVT

PVI PVO

U1

V1

W1

N

U2

V2

W3

N

Page 3: DIGITAL VOLTAGE REGULATOR DIGITAL+VOLTAGE+REGULATOR+ … · StacoDVR-5 60kVA to 6000kVA StacoDVR)5+ DIGITAL VOLTAGE REGULATOR DATASHEET DIGITAL+VOLTAGE+REGULATOR+ April!2016! StacoDVR)5:3)ph.VoltageRegulator+

 

StacoDVR-5 60kVA to 6000kVA StacoDVR-­‐5  

DIGITAL VOLTAGE REGULATOR DATASHEET DIGITAL  VOLTAGE  REGULATOR  

 

April  2016  

Signals Line  voltage  out  of  range  ('Maximum  voltage'  and  

'Minimum  voltage'  LEDs)   Excessive  phase  current  ('Maximum  current'  LED)   Regulation  reaching  the  limit  switches  ('Top  limit  switch'  

and  'Bottom  limit  switch'  LEDs)  

Voltage  regulator  rollers  overheating  ('Roller  overheating'  LED)   Enclosure  overheating  ('Overheating'  LED)   Line  phase  failure  on  the  line  (Local  display)   Alteration  of  the  three-­‐phase  cycle  (Local  display)  

The  intervention  of  any  of  the  above  mentioned  protections  (except  for  the  fuses  intervention)  is  signalled  by  luminous  and  acoustic  alarms.  

Remote communication system Thanks  to  its  capability  to  connect  with  ETHERNET  and  GPRS  protocols,  the  control  system  can  interface  with  the  Internet,  thus  allowing  for  remote  monitoring  even  from  headquarters.  Communication  with  the  unit  can  be  established  also  via  the  ModBus  TCP/IP  protocol  (commonly  used  for  electronic  industrial  devices)  through  an  Ethernet  connection  (Rj45  cable).  .  The  control  system  is  also  provided  with  a  USB  port  for  downloading  data  on  a  memory  key  and  uploading  setting  parameters  should  operating  amendments  in  the  system  be  required.  When  connected,  information  concerning  the  status  of  the  regulator  can  be  transferred  to  a  dedicated  server.  Data  can  be  analysed  from  a  remote  location,  thus  allowing  for  actively  monitoring  the  functioning  mode  and,  if  necessary,  altering  the  setting  of  some  parameters  wherever  the  unit  might  be  installed.  Downloading  and  uploading  software,  data  and  functioning  parameters  can  be  carried  out  either  locally  or  remotely.  

Stabimon Once  the  remote  communication  is  established,  the  dedicated  software  provided  with  the  regulator  enables  the  remote  monitoring  of  the  installation.  A    dashboard  on  a  PC  shows  I/O  parameters,  alarm  situation  and  phase  status  of  the  LEDs  duplicating  the  regulator's  external  control  panel.                    

   In  case  of  multiple  installation,  another  window  shows  the  general  situation  indicating  whether  a  regulator  is  connected  for  remote  communication  (green  LED)  or  not  (transparent  LED)  and  if  an  alarm  condition  is  active  (red  LED).    

 regulator  

 Ethernet  

 GPRS  modem  

 SERVICE  

 data  analysis  

 online  

assistance  

 local  

assistance  

Page 4: DIGITAL VOLTAGE REGULATOR DIGITAL+VOLTAGE+REGULATOR+ … · StacoDVR-5 60kVA to 6000kVA StacoDVR)5+ DIGITAL VOLTAGE REGULATOR DATASHEET DIGITAL+VOLTAGE+REGULATOR+ April!2016! StacoDVR)5:3)ph.VoltageRegulator+

 

StacoDVR-5 60kVA to 6000kVA StacoDVR-­‐5  

DIGITAL VOLTAGE REGULATOR DATASHEET DIGITAL  VOLTAGE  REGULATOR  

 

April  2016  

 TECHNICAL  DATA  PART  NUMBER   Unit  Specif ic    

RATED  POWER   Unit  Specif ic     [kVA]  

INPUT  VARIATION  RANGE   +/-­‐15,  +/-­‐20,  +/-­‐25,  +/-­‐30,  +15/-­‐35,  +15/-­‐45          Unit  Specif ic    

[%]  

RATED  VOLTAGE  208-­‐220-­‐230-­‐240-­‐380-­‐400-­‐415-­‐480            Unit  Specif ic    

[V]  

MAX  INPUT  CURRENT   Unit  Specif ic     [A]  

OUTPUT  CURRENT   Unit  Specif ic     [A]  

OUTPUT  ACCURACY  +/-­‐0.5%  or  +/-­‐  1%            Unit  Specif ic    

[%]  

FREQUENCY  50/60Hz  +/-­‐  5%    or  60Hz  +/-­‐5%            Unit  Specif ic    

[Hz]  

REGULATION  SPEED  10  to  48            Unit  Specif ic    

[msec/V]  

EFFICIENCY    >  97   [%]  

ADMITTED  LOAD  VARIATION   0  -­‐  100   [%]  

ADMITTED  PHASE  ASIMMETRY   0  -­‐  100   [%]  

MAINS  WAVEFORM  DISTORTION  INCREMENT   None  introduced   [%]  

ADMITTED  OVERLOAD   200%  2min    -­‐    

COOLING   Natural  a ir  venti lat ion  (aided  with  fans  over  45°C)    -­‐    

AMBIENT  TEMPERATURE   -­‐25/+45   [°C]  

STORAGE  TEMPERATURE   -­‐25/+60   [°C]  

RELATIVE  HUMIDITY   95   [%]  

DIMENSIONS  [W    x  D  x  H]   Unit  Specif ic     [mm]  

WEIGHT   Unit  Specif ic     [kg]  

ENCLOSURER  TYPE  PROTECTION   Standard  IP  21  /  Nema  1,  Optional  Unit  Specif ic   -­‐  

COLOUR   RAL  7035   -­‐  

INSTALLATION   INDOOR   -­‐  

INSTRUMENTATION  Input  and  Output  digital  mult imeter  with  RS485  port  LCD  display  

REGULATOR  OVERLOAD  PROTEСTION  

Automatic  c ircuit  breaker  to  protect  regulator  power  path  via  digital  control  e lectronic  protection  system  Fuses  to  protect  auxi l iary  c ircuits  

COMMUNICATION  SYSTEM  PARAMETERS  SETTING  

local ly  v ia  PC  and  USB  remotely  v ia  Ethernet,  GPRS  modem  or  MODBUS  

OVERVOLTAGE  PROTECTION  

SPD  Surge  Arrestor  Class   I   ( input)  SPD  Surge  Arrestor  Class   I I   (output)  Soft  start  through  super  capacitors   in  case  of  mains  fai lure  

N.B.   -­‐  Other  configurations  are  available  on  specific  request.  The  technical  data  in  the  above  tables  can  be  altered  by  the  Company  without  prior  notice  

     

Page 5: DIGITAL VOLTAGE REGULATOR DIGITAL+VOLTAGE+REGULATOR+ … · StacoDVR-5 60kVA to 6000kVA StacoDVR)5+ DIGITAL VOLTAGE REGULATOR DATASHEET DIGITAL+VOLTAGE+REGULATOR+ April!2016! StacoDVR)5:3)ph.VoltageRegulator+

 

StacoDVR-5 60kVA to 6000kVA StacoDVR-­‐5  

DIGITAL VOLTAGE REGULATOR DATASHEET DIGITAL  VOLTAGE  REGULATOR  

 

April  2016  

 OPTIONAL  FEATURES  Part  Number  suffix    B1    Bypass  switch-­‐-­‐ Internal-­‐-­‐ Input  Disconnect  and  Output  changeover   interlocked  switch  

Unit  Specif ic     [A]  

B2    Bypass  switch-­‐-­‐ Internal-­‐-­‐ Input  Circuit  Breaker  and  Output  changeover   interlocked  switch  

Unit  Specif ic     [A]  

B3    MAINTENANCE  BY-­‐PASS  FULL  PROTECTION  KIT               Internal—(Input-­‐Bypass-­‐Output)  Circuit  Breakers   interlocked.               (A+B+C+phase  fai lure/sequence  error),  Over  /  Under  Voltage  Protection.                Output  Contactor  320  A  and  under,  Output  Circuit  Breaker  >320A  

Unit  Specif ic   [A]  

E        EMI  /  RFI  Output  Fi lter ing   Unit  Specif ic      L         (A+B+C+phase  fai lure/sequence  error),  Over  /  Under  Voltage  Protection.              Output  Contactor  320  A  and  under,  Output  Circuit  Breaker  >320A  

Unit  Specif ic     [A]  

P        PRIMARY  INPUT  CIRCUIT  BREAKER  with/without  Thermal  Magnetic  Release   Unit  Specif ic     [A]  S        SECONDARY  OUTPUT  CIRCUIT  BREAKER  with/without  Thermal  Magnetic  Release   Unit  Specif ic     [A]  T1     INPUT  SPD  class   I  SURGE  ARRESTORS   Unit  Specif ic    T2    OUTPUT  SPD  class   I I  SURGE  ARRESTORS   Unit  Specif ic      

Z    TROPICALIZATION   Unit  Specif ic      

   Manual  By-­‐Pass  switch  for  maintenance  and  repair  works  2000/1600A  rated:  a)   Input  Automatic  Circuit  Breaker    ABB  4P  –  2000A    rated  (short  circuit  protection,    complete  with    Phase  Rotation/Phase  Failure  Relay)  b)  Interlocked  By-­‐Pass  Automatic  Circuit  Breaker  ABB  4P  2000A  rated    c)  Output  interlocked  Magneto  Thermal  Circuit  Breaker  ABB  4P  –  1600A  rated  (Overload  protection  and  Over/Under  voltage  protection  with  adjustable  time  delay)  for  phase  failure  and  phase  reversal  protection  excludable  by  key  selection                                    

 

STACO ENERGY PRODUCTS COMPANY 1229 Byers Road, Miamisburg Ohio 45342 - USA www.stacoenergy.com