AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) Page 1 of 17 © Copyright Annicom 2019. All Rights Reserved ANNICOM Ltd Unit 21 Highview, High Street, Bordon, Hampshire. GU35 0AX Tel: +44 (0)1420 487788 Fax: +44 (0)1420 487799 Email: [email protected] Website: www.annicom.com Product overview The AX-CNDR-X range of Digital Room Controllers feature a high-contrast blue backlit display with white text, and fit a standard single gang pattress. The unit has selection for an internal or external temperature sensor and provides an adjustable proportional and integral heating and cooling outputs or on/off control depending on unit type. The clear display indicates room temperature, fan speed, occupancy and window status. Timeclock option available with 2 on/off times per day (with independent setpoints) and 5/2 day (Week/weekend) or 7 day (All week) timer actions. The unit has a keycard / occupancy input with adjustable set back and exit delay and a window contact input. Network connectivity is provided with an isolated BACnet MSTP / RTU link, supports COV. (BN version). 0-10V PI heating and cooling outputs 0-10V PI cooling with On/Off heating (CRX versions) 0-10V fan speed control with Auto (XXE versions) On/off heating /cooling control (RXX versions) 3 speed fan speed control with Auto (XX3 versions) Isolated BACnet MSTP / RTU, supports COV Adjustable setpoint range Features Keycard / occupancy input, adjustable exit delay Window contact input 3 point fan speed voltage profile, limit noise Unused Keycard / Window contact inputs available as BACnet binary inputs Fits a standard single gang deep back box Two part plug-in connectors for easy installation Built in terminating resistor (BN version) Order codes for the AX-CNDR- range of Digital Room Controllers, all with 2 digital inputs Code Description Heat Cool Fan Speed BAC net Supply Time- clock AX-CNDR-HCE 0-10V heating, cooling and fanspeed 0-10V 0-10V 0-10V 24V AX-CNDR-HCEBN 0-10V heating, cooling and fanspeed 0-10V 0-10V 0-10V ü 24V AX-CNDR-HC3 0-10V heating and cooling, 3 fanspeed relays 0-10V 0-10V 3 relays 24V AX-CNDR-HC3-230 0-10V heating and cooling, 3 fanspeed relays 230Vac supply 0-10V 0-10V 3 relays 90- 265Vac AX-CNDR-HRCE On/off heating, 0-10V cooling and fanspeed On/off relay 0-10V 0-10V 24V AX-CNDR-HC 0-10V heating and cooling, no fans 0-10V 0-10V 24V continued on next page…………

Transcript of Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN)...

Page 1: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 1 of 17© Copyright Annicom 2019. All Rights Reserved

ANNICOM LtdUnit 21 Highview, High Street, Bordon, Hampshire. GU35 0AX

Tel: +44 (0)1420 487788 Fax: +44 (0)1420 487799Email: [email protected] Website: www.annicom.com

Product overviewThe AX-CNDR-X range of Digital Room Controllersfeature a high-contrast blue backlit display with white text,and fit a standard single gang pattress.

The unit has selection for an internal or externaltemperature sensor and provides an adjustable proportionaland integral heating and cooling outputs or on/off controldepending on unit type.

The clear display indicates room temperature, fan speed,occupancy and window status.

Timeclock option available with 2 on/off times per day(with independent setpoints) and 5/2 day (Week/weekend)or 7 day (All week) timer actions.

The unit has a keycard / occupancy input with adjustableset back and exit delay and a window contact input.

Network connectivity is provided with an isolated BACnetMSTP / RTU link, supports COV. (BN version).

● 0-10V PI heating and cooling outputs

● 0-10V PI cooling with On/Off heating (CRX versions)

● 0-10V fan speed control with Auto (XXE versions)

● On/off heating /cooling control (RXX versions)

● 3 speed fan speed control with Auto (XX3 versions)

● Isolated BACnet MSTP / RTU, supports COV

● Adjustable setpoint range

Features● Keycard / occupancy input, adjustable exit delay

● Window contact input

● 3 point fan speed voltage profile, limit noise

● Unused Keycard / Window contact inputs available asBACnet binary inputs

● Fits a standard single gang deep back box

● Two part plug-in connectors for easy installation

● Built in terminating resistor (BN version)

Order codes for the AX-CNDR- range of Digital Room Controllers, all with 2 digital inputsCode Description Heat Cool Fan

SpeedBACnet

Supply Time-clock

AX-CNDR-HCE 0-10V heating, cooling and fanspeed 0-10V 0-10V 0-10V − 24V −

AX-CNDR-HCEBN 0-10V heating, cooling and fanspeed 0-10V 0-10V 0-10V ü 24V −

AX-CNDR-HC3 0-10V heating and cooling, 3 fanspeed relays 0-10V 0-10V 3 relays − 24V −

AX-CNDR-HC3-230 0-10V heating and cooling, 3 fanspeed relays230Vac supply

0-10V 0-10V 3 relays − 90-265Vac

AX-CNDR-HRCE On/off heating, 0-10V cooling and fanspeed On/offrelay

0-10V 0-10V − 24V −

AX-CNDR-HC 0-10V heating and cooling, no fans 0-10V 0-10V − − 24V −

continued on next page…………

Page 2: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 2 of 17© Copyright Annicom 2019. All Rights Reserved

Power Supply 24Vac/dc,except 90-265Vac for -230 version

Inputs External temperature sensor

VFC inputs for Occupancy / Keycard contact and Window contact.

Heat, Cool, Fan speed outputs 0-10Vdc at 5mA maximum

Fan PWM output 5V at 5mA max, 100Hz, 10mS cycle time

Fan Relays (If fitted) 8A resistive at 250Vac

On/Off Relays (If fitted) 8A resistive at 250Vac

Network BACnet MSTP / RTU 19K2, 38K4, 57K6, 76K8 and 115K2 baud rates

Finish (Plate) Vertical brushed stainless steel

Weight & Dimensions 250gms (approx) 86 x 86 x 35mm (approx)

Backbox Depth 45mm

Ambient Temperature Range 0˚C to 60˚C

Country of Origin United Kingdom

Order codes continued

Product specifications (Dependant on specific unit)

Code Description Heat Cool FanSpeed

BACnet

Supply Time-clock

AX-CNDR-HCBN 0-10V heating and cooling, no fans, BACnet 0-10V 0-10V − ü 24V −

AX-CNDR-HCP 0-10V heating, cooling and PWM fanspeed 0-10V 0-10V PWM − 24V −

AX-CNDR-HCPBN 0-10V heating, cooling and PWM fanspeed,BACnet

0-10V 0-10V PWM ü 24V −

AX-CNDR-AP 0-10V heating or cooling, PWM fanspeedwith double output

0-10Vone only

PWMX2

− 24V −

AX-CNDR-APBN 0-10V heating or cooling, PWM fanspeedwith double output

0-10Vone only

PWMX2

ü 24V −

AX-CNDR-CPMBN 0-10V cooling and mirrored PWM fanspeed,BACnet

− 0-10V PWMX2

ü 24V −

AX-CNDR-RE On/off heating or cooling, 0-10V fanspeed On/off relayone only

0-10V − 24V −

AX-CNDR-R3 On/off heating or cooling, 3 fanspeed relays On/off relayone only

3 relays − 24V −

AX-CNDR-HCET 0-10V heating, cooling and fanspeed,timeclock

0-10V 0-10V 0-10V − 24V ü

AX-CNDR-HC3T 0-10V heating and cooling, 3 fanspeedrelays, timeclock

0-10V 0-10V 3 relays − 24V ü

AX-CNDR-HRCET On/off heating and 0-10V cooling andfanspeed, timeclock

On/offrelay

0-10V 0-10V − 24V ü

AX-CNDR-HCT 0-10V heating and cooling, timeclock 0-10V 0-10V − − 24V ü

AX-CNDR-HCF 0-10V heating, cooling, for remote fan relaysuses AX-CNDR-RMAF modules

0-10V 0-10V Remoteunit

− 24V −

AX-CNDR-HCFBN 0-10V heating, cooling, for remote fan relaysuses AX-CNDR-RMAF modules, BACnet

0-10V 0-10V Remoteunit

ü 24V −

AX-CNDR-D57B Used with AX-CNDR-RMD modules Refer to AX-CNDR-RMD data sheet −

AX-CNDR-A57 Used with AX-CNDR-RMA modules Refer to AX-CNDR-RMA data sheet −

Page 3: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 3 of 17© Copyright Annicom 2019. All Rights Reserved

MenuFollow the steps below to enter the menu, listed optionsnot available on all units

1. Switch unit off

2. Press and hold ON switch

3. Keep ON switch pressed and press and hold setpointincrease at the same time

4. Keep both switches pressed for 10 seconds. Thedisplay will change to the setpoint high limit option.

5. Press ON button to scroll menu options describedbelow. When required option is displayed press setpointdecrease or setpoint increase to adjust value orenable/disable option. When changes are complete donot press any buttons for 10 seconds and the unit willstore new values and return to normal operation.

Menu options [Menu display mnemonic](Default value)

Setpoint high limit [SPHi]

This sets the highest value the user can adjust thesetpoint to. Range 25 - 30 ºC. (28)

Setpoint low limit [SPLo]

This sets the lowest value the user can adjust the setpointto. Range 15 - 20 ºC. (18)

Datasheet contentsEvery effort has been taken in the production of thisdata sheet to ensure accuracy. Annicom do not acceptresponsibility for any damage, expense, injury, loss orconsequential loss resulting from any errors oromissions. Annicom has a policy of continuousimprovement and reserves the right to change thisspecification without notice.

InstallationThe unit should be installed by a suitably qualifiedtechnician in conjunction with any guidelines for theequipment it is to be connected to and any localregulations. Field wiring should be installed to satisfythe requirements set out by the manufacturer of theequipment that the module is being connected to.

Sensor selection [SEnS]

This selects between the internal and externaltemperature sensor. Selection Int / Ets. (Int)

Temperature offset [OFSt]

This offsets the temperature from the calculated value.Positive values increase the temperature and negativevalues decrease the temperature. Range -10 to +10 ºC.(0)

Operating mode [OPEr]

This sets the unit operating mode. Available optionsheating / cooling / heating and cooling. (HC)

Proportional band [Pbnd] (PI versions)

This sets the heating and cooling proportional band.Range 1 - 30 ºC. (5)

Fan band [Fbnd] (On/off only versions)

This sets the auto band for fan control. Range 1 - 30 ºC.(5)

Integral time [Int] (PI versions)

This sets the heating and cooling integral time. RangeOFF / 1 - 600 seconds. (200)

Deadband [ddbn] (PI versions)

This sets the deadband range between the proportionalheating and cooling outputs. Range 0.5 - 10 ºC. (5)

Hysteresis [hYSt] (On/off only versions)

This sets the switching hysteresis for On/off control.Range 0.5 - 10 ºC. (5)

Fan speed steps [FnSt] (0-10V fanspeed version only)

This sets the number of steps that cover the output fanspeed. For example selecting 10 will cause the outputto change in 10 steps, 1 volt increments. Selection 3 /10. (3)

Fans speed Low [FSLo]

When in 3 step mode this sets the fan speed low outputvoltage as a percentage, 33% = 3.3V etc. When in 10step mode this sets the output voltage profile at a virtualstep of 3.3. Range 0 to 50%. (33)

Fans speed Medium [FSnE]

When in 3 step mode this sets the fan speed mediumoutput voltage as a percentage, 66% = 6.6V etc. When

Page 4: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 4 of 17© Copyright Annicom 2019. All Rights Reserved

in 10 step mode this sets the output voltage profile at avirtual step of 6.6. Range 25 to 75%. (66)

Fans speed High [FSHi]

When in 3 step mode this sets the fan speed high outputvoltage as a percentage, 100% = 10V etc. When in 10step mode this sets the output voltage profile at step 10.Range 50 to 100%. (100)

Keycard / occupancy input [CArd]

This enables or disables the keycard / occupancy input.The Setback and Exit delay options are only availablewhen the keycard / occupancy input is enabled. (DIS)

Setback [SbAc]

This sets the amount the heating and cooling will besetback when the room is empty. The Setback option isonly available when the keycard / occupancy input isenabled. Range 1 - 20 ºC. (5)

Exit delay [EdEL]

This sets the time delay before the heating and coolingis setback and the fan is set to low speed when the roomis empty. The Exit delay option is only available whenthe keycard / occupancy input is enabled. Range 0 - 90minutes, in 5 minute steps. (50)

Window input [UUin]

This enables or disables the window contact input. (DIS)

Setpoint switch actions [SPAc]

This enables or disables the setpoint buttons. (EN)

Fanspeed switch actions [FSAc]

This enables or disables the fanspeed buttons. (EN)

On Off switch actions [OnAc]

This enables or disables the on off button. (EN) (Menuentry will not be disabled)

MSTP address [Addr] (BN version only)

This sets the unit BACnet MSTP address. This must beset to be a unique number on the local MSTP networkor communication conflicts will occur. Range 0 to 127.(16)

Maximum MSTP address [UPAd] (BN version)

This sets the maximum MSTP address that the unit willpoll when looking for other units. If this is set lowerthan the address of the next unit polling will loop backto address 0 and the next unit will not be found. Range0 to 127. (64)

Baud rate [bAud] (BN version)

This sets the unit MSTP baud rate. This should be setto the same value as current units on the network.Available options 19K2, 38K4, 57K6, 76K8 and 115K2.(38K4)

BACnet device instance [din1] to din7

This sets the BACnet device instance seen on thenetwork. This should eventually be set to a networkwide unique value in the range 0 to 4194302. (898000)

Press SP- to scroll through the digits from left to right.The display will show din1 when the first digit (leftdigit) is selected increasing to din7 when the last digit(right digit) is selected. Press SP+ to modify the selecteddigit. All digits should be set including leading zeroes.For example a value of 0 would be set as 0000000 anda value of 898 would be set as 0000898.

BACnet reset [bnrS] (BN version only)

This sets all BACnet MSTP object names and instancesto default values. Select 123 on the display and wait formenu to time out. The thermostat operating values arenot modified.

Pressing the BACNET RESET button for 10 secondswill also reset these values.

OperationPI versions

The AX-CNDR-XXX controls room heating andcooling. The unit provides a 0-10V heating and / orcooling output relative to the setpoint / setback /deadband and proportional band. ( On/off heating onCR3 version) If the integral time is set the output willalso vary with temperature error over time. The fanspeed can be set in 3 or 10 steps in manual or when autois set the fan speed is automatically controlled in 3 or10 steps relative to the 0-10V heating and coolingoutput. (10 steps only available on 0-10V fan speedversions)

Page 5: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 5 of 17© Copyright Annicom 2019. All Rights Reserved

On/off versions

The AX-CNDR-XXX controls room heating andcooling. The unit provides On/off heating and / orcooling output relative to the setpoint / setback /hysteresis. The fan speed can be set in 3 steps in manualor when auto is set the fan speed is automaticallycontrolled in 3 steps relative to the Fan band setting.

Key card contact / occupancy input

This accepts a volt free output from a keycard oroccupancy sensor (or similar device). When the inputis closed the room will be considered occupied (thePerson symbol is displayed in the House symbol). Ifthis input is enabled in the menu the heating and coolingwill be set back by the setback value and the fan set tolow speed when the room has been un-occupied for theexit delay time. A count down of the exit delay isdisplayed. If this input is connected to a PIR (forexample) and the exit delay is set the PIR’s internaldelay should be set to zero. If the key card actions arenot required they can be disabled and the input used asa digital input.

AX-CNDR-HCF / AX-CNDR-HCFBN

Unit operates as standard AX-CNDR-HCE/BN unitexcept the analogue fan output is preset to drive anAX-CNDR-RMAF 3 fan interlocked relay module.

AX-CNDR-HC / AX-CNDR-HCBN

Unit operates as standard AX-CNDR-HCE/BN unitwithout any fan controls or output.

AX-CNDR-HCP / AX-CNDR-HCPBN

Unit operates as standard AX-CNDR-HCE/BN exceptthe fan output is 5V, 100Hz PWM, 10mS cycle time.

AX-CNDR-AP / AX-CNDR-APBN

Unit operates as AX-CNDR-HCE/BN but it has twoidentical 5V, 100Hz PWM 10mS cycle time fan outputsand only 1 0-10V heating or cooling output.

Window contact input

This accepts a volt free contact from a window switch.The switch should be closed when the window is closed.If the window input is enabled in the menu and thewindow is open the heating and cooling output is set tozero and the fan is set to speed low (UUin is displayed).If the window contact actions are not required they canbe disabled and the input used as a digital input.

User controlsOn / Off

The user can switch the unit on or off. When the unit isoff the cooling output will be zero and the fan is off. On/ Off switch actions can be disabled via the operatingmenu.

Setpoint

The user can adjust the setpoint between the Setpointhigh and Setpoint low limits set in the menu. Fortimeclock versions the setpoint will only change for theremainder of the current time period reverting back tothe preset value during the next cycle. Setpoint switchactions can be disabled via the operating menu.

Fan speed

0-10V fan speed version

The user can set the fan speed in 3 or 10 steps as selectedor auto. When auto is selected the fan speed will be setin 3 or 10 steps relative to the 0-10V heating or coolingoutput. The fan speed is displayed in three or ten stepson the bottom display bar. To provide more control andreduce noise each 3 step high/med/low fanspeed outputcan be set individually or a 3 point output profile canbe set for 10 step operation.

3 relay fan speed version

The user can set the fan speed to low/med/high or auto.When auto is selected the fan speed will be set relativeto the 0-10V heating or cooling output for PI versionsor relative to the Fan band for On/off versions. The fanspeed is displayed in three steps on the bottom displaybar.

Fan speed switch actions can be disabled via theoperating menu.

Fitting and removing front plate

To fit front plate with the back plate fitted to the wallcarefully bring front plate towards back plate and locateswitches in front plate holes then move plate to one sideand clip over one side of back plate then push front platein opposite direction and push front to clip onto backplate.

To remove front plate carefully insert slottedscrewdriver into slot on side of thermostat and leverforward making sure plate does not fall.

Page 6: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 6 of 17© Copyright Annicom 2019. All Rights Reserved

Fan output voltage profile

Using the menu the three points FANSPEED LOW/MEDIUM / HIGH are set. A value of 45% equates to4.5V etc. When three step mode is selected these threepoints set the LOW / MEDIUM / HIGH voltage outputs.When in 10 step mode these three settings are used toplot the output voltage profile at steps of 3.3 6.6 and 10as shown on the graph below. This is then used tocalculate the output voltages for steps 1 to 10.

FANSPEEDHIGH

FANSPEEDMEDIUM

FANSPEEDLOW

0 1 2 3 4 5 6 7 8 9 10FANSPEED

FAN

VO

UT

NETCOMMONNET +NET -

BACnetRESET

TERMINATIONRESISTOR

BACnetconnections

AX-CNDR-HCE/BNAX-CNDR-HCF/BN

24V0V

0V

0VKEYCARDWINDOW

0-10V FAN SPEED

0-10V HEATING

EXTERNAL

0-10V COOLING

SENSOR

SUPPLY

COMMON 0V CONNECTION

BACnet connections only on BN versions

AX-CNDR-AP/BN

PWM FAN SPEED

BACnetRESET

TERMINATIONRESISTOR

NETCOMMONNET +NET -

BACnetconnections

24V0V

0V

0VKEYCARDWINDOW

PWM FAN SPEEDEXTERNAL SENSOR

0-10V HEAT or COOLSUPPLY

(MIRRORED)

COMMON 0V CONNECTION

AX-CNDR-HC/BN

TERMINATIONRESISTOR

BACnetRESET

NETCOMMONNET +NET -

BACnetconnections

24V0V

0V

0VKEYCARDWINDOW

0-10V HEATING

EXTERNAL0-10V COOLING

SENSOR

SUPPLY

COMMON 0V CONNECTION

Page 7: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 7 of 17© Copyright Annicom 2019. All Rights Reserved

AX-CNDR-RE

COOLING / HEATINGRELAY

24V0V

0V

0VKEYCARDWINDOW

0-10V FAN SPEEDEXTERNAL

SENSOR

SUPPLY

COMMON 0V CONNECTION

AX-CNDR-HCP/BNTERMINATION

RESISTOR

BACnetRESET

NETCOMMONNET +NET -

BACnetconnections

24V0V

0V

0VKEYCARDWINDOW

PWM FAN SPEED

0-10V HEATING

EXTERNAL

0-10V COOLING

SENSOR

SUPPLY

COMMON 0V CONNECTION

AX-CNDR-HRCE

24V0V

0V

0VKEYCARDWINDOW

0-10V FAN SPEEDEXTERNAL

0-10V COOLING

SENSOR

SUPPLY

HEATINGRELAY

COMMON 0V CONNECTION

N

L

AX-CNDR-HC3-230

230VacSUPPLY

0V

0VKEYCARDWINDOW

0-10V HEATING

EXTERNAL0-10V COOLING

SENSOR

3 / HIGH

COMMON1 / LOW2 / MED

FANSPEED RELAYS

COMMON 0V CONNECTION

BACnet connectionsonly on BN version

Page 8: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 8 of 17© Copyright Annicom 2019. All Rights Reserved

AX-CNDR-HC3

24V0V

0V

0VKEYCARDWINDOW

0-10V HEATING

EXTERNAL0-10V COOLING

SENSOR

SUPPLY

3 / HIGH

COMMON1 / LOW2 / MEDFANSPEED

RELAYS

COMMON 0V CONNECTION

AX-CNDR-R3

24V0V

0V

0VKEYCARDWINDOW

EXTERNALSENSOR

SUPPLY

VALVE

3 / HIGH

COMMON1 / LOW2 / MED

FANSPEED RELAYS

COMMON 0V CONNECTION

Network connections ((BN versions)

It is not recommended to connect more then 32 deviceson a single network. This number is dependent on localwiring and conditions, ie cable lengths, interference etc.

It recommends to use twisted pair cables specificallydesigned for RS-485 networks to reduce anyinterference. All devices should be connected NET+ toNET+ and NET- to NET-. A NETCOMMON terminalis provided and if required all the units on the networkshould be connected to the same NETCOMMON whichshould be grounded at one point. The devices shouldideally be connected in a single chain with no stubs.

On board termination resistors are provided and onlythe devices at each end of the chain should have theirresistors connected, place TERM jumper in EL position.All other devices should be set to the none EL position.It is also recommended that a fail safe voltage is appliedat one point on the network, usually at the maincontroller or router.

Page 9: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 9 of 17© Copyright Annicom 2019. All Rights Reserved

Timeclock (T version)

The time clock operates on either a 5/2 day cycle or a7 day cycle. Each part of the cycle has 2 on / off timesettings, 1 On / 1 Off and 2 On / 2 Off. The unit has 2timeclock setpoints, SP1 is used during 1 On / 1 Offperiods and SP2 is used during 2 On / 2 Off periods. Ifthe setpoint is adjusted during a timer period the in usevalue will change for the remainder of that period butit will not be stored and will revert back to SP 1 or SP2 for the next cycle.

If 1 On / 1 Off and 2 On / 2 Off periods overlap SP2 haspriority. This allows 1 On / 1 Off to be set for the wholeday and 2 On / 2 Off to be set for a time within the day.

ModePress On/Off button to cycle through the modes, On /Auto / Off. When auto mode is selected the time displayshows Auto for 5 seconds followed by the time. Thetime display will then continue to change between timeand Auto to show the unit is in Auto mode.

Timeclock MenuFollow the steps below to enter the menu, listed optionsnot available on all units

1. Press and hold ON switch for 5 seconds. The displaywill change to the timeclock set year option.

5. Press ON button to scroll menu options describedbelow. When required option is displayed presssetpoint decrease or setpoint increase to adjust valueor enable/disable option. When changes are completedo not press any buttons for 10 seconds and the unitwill store new values and return to normal operation.

Set year [YEAr]

Timeclock year setting. Range 15 - 65 for 2015 to2065.

Set month [MMon]

Timeclock month setting. Range 1 - 12 for January toDecember.

Set date [dAtE]

Timeclock year setting. Range 1 - 31 for day ofmonth.

Set hour [Hour]

Timeclock hour setting. Range 0 - 23.

Set minute [MMin]

Timeclock year setting. Range 0 - 59.

Set 12 / 24 hour mode [1224]

12 or 24 hour clock display setting. Section. 12 or 24.

Setpoint 1 [SP 1]

Sets the setpoint value used during on/off time 1.Range, setpoint low to setpoint high limits as set.

Setpoint 2 [SP 2]

Sets the setpoint value used during on/off time 2.Range, setpoint low to setpoint high limits as set.

Set time cycle [CYCL]

Selects between 5/2 day (Week/weekend) and 7 day(All week) timer actions. Selection 52 or 7.

Set on / off times

The display will show either Mon-Fri, Sat Sun or Mon- Sun along with settings for 2 on off actions [1-On],[1Off],[2-On], [2Off]. When the required option isshown press setpoint decrease or setpoint increase toadjust time in 15 minute steps.

Page 10: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 10 of 17© Copyright Annicom 2019. All Rights Reserved

Analogue output objects / [Instance]

Cooling output (PV read only) [20]

Heating output (PV read only) [21]

Fan output (PV read only) [22]

Analogue value objects / [Instance] (Default)

Temperature offset adjustment [32] (0)

Proportional band [33] (5)

Integral time [34] (200)

Current setpoint [35] (20)

Minimum setpoint [36] (18)

Maximum setpoint [37] (28)

Unoccupied setback [38] (5)

Room exit delay [39] (50)

Current fan speed (PV read only) [40]

Deadband [41] (5)

Manual fan speed [42]

Fanspeed Low [44] (33)

Fanspeed Medium [45] (66)

Fanspeed High [46] (100)

MSTP address [101] (16)

Device instance [103] (898000)

Upper MSTP address [13] (64)

Binary input objects / [Instance]

Card contact input (PV read only) [104]

Window contact input (PV read only) [105]

Binary value objects / [Instance] (Default)

Enable card input actions [144] (0 - Disabled)

Enable window contact actions [145] (0 - Disabled)

Select sensor Internal / external [146] (0 - Internal)

Inhibit setpoint switch actions [147] (0 - Enabled)

BACnet (BN version)

PROTOCOL IMPLEMENTATION CONFORMANCE

Vendor Name: Annicom Ltd.

Vendor ID: 898

Product Name: AX-CNDR-XXX

Product Description

The AX-CNDR-XXX BACnet digital room controllercommunicating thermostat has been specificallydesigned for heating / cooling applications to bemonitored on a BACnet MS-TP ® RTU network.

Supported BACnet Services

Data Sharing – Read Property

Data Sharing – Read Property Multiple

Data Sharing – Write Property

Data Sharing – Subscribe cov

Data Sharing – Subscribe cov property (PV only)

Supported BACnet Objects

Device

Analogue input

Analogue output

Analogue values

Binary input

Binary values

Multi state values

Note The controller does not support segmentationrequests or responses

Change of value

This unit supports COV subscriptions on all objectpresent value properties, this includes status flagmonitoring. Only analogue objects have COVincrement properties. Binary and multistate objectsmonitor for any change in present value.

Analogue input objects / [Instance]

Current sensor temperature (PV read only) [0]

Page 11: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 11 of 17© Copyright Annicom 2019. All Rights Reserved

Object Type: Analogue input

Present value: From sensor (RO)

COV increment: 1.0 (W)

Units: Degrees centigrade

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Output object properties

Analogue Output instance 20

Description: Cooling output

Name: Cooling output

Object Type: Analogue output

Present value: Set by control actions (RO)

Units: Percentage

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Output instance 21

Description: Heating output

Name: Heating output

Object Type: Analogue output

Present value: Set by control actions (RO)

Units: Percentage

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Output instance 22

Description: Fan output

Name: Fan output

Object properties

Only properties marked (W) can be written. Presentvalue (PV) properties marked (RO) are read only.

Device object properties

Device instance 898 (Default)(W)

Vendor name: Annicom Ltd.

Vendor Identifier: 898

Object list: As this list

Model Name: AX-CNDR-XXX

Max ADPU length accepted: 480

Max masters: 64 (Default), 1 to 127. (W)

Segmentation supported: No segmentation

Description: BACnet thermostat.

Object Name: Default BACnet thermostat. (W)

Object Type: Device

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Input object properties

Analogue Input instance 0

Description: Current sensor temperature

Name: Temperature

Inhibit fan speed switch actions [148] (0 -Enabled)

Inhibit On / Off switch actions [149] (0 - Enabled)

Unit On / Off [150]

Multistate value objects / [Instance] (Default)

Fan step [184] (0 - 3 Steps)

Operating mode [185] (3 - Heat and Cool)

Baud rate [197] (2 - 38K4)

Page 12: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 12 of 17© Copyright Annicom 2019. All Rights Reserved

Object Type: Analogue output

Present value: Set by control actions (RO)

Units: Percentage

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value object properties

Analogue Value instance 32

Description: Temperature offset adjustment

Name: Temperature offset

Object Type: Analogue value

Present value: As set, -10.0 to +10.0. (0.0) (W)

Units: Degrees centigrade

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 33

Description: Proportional band

Name: Proportional band

Object Type: Analogue value

Present value: As set, 1 to 30. (5.0) (W)

Units: Degrees centigrade

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 34

Description: Integral time

Name: Integral time

Object Type: Analogue value

Present value: As set, 0 (Off) to 600. (20) (W)

Units: Seconds

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 35

Description: Current setpoint

Name: Setpoint

Object Type: Analogue value

Present value: As set, see min max user setpoint.(20.0) (W)

COV increment: 1.0 (W)

Units: Degrees centigrade

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 36

Description: Minimum user setpoint

Name: Minimum setpoint

Object Type: Analogue value

Present value: As set, 5 to 15. (18) (W)

Units: Degrees centigrade

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 37

Description: Maximum user setpoint

Name: Maximum setpoint

Object Type: Analogue value

Page 13: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 13 of 17© Copyright Annicom 2019. All Rights Reserved

Present value: As set, 25 to 35. (28) (W)

Units: Degrees centigrade

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 38

Description: Setback

Name: Setback

Object Type: Analogue value

Present value: As set, 0 to 20. (5) (W)

Units: Degrees centigrade

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 39

Description: Room exit delay

Name: Room exit delay

Object Type: Analogue value

Present value: As set, 0 to 90. (50) (W)

Units: Minutes

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 40

Description: Current fan speed

This is a read out of the current fan speed. To setthe fan speed use Manual fan speed.

Name. Actual fan speed

Object Type: Analogue value

Present value: As set, 1 to 10. (RO)

Units: None

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 41

Description: Deadband

Name: Deadband

Object Type: Analogue value

Present value: As set, 0.5 to 10. (5) (W)

Units: Degrees centigrade

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 42

Description: Manual fan speed

This sets the manual fan speed. The current fanspeed may differ depending on the thermostatactions, read current fan speed to see actual speed.

Name. Manual fan speed

Object Type: Analogue value

Present value: As set, 0 to 10. (W)

0 = Auto fan speed

Units: None

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 44

Description: Fan speed low

Page 14: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 14 of 17© Copyright Annicom 2019. All Rights Reserved

When in 3 step mode this sets the fan speed lowoutput voltage as a percentage, 50%. = 5V etc.When in 10 step mode this sets the output voltageprofile at a virtual step of 3.3.

Name. Fan speed low

Object Type: Analogue value

Present value: As set, 0 to 50. (33) (W)

Units: Percent

Status flags: In Alarm / Fault / Overridden / Out ofService

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 45

Description: Fan speed medium

When in 3 step mode this sets the fan speedmedium output voltage as a percentage, 50%. = 5Vetc. When in 10 step mode this sets the outputvoltage profile at a virtual step of 6.6.

Name. Fan speed medium

Object Type: Analogue value

Present value: As set, 25 to 75. (66) (W)

Units: Percent

Status flags: In Alarm / Fault / Overridden / Out ofService

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 46

Description: Fan speed high

When in 3 step mode this sets the fan speed highoutput voltage as a percentage, 100%. = 10V etc.When in 10 step mode this sets the output voltageprofile at step 10.

Name. Fan speed high

Object Type: Analogue value

Present value: As set, 50 to 100. (100) (W)

Units: Percent

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 103

Description: Device instance

Name. Device instance.

Object Type: Analogue value

Present value: 898000 (Default), 0 to 4194302.(W)

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 101

Description: Address

Name. Address.

Object Type: Analogue value

Present value: As set , 0 to 127. (16) (W)

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Analogue Value instance 102

Description: Maximum address

Name. Maximum address.

Object Type: Analogue value

Present value: As set, 1 to 127. (64) (W)

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Page 15: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 15 of 17© Copyright Annicom 2019. All Rights Reserved

Binary Input object properties

Binary input instance 104

Description: Card contact input

Name: Card input.

Object Type: Binary input

Present value: As set, Inactive / Active.

Inactive text: Not occupied

Active text: Occupied

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Binary input instance 105

Description: Window contact input

Name: Window input.

Object Type: Binary input

Present value: As set, Inactive / Active.

Inactive text: Window closed

Active text: Window open

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Binary Value object properties

Binary value instance 144

Description: Enable card contact input

Name: Card contact actions.

Object Type: Binary value

Present value: As set, 0 or 1. (0) (W)

Inactive text: 0 / Card input disabled

Active text: 1 / Card input enabled

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Binary value instance 145

Description: Enable window contact input

Name: Window contact actions.

Object Type: Binary value

Present value: As set, 0 or 1. (0) (W)

Inactive text: 0 / Window input disabled

Active text: 1 / Window input enabled

Status flags: In Alarm / Fault / Overridden / Out ofService

Event State: On Normal / Off Normal

Out of Service: False / True

Binary value instance 146

Description: Internal / external sensor selection

Name: Select sensor.

Object Type: Binary value

Present value: As set, 0 or 1. (0) (W)

Inactive text: 0 / Internal sensor

Active text: 1 / External sensor

Status flags: In Alarm / Fault / Overridden / Out ofService

Event State: On Normal / Off Normal

Out of Service: False / True

Binary value instance 147

Description: Enable/ disable setpoint switches

Name: Setpoint switch action.

Object Type: Binary value

Present value: As set, 0 or 1. (0) (W)

Inactive text: 0 / Enabled

Active text: 1 / Disabled

Page 16: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 16 of 17© Copyright Annicom 2019. All Rights Reserved

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Binary value instance 148

Description: Enable/ disable fanspeed switches

Name: Fanspeed switch action.

Object Type: Binary value

Present value: As set, 0 or 1. (0) (W)

Inactive text: 0 / Enabled

Active text: 1 / Disabled

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Binary value instance 149

Description: Enable/ disable on off switch

Name: On off switch action.

Object Type: Binary value

Present value: As set, 0 or 1. (0) (W)

Inactive text: 0 / Enabled

Active text: 1 / Disabled

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Binary value instance 150

Description: Unit on / off

Name: Unit on / off.

Object Type: Binary value

Present value: As set, 0 or 1. (W)

Inactive text: Unit off

Active text: Unit on

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Multistate Value object properties

Multi state value instance 184 (0-10V fanspeed versiononly)

Description: Fan steps

Name: Fan steps selection.

Object Type: Multi state value

Number of states: 2

Present value: As set, 1 or 2. (1) (W)

State 1 text: 3 steps

State 2 text: 10 steps

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Multi state value instance 185

Description: Operating mode

Name: Operating mode. (W)

Object Type: Multi state value

Number of states: 3

Present value: As set, 1 to 3. (3) (W)

State 1 text: Cool only

State 2 text: Heat only

State 3 text: Heating and cooling (Dual output H&Cversions only)

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True

Page 17: Digital Room Controller (BACnet BN) (Timeclock T) · AX-CNDR-X Digital Room Controller (BACnet BN) (Timeclock T) Issue 2.20 (5/1/19) © Copyright Annicom 2019. All Rights Reserved

AX-CNDR-XDigital Room Controller (BACnet BN) (Timeclock T)

Issue 2.20 (5/1/19) Page 17 of 17© Copyright Annicom 2019. All Rights Reserved

Multi state value instance 197

Description: MSTP baud rate

Name: MSTP baud rate. (W)

Object Type: Multi state value

Number of states: 6

Present value: As set, 1 to 5. (2) (W)

State 1 text: 19200

State 2 text: 38400

State 3 text: 57600

State 4 text: 76800

State 5 text: 115200

Status flags: In Alarm / Fault / Overridden / Outof Service

Event State: On Normal / Off Normal

Out of Service: False / True