GE Consumer & Industrial Power Protection ISM_Cabinet_GE_01 Operating Manual Uninterruptible Power supply Digital Energy™ ISM Intelligent Synchronization Module SG Series 80 –200 kVA / 400Vac CE & SG Series 10 –500 kVA / 480Vac UL SitePro 10 – 500 kVA / 400Vac CE / From Series 6 & SitePro A 10 – 300 kVA / 480Vac UL / Series 6 Manufactured by: GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 51 44 www.gedigitalenergy.com GE imagination at work

Transcript of Digital Energy™ ISM - GE...

Page 1: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

GE Consumer & Industrial Power Protection

TM

ISM

_Cab

inet

_GE_

01

Operating Manual Uninterruptible Power supply

Digital Energy™

ISM Intel l igent Synchronization Module

SG Series 80 –200 kVA / 400Vac CE & SG Series 10 –500 kVA / 480Vac UL

SitePro 10 – 500 kVA / 400Vac CE / From Series 6 & SitePro A 10 – 300 kVA / 480Vac UL / Series 6 Manufactured by:

GE Consumer & Industrial SA General Electric Company CH – 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850 51 51 F +41 (0)91 / 850 51 44

www.gedigitalenergy.com

GE imagination at work

Page 2: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 2/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

Model: ISM - Intel l igent Synchronization Module / Series 0

Date of issue: 01.10.2005

File name: OPM_ISM_OPT_10K_M50_0GB_V021

Revision: 2.1

Identification No.

Up-dating

Revision Concerns Date

2.0 GE House-style & Configuration Warnings in Section 4 - Installation 15.01.2005

2.1 GE Consumer & Industrial SA 01.10.2005 COPYRIGHT © 2005 by GE Consumer & Industrial

All rights reserved.

The information contained in this publication is intended solely for the purposes indicated.

The present publication and any other documentation supplied with the ISM system is not to be reproduced, either in part or in its entirety, without the prior written consent of GE.

The illustrations and plans describing the equipment are intended as general reference only and are not necessarily complete in every detail.

The content of this publication may be subject to modification without prior notice.

Page 3: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 3/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

Dear Customer, We thank you for selecting our products and are pleased to count you amongst our very valued customers at GE. We trust that the use of the ISM Intelligent Synchronization Module, developed and produced to the highest standards of quality, will give you complete satisfaction. Please read carefully the Operating Manual, which contains all the necessary information and describes all you need to know about the use of the ISM.

Thank you for choosing GE!

Manufactured by: Distributed by: Your service contact:

g

GE Consumer & Industrial SA General Electric Company

CH – 6595 Riazzino (Locarno) Switzerland

Page 4: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 4/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

Table of contents Page

1 SAFETY RULES............................................................................................................................................... 5 1.1 IMPORTANT SAFETY RULES...............................................................................................................................................................6 1.2 SAFETY SYMBOLS AND WARNINGS ..............................................................................................................................................7

2 DESCRIPTION................................................................................................................................................ 8 2.1 SCB - SYNCHRONIZATION OF CRITICAL BUSES .......................................................................................................................8

2.1.1 STS - Static Transfer Switch ................................................................................................................................................................... 9 2.2 SERVICE AND TECHNICAL SUPPORT.......................................................................................................................................... 10 2.3 WARRANTY............................................................................................................................................................................................ 10 2.4 RECYCLING AT THE END OF SERVICE LIFE .............................................................................................................................. 10

3 LAYOUT........................................................................................................................................................ 11 3.1 LAYOUT ISM .......................................................................................................................................................................................... 11

4 INSTALLATION............................................................................................................................................ 12 4.1 TRANSPORT........................................................................................................................................................................................... 12

4.1.1 Dimensions and weight ........................................................................................................................................................................ 12 4.2 DELIVERY................................................................................................................................................................................................ 13 4.3 STORAGE................................................................................................................................................................................................ 13 4.4 PLACE OF INSTALLATION................................................................................................................................................................ 14 4.5 ELECTRICAL WIRING ......................................................................................................................................................................... 15 4.6 CONTROL BUS CABLES CONNECTION...................................................................................................................................... 18 4.7 UPS CONFIGURATION REQUIREMENTS.................................................................................................................................... 20

5 CONTROL PANEL........................................................................................................................................ 21 5.1 CONTROL PANEL ................................................................................................................................................................................ 21 5.2 TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL.................................................................................. 21

6 LCD SCREEN................................................................................................................................................ 24 6.1 METERING MODE................................................................................................................................................................................ 25 6.2 ALARM..................................................................................................................................................................................................... 26

6.2.1 Events (Alarms and Messages) .......................................................................................................................................................... 27 6.2.1.1 Alarms list ............................................................................................................................................................................................................... 27 6.2.1.2 Messages list......................................................................................................................................................................................................... 28 6.2.1.3 Event report ISM .................................................................................................................................................................................................. 29

6.3 USER PARAMETERS ........................................................................................................................................................................... 30

7 OPERATION................................................................................................................................................. 31 7.1 PROCEDURES FOR SCB - SYNCHRONIZATION OF CRITICAL BUSSES.......................................................................... 31

8 MAINTENANCE ........................................................................................................................................... 32

9 NOTES .......................................................................................................................................................... 33 9.1 NOTES FORM........................................................................................................................................................................................ 33

10 ANNEXE ................................................................................... ERRORE. IL SEGNALIBRO NON È DEFINITO. 10.1 TECHNICAL DIAGRAMS............................................................................. ERRORE. IL SEGNALIBRO NON È DEFINITO.

Page 5: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 5/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

1 SAFETY RULES With this document, GE gives to the user all the necessary information about the correct installation and connection of the ISM. Please read carefully this Operating Manual before installing or operating the equipment. If any problems are encountered with the procedures contained in this Operating Manual, please contact the nearest Service Centre before you proceed. All ISM installation, maintenance and service work should be performed by qualified service personnel only.

The KNOWLEDGE and the FULLY compliance of the safety instructions and the warning contained in this manual are

THE ONLY CONDITION to avoid any dangerous situations during installation, operation, maintenance work, and to preserve the maximum reliability of the UPS system.

NOTE !

While every care has been taken to ensure the completeness and accuracy of this manual, GE assumes no responsibility or liability for any losses or damages resulting from the use of the information contained in this document.

GE Refuses any responsibility in case of non-observance, unauthorised alterations or improper use of the delivered UPS.

Page 6: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 6/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

1.1 IMPORTANT SAFETY RULES SAVE THESE INSTRUCTIONS This manual contains important instructions for model ISM - Intelligent Synchronization Module that should be followed during installation and maintenance of the unit. GENERAL • Move the cabinet in a horizontal position in its original package to the final destination room. • To lift the cabinets, use a forklift or lifting belts with spreader bars. • Check for sufficient floor and elevator loading capacity. • Check carefully the integrity of the ISM equipment.

In case you note some visible damage, do not put the ISM under voltage, but contact the nearest Service Centre.

• WARNING! RISK OF ELECTRICAL SHOCK: Do not remove covers; there are no user serviceable parts inside.

• This unit contains potentially hazardous voltages. • All maintenance and service work should be performed by qualified service personnel. INSTALLATION • This equipment must be installed and connected only by trained personnel. • This equipment is intended for use in a controlled indoor environment free of conductive

contaminants and protected against animals intrusion. • WARNING! HIGH EARTH LEAKAGE CURRENT: earth connection is essential before connecting to AC

input! • Do not install the equipment in an excessively humid environment or near water. • Avoid spilling liquids on or dropping any foreign object into the equipment. • The unit must be placed in a sufficiently ventilated area; the ambient temperature should not

exceed 35°C (95°F). • It is important that air can move freely around and through the unit. • Do not block the air vents. • Avoid locations in direct sunlight or near heat sources. STORAGE • Store the equipment in a dry location; storage temperature must be within -25°C to 55°C

(-13°F to 131°F).

WARNING ! The installation and cabling of the options must be performed by a QUALIFIED SERVICE PERSON. Before operating be sure the installation is completely switched off and voltage free

Page 7: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 7/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

1.2 SAFETY SYMBOLS AND WARNINGS Safety warnings The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to the UPS system and the supplied critical loads. The non-observance of the warnings reminding hazardous situations could result in human injury and equipment damages. Please pay attention to the meaning of the following warnings and symbols:

WARNING ! Referred to procedures or operations which could cause damages to the persons or to the system, when not correctly operated.

NOTE !

Warns the user about important operations or procedures described in this manual.

Safety symbols

When the text includes one or more of the following symbols, that means exist a potentially hazardous situations. Please remind the meaning of each symbol.

CAUTION

Related to all the potentially hazardous situations which may result in injury.

DANGER OF PARTS ELECTRICALLY LIVE

Related to all the situation with potentially hazardous voltage.

DANGER OF EXPLOSION

Used to indicate conditions where exploding parts can cause serious injury.

DANGER OF CRUSHING

Used when moving the equipment due to the heavy weight.

DANGER OF OVERHUNG LOAD

Used when the equipment is lifted by a crane.

DO NOT TOUCH

Risk of parts with hazardous voltages or parts in movement.

Page 8: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 8/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

2 DESCRIPTION 2.1 SCB - SYNCHRONIZATION OF CRITICAL BUSES

Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram

The UPS configuration in Fig. 2.1-1 enhances security, reliability and safety of a system for the power supply to extremely critical loads. Basically it is composed of 4 major blocks, see Fig 2.1-1: • UPS Group A: this group can be minimum 1, maximum 6 units.

• UPS Group B: this group can be minimum 1, maximum 6 units.

• ISM – Intelligent Synchronization Module. ISM (Intelligent Synchronization Module) allows synchronizing of two independent groups of parallel UPS’s, each having a maximum of 6 UPS units of equal rating from 10 – 500 kVA.

• STS – Static Transfer Switch. A Static Transfer Switch can select between 2 sources (UPS groups). As standard the Static Transfer Switch will supply the load from the preferred source. In case the source would fail it will transfer the load to the second source. A condition is that both sources are synchronized continuously, also on battery operation.

Each group of UPS’s are independent and capable to supply the full load, eventually redundant. Each unit in the group is synchronized to its Master, which in return synchronizes to the utility voltage, if available.

Page 9: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 9/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

Features & benefits:

• Redundant Power Supply providing highest reliability.

• Redundant Communication Bus tolerating an accidental cable cut.

• CRC Code (Cyclic Redundancy Check) for error free communication.

• High Precision Synchronization offering seem less transfer from one source to the other.

• Top and Bottom Cable access for easy installation.

• Compatible with GE SitePro (only series 6) and SG Series UPS and with GE’s unique RPA concept.

• Global Power Supply Voltage for worldwide usage (208, 400 or 480 VAC – 50 / 60 Hz).

• Synchronizes 2 groups of max. 6 UPS units (ranging from 10 - 500 kVA) each offering great flexibility.

• User Friendly Control Panel providing complete information on the spot. 2.1.1 STS - Static Transfer Switch

Fig. 2.1.1-1 STS - Static Transfer Switch block diagram

The STS is designed for the switching of two alternativepower sources without interruption of the supply toenergy receivers. The STS is connected to two sources of electrical powerwith terminal X01 for the Group A source and X02 forthe Group B source. Depending on current settings and system status, oneof the two sources (Group A or Group B) is connected tothe output terminal X03 (STS Output). K1, K2, K3, K4 and K5 are manually operated circuitbreakers. K1 and K2 are normally open, while K3, K4 and K5 arenormally closed. X01, X02 and X03 are terminals.

NOTE !

For installation procedures and functional descriptions of the STS, please consult the appropriate Operating Manual.

Page 10: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 10/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

2.2 SERVICE AND TECHNICAL SUPPORT

For any request of technical support please contact the supplier who provided the system.

Stamp of your Dealer or local responsible of the Technical Assistance (see page 3)

2.3 WARRANTY

GE operates through its authorised agents and warrants that the standard products will be free of defects in materials and workmanship for a period of 12 months, after the date of the invoice, or such other period as may be specified.

NOTE !

This warranty does not cover failures of the product which result from incorrect installation, misuse, alterations by persons other than authorised agents, or abnormal working conditions.

2.4 RECYCLING AT THE END OF SERVICE LIFE

NOTE !

This product has been designed to respect the environment, using materials and components respecting eco-design rules.

It does not contain CFCs (Carbon Fluor Clorid) or HCFCs (Halogen Carbon Fluor Clorid).

GE, in compliance with environment protection recommends to the User that the ISM equipment, at the end of its service life, must be recovered conforming to the local applicable regulations.

Page 11: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 11/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

3 LAYOUT 3.1 LAYOUT ISM

TM

ISM

_Cab

inet

_GE_

01

Fig. 3.1-1 ISM general view

ISM

_LB

S_C

abin

et o

pen_

01

Fig. 3.1-2 ISM internal view

ISM

_LB

S_C

abin

et o

pen_

02

Fig. 3.1-3 ISM internal view

MAINTENANCE MAINTENANCE

SYNC ALARM SERVICE

MUTE

LOAD

BYPASS

INVERTER

BYPASS

INVERTER

GROUP BGROUP A

BYPASS OK

INVERTER OK

B SYNC TO AA SYNC TO B

INVERTER OK

BYPASS OKSTS

SYNC MASTER

A B

METERING

ALARMS

PARAMETERS

+

-ENTER

AUTOSYNCOFF

ISM_LBS_Control panel_01

Fig. 3.1-4 Control panel

Page 12: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 12/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

4 INSTALLATION 4.1 TRANSPORT

The ISM is fixed on a transport socket suitable for a forklift, which includes a special layer of Ethafoam to protect the equipment against the transport shock. Normally the ISM is packaged within a carton box. On request the equipment can be packaged in a wooden case.

Move the ISM in its original package to the final destination room. Do not stack other packages on top: they could damage the cabinet.

NOTE !

When moving the ISM, pay attention to: FRAGILE

SENSITIVETO DAMPNESS TO HEAT

SENSITIVE

TO FROSTSENSITIVE

WARNING !

When loading / downloading and when moving the ISM, it is forbidden: When loading / downloading and when moving the ISM, pay attention to:

4.1.1 Dimensions and weight

Dimensions ISM

350 mm x 190 mm x 584 mm

13.78” x 7.48” x 23.00 inches

Weight ISM

ISM ISM with standard package

20 Kg / 44 lbs 30 Kg / 66 lbs

TM

ISM

_Cab

inet

dim

ensi

ons_

GE

_01

350mm

264mm43mm

190mm

584m

m

42m

m50

0mm

42m

m1.

66"

23.0

0"

19.6

9"1.

66"

7.48"

43mm1.70"

10.39"1.70"

13.78"

14m

m0.

55"

Fig. 4.1.1-1 ISM cabinet dimensions

NOTE ! The weight is marked outside the package!

Page 13: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 13/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

4.2 DELIVERY When delivered, check carefully the package integrity and the physical conditions of the ISM equipment. In case of any damage sustained during transport, immediately inform the carrier and contact your local Service Centre. A detailed report of the damage is necessary for any insurance claim.

NOTE !

A damaged ISM must never be installed or connected to power!

4.3 STORAGE

The equipment is carefully packed for transport and storage so that it is in a perfect condition when eventually installed. Never leave an ISM outside the building and do not store the ISM one on top of the other. It is recommended to store the ISM in its original package in a dry, dust free room and far away from chemical substances, with temperature not exceeding -25°C to 55°C (-13°F to 131°F).

Some important functions of the ISM are defined by parameters stored in a RAM memory. The RAM is supplied by a small backup battery located on the Control Unit board. If the storage time of the ISM exceeds 1 year, these functions should be verified by an authorised Service Centre before putting the ISM into operation.

NOTE !

In case of storage of the ISM pay attention to: FRAGILE

SENSITIVETO DAMPNESS TO HEAT

SENSITIVE

TO FROSTSENSITIVE

Page 14: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 14/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

4.4 PLACE OF INSTALLATION The ISM should be installed in a restricted area where only qualified personnel should be admitted. The place of installation should be clean, dust-free, and provided with proper ventilation or air-conditioning. We strongly advice that the ambient temperature should not exceed 20° to 25°C / 68° to 77°F (max. 35°C / 95°F).

NOTE ! The installation of the ISM must be executed by QUALIFIED PERSONNEL ONLY.

A single-phase power outlet should be provided near the ISM for connection of power tools or test equipment. This outlet must be grounded. ISM positioning

ISM

_LB

S_C

abin

et d

ispo

sitio

n_01

GB

UPS 3UPS 2

UPS 1

UPS 1UPS 2

UPS 3

GROUP A

GROUP BISM

_Cab

inet

_GE_

03

TM

400mm / 16"Min.

Fig. 4.4-1 ISM positioning

The ISM should be mounted flush to a wall. Clearance around the front of the ISM should be sufficient to enable free passage of personnel with the door fully open, and to allow sufficient airflow for the ventilation.

Recommended minimum clearance between the ceiling and the top of the ISM should be 400 mm (16 “) for proper cooling air exhaust.

NOTE ! The bolts used for fixing the ISM to the wall must be adequate for its weight.

Page 15: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 15/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

4.5 ELECTRICAL WIRING

WARNING ! The installation and connection must be performed by QUALIFIED SERVICE PERSONNEL only. Refer to the “Safety prescriptions - Installation” described on page 6.

Carefully read the following recommendations before proceeding: • Ensure that the AC external isolators are Off, and prevent their inadvertent operation. • Do not close any external isolators prior the commissioning of the equipment. • The input / output cables must be put in order and fixed, taking care to avoid risk of short-circuit

between different poles. • The earthing connection of the electrical system must be in accordance with local regulation. Input overcurrent protection and wire sizing

Fig. 4.5-1 Input overcurrent protection and wire sizing

For correct rating of fuses and cable sections for input power of the ISM see data indicated in the tables below.

Fuses AgL or Circuit breakers

Group A: F5 – F6 & Group B: F7 – F8 2 x (2 x 2 A)

Wire sizing

Group A: L1 + L2 + PE & Group B: L1 + L3 + PE Min. 3 x 1.5 mm2 / Max. 3 x 2.5 mm2

Min. 3 x 16 AWG / Max. 3 x 14 AWG

NOTE ! The delivery and installation of fuses and input connections of the ISM are at the customer’s expense, unless agreed otherwise.

Page 16: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 16/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

Openings for input and output cable connections

ISM

_LBS

_Cab

inet

inpu

t cab

le_0

1

A

B

B

A

B

Fig. 4.5-2 Opening on top/bottom of the cabinet for input and output cables

ISM openings are provided either on top or on the bottom of the cabinet for the connection of input and output cables. Pay attention to the position of these openings, when choosing the placement of the ISM. Position of the input and the output can be modified by exchanging the cover plates “A and B” (see Fig. 4.5-2).

Connection of power supply cables

ISM

_LB

S_T

R1-

TR2_

01

0

Fig. 4.5-3 Transformer TR1 and TR2

NOTE ! Verify the input voltage for power supply and connect the cable without label to the corresponding input of the terminal. Possible voltages are 208V, 400V and 480V (Phase – Phase. See Fig. 4.5-3).

Page 17: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 17/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

Fuses rating

ISM

_LB

S_F

1-2-

3-4_

01

F1-F2-F3-F4

Fig. 4.5-4 Fuses rating

NOTE ! Verify for correct fuse rating “F1 - F2 - F3 - F4” on dependence of the power supply input voltage, according to the table below. In case of replacement the same type and the same rating must be used. The replacement of fuses must be performed by QUALIFIED SERVICE PERSONNEL only.

For 208 VAC 0.75 A Fuse type Class CC – Time Delay – 13/32” x 1 1/2” – 600 VAC

For 400 VAC 0.3 A Fuse type Class CC – Time Delay – 13/32” x 1 1/2” – 600 VAC

For 480 VAC 0.3 A Fuse type Class CC – Time Delay – 13/32” x 1 1/2” – 600 VAC

Connection of power supply input cables

ISM

_LB

S_C

onne

ctio

n po

wer

_01

L1

L2

PE

PE

L3

L1

GR

OU

P A

GR

OU

P B

Group A Group B

Fig. 4.5-4 Connection of power supply input cables

Input glands are suitable for cables having diameters: from 6 mm to 12 mm / 2.37” to 4.73”

ISM Input A

L1 Phase L1 from Output Load Group A PE Ground from Output Load Group A L2 Phase L2 from Output Load Group A

ISM Input B

L1 Phase L1 from Output Load Group B PE Ground from Output Load Group B L3 Phase L3 from Output Load Group B

Page 18: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 18/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

4.6 CONTROL BUS CABLES CONNECTION

WARNING ! The installation and connection must be performed by QUALIFIED SERVICE PERSONNEL only. Refer to the “Safety prescriptions - Installation” described on page 6.

Carefully read the following recommendations before proceeding: • Ensure that the AC external isolators are Off, and prevent their in adverted operation. • Do not close any external isolators prior to the commissioning of the equipment. • The input / output cables must be put in order and fixed, taking care to avoid risk of short-circuit

between different poles. • The earthing connection of the electrical system must be in accordance with local regulations.

Fig. 4.6-1 Diagram showing the maximum allowable length of communication cables

The standard length of the control bus cable between ISM and the first unit of each group is 12 m / 40 ft. Maximum distance between ISM and the last unit of each group is 85 m / 279 ft.

L max. : 85 m – [(No. of UPS – 1) x 12 m] 279 ft – [(No. of UPS – 1) x 40 ft]

Maximal number of UPSs in one group is 6.

ISM

_LBS

_CBC

con

nect

ion_

01G

B

P6P5

J52J53

J63J62

JA2

JA1

JB2

JB1

JB1

JB2

JA1

JA2

Control bus cablesGroup A

Control bus cablesGroup B

Fig. 4.6-2 Connection of the cables of the communication

bus to P5 / P6 – Parallel bus interface

Control bus cablesGroup B

Control bus cablesGroup A

ISM

_LBS

_CBC

con

nect

ion_

02G

B

Fig. 4.6-3 Internal connection of the communication bus cables

Page 19: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 19/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

ISM

_LB

S_C

BC

con

nect

ion_

03G

B

UPS 3UPS 2

Q1

Q2

OFF

ON

ON

OFF

Q2

OFF

ON

OFF

ON

Q1

UPS 1

OFF

OFF

Q2

ON

ON

Q1

UPS 1

UPS 3UPS 2

Q2

Q2

ON

OFF

ON

Q1

OFF

Q2

ON

OFF

Q1

OFF

ON

OFF

ON

Q1

OFF

ON

P5P6

GROUP A

GROUP B

Fig. 4.6-1/2

ISM

From ISM to UPS 1 / Group AControl bus cables Group A

Control bus cables Group B(from ISM to UPS 1 / Group B)

See Fig. 4.6-5/6

See Fig. 4.6-5/6 Fig. 4.6-4 Connection of the communication bus cables from ISM to UPS’s Group A and Group B

Control bus cables routing

Place and fix the cables JA and JB with the appropriate clamps inside the UPS cabinets. Pay attention to the fact, that routing of cables shall allow the removal of the protection covers.

NOTE ! Pay attention when cabling and routing the bus cables JA and JB inside the UPS cabinet. In case the unit should be removed from the system, the control bus cables Group A and Group B must be removed from the cabinet without disconnecting them from the metal plates where are located the sockets JA and JB. Please contact your Service Centre.

For reliability reasons the cables JA and JB connecting the units should be run in separated protected conduits, as well as separated from the power cables. It is important that the cable JA is as long as cable JB.

ISM_LBS_RPA-IM0048_01

JP3

JP1

JP4

IM 0048

JP2

JP1 JP2

JP4JP3

JB1

JA1

JB

JA

Fig. 4.6-5 PCB “P34 – Parallel Bus Interface” of UPS number 1 of either

Group A or B, prior to the connection with ISM

JP2JP1

JP3JP4

JP3

JP2

JP1

JP4

IM 0048Control Bus cable from ISM

Control Bus cable from ISM

ISM_LBS_RPA-IM0048_02GB

JA

JBJB

JA

Fig. 4.6-6 PCB “P34 – Parallel Bus Interface” of UPS number 1 of

either Group A or B, after the connection with ISM

The Jumpers JP1, JP2, JP3 and JP4 ARE INSERTED.

The Jumpers JP1, JP2, JP3 and JP4 MUST BE REMOVED.

NOTE ! Since the position of PC Board “P34 – Parallel Bus Interface” inside the UPS changes between the various UPS output powers, it’s recommended to consult the appropriate Operating Manual for cable connections.

Page 20: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 20/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

4.7 UPS CONFIGURATION REQUIREMENTS

WARNING !

The installation and connection must be performed by QUALIFIED SERVICE PERSONNEL only. Refer to the “Safety prescriptions - Installation” described on page 6.

NOTE ! The UPSs are already correctly configured, if they have been ordered and supplied with the ISM. Otherwise please make sure that UPSs connected with the ISM mount:

• P13 - IM0086 RPA Board with same software version as on the ISM. • Following software versions on P3 - IM0007 Control Board:

- For SitePro units: U2, U3: version 2.08 or higher; U36: version 7.0 or higher. - For SG Series units: U2, U3: version 3.06 or higher; U36: version 7.0 or higher.

Page 21: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 21/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

5 CONTROL PANEL 5.1 CONTROL PANEL

MAINTENANCE MAINTENANCE

SYNC ALARM SERVICE

MUTE

LOAD

BYPASS

INVERTER

BYPASS

INVERTER

GROUP BGROUP A

BYPASS OK

INVERTER OK

B SYNC TO AA SYNC TO B

INVERTER OK

BYPASS OKSTS

SYNC MASTER

A B

METERING

ALARMS

PARAMETERS

+

-

ENTER

AUTOSYNCOFF

ISM_LBS_Control panel_01 Fig. 5.1-1 General Control Panel

5.2 TABLE OF FUNCTIONS AND INDICATIONS ON CONTROL PANEL

SYNC ALARM SERVICEAUTO

SYNCOFF

ISM_LBS_CP 1_01

Fig. 5.2-1 Control Panel – Part 1

SYNCAUTO

SYNC AUTO – Green LED When lit, it indicates that the sync command is active and that the inverters of Group A and B will be synchronized to the selected “Super Master”. The “Super Master” will be automatically chosen.

OFFSYNC SYNC OFF – Red LED

When lit, it indicates that the sync command is disabled due to one or both of the following conditions: • SYNC command is OFF; • One of the two (2) UPS groups is not present.

ALARM ALARM – Yellow LED General alarm condition. It blinks when one or more alarm is activated. The internal buzzer is ON. The LED remains lighted (with alarm condition still present) and the buzzer stops as the key “mute” has been pressed.

SERVICE SERVICE – Yellow LED When lit it indicates that a regular maintenance service is needed. May be reset by a service technician only. See Section 8 – Maintenance.

Page 22: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 22/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

MAINTENANCE MAINTENANCE

LOAD

BYPASS

INVERTER

BYPASS

INVERTER

GROUP BGROUP A

BYPASS OK

INVERTER OK

B SYNC TO AA SYNC TO B

INVERTER OK

BYPASS OKSTS

SYNC MASTER

A B

ISM_LBS_CP 2_01 Fig. 5.2-2 Control Panel – Part 2

A

B

SYNC MASTER A (B) – Green LED Pushbuttons commands: A When pressed, Group A will be the synchronization “Super Master” and Group

B will synchronize to Group A. The “SYNC MASTER A” LED will be lit. Pressing this button disables the automatic “Super Master” selection.

B When pressed, Group B will be the synchronization “Super Master” and Group A will synchronize to Group B. The “SYNC MASTER B” LED will be lit. Pressing this button disables the automatic “Super Master” selection.

The SYNC MASTER A (B) green LED, indicates whether Group A or B is the Super Master.

OUTPUT SYNC – Green LED When lit, it indicates that the UPS outputs of Groups A and B are synchronized and within the allowed limits. This indication is derived from comparing the output of the second UPS group to the output of the selected “Super Master” group. When blinking, it indicates that the UPS outputs of Groups A and B are synchronizing.

MAINTENANCE

BYPASS

INVERTER OUTPUT – Green LED The corresponding LED will be lit, depending on the UPS output status of Group A (or B): INVERTER, BYPASS (Automatic Bypass) or MAINTENANCE (Manual Bypass).

INVERTER OK INVERTER OK – Green LED

When lit it indicates that the inverter power to UPS Group A (or B) is available and it is within the allowed tolerance.

BYPASS OK BYPASS OK – Green LED

When lit, it indicates that the bypass power to UPS Group A (or B) is available and it is within the allowed tolerance.

A SYNC TO B A SYNC TO B – Green LED

When lit, it indicates that the UPS outputs of Groups A and B are synchronized and within the allowed limits. Group B is the synchronization Super Master.

B SYNC TO A B SYNC TO A – Green LED

When lit, it indicates that the UPS outputs of Groups A and B are synchronized and within the allowed limits. Group A is the synchronization Super Master.

Page 23: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 23/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

MUTE

ISM_LBS_CP 2_01

Fig. 5.2-3 Control Panel – Part 3

LAMP TEST Key to test the control panel LED’s and buzzer. (Pressing this key causes all the LED’s to light and the buzzer to sound 3 times).

MUTEMUTE Key to reset general alarm and buzzer.

METERING

ALARMS

PARAMETERS

+

-ENTER

ISM_CP LCD_01

Fig. 5.3-1 Control Panel - LCD screen See Section 6 – LCD SCREEN

Page 24: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 24/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

6 LCD SCREEN

METERING

ALARMS

PARAMETERS

+

-ENTER

ISM_CP LCD_01

Fig. 6-1 LCD screen The user interface consists of a back lit LCD screen having:

• 4 lines with 20 characters (standard version for Latin characters);

and

• 6 keys (the function is described for each operating mode).

The operation is extremely simple and is structured on three important main menus related to the ISM operation, as follows: METERING An ISM must offer some metering information for the user to be able to examine

the operating status at any time.

ALARMS In case of abnormal functioning, the ISM must keep a history of what has happened as a series of events.

PARAMETERS The user must be able to program certain functions of the ISM (user parameters, accessible without password) to his needs.

LCD screen standard version

METERING

ALARMS

PARAMETERS

+

-ENTER

LCD screen

4 rows x20 characters

The 3 buttons existing on the left side of the screen are used to activate the operating modes, while the buttons on the right side are used to carry out functions inside these operating modes.

Page 25: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 25/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

6.1 METERING MODE The metering mode is entered any time when the metering button is pressed. While in this mode the LCD will display a series of screens containing metering information.

In this mode the buttons perform the following functions:

METERING Scrolls forward to the next screen. ALARMS Abandons the metering mode and enters the alarms mode. PARAMETERS Abandons the metering mode and enters the parameters mode. + Scrolls forward to the next screen. – Scrolls backward to the previous screen. ENTER Displays the main screen for this mode.

INTELL. SYNC MODULE

A sync to B A: LOAD ON INVERTER B: LOAD OFF PARAMETERS

METERING

ALARMS

ENTER

- +

This screen displays the current status of the synchronization command and the UPS outputs (for both Group A and B). The information offered by this screen consists of: • Synchronization: The status of the synchronization command (A sync to B, B sync to A or Sync

OFF). • Group A: The source of the power supplied to the Load (LOAD ON INVERTER, LOAD ON

BYPASS, LOAD ON MAN. BYP. or LOAD OFF). • Group B: The source of the power supplied to the Load (LOAD ON INVERTER, LOAD ON

BYPASS, LOAD ON MAN. BYP. or LOAD OFF).

OUTPUT STATUS

Synchronized Load A = 50% Load B = 20% PARAMETERS

METERING

ALARMS

ENTER

- +

This screen displays the load of UPSs output (for both Group A and B). The information offered by this screen consists of: • Synchronization status between UPSs of Group A and B; • The load amount as a percentage of the nominal load of Group A (referred to the most loaded

phase); • The load amount as a percentage of the nominal load of Group B (referred to the most loaded

phase).

MISCELLANEOUS

ISMOperTime : 123451h SW Version : XXX-YYYS/N: 72-97756 PARAMETERS

METERING

ALARMS

ENTER

- +

This screen displays miscellaneous information. The information offered by this screen consists of: • The total operating time of the ISM (in hours). • The software version. • The serial number.

Page 26: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 26/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

6.2 ALARM The alarms mode is entered any time when the ALARMS button is pressed. The LCD will display a series of screens corresponding to the last 256 events, one event per screen. The buttons perform the following functions: METERING Abandons alarms mode and enters metering mode. ALARMS Next screen. PARAMETERS Abandons the alarms mode and enters the parameters mode. + Scrolls forward to the next screen. – Scrolls backward to the previous screen. ENTER Displays the main screen for this mode. The events displayed are the standard GE events as described in the Section 6.2.1 - EVENTS (Alarms and Messages). The information displayed includes:

• The exact date and time when the event occurred.

• The number of the event, 255 being the most recent event, and 0 the oldest.

• The standard GE code for the event and the machine status word.

• An explicit text description of the event.

15.09.2003 22:11:51 NR = 255 Status=FA12 4000: SETUP VALUES

LOST PARAMETERS

METERING

ENTER

- +

ALARMS

The initial screen of this mode is the one showing the most recent event.

Page 27: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 27/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

6.2.1 Events (Alarms and Messages)

Each of the following listed events can be displayed on the LCD screen. Alarms and Messages are differently specified because the alarms are indicating an abnormal functioning of the ISM (which are additionally signalled with the LED alarm and acoustically with the buzzer), while the messages indicate the various states of operation of the ISM (stored in the events list, but not activating the LED alarm and the buzzer). When in alarms mode, the LCD screen displays a time ordered sequence of screens corresponding to the last 256 alarms and messages, each screen indicating:

The number of the event (255 = the most recent).

The date and time when the event occurred.

The standard code and the status word.

An explicit text description of the events.

6.2.1.1 Alarms list

Code Alarm Meaning

4000 SETUP VALUES LOST

Parameters are lost and have been replaced with default values. Call nearest Service Centre for intervention.

4001 REGULATION BOARD FAILURE

Verification of correct ID number setting on the control board IM0007. Must always be set to 8. Verification of the correct function of the parallel board IM0086 and IM0007. In case of failure detection the functions of the ISM will be disabled.

4005 GROUP FAILURE ON ISM SYSTEM

Detection of missing communication: The synchronization between Group A and B is disabled by the ISM.

4579 GROUP A AND B NOT SYNCHRONIZED

Despite command for Group A and B synchronization, a phase shift error was detected superior to the value set in the respective parameter. If the error condition persists for more than 2 seconds (value set by service parameter), this alarm will be issued. When starting synchronization, the alarm will be issued if the error condition persists for more than 10 seconds (value set by service parameter).

Page 28: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 28/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

6.2.1.2 Messages list

Code Message Meaning

4576 SYNCHRONIZE TO GROUP A

The command for the synchronization of Group A and B is active and Group A was chosen to be the Super Master.

4577 SYNCHRONIZE TO GROUP B

The command for the synchronization of Group A and B is active and Group B was chosen to be the Super Master.

4578 GROUP A AND B SYNCHRONIZED

The command for the synchronization of Group A and B is active and the phase error measured between the inverters of Group A and B stays below the value specified in the respective parameter.

4582 COMMAND NOT TO SYNCHRONIZE

ISM disabled the synchronization between Group A and B, because the either key SYNC OFF was pressed or missing communication was detected.

4583 COMMAND TO SYNCHRONIZE

ISM enabled the synchronization between Group A and B, because either the key SYNC AUTO or one of the keys SYNC MASTER A or SYNC MASTER B was pressed.

Page 29: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 29/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

6.2.1.3 Event report ISM In case of failure or malfunctioning, before calling the nearest Service Centre, please note the most important data of your UPS and the most recent events. In order to make the diagnosis easier from our Diagnostic Centre we suggest that you make a copy of this page, fill it out with the requested data and send it by fax. ISM No.: __ __ __ __ __ - __ __ __ __ - __ __ __ __ Series No.: …………….…...

Customer: ..........................................……………..…. Place: ..................…..……………………….......................…........

Date: ...……..... / .....…...... / .....……..….....….. Sent by: .....…................………………………....................….......… On the LCD panel, enter the alarms mode and record the alarms/messages in the list below indicating at least 5 events before the failure time. Remark: exact data and time are very important.

Event No.

Event Code

UPS Status Date Time

H. M. S

255

254

253

252

251

250

Description of repair actions taken:

.........................……………………………........…………………..........................………............................................………...............

.........................……………………………........…………………..........................………............................................………...............

.........................……………………………........…………………..........................………............................................………...............

.........................……………………………........…………………..........................………............................................………...............

249

248

247

246

245

244

243

Actual situation:

.........................……………………………........…………………..........................………............................................………...............

.........................……………………………........…………………..........................………............................................………...............

.........................……………………………........…………………..........................………............................................………...............

.........................……………………………........…………………..........................………............................................………...............

242

241

240

239

238

237

236

Remarks:

.........................……………………………........…………………..........................………............................................………...............

.........................……………………………........…………………..........................………............................................………...............

.........................……………………………........…………………..........................………............................................………...............

.........................……………………………........…………………..........................………............................................………...............

235

Page 30: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 30/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

6.3 USER PARAMETERS The parameters mode is entered any time when the PARAMETERS button is pressed.

The LCD will display a series of screens containing the user parameters, accessible without password protection. The buttons perform the following functions:

METERING Abandons parameters mode and enters metering mode.

ALARMS Abandons parameters mode and enters alarms mode.

PARAMETERS Scrolls forward to the next screen.

+ Scrolls forward to the next screen.

– Selects from the current screen the parameter to edit.

ENTER Starts the editing for the currently selected parameter.

NOTE ! During parameters mode there is no means to perform scroll back on the display.

Example of operation within parameters mode: Purpose: To correct a wrong parameter:

PROCEDURE DATE TIME LANG.

- Enter parameters mode (PARAMETERS). The first screen is displayed. √ √ √ - Scroll to the next screen (+). The second screen is displayed. √ - Move the selection (underscore cursor) to the next parameter in this page (-). √ - Enter Edit mode for the currently selected parameter (ENTER). √ √ √

DATE AND TIME

D M Y Date: 15.09.2003 Time: 12:15:45 PARAMETERS

ALARMS

ENTER

- + METERING

1- DATE AND TIME • D = Day M = Month Y = Year. • Date The set value is thoroughly checked to be a correct format “dd.mm.yyyy”. • Time The set value is thoroughly checked to be a correct format “hh.mm.ss”.

LCD DISPLAY

Language = ENGLISH

PARAMETERS

ALARMS

ENTER

- + METERING

2- LCD DISPLAY • Language This parameter allows the choice of language used to display the information.

Valid choice is English.

Page 31: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 31/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

7 OPERATION

WARNING !

Before connecting hazardous voltages, make sure that: • The cables for ISM supply and communication are correctly connected and in

accordance with existing standards; • The equipment frame has been correctly grounded to the earth; • All panels, which had been previously removed to allow ISM connection, have been

correctly reinstalled; • Make sure fuse holders “F1, F2, F3, F4” inside the ISM cabinet and “F5, F6, F7, F8” in

the distribution cabinet(s) are closed.

7.1 PROCEDURES FOR SCB - SYNCHRONIZATION OF CRITICAL BUSSES Procedure for SCB - Synchronization of Critical busses start-up As soon as one of the UPS’s, either from Group A or Group B supplies the load, the ISM system will automatically start-up.

NOTE ! As the ISM system starts-up, an Alarm is issued and the Buzzer starts sounding if the synchronization at the last shutdown was disabled (“SYNC OFF”).

To enable synchronization, press either the key “SYNC AUTO” for automatic choice of the synchronization source, or “SYNC MASTER A” / “SYNC MASTER B” to choose manually one of the two. Condition for the above is that at least one UPS of a group has it’s electronics supplied and at least one parallel group supplies the load, and consequently the ISM. To switch from automatic to manual synchronization, press one of the keys marked “SYNC MASTER A” or “SYNC MASTER B”, depending on which group is desired to be the Super Master. To change from manual synchronization to automatic, press the key “SYNC AUTO”. To disable synchronization press key “SYNC OFF”.

NOTE ! If a parallel system with an active synchronization command is shutdown (including electronics), the command for synchronization will be disabled and the “Alarm 4005 - Group failure on ISM system” is issued, together with an acoustical signal from the buzzer.

Procedure for SCB - Synchronization of Critical busses shutdown If no UPS of either Group A or B supplies the load, the ISM system is shutdown automatically.

Page 32: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 32/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

8 MAINTENANCE An ISM system, like other electrical equipment, needs periodic preventive maintenance. A regular maintenance check of your installation guarantees higher reliability of your ISM. Preventive maintenance work on the ISM can be done only by trained Service Technicians. We therefore recommend you sign a Maintenance and Service contract with the local Service Centre organisation. The ISM follows the same service program and intervals as for UPS systems. Service check If this LED lights up during the normal operation, that means that the unit has not been serviced for the last 20’000 hours by a GE Trained Technician. We highly recommend that you contact your Service Centre for preventive maintenance work. ISM room conditions and temperature The ISM room has to be maintained clean and free from dust. A high temperature of the ISM room affects the lifetime of several components inside the equipment. Component with limited lifetime We recommend the replacement of component such as lithium battery for the backup of data on the control boards of the units every 50’000 hours.

Page 33: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 33/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module

9 NOTES 9.1 NOTES FORM It is recommended to note in this section Notes, with dates and short descriptions, of all the operations performed on the ISM, such as: maintenance, components replacement, abnormal situations, etc. .

Date Description Done by

Page 34: Digital Energy™ ISM - GE Industrialapps.geindustrial.com/publibrary/checkout/OPM_ISM_OPT_10K...Fig. 2.1-1 SCB – Synchronization of Critical Busses block diagram The UPS configuration

Modifications reserved Page 34/34 OPM_ISM_OPT_10K_M50_0GB_V021.doc Operating Manual ISM – Intelligent Synchronization Module