DIGITAL CONTROLLERS - Marsh Bellofram Corporation...(20 min. of warm up time for TC inputs.) For RTD...
Transcript of DIGITAL CONTROLLERS - Marsh Bellofram Corporation...(20 min. of warm up time for TC inputs.) For RTD...
DIGITALCONTROLLERS
ATCDIGITEC.COM
222 DigiTec Division 800.727.5646 DigiTec Division DigiTec Division 800.727.5646 DigiTec Division
PANE
L DI
SPLA
YDT
C PI
D Co
ntro
ller S
erie
s
48mm DTC50096x48mm DTC11096x96mm DTC330
CONTROL OUTPUT Relay 0 12VDCSSRDrive 1 4-20mA(Current) 2 0-10V(Voltage) 3 0-5V(Voltage) 4 0-20mA(Current) 5
ALARM OUTPUT Relay 0 12VDCSSRDrive 1
AUXILLARY OUTPUT/SPECIAL OnlyOutput1&Output2 00 Output3(Relay) 01 Output3(12VDCSSRdrive) 02 CommunicationRS485 03 Output3(Relay)+ CommunicationsRS485 04 Output3(12VDCSSRdrive)+ 05 CommunicationsRS485 CTInput 06 Output3(Relay)+CTInput 07 Output3(VDCSSRdrive)+CTInput 08 CTInput+CommunicationsRS485 09 SecondAnalogInput (Valvepositionstype) 10 SecondAnalogInput 11 (Valvepositionstype+ CommunicationsRS485 SecondAnalogInput (Remotesetpointtype) 12 SecondAnalogInput 13 (Remotesetpointtype)+ CommunicationRS485
SUPPLY VOLTAGE 85-270AC/DC 0 24VAC/DC 24
DTC500 3 9 01
TheDTCseriesof PIDControllersofferfrontpanelselectionof alloperatingfunctionsexceptforsomeinputtypes.TheDTCseriesoffersmoreflexibilityincontrols,andmorecontroloutputoptionstoDigiTec'sPIDcontrollerline.
TheDTCoffersoptionalMotorizedValveControl,RS-485Communi-cation,HeaterCurrentMonitoring,orRemoteSetpoint.
Auto-tunecontrolwillmonitorthesystemoutputresponseandafter3cyclesitwillautomaticallycalculateandreplacethePIDconstantswithoptimalprocesscontrolparameters.
ControllerAccuracy: ForTCinputs:0.25%ofF.S.±1degree ForR&Sinputs:0.5%ofF.S.±2degree (20min.of warmuptimeforTCinputs.) ForRTDinputs:0.1%ofF.S.=/-1degree ForAnaloginputs:0.5%±1digit
Note: Inputisuserselectable OnlyModelname&outputneedstobespecifiedinthe orderingcode.
Output3(Relay)Output2(Relay)Output1(Voltage)
• UniversalInput 17userselectabletypeinputs
• ZonePID 4Programmablecontrolzones
• AnalogOutputConfigurable AnalogOutputsareselectablefor ControlorRetransmissionoutputs
• SpecialModes UserSelectablemodeof operation –Heat-CoolPID –Auto/Manual –Singlepointramp/soak –SoftStart
• HeaterCurrentMonitoring (optional)
• RemoteSetpoint (optional)
• MotorizedValveControl (optional)
• RS-485Communications (optional)
• IP65forfaceplate
ORDERING CODE
ORDERING EXAMPLE
E339488
DigiTec Division 800.727.5646 DigiTec Division 223DigiTec Division 800.727.5646 DigiTec Division
PANE
L DI
SPLA
YDT
C PI
D Co
ntro
ller S
erie
s
SENSORTYPE RANGE SENSORTYPE RANGE
J -200to750°C E -200to750°C K -200to1350°C B +149to1820°C T -200to400°C N -200to1300°C R 0to1750°C L -200to600°C S 0to1750°C U -200to900°C C 0to2300°C W 0to2300°C PlatinelII 0to1300°C PT100 -100to850°C
CONTROL ACTION 1)PID 2)ON-OFF
HEAT COOL PID ControlAction PID CycleTime 0.1to100sec. Deadband Programmablefromsetpointlowlimittosetpointhighlimit
ALARMS Modes Deviationhigh/low,Absolutehigh/low,Band,SensorBreak Hysteresis 0.1to99.9degree
RAMP SOAK RampRate 1to9999degree/hr SoakTime 0to1440min SoftStartTime 0to999min
CONTACT RATING (SPST)5A@230VAC/30VDCResistive
SSR DRIVE 18VDC@20mA(voltagepulse)
CURRENT 0.4to20mA(max.500ohmloopimpedence)
VOLTAGE 0to5/10VDC(loadresistance10Kohmmin.)
SUPPLY VOLTAGE 85to270VAC/DC(50/60Hz) Optional-24VAC/DC±10%
POWER 6VAmax@230VACCONSUMPTION
WEIGHT 0.727lbs.
IP65 fACEPLATE 0TO50°COPERATING TEMP
INPUTTYPE RANGE
LinearmV -5to56mV Voltage 0to10VDC Current 0to20mA
TYPE INPUTS
SIGNAL INPUTS
fUNCTIONAL SPECIfICATIONS
OUTPUT SPECIfICATIONS
GENERAL SPECIfICATIONS
224 DigiTec Division 800.727.5646 DigiTec Division DigiTec Division 800.727.5646 DigiTec Division
PANE
L DI
SPLA
YDT
C PI
D Co
ntro
ller S
erie
s OVERALL DIMENSTIONS (mm)
TERMINAL CONNECTIONS
MODELS/DIM(mm) A B C D E F G
DTC500 48 48 100 45 10 46 46 DTC110 99 50 88 91 10 92 46 DTC330 97 97 88 91 10 92 92
Front Side
DigiTec Division 800.727.5646 DigiTec Division 225DigiTec Division 800.727.5646 DigiTec Division
PANE
L DI
SPLA
YDT
C PI
D Co
ntro
ller S
erie
sSERIAL COMMUNICATION
NOTE:
1. Maximum32slavecontrollerscanbeconnectedtothemaster.2. Thetotalcablelengthshouldnotexceed500meters.3. Useshieldedtwisted-paircablesforRS485connections.4. Useterminatorshavingaresistanceof 100ohm(1/2watt)
RS485-RS232ConverterPartno.160-710-00
226 DigiTec Division 800.727.5646 DigiTec Division DigiTec Division 800.727.5646 DigiTec Division
SUPPLY POWER 12-24VDC±10%<150mA@24VDC
INTERfERENCE ISOLATION voltage1500Vp-p,pulseperiod1us, sustain1s
WITHSTANDING VOLTAGE TEST 500VAC1minute
INSULATION RESISTANCE Over10Mohm@500VDC
SEISMIC TEST 10-25Hz(X,Y,Z,direction2G 30minutes)
PROTECTION LEVEL IP65(frontpanel)
WORKING ENVIRONMENT -10°C-60°C(14°F-140°F)TEMPERATURE
WORKING ENVIRONMENT -20-90%RH(non-condensation)HUMIDITY
STORAGE TEMPERATURE -20°C-70°C(-4°F-158°F)
HOUSE MATERIAL IndustrialplasticsABS+PC
fRAME DIMENSION 171.8x84.2x38.6mm (6.76"x3.3"x1.52")
DISPLAY DIMENSION 97.0x34.5mm(3.82"x1.36")
INSTALLATION DIMENSION 165x84mm(6.50"x3.31")
COOLING METHOD NaturalAirCooling
WEIGHT 260G(0.57LB.)
COMPATIBILITY Mitsubishi(FXSeries) Siemens(S7-200),ADC(DL05), Omron(CPM1Series),Koyo(S), Panasonic(FPI,FPO)*
SCREEN 4.3"LCDDisplay
RESOLUTION 192x64Pixels
LCM LIfE 50,000hoursat25°±2°C,65 ±10%RH
BRIGHTNESS 60cd/m2
COLOR Blue
CONTRAST AdjustableResistor
BACKLIGHT LonglifeBlueLED
MEMORY 110KBFlashROM
COMMUNICATION RS232&PLCRS485/422& PORTPCPLCRS232
fUNCTION KEY 14ProgrammableButtons
ALLOWABLE 20mSPOWERDISRUPTION
Panel Display
PANE
L DI
SPLA
YDM
T 30
0 Se
ries HMIPanelDisplaypresentsthesystemprocessesinbothtextand
graphicsfortheuser.Easytousedisplayprovidesacustomuserinter-facetotheprocessforbothmonitoringandsystemcontrol.
Fromviewingdatatomakingchangestotimersandcounters,theDigiTecDMT300makesiteasy.
CompatiblewithPLCsfrom:
•ADC(Dl05)
•Koyo(S)
•Omron(CPM1Series)
• Monitorsthedata,curve,graph,orcharacterstodisplay thePLCsinternalfunctionandstoreddata,thusintuitively reflectingthecontrolsystem,flowandtrendhistory.
• AllowscustomertochangethePLCinternalstatusthrough aprogrammablekey,allowingsetpointchanges.Forexample: changingalarmsetpoints,realtimeclocksettings,etc.
• Simultaneousrealtimedisplayandalarminformation.
• StandardLCDwithbackgroundlight.Fourrowswith24 charactersineveryrow.
• Thefrontpanelof theDMT300isIP65standard,washdown compatible.
HARDWARE SPECIfICATIONS GENERAL SPECIfICATIONS
DIMENSIONS (MM)
•Mitsubishi(FXSeries)
•Panasonic(FPI,FPO)
•Siemens(S7-200)
Panel Cutout DIN rail installation (standard 35mm)
Surface MountDimensions
85 m
m98
.8 m
m
91.4
1 m
m
165 mm
171.8 mm 70.00 mm
DigiTec Division 800.727.5646 DigiTec Division 227DigiTec Division 800.727.5646 DigiTec Division
APPROVALS CE,UL
PROGRAMMING METHOD fBD (FunctionalBlockDiagram)
PROGRAM MEMORY 127FunctionBlocks
LCD DISPLAY 4linesof 9charactersperline
fUNCTION BLOCK TYPES CombinedTotalof 127Blocks:
• COUNTER •upto127Blocks
• TIMER •upto127Blocks
• RTC (REAL TIME CLOCK) •upto127Blocks
STORAGE TEMPERATURE -40°Cto+70°C(-40°Fto158°F)
OPERATING TEMPERATURE -20°Cto+70°C(-4°Fto158°F)
MOUNTING DIN railmountedorsurfacemounted
POWER 100to240VAConACpoweredmodels, 12to24VDConDCpoweredmodels
NETWORK READY RS485Communicationsallowseasy networkingcapabilities
Programmable Logic Controller
PROG
RAM
MAB
LE L
OGIC
CON
TROL
LER
DMT
900
Seri
es
SPECIfICATIONS
fEATURES
OPTIONAL ACCESSORIES
DIMENSIONS (MM)
PhoneRemoteControl
RealTimeClockFunction
Network&MonitoringFunction
VoiceWarning
DMT912 DMT922
OptionalVoiceBox
DMT-PSL
• Expansionupto122I/O(74Inputs/48outputs)
• Specialtymodulesfortelephonefunctionsandalarming
• Optionalfacemountorpanelmount,4linedisplay
• FreeProgramSoftware
• RemoteMountingof theHMIModule
• VoiceModule(dialout,remotecontrol)
• RemoteControl(wirelesscontrolof 6inputs)
• ULListed(912A-Rand922D-AR)
• CopyModul
• PrintModule
• Telephone/VoiceModule
• RemoteControlTransmitterModule
• HMIPanelDisplay(DMT300)
228 DigiTec Division 800.727.5646 DigiTec Division DigiTec Division 800.727.5646 DigiTec Division
MODEL VOLTAGE INPUT NOTES
DMT912A-R 100–240VAC 8pointsACinput 4pointsrelayoutput WithrealtimeclockDMT912D-AR 12–24VDC 8pointsDCinput(with6pointsanalog) 4pointsrelayoutputDMT912D-AT 12–24VDC 8pointsDCinput(with6pointsanalog) 4pointstransistoroutput (equivalentNPN)DMT922A-R 100–240VAC 14pointsACinput 8pointsrelayoutputDMT922D-AR 12–24VDC 14pointsDCinput(with8pointsanalog) 8pointsrelayoutputDMT922D-AT 12–24VDC 14pointsDCinput(with8pointsanalog) 8pointstransistoroutput (equivalentNPN)
DMT920A-R 100–240VAC 12pointsACinput 8pointsrelayoutput 20PointsextendedmoduleDMT920D-R 12–24VDC 12pointsDCinput 8pointsrelayoutputDMT920D-T 12–24VDC 12pointsDCinput 8pointstransistoroutput (equivalentNPN)
DMT-AVMA 100–240VAC Telephoneandvoicemodule,auto-dialing,alarmandremotecontrolDMT-DVMA 12–24VDC
DMT-ARM 100–240VAC RemotecontrolandreceivingmoduleDMT-DRM 12–24VDC
DMT-TXM 3VDC(twoNo.5batteries) Remotecontroltransmitter
DMT-HMI HumanMachineInterface Upto64pageshuman-interface,displaycurrentvalueandchange pre-set(LCDpanel)value(withthewide-rangeoperatingtemperature -20°C-70°C(-4°F-158°F)DMT-HMI-BL BacklitHumanMachineInterface(LCDpanel)
DMT-WRT Programmingkeypaddisplay Convenientprogrammingforuserinthefield
DMT-ACPAC TypeProgrammingcable CommunicationcablebetweenDMTandPC(profileplugtype)
DMT-DCP SerialProgrammingcable CommunicationcablebetweenDMTandPC(frontpieceplugtype)
DMT-ACB ACTypeBridgeConnection ToconnectDMThostandtheothermoduleDMT-DCB DCTypeBridgeConnection
DMT-RMR RemotemountingrackforLCDpanel RemotelyconnectDMT900andDMT-HMIallowingtheDMTtobeplaced insidethecabinetandputtheDMT-HMIoutsidethecabinetfor observationandoperation
DMT-ACBA ACTyperemoteconnectorbridge ToremotelyconnectDMThostandtheextendedmoduleetc.DMT-DCBA DCTyperemoteconnectorbridge
DMT-ANT RemoteAntennaKit ExtendedrangeantennaofDMT-ARM/DMT-DRM
DMT-AUD Recordingcable ThewiresbetweenPCsoundcardandtheDMT-AVMA/DMT-DRM
DMT-USBPC USBProgrammingCable ThecablebetweenDMTandPCUSBport
DMT-PSL 24voltpowersupply Powersupplyfor24VDCunits
DMT-300 12-24VDC PanelDisplay
PROG
RAM
MAB
LE L
OGIC
CON
TROL
LER
DMT
900
Seri
es SPECIfICATIONS
ACCESSORIES
DigiTec Division 800.727.5646 DigiTec Division 229DigiTec Division 800.727.5646 DigiTec Division
MODEL NUMBER DESCRIPTION
D2040 3-1/2DigitLoopPoweredMeter
OPTIONALACCESSORIES
9801 Nema4XWallMountedEnclosure 9802 Nema4XWallmountedEnclosure -doublecutout
INPUTS Currentloopmeasurementof 4-20mAand10-50mA
DISPLAY RANGE .000to±1.999 0.00to±19.99 00.0to±199.9 000to±1999
ACCURACY ±0.1%rdg.±1digit
POWER REQUIREMENTS Looppowered;voltagedropless than5.0Vwitha20mAinput
RESPONSE TIME Under1sec.,typically
DISPLAY 0.6"LCDDigits
DISPLAY UPDATE RATE 2.5updatespersecond
DECIMAL POINTS 1.XXX 1X.XXsetbyinternal 1XX.Xjumper 1XXX
POLARITY NegativeCount minussignatleft. PositiveCount plussignatleft.
RECALIBRATION 1yearwithinratedaccuracySCHEDULE
HUMIDITY 80%RH@40°Cmax.; 70%RH@60°Cmax.
fRONT PANEL NEMA4
TEMPERATURE RATING Storage-4°to158°F(-20°Cto70°C)
SIZE 2.3"Hx4.13"Wx1.25"D PanelCutout:3.55"Wx1.72"H
WEIGHT Approx.2oz.LO
OP P
OWER
ED IN
DICA
TORS
D204
0 Se
ries
3-1/2 Digit Loop-Powered MeterSPECIfICATIONS
DIMENSIONS (INCHES/MILLIMETERS)
ORDERING INfORMATION
TheDigitecD2040loop-powereddisplayisa3-1/2Digit,shortdepthLCDdisplay.Thedisplaycanindicatelevel,%flow,orpressureina4-20mAprocessloop.
TheD2040alsoiswellsuitedtobeusedasaremotedisplay.Userad-justablescale(gain),offsetanddecimalpointallowimmediatecalibra-tionof measurementbeingdisplayed.
PROCESSAPPLICATIONS
• Level
• Pressure
• Flow
• Poweredbythecurrentbeingmeasured
• 3-1/2Digitfull-sizeLCD0.6"high
• Smallsize:2.3"x4.13"x1.25"
• NEMA4FrontPanel
• 1/8DINAnodizedAluminumCase
• Selectabledecimalpoint
• Two(2)wiresfortotalhook-up
• Shortdepthcase(1.25")
230 DigiTec Division 800.727.5646 DigiTec Division DigiTec Division 800.727.5646 DigiTec Division
INPUTS 4-20mA
OUTPUT (OPEN DRAIN) 25VDC@150mA;Isolatedto500VDC
DISPLAY RANGE DecimalPointProgrammable0-19.999
ACCURACY ±0.02%±1count
SQUARE ROOT ±.2%
DISPLAY 4-1/2Digit,.5"LCD
LOW fLOWS ADJUSTABLE 22%ofFullScale
ALARM STATUS AlternatingDisplay—Betweenthe processreadingandthehighalarms (AL1orAL2)
MAXIMUM VOLTAGE DROP <3.5V@20mA
fRONT PANEL NEMA4X
TEMPERATURES RATING Operating 32°to122°F(0°to50°C)
SIZE 2.3"Hx4.13"Wx1.25"D PanelCutout:3.55"Wx1.72"H
WEIGHT Approx.2oz.
LOOP
POW
ERED
INDI
CATO
RSD2
080
Seri
es
4-1/2 Digit Loop-Powered Meter
SPECIfICATIONS
TheDigitecD2080isalooppoweredindicatorthatmeasures,displaysandtotalizesthecurrentina4-20mAcircuit.Althoughtheinstrumentislooppowered,itonlyproduces<3.5Vdropallowingittobeusedinserieswithalmostany4-20mAapplication.Modularaccessoriesen-abletheusertoselectthelowestcostconfigurationwhileretainingfullinterchangeabilitybetweeninstruments.
Optionalhighalarmsprovidetwoisolatedopendrainoutputswhichmaybeindependentlyprogrammedwithahightrippoint.Whenanalarmistripped,thealarmandcurrentreadingalternateontheindicator.
• 4-1/2DigitFullSizeLCD
• NEMA4XFrontPanel
• 1/8DINAnodizedAluminumCase
• ShortDepthCase(2-1/4")
• FrontPanelMenuAccess
• 2IsolatedOpenDrainAlarm Outputs
• SquareRootExtractions
PROCESSAPPLICATIONS
•Level
•Pressure
•Flow
ORDERING INfORMATION
MODEL NUMBER DESCRIPTION
D2080 4-1/2DigitLoopPoweredMeter withTotalizer
OPTIONALACCESSORIES
9801 Nema4XWallMountedEnclosure 9802 Nema4XWallmountedEnclosure -doublecutout
DIMENSIONS (INCHES/MILLIMETERS)
DigiTec Division 800.727.5646 DigiTec Division 231DigiTec Division 800.727.5646 DigiTec Division
MODEL NUMBER DESCRIPTION
D2090 3-1/2DigitLoopPoweredIndicatorin NEMA4XEnclosure D2095 4-1/2DigitLoopPoweredIndicatorin NEMA4XEnclosure
LOOP
POW
ERED
INDI
CATO
RSD2
090/
D209
5 Se
ries
Loop Powered Indicator in NEMA 4X Enclosure
SPECIfICATIONS – D2090
SPECIfICATIONS – D2095
INPUTS 4-20mAor10-50mA
DISPLAY 0.5"highLCD,3-1/2Digitwithuser selectabledecimalpoint.
DISPLAY RANGE 0-1999
DECIMAL POINTS Setbyinternaljumper
UPDATE RATE 2.5Updates/second
CALIBRATION 2-stepzeroandspanadjustment
ACCURACY ±0.1%reading,±1Digit
CONNECTIONS Removablescrewterminalblockincluded
VOLTAGE DROP <5.0VDC@20mA
TEMPERATURE RATING Operating32°to122°F(0°to50°C)
WEIGHT 4oz.
INPUTS 4-20mA
OUTPUT (OPEN DRAIN) 25VDC@150mA;Isolatedto500VDC
DISPLAY 0.5"highLCD,4-1/2Digitwith programmabledecimalpoint.
DISPLAY RANGE 0-19999
DECIMAL POINTS MenuSelected
UPDATE RATE 2.5Updates/second
CALIBRATION FullyProgrammable
ACCURACY ±0.2%reading,±1Digit
CONNECTIONS Removablescrewterminalblockincluded
VOLTAGE DROP <3.5VDC@20mA
TEMPERATURE RATING Operating32°to122°F(0°to50°C)
WEIGHT 5oz.
• NEMA4XEnclosure
• EasyCalibrationandInstallation
• 3-1/2and4-1/2DigitVersions
• 4-20mAor10-50mAinputs
• D2095:Optionalalarmoutputs
• RemoteDisplay
PROCESSAPPLICATIONS
• Flow
• Level
• Pressure
• Temperature
ORDERING INfORMATION
TheDigitec D20903-1/2Digit,loop-poweredindicatorisperfectforprocessapplicationswherenopowerisavailable,aNEMA4Xenclosureisneededandcostisaconsideration.
Designedforeasyinstallation,thetwowireconnectionisallthatisrequiredtopowerandoperatetheunit.TheD2090canbewallorpanelmounted.
TheDigitecD20954-1/2Digit,loop-poweredindicatorisperfectforprocessapplicationswherenopowerisavailable,andaNEMA4Xenclosureisneeded.Designedforeasyinstallation,thetwowirecon-nectionisallthatisrequiredtopowerandoperatetheunit.TheD2095canbewallorpanelmounted.Twoisolatedopendrainalarmsaddfunctionalityonanasneededbasis.
232 DigiTec Division 800.727.5646 DigiTec Division DigiTec Division 800.727.5646 DigiTec Division
MUL
TI-C
HANN
EL P
ROCE
SS C
ONTR
OLLE
RSD3
700A
Ser
ies
Motor-Driven Cycle Progress Timer
• 6-DigitRedLEDDisplay
• 1/8DINextrudedaluminumcase
• NEMA4XRatedFront
• Upto4RelayOutputs
• 20-pointLinearization
• UserProgrammableKeysandRemoteInputs
• MathChannel
• RelayforAlarm/shuntCalibration
•3722A:Twoinputchannelsandthirdmathchannel
•3722A:Independentsetupandscalingforall3channels
IND.CONT.EQ.13NC
TheDigiTecD3700AseriesdigitalpanelmetersareavailableaseithertheSINGLE-CHANNEL D3720AortheDUAL-CHANNEL D3722A.Thesefull-featuredmetersincludea6-digitLEDdisplay,auser-friendlyconfigurationmenuandhigh-speedmeasurementrateforthemostdemandingapplications.Combineallof thiswithitscleanappearance,industrializedaluminumcase,NEMA4Xconstructionandsnap-actionbuttonsandyouhaveameterreadyforallapplications.
3 TYPES Of CALIBRATION:
USER-calibrationallowstheentryof thelowandhighinputvaluesandthecorrespondinglowandhighdisplayengineeringvalues.
LOAD-calibrationallowssetupviaknowninputvalues.Simplyapplythelowinputandsetitscorrespondingdisplayvalue,thenapplythehighinputandsetitsvalue.Thelowandhighvaluescanbeprogrammedatdifferenttimesandthenenabled.
SHUNT-calibrationallowssetupviaanexternalshuntcalibratorresis-tor.Simplysetthedisplaylowvalueandtheshuntcaldisplayvalue,thenthemeterwillautomaticallymeasuretheunloadedbridgeforthezerovalue;thenclosestheinternalshuntcalrelayandmeasurestheshuntcalibratedinput.
PROGRAM MENU STEPS LOCKOUT:Theusercanprogramthemajorityof themenustepstonotbeaccessible.Thissimplifiestheprogram-mingof themeterallowingonlynecessarymenustobedisplayedintheSETUPmode.Themetercaninitiallybeconfiguredtothedesiredsetup,andthentheusercanlockoutalltheunnecessarymenusteps.
AUTOTARE:Thisfunctionallowstheusertosettheselecteddisplay/inputtozero.Itcanbeperformedviaafrontpanelkeyorremoteinput.Setupisavailabletoswitchthedisplayfromnettogross.
NET/GROSS:Thenetvalueorthegrossvaluecanbedisplayedviaafrontpanelkeyorremoteinput.Alarmlimits,analogoutorpeakvaluesmaybeassignedtothenetorgrossvalues.
LINEARIZATION:U-plot20-pointlinearizationallowstheusertoprogramupto20knownvaluesof non-linearcurvaturealongwiththecorrespondingdisplayreadings.Typicalusesarefornon-linearoutputsfromtransducers,loadcells,etc.andfordisplayof volumeinnon-linearstoragevessels.
MATH CHANNEL:TheD3700Aseriescomeswithanextrachannelthatisanoninputchannel.Thiscanbeusedtoduplicateaninputchannelforcompletelynewscalingandalarmsetups.ThetwochannelinputmodelD3722AcanbeusedtoperformA+B,A–BorA÷Bmathfunctions.(ConsultATCDigiTecforyourspecialequations)
SECOND SCALE:Thisfunctionallowstheusertosetasecondscalingtotheinput.Theinputwillthenbedisplayedintwoengineeringunits(typicallyforEnglish/Metricdisplays).
PEAK 1 AND PEAK 2:Peak1andpeak2arebothassignabletocapturethemaximumorminimumdisplayvalue.Theyareassignabletoanychannelandthenetorgrossvalue.Itcanberesetthroughafrontpanelkeyorremoteinput.Capturerateis20/SEC.
DIMENSIONS (INCHES/MILLIMETERS)
STANDARD TERMINAL 30-PinDoubleSided
DigiTec Division 800.727.5646 DigiTec Division 233DigiTec Division 800.727.5646 DigiTec Division
MODEL NUMBER D372 01
CHANNEL(S) SINGLE CHANNEL 1/8DIN;6-Digit;LED;NEMA4X; 0A 20-PointLinearization(switch selectable±30mV,100mV,2V, 10V,20mA)
DUAL CHANNEL 1/8DIN;6-Digit;LED;NEMA4X; 2A 20-PointLinearization;Thirdmath channel(switchselectable±30mV, 100mV,2V,10V,20mA)
OPTIONS 3relays(FormCforAlarms) C *Combinationof OptionCandOptionH CH Combinationof OptionCandOptionP CP FactoryScaling(provideinputrange,displayrange) F *16bitanalogoutput H Excitationsupply(10VDC,24VDC) P RS232Communication T Preconfiguredfor240VACpower S
*IncludesOption"P"
MUL
TI-C
HANN
EL P
ROCE
SS C
ONTR
OLLE
RSD3
700A
Ser
iesPROGRAMMABLE LOCKOUT CODE:A2-digitcodeforset-upisprogram-
mable.Setupcanalsobeprotectedviaaremoteinput.
DIGITAL fILTER:Thisfunctionallowstheusertoselectadigitalfilter.Thisisusedfornoisy,unstableinputs.
ALARMS:Eachmeterisstandardwith4programmablealarmsthatcontrolthefrontpanelLEDstatusandtheonestandardrelay(FormA)andoptional3relayoutputs(FormC).
Eachalarmis:
• AlternateHi/Lowonalarm1&2
•Assignabletoanychannel
•Programmableforhighorlowlimit
•Programmablesetpointvalue
• Programmablehysteresisforcompletedisplayrange
• Programmableforlatching
• ProgrammabletoFlashDisplayonalarm
• Alarm#1isprogrammableforfailsafeoperationforallthealarms. (Failsafeoperationallowstherelaytode-energizeonlossof power.
NON-VOLATILE MEMORY:Allsetupdataenteredbytheuserisstoredinanon-volatilememory.Nobatteriesneededandnoneedtore-programthemeterafterpowerdown.
RELAY OUTPUT: 1FormArelay240VAC@1A,isprovidedstandardforuseasanalarmoutputorshuntcalrelay.
DISPLAY:6Digit.56”RedLEDdisplayforreadingsof -199999to999999withselectabledecimalpoints.
INPUT:Processinputsof plusandminusinputsof 30mV,100mV,200mV,2Vand10V.20mAinputissolderselectableonmainboard.Displayandoutputsareupdatedatselectedresolution.
SELECT KEY:Movesdecimalpointlocation,selectsthechoiceof thefunctionswithinthecurrentmenuorallowstheselectionof thedigittobechanged.
UP ARROW KEY:Increasesthecurrentvalueof theflashingdigitbyoneunitperpress.
DOWN ARROW KEY: Decreasesthecurrentvalueof theflashingdigitbyoneunitperpress.
EXIT KEY: ReturnsyoutoRUNmodewhenatmainmenuorreturnsyoutomainmenupromptwheninprogrammingmenu.
ENTER KEY:Entersselectedmainprogrambranch.Movesyoudownintheprogrammenus.Entersselectedchoicetomemory.
TheF1-F4frontpanelrun-timekeyscanbeprogrammedforanyof thefollowing:
•ALARM1ViewandSet • Channel2Display
•ALARM2ViewandSet • Channel3Display
•ALARM3ViewandSet •Reset
•ALARM4ViewandSet •Scale2select
•Channel1Tare/Autozero •Net/Grossselect
•Channel2Tare/Autozero •Shuntcaldisplay/calibration
•Channel3Tare/Autozero •Peak1display
•Channel1Display •Peak2display
REMOTE INPUTS:2remoteinputfunctionselections
•Channel1display •Peak1
•Channel2display •Peak2
•Channel3display •Reset
•Scale2 •Net/gross
•Decimalpointselection •Alarmdisable
OPTIONS:
C 3eachForm-C,SPDTrelaysratedat5A@240VAC, 5A@30VDC
*CH Combinationof OptionCandOptionH
CP Combinationof OptionCandOptionP
f Factoryscalingcalibration(userprovidesinputrange anddisplayrange)
*H 16bitanalogoutput-menuselectablefor4-20mA, 0-10V,0-5V,-5V-+5V
P Excitationoutputvoltagesupplies24VDC@150mA, 10VDC@250mAsupply
T RS232CBidirectionalserialcommunication@9600baud, noparity,8data,1stopbit**
*IncludesOptionP
**Consultfactoryforotherbaudrates
MODEL NUMBER
DISPLAY UPDATE:30/SECfixed.
EXCITATION:Optional,10VDC@250mA,[email protected]@100mA.
234 DigiTec Division 800.727.5646 DigiTec Division DigiTec Division 800.727.5646 DigiTec Division
INPUTS 4-20mA± 30mV± 100mV± 200mV± 2V± 10V±
ACCURACY 0.02% 0.02% 0.02% 0.02% 0.02% 0.02%
ZERO DRIfT 0.02% 0.02% 0.02% 0.02% 0.02% 0.02%
SPAN DRIfT 10ppm/°C 10ppm/°C 10ppm/°C 10ppm/°C 10ppm/°C 10ppm/°C
INPUT IMPEDANCE 50Ohms 10Mohms 10Mohms 10Mohms 10Mohms 10Mohms
4-1/2 DIGIT RESOLUTIONS 1uA 1uV 10uV 10uV 10uV 1mV
OVER-RANGE CAPABILITY MIN. 10% 10% 10% 10% 10% 10%
DISPLAY UPDATE 30/SEC.DualChannel-35/SEC
NORMAL MODE REJECTION RATIO 63dB
COMMON MODE REJECTION RATIO 130dB
ANALOG RESPONSE TIME 25/SECAnalogOutput
INTERNAL RESOLUTUION 22bits
RELAY UPDATE 35/SEC
DIGITAL fILTER 60Hz
WARM UP TIME 15minutes
OPERATING TIEMP. RANGE -20°Cto60°C
STORAGE TEMP. RANGE -20°Cto85°C
HUMIDITY to95%,non-condensing
AC SUPPLY VOLTAGE 115/230VAC
POWER CONSUMPTION 15Wattsmaximum(alloptionsinstalled)
ISOLATION SignalInputtoEarthGround Safetyratedto450rms,220Vms,highvoltagetest OptionboardtoEarthGround Safetyratedto450rms,220Vms,highvoltagetest OptionboardtoSignalInput 400Vp PowertoEarthGround Safetyratedto450rms,220Vms,highvoltagetest
WEIGHT 0.84lbs.
MUL
TI-C
HANN
EL P
ROCE
SS C
ONTR
OLLE
RSD3
700A
Ser
ies
SPECIfICATIONS
DigiTec Division 800.727.5646 DigiTec Division 235DigiTec Division 800.727.5646 DigiTec Division
INPUTS 4-20mA± 30mV± 100mV± 200mV± 2V± 10V±
ACCURACY 0.02% 0.02% 0.02% 0.02% 0.02% 0.02%
ZERO DRIfT 0.02% 0.02% 0.02% 0.02% 0.02% 0.02%
SPAN DRIfT 10ppm/°C 10ppm/°C 10ppm/°C 10ppm/°C 10ppm/°C 10ppm/°C
INPUT IMPEDANCE 50Ohms 10Mohms 10Mohms 10Mohms 10Mohms 10Mohms
4-1/2 DIGIT RESOLUTIONS 1uA 1uV 10uV 10uV 10uV 1mV
OVER-RANGE CAPABILITY MIN. 10% 10% 10% 10% 10% 10%
NORMAL MODE REJECTION RATIO 63dB
COMMON MODE REJECTION RATIO 130dB
RESPONSE TIME 4/SEC
ANALOGOUTPUT 3/SEC
RELAY OUTPUT 3/SEC
INTERNAL RESOLUTION 22bits
CONVERSION TIME 52msperchannel
DIGITAL fILTER 60Hz
WARMUPTIME 15minutes
OPERATING TEMP. RANGE -20°Cto60°C
STORAGE TEMP. RANGE -20°Cto85°C
HUMIDITY to95%,non-condensing
AC SUPPLY VOLTAGE 115/230VAC
MUL
TI-C
HANN
EL P
ROCE
SS C
ONTR
OLLE
RSD3
900
Seri
es
Intelligent High Resolution Multi-Channel Panel Meters
SPECIfICATIONS
TheDigiTec D3924Seriesdigitalpanelmetersarethemostversatileandpowerfulmetersonthemarket.The6digitdisplay,highspeedmeasurement(4/SEC)updateratemakesthistheperfectchoiceforthosemostdemandingapplications.The3900alsoincludes4assign-ablefrontkeys,2assignableremoteinputsandavarietyof menulockoutfeatures.
TheD3924offersfourinputchannelswithafifthchannelformathemati-calcalculations.StandardformulaincludessumandAVG.
AcompletemathpackisintheD3924firmware.PleasecontactATCDigiTecforimplementingyourspecialequation.
Optionsinclude3formCrelays,4analogsampleandholdoutputs.RS232bidirectionalcommunication,excitationsuppliesandscrewterminalconnectors.
ProductIdentity13NC
•6-Digit.56”RedLEDDisplay
•Independentsetupandscaling forall5channels
•Four(4)inputchannelsand fifthmathchannel
•1/8DINextrudedaluminumcase
•NEMA4Xratedfront
•Upto4RelayOutputs
•Userprogrammablekeys andremoteinputs
•ScanMode (SelectableScanning)
•MathChannel
APPLICATIONS
•StrainGage,Pressure Transducer,andTransmitter Display
•LeakTesting
•Peak/StressTesting
•Pump/CompressorMonitor
•BottleFilling/Weighing
•ProductionTestMonitoring
• NonDestructiveTesting
POWER CONSUMPTION 15Wattsmaximum (alloptionsinstalled)
ISOLATION SignalInputtoEarthGround Safetyratedto450rms, 220Vms,highvoltagetest OptionboardtoEarthGround Safetyratedto450rms, 220Vms,highvoltagetest OptionboardtoSignalInput 400Vp PowertoEarthGround Safetyratedto450rms, 220Vms,highvoltagetest
WEIGHT 0.84lbs.
236 DigiTec Division 800.727.5646 DigiTec Division DigiTec Division 800.727.5646 DigiTec Division
MUL
TI-C
HANN
EL P
ROCE
SS C
ONTR
OLLE
RSD3
900
Seri
es 2 TYPES Of CALIBRATION: USER-calibrationallowstheentryof thelowandhighinputvaluesandthecorrespondinglowandhighdisplayengineeringvalues.
LOAD-calibrationallowssetupviaknowninputvalues.Simplyapplythelowinputandsetitscorrespondingdisplayvalue,thenapplythehighinputandsetitsvalue.Thelowandhighvaluescanbepro-grammedatdifferenttimesandthenenabled.
PROGRAM MENU STEPS LOCKOUT:Theusercanprogramthemajorityof themenustepstonotbeaccessible.Thissimplifiestheprogram-mingof themeterallowingonlynecessarymenustobedisplayedintheSETUPmode.Themetercaninitiallybeconfiguredtothedesiredsetup,andthentheusercanlockoutalltheunnecessarymenusteps.
AUTOTARE:Thisfunctionallowstheusertosettheselecteddisplay/inputtozero.Itcanbeperformedviaafrontpanelkeyorremoteinput.Setupisavailabletoswitchthedisplayfromnettogross.
NET/GROSS:Thenetvalueorthegrossvaluecanbedisplayedviaafrontpanelkeyorremoteinput.Alarmlimits,analogoutorpeakvaluesmaybeassignedtothenetorgrossvalues.
MATH CHANNEL: TheD3924seriescomeswithanextrachannelthatisanoninputchannel.Thiscanbeusedtoduplicateaninputchannelforcompletelynewscalingandalarmsetups.TheD3924canbeusedtoperformsumandavg.mathfunctions.(ConsultATCforyourspecialequations)
SECOND SCALE: Thisfunctionallowstheusertosetasecondscalingtotheinput.Theinputwillthenbedisplayedintwoengineeringunits(typicallyforEnglish/Metricdisplays).Scale2issetupbyenteringtheinputlowandhighvaluesandcorrespondingdisplayvalues.
PEAK 1 AND PEAK 2:Peak1andpeak2arebothassignabletocap-turethemaximumorminimumdisplayvalue.Theyareassignabletoanychannelandthenetorgrossvalue.Itcanberesetthroughafrontpanelkeyorremoteinput.
PROGRAMMABLE LOCKOUT CODE & PASSWORD:A2digitaccesscodeforset-upisprogrammable.Setupcanalsobeprotectedviaaremoteinput.Thisprovidesprotectionagainsttamperingof metersetup.
DEfAULT:TheD3924seriesallowsthemetertoberesettothefactorysetup.Thisfunctionallowseasyresettofactorysetupprogram.
ALARMS:Eachmeterisstandardwith4programmablealarmsthatcontrolthefrontpanelLEDstatusandtheonestandardrelayandoptional3relayoutputs.Eachalarmis:
•Assignabletoanychannel
•Programmableforhighorlowlimit
•Programmablesetpointvalue
•Programmablehysteresisforcompletedisplayrange
•Programmableforlatching
•ProgrammabletoFlashDisplayonalarm
•Alarm#1isprogrammableforfailsafeoperationforallthe alarms.(Failsafeoperationallowstherelaytode-energizeon lossof power.
NON-VOLATILE MEMORY:Allsetupdataenteredbytheuserisstoredinanon-volatilememory.Nobatteriesneededandnoneedtore-programthemeterafterpowerdown.
RELAY OUTPUT: 1FormArelay240VAC@1A,isprovidedstandardforuseasanalarmoutputorshuntcalrelay.
DISPLAY: 6Digit.56”RedLEDdisplayforreadingsof -19999to999999withselectabledecimalpoints.
INPUT CARD:Processinputsof plusandminusinputsof 30mV,100mV,200mV,2Vand10Vareprogrammableinputs.The20mAinputissolderselectableonmainboard.
DISPLAY UPDATE:ScanMode-1seconddwelltime;NormalMode-4updatesperSEC.
EXCITATION (OPTIONAL):Optionboard:10VDC@250mA,24VDC@150mA.
DigiTec Division 800.727.5646 DigiTec Division 237DigiTec Division 800.727.5646 DigiTec Division
MODEL NUMBER D3924
CHANNEL fOUR CHANNEL: D3924 ScanMode;1/8DIN;6-Digit LED;NEMA4X; Fifth(5th)mathchannel
OPTIONS 3relays(FormCforAlarms) C *Combinationof OptionCandOptionHCHCH Combinationof OptionCandOptionP CP FactoryScaling(provideinputrange,displayrange) F *16bit4analogsampleandholdoutputs H (4-20mA,0-10VDC)—includesOptionP Excitationsupply P (10VDC@280mA,24VDC@150mA) RS232Communication T
*OptionPisincluded
MUL
TI-C
HANN
EL P
ROCE
SS C
ONTR
OLLE
RSD3
900
Seri
es
SELECT KEY:Movesdecimalpointlocation,selectsthechoiceof thefunctionswithinthecur-rentmenuorallowstheselectionof thedigittobechanged.
UP ARROW KEY: Increas-esthecurrentvalueof theflashingdigitbyoneunitperpress.
DOWN ARROW KEY: Decreasesthecurrentvalueof theflashingdigitbyoneunitperpress.
EXIT KEY:ReturnsyoutoRUNmodewhenatmainmenuorreturnsyoutomainmenupromptwheninprogrammingmenu.
ENTER KEY: Entersselectedmainprogrambranch.Movesyoudownintheprogrammenus.Entersselectedchoicetomemory.
TheF1-F4frontpanelrun-timekeyscanbeprogrammedforanyof thefollowing:
• ALARM1ViewandSet • Channel2Display
• ALARM2ViewandSet • Channel3Display
• ALARM3ViewandSet • Channel4Display
• ALARM4ViewandSet • Channel5Display
• Channel1Tare/Autozero • Reset
• Channel2Tare/Autozero • Scale2select
• Channel3Tare/Autozero • Net/Grossselect
• Channel1Display • Shuntcaldisplay/calibration
• Peak1display • Peak2display
• Lockout • Peak1
• Channel1display • Peak2
• Channel2display • Reset
• Channel3display • Net/gross
• Channel4display • Alarmdisable
• Channel5display • Hold
• Scale2
• Decimalpointselection
DIMENSIONS (INCHES/MILLIMETERS)
SETUP MODE KEY fUNCTIONS
ORDERING CODE
STANDARD TERMINAL 30-PinDoubleSidedScrewTerminal(XOperation)
238 DigiTec Division 800.727.5646 DigiTec Division DigiTec Division 800.727.5646 DigiTec Division
MODEL NUMBER D3980
RelayOutputs CAnalogOutputs(HOptionincludesPOption) HExcitation10VDCand24VDC P220VACpowered S1200BaudInput B12
REM
OTE
DISP
LAY
D398
0 Se
ries
Remote Display
• Extract6-digitnumericdatafromwithinadatastream
• RemoteDisplayforall3800/3900modelswiththe “T”option(SerialOutput)
• ConvertsSerialtoAnalogOutput
• NumericDisplayforPC/PLCserialoutputwithalarm relaycapability
• ScaleandOffsetrawserialdataanddisplayas intelligentinformation
• Displaysdirectinputfromdigitaltransmitters
ORDERING CODE
DIMENSIONS (INCHES/MILLIMETERS)
TheDigiTec D3980istrulyanintelligentremotedisplay.UsingRS232serialinputtheD3980offersunmatchedapplicationflexibility.
TheD3980offersanoptionof settinga6-digitwindowtolookwithinadatastream.Thiswindowallowstheextractionorparsingof datawithinadatastream.
SERIAL INPUT:SerialASCIIRS232C.Receives,processesanddisplaysupto6digitsof data.Decimalpointisprogrammablethroughfrontkeypad.
9600 BAUD RATE:DataFormat:8databit,1stopbit,noparitycheck.Optional1200baudrateavailable(consultfactory.)
DISPLAY fORMAT:6Digit(999,999)counts,or5digits(-99,999)counts.
DigiTec Division 800.727.5646 DigiTec Division 239DigiTec Division 800.727.5646 DigiTec Division
(13NC)
SING
LE-C
HANN
EL P
ROCE
SS C
ONTR
OLLE
RS &
TEM
P. D
ISPL
AYS
D382
0/D3
830
Seri
es
Process Meter with Totalizer
DIMENSIONS (INCHES/MILLIMETERS)
TheDigitecSeriesD3800 Panel Metersoffermanyfeaturesandperformancecapabilitiestosuitawiderangeofindustrialapplications.
TheD3820andD3830areavailableintherangesof 4-20mA,0-10VDC,or0-5VDC.10VDCand24VDCexcitationisavailableasanoption.Thesecontrollersincludea30pointlinearizationcapabilityforcompensationof non-linearprocesses.
TheD3830 Totalizercanbeusedtocomputeatime-inputproduct.Thiscanbeusedtoprovidereadoutintotalizedflow,batchorweighingoperations.
Theunitscanhaveupto4setpointalarmsassignabletoRate,Totalizer(D3830),orbothRateandTotalizer.
Fourfrontkeysareeasilyprogrammedforspecialfunctionsallowingquickaccesstoalarms,viewPeaks,resettotalsorswitchscalingfromgallonstobarrels.
TheD3820/D3830comesstandardwith(1)FormArelay240VAC@1Athatcanbeusedasanalarmoutput.
PRODUCTION RATE: Unitspersecond/minute/hourcomputedanddisplayedinthetimeofoneinputperiod.Alsocomputedindozens,gross,orotherpackagingunits.
ROTATION:SpeedindicatedasRPS,RPH,RPM,oraslinearmotion(feet/second,meters/hours,etc).
PUMP UP/DOWN: Thealternatingrelayoptionallowsthe3820tocontrolaDuplexpumpingapplication.Theunithasauserprogramma-bletimedelaytoallowadelayof bothpumpscomingonafterapoweroutage,The3820alsocanprovideadditionallowandHighAlarms.
TOTALIZER:Totalizermodedisplaysaccumulatedtotalof unitsorevents(ie,-gallons,pounds.etc.)sincepower-uporlastresetalowflowcutoff settingisavailable.
Exponentmodeisavailabletototalizeupto999E99.
AnoptionalTotalizerSSR20msec.pulseoutputwithselectableautomaticresetof totalvalueallowsbatchingoperations.
fLOW:Sensorinputscaledtogallons/minute,liters/hour,pounds/minute,ACFM.etc.
• 6-DigitRedLEDDisplay
•1/8DINextrudedaluminumcase
•D3830TotalizerOptionalwithaExponentMode
•NEMA4X(IP65)FrontPanel
•Fourprogrammablealarmsetpoints,upto4relayoutputs
•Selectableupdaterateof.1,2,10,20/SEC
•Fourprogrammablefunctionkeys
•AlternatingRelayFunction(Alarm1andAlarm2)
•SquareRoot,Flume,Weirreadings
• 30pointlinearization
240 DigiTec Division 800.727.5646 DigiTec Division DigiTec Division 800.727.5646 DigiTec Division
DISPLAY 6digits,7segment,redLED,0.5.high,with overflowandover-rangedisplays.
DISPLAY UPDATE 0.l,2,10,and20persecond
RANGE Userprogrammabledecimal,scalingallowing adisplayrangeof-99999to999999. Totalizershaveanexpandeddisplaymode thatallowsaScientificNotationmodethat totalstoover1billion.
POWER 115or230VAC
INPUT 38x0-270-20mA 38x0-230-5VDC 38x0-250-10VDC
TEMPERATURE Operating 32°to131°F(0°to55°C)RATING Storage -40°to185°F(-40°to85°C)
RELATIVE 20to80%,non-condensingHUMIDITY
INTERNAL CLOCK 22.1184MHzcrystaloscillator. Agingrate:5ppm/year.
OPTIONAL 10VDC@250mAEXITATION SUPPLY24VDC@150mA
DISPLAY SCALING Operatorsimplyenterstheinputlowandhigh valuesplusthedisplaylowandhighvalues. The3820/3830calculatestheproperscaling andoffsetvaluesautomatically. Decimalpoint:userselectable
EXTERNAL HOLD Acontactclosurewillfreezethedisplay.The unitisfullyfunctionalwhilecontactis maintained,thedisplayholdslastvalue.
MEASUREMENT Range -9999to99999units/second. Accuracy .05%±1digitof F.S.
TERMINATION ScrewTerminalconnector
CASE AnodizedAluminum1/8DINcutout,NEMA4X frontpanelsealedgasket.
WEIGHT 0.84lbs.
MODEL NUMBER D38
BASIC MODELBasic 20WithTotalizer 30
RANGE 0-5VDC 230-10VDC 250-20mA 27
OUTPUT OPTIONS3Form“C”5amprelaysactivatewhenhighand Clowlimitsareexceeded.PermitsOn-off controlof externalcircuitry,oralarmstatuscommunicationswithotherequipment1,2,or4-Analogoutputchannels,0to10VDC, H0to+5VDC,±5VDC,4to20mA.Accuracyis.35%.Outputsignalsproportionatetometerdisplay,withindividualselectionof offsetandscalesettings.(IncludesOptionP)ExcitationSupply10VDCand24VDC PIsolatedupto1,500VpeakfrominputcircuitsRS232Cserialdatabi-directionalcommunication9600baud TRS232Cserialdatabi-directionalcommunication9600baud V
SING
LE-C
HANN
EL P
ROCE
SS C
ONTR
OLLE
RS &
TEM
P. D
ISPL
AYS
D382
0/D3
830
Seri
es ORDERING CODESPECIfICATIONS
DigiTec Division 800.727.5646 DigiTec Division 241DigiTec Division 800.727.5646 DigiTec Division
DISPLAY 0.50”RedLed
NMR 63dB,50/60Hz
CMV 130dB,50/60Hz.
POWER 115/230VACREQUIREMENTS
DISPLAY UPDATE 10persecondRATE
RESPONSE TIME 100mSecondMax.Todisplay
TERMINATION ScrewTerminalConnector
SELfCAL 1timeevery500mSeconds
ENVIRONMENT -20°to60°C
CASE AnodizedAluminum
WEIGHT 0.84lbsSI
NGLE
-CHA
NNEL
PRO
CESS
CON
TROL
LERS
& T
EMP.
DIS
PLAY
SD2
800B
Ser
ies
Single Channel Panel Meter
SPECIfICATIONS
MicroprocessortechnologymakesDigiTec’s 2800Bseriesof digitalpanelmeterstheidealsolutionformeetingthemeasurement,displayandcontrolrequirementsof industrialapplications,OEM’sandsystemdesigners.
Modelsareavailableforvoltage,andcurrentwith3-1/2,4,4-1/2digitdisplays.Eachunithasfieldselectable115/230VACinputpowerviainternaljumperselection.
four Separate Setpoint Limits:Fourseparatesetpointsmaybeoperatorprogrammedtoindicate“outof limit”conditionsbasedondisplayvalue.Eachlimitcanbeassignedasinglerelayoutputwithop-tion“C”installed.Thesetpointscanbeprogrammedalsotomakethedisplayflashwheninthealarmcondition.
Lockout Code for Security:Toeliminateunauthorizedchangesbytheoperatingpersonnel,anyalterationof theinstrumentsetupdatarequiresentryof usersecuritycodeforaccess.
SECOND SCALE:Thisfunctionallowstheusertosetasecondscalingtotheinput.Theinputwillthenbedisplayedintwoengineeringunits(typicallyforEnglish/Metricdisplays).
PEAK 1 AND PEAK 2:Peak1andpeak2arebothassignabletocapturethemaximumorminimumdisplayvalue.Theyareassignabletoanychannelandthenetorgrossvalue.Itcanberesetthroughafrontpanelkeyorremoteinput.Capturerateis20/SEC.
DigiTecrecognizestheimportanceof customersupport.Oneaspectof thissupportiscustomizedengineeringtomeetourcustomerspecificmarketrequirements.
FUNCTIONALREPLACMENTFORTHE2800A
• FailSafeAlarmReadyOperation
• NoFlashof DisplayonAlarms
• OptionalExcitationSupplies10,24,or5VDC
• CustomizedFastEntryforAlarmSetup
• U-PlotLinearization
• NEMA4XFrontFrame
DIMENSIONS (INCHES/MILLIMETERS)
242 DigiTec Division 800.727.5646 DigiTec Division DigiTec Division 800.727.5646 DigiTec Division
MODEL NUMBER INPUT RANGES
3-1/2DigitDisplay D2810B-01 ±199.9mVDC D2810B-02 ±1.999VDC D2810B-03 ±19.99VDC D2810B-04 ±199.9VDC D2810B-08 ±199.9uADC D2810B-09 ±1.999mADC D2810B-10 ±19.99mADC D2810B-11 ±199.9mADC D2810B-12 ±1.999ADC
4DigitDisplay D2811B-00 ±99.99mVDC D2811B-01 ±999.9mVDC D2811B-02 ±9.999VDC D2811B-03 ±99.99VDC D2811B-04 ±999.9VDC D2811B-08 ±999.9uADC D2811B-09 ±9.999mADC D2811B-10 ±99.99mADC D2811B-11 ±999.9mADC
4-1/2DigitDisplay D2812B-01 ±199.99mVDC D2812B-02 ±1.9999VDC D2812B-03 ±19.999VDC D2812B-04 ±199.99VDC
Process4-1/2DigitDisplay D2820B-23 ±5and1-5VDC D2820B-25 ±10and0-10VDC D2820B-27 0-20and4-20mADC D2820B-29 0-50and10-50mADC
SING
LE-C
HANN
EL P
ROCE
SS C
ONTR
OLLE
RS &
TEM
P. D
ISPL
AYS
D280
0B S
erie
sMODEL NUMBER D28 B
DISPLAY 3-1/2Digit 10 4Digit 11 4-1/2Digit 12 Process4-1/2Digit 20
INPUT RANGE Seerangechart
OPTIONS Useanycombinationof Options 3formC(singlepoledoublethrow)relaysratedat C 5amp@240VAC,5amps@30VDC. Locatedontheoption/topprintedcircuitboard Factorycalibration(userprovidesinputrangeand F displayrange) Analogoutputwithmenuselectionof 0-20mA,4-20mA, H 0-5VDC,0-10VDCand+5/-5VDC Updaterateof 25/second Resolution-16bitD/A Locatedontheoption/topprintedcircuitboard 24VDC@150mAAccuracy:.5% P 10VDC@250mAsupply SerialRS-232CCommunication. TConfigurationof 9600baud,NOParityCheck,8DATABits.
ORDERING CODE RANGE CHART
DigiTec Division 800.727.5646 DigiTec Division 243DigiTec Division 800.727.5646 DigiTec Division
SING
LE-C
HANN
EL P
ROCE
SS C
ONTR
OLLE
RS &
TEM
P. D
ISPL
AYS
D310
0 Se
ries
Process Indicator with Outputs
VOLTAGE/CURRENT MODELS (D3110/D3112 SERIES):Thesemodelsincludestandardvoltageandcurrentinputtypeswithfullscalerangesof ±1,999and±19,999.Standardwithscaling,relaysandanalogoutput.Accuracy.05%ofFS±1ct.
PROCESS MODEL(D3120/D3122 SERIES):Thismodelacceptscommon4-20mAsignalsfromstandardprocesstransmitters.Thismetercanalsobeuserconfigured(viabergjumper)for0-10Vand1-5Vsignalinputs.Standardwithscaling,2relays,excitationandanalogoutput.Thesemodelsoffer3-1/2digit(3120)or4-1/2digit(D3122)resolution.Ac-curacy0.5%FS,±1ct.
THERMOCOUPLE TEMPERATURE MODEL (D3130/D3132 SERIES): Twomodelsareavailableinthislow-costseries,JandKtypethermo-couples.Standardwith2relaysandanalogoutput.Thesemodelsoffer1°(D3130)or0.1°(D3132)temperatureresolution.Selectable°Cor°F.ThetemperaturerangesfortheD3130modelsare:
313X-03J-148°to1292°F(-100°to+700°C) 313X-05K-148°to1999°F(-100°to+1200°C)
Accuracyis±2°Cor±4°F.Themeterwillflashalldigitsif thethermo-coupleopens.
STRAIN GAUGE METER (D3140/D3142 SERIES):Thesemodelsaredesignedtooperatewith20mVinputwitha+10voltexcitationsuppliedbythemeter.Therearetwomodelsavailablewithresolutionsof 3-1/2digit(D3140)or4-1/2-digit(D3142).Thesensitivityof the3140is10µV/countandthe3142is1µV/count.The10V@120mAexcitationsupplyiscapableofpoweringuptofour350Ωloadcellswhichmakesthesemodelsidealforscaleapplications.Accuracy0.1%ofFS±1ct.Standardwithscaling,2relays,excitationandanalogoutput.
Note:RefertoD3700seriesformoresophisticatedfeatures.
TRUE AC RMS METER (D3150/D3152 SERIES): Thesemodelsaredesignedtomeasuretheroot-mean-squarevalueof complexwaveforms.Thereare10rangestochoosefromcoveringthemostcommoninputs.Allmodelsareprovidedwithinternalvoltagedividersorshunts.Thespecial5Acurrentrangeallowsdirectconnectiontoacurrenttrans-former(CT)witha5Asecondary,withoutrequiringastepdowntrans-former.Standardwith2relaysandanalogoutput.Accuracyis±0.1%ofreading±10ct.
RTD TEMPERATURE (D3160/D3162 SERIES): Therearetwomodelsavailableinthisseries(D3160)1°resolutionand(D3162).1°resolu-tion.Inputis100Ωplatinum0.00385alpha.
TheseRTDmetersaredesignedfor2or3-wireRTDprobes.(Applica-tionsrequiringa4-wireconnectionornon-standardsensorcurverefertotheD3200series).
If theRTDsensoropensorthewiringbecomesfaultythedisplaywillflashalldigits.ThemeterisfactoryconfiguredfortheFahrenheitscalebut,itcanbere-configuredeasilyinthefieldforCelsius.Temperaturerangeof-148°to1472°F(-100°to800°C).Standardwith2relaysandanalogoutput.
AC AVERAGE SENSING (D3170/D3172 SERIES):Theselow-costmod-elsuseaprecisionop-amprectifiercircuitandarecalibratedtomeasuretheRMSvalueof sinusoidalwaveforms.Thereare10rangestochoosefromcoveringthemostcommoninputs.Allareprovidedwithinternalvoltagedividersorshunts.Standardwith2relaysandanalogoutput.Accuracyis±0.1%ofreading±10ct.
• Bright,longlastingLEDdisplay,0.56"LED
• 2RelayOutputs
• 4-20mAor0-10Vanalogoutput(userselection)
• Drip-proofanddusttightFrontCoverNEMA12
• Compact1/8DINcase
• Pluginscrewterminalconnectors
• Widerangeofengineeringunits
• Slotoninsideof frontpanelfordisplayingunitof measure fromfurnisheddecalsheet
• Excitationsuppliesof 10VoltDC@120mA,maximumof +24Volt@50mA(userselectable)standardonStrain GaugeandProcessModels.
SEVENMODELS
• Voltage/Current
• Process
• Thermocouple(J&K)
• RTD
• TrueACRMSVoltage/Current
• ACAverage
VOLTAGE/CURRENT
• StrainGauge
OPTIONS
• BlackCase
• CustomCalibration
• NEMA4XCover
A/D DualslopeA/Dwith2.5readingSEC
POWER 115/230VACpowered
TEMPERATURE 32°to122°F(0°to50°C)RATING
CUTOUT 1/8DIN(92x45mm)
DEPTH 4.04"(102.5mm)
WEIGHT 16oz.
COMMON SPECIfICATIONS
244 DigiTec Division 800.727.5646 DigiTec Division DigiTec Division 800.727.5646 DigiTec Division
3-1/2 DIGIT 3-1/2 DIGIT INPUT RANGES
D3110-01 D3112-01 -199.9(9)mVto+199.9(9)mVDCD3110-02 D3112-02 -1.999(9)Vto+1.999(9)VDCD3110-03 D3112-03 -19.99(9)Vto+19.99(9)VDCD3110-04 D3112-04 -199.9(9)Vto+199.9(9)VDCD3110-05 D3112-05 -650(.0)Vto+650(.0)VDCD3110-11 D3112-11 -199.9(9)uAto+199.9(9)uAD3110-12 D3112-12 -1.999(9)mAto+1.999(9)mAD3110-13 D3112-13 -19.99(9)mAto+19.99(9)mAD3110-14 D3112-14 -199.9(9)mAto+199.9(9)mAD3110-15 D3112-15 -1.999(9)Ato+1.999(9)AD3120 D3122 4-20mAor0-10VDCProgressD3140 D3142 StrainGaugeInputD3130-03 D3132-03 1°resolution,JD3130-05 D3132-05 0.1°resolution,KD3150-01 D3152-01 0Vto199.9(9)mVACD3150-02 D3152-02 0Vto1.999(9)VACD3150-03 D3152-03 0Vto19.99(9)VACD3150-04 D3152-04 0Vto199.9(9)VACD3150-05 D3152-05 0Vto650(.0)VACD3150-11 D3152-11 0µAto199.9(9)µAACD3150-12 D3152-12 0mAto1.999(9)mAACD3150-13 D3152-13 0mAto19.99(9)mAACD3150-14 D3152-14 0mAto199.9(9)mAACD3150-15 D3152-15 0Ato1.999(9)AACD3150-16 D3152-16 0Ato5.00(0)AACD3170-01 D3172-01 0Vto199.9(9)mVACD3170-02 D3172-02 0Vto1.999(9)VACD3170-03 D3172-03 0Vto19.99(9)VACD3170-04 D3172-04 0Vto199.9(9)VACD3170-05 D3172-05 0Vto650(.0)VACD3170-11 D3172-11 0µAto199.9(9)µAACD3170-12 D3172-12 0mAto1.999(9)mAACD3170-13 D3172-13 0mAto19.99(9)mAACD3170-14 D3172-14 0mAto199.9(9)mAACD3130-15 D3172-15 0Ato1.999(9)AACD3130-16 D3172-16 0Ato5.00(0)AACD3130-17 D3172-17 0-10AACAC
MODEL NUMBER D31
DISPLAY 3-1/2DigitVoltage/Current 10 4-1/2DigitVoltage/Current 12 3-1/2DigitProcessModel 20 4-1/2DigitProcessModel 22 3-1/2DigitThermocoupleTemp. 30 4-1/2DigitThermocoupleTemp. 32 3-1/2DigitStrainGage 40 4-1/2DigitStrainGage 42 3-1/2DigitTrueACRMSMeter 50 4-1/2DigitTrueACRMSMeter 52 3-1/2DigitRTDTemperature 60 4-1/2DigitRTDTemperature 62 3-1/2DigitACAVGSensing 70 4-1/2DigitACAVGSensing 72
INPUT RATES Seerangechart
OPTIONS BlackCase B Prescaled F NEMA4CoverwithGasket N 230VACPower S
*D3120,D3122,D3140&D3142donotincluderangeoption.
SING
LE-C
HANN
EL P
ROCE
SS C
ONTR
OLLE
RS &
TEM
P. D
ISPL
AYS
D310
0 Se
ries ORDERING CODE RANGE CHART
DigiTec Division 800.727.5646 DigiTec Division 245DigiTec Division 800.727.5646 DigiTec Division
RATE
MET
ER/T
OTAL
IZER
/BAT
CH C
ONTR
OLLE
RD3
870
Seri
es
6-Digit Frequency Input Indicator/Totalizer
MODEL NUMBER D3870 chooseany combination
OPTIONS3Form-C5amprelaysactivatewhenprogrammable Chighandlowlimitsareexceeded.Permitson-off controlof externalcircuitry,oralarmstatuscommunicationwithotherequipment.Inputamplifier,30mVpeakinputat5Hz Gto99,999Hz.4analogoutputs,0-5VDC,±VDCor4-20mA, HAccuracyis0.35%ofoperatingrange.Outputsignalsareassignabletorateandtotal.230VACPower SRS232Cserialdatacommunicationinterfaceat T9600BaudrateExcitation10VDC/24VDC P
ORDERING CODE
DIMENSIONS (INCHES/MILLIMETERS)
TheDigitec D3870providesfast,accuratemeasurementsevenwithverylowfrequentinputs(aslowasonepulseper100seconds).Allpulseorfrequencyinputsareeasilydisplayedasrate.Easysetupwithnoprogrammingorcalcu-lationsrequired.Setupentriesincludetimebase,scale,offset.
TheD3870featuresa6-digittotalizermodethatcanbeindependentlyscaledanddisplayed.Thetotalizermodecanaccumulatetotalsforunitsorevents(i.e.gallons,revolutions,pounds,etc.)sincepower-uporlastreset.
TotalizerincludesaselectablepresetvalueandoptionalSSR20msec.output.
TheD3870ispackagedinananodizedaluminumcasewithaNEMA4Xfrontcover.One(1)FormArelay240VAC@1Athatcanbeusedasanalarmoutputisincluded.
PROCESSAPPLICATIONS
• Level • Pressure • Flow
INPUT RESPONSE 0.0005to99,999Hz
DISPLAY RANGE Userprogrammabledecimal,scalefactorsand insignificantzeroblankingyieldadisplayrange of 0.00001to999999.
PROTECTION ±200Vpeak
SENSITIVITY TTL,CMOSorcontactcompatible
PULSE WIDTH 5microsecondsminimum
TRIGGER MODE Negativeedgeof inputpulse
INPUT 12kΩIMPEDANCE
fILTER/ FrontpanelprogrammabledigitalfilterDEBOUNCE
WEIGHT 0.84lbs.
SPECIfICATIONS
246 DigiTec Division 800.727.5646 DigiTec Division DigiTec Division 800.727.5646 DigiTec Division
NEM
A SI
ZE P
ROCE
SS D
ISPL
AYS
D243
5A S
erie
s
MODEL RANGE 115 VAC 230 VAC MODEL RANGE 115 VAC 230 VAC
2435A 200mV 0285238 0285242 2435A 200µA 0286620 0286625 2V 0285239 0285243 2mA 0286621 0286626 20V 0285240 0285244 20mA 0286622 0286627 200V 0285241 0285245 200mA 0286623 0286628 500V 0284005 0284006 2A 0286624 0286629
RANGE ACCURACY RESOLUTION INPUT MAX. INPUT (20 -26 C) IMPEDANCE VOLTAGE (PEAK)
200mV 100µV >2000MΩ ±50V2V 0.05%rdg. 1mV >2000MΩ ±50V20V –1digit 10mV >5MΩ ±500V200V (typical) 100mV >5MΩ ±500V500V 0.05%rdg. 1V >5MΩ ±500V
NEMA Size Panel Meter
TheNEMA Sized Digitec D2430A Seriesisafamilyof 3-1/2digitLEDdisplay,single-range,line-poweredpanelmetersofferingawideselec-tionof standardrangesandfunctions.
DC VOLTAGE MEASUREMENT: (5ranges)199.9mVto500V
DC CURRENT MEASUREMENT:(5ranges)19.99µAto1.999A
PROCESS MONITOR: 4-20mA,1-5volts(Parametersestablishedtocustomer'srequirements).
• 3-1/2DigitLEDDisplay
• 0.05%Accuracy
• NEMASized
• 0°-65°COperation
• Auto-zero
• UniversallyPowered
• 3OutputVoltagestoPowerAuxiliaryCircuits
• 3DifferentReading-RateCapabilities
INPUT CIRCUIT & ACCURACY (Single-ended input)
ORDERING INfORMATION
DigiTec Division 800.727.5646 DigiTec Division 247DigiTec Division 800.727.5646 DigiTec Division
NEM
A SI
ZE P
ROCE
SS D
ISPL
AYS
D243
5A S
erie
s
DISPLAY Scalelength ±1999 Typeofdisplay 0.55"highLED. Polarity Negativeinput:Minussignatfarleft Positiveinput Plussignatfarleft2435A. OverrangeIndication Themostsignificantdigitwillremainpermanentlyonwhileall otherdigitswillbeblanked.Polaritysignwillbepreserved. Decimal-points Availableatanyofthefollowingthreepositionsbyconnectingthe selectedterminaltoPinN:1.XXX1X.XX1XX.X
RANGES DCVolts200mV,2V,20V,200V,500V
CONVERSION TECHNIQUE DualSlopeA/Dwithautozeroingandsinglereference.
CONVERSION RATE 3readings./SEC
SIGNAL INTEGRATION Time:83mS@3rdg/SEC
RESPONSE TIME Typically1secondtowithin0.5%offinalvalue
WARM UP REQUIREMENTS F.S.Calibration:5minuteswithin0.1%rdg±1digit.
LONG TERM STABILITY 180dayswithinratedaccuracy
POWER REQUIREMENTS 115/230VAC±15%,47Hzto440Hz ModelsD2435A max.at115or230VAC,60Hzwithdisplayfullylit.
TEMPERATURE Operating 32°to149°F(0°Cto65°C)@60Hzoperation. Storage -40°to185°F(-40°to85°C)
HUMIDITY 85%R.H.
NMRR 30dBat60Hz
CMRR 100dBat60Hztypical
MAX. CMV 500VRMS
LINEARITY ±0.05%F.S.
HYSTERESIS <0.3counts
TEMPERATURE ±0.01%F.S./°CCOEffICIENT
TEMPERATURE 3µV/°CCOEffICIENT Of ZERO
DIMENSIONS Bezel 4"Wx1.75"Hx.56"D(101.6x44.45x14.22mm) Body 3.875"Wx1.67"Hx4.0"D(98.42x42.42x101.6mm)
PANEL CUTOUT 3.924"Wx1.682"H(99.67x42.72mm)
WEIGHT Approximate13ounces(368grams)
SPECIfICATIONS
248 DigiTec Division 800.727.5646 DigiTec Division DigiTec Division 800.727.5646 DigiTec Division
TEM
PERA
TURE
CON
TROL
LERS
TOS
Seri
es
1/16 DIN Analog Temperature Controller
OPERATIONThe1/16DINTOS,isoneofthemostcommonlyusedtemperaturecontrolsbe-causeofitslowcostandoperationsimplicity.PrimarilyemployedinON/OFFoutputapplications,theunitisalsoavailablewithproportionalcontrolif desired.
Operationof theTOSissimple.Setthedialtotherequiredtemperatureandthecontrolprovidesanoutputuntilthetemperaturesettingisachieved.Theunithasahysteresisof 0.2to0.5%offullscaletoprovidefairlyconsistentcontrol.Outputcanbeorderedineitherrelaycontact(2A@250VAC,FormC)oroutputforsolidstaterelay(12VDC,20mA).Thisoutputflexibilityplusselectionof JorKthermo-coupleinputprovidesarangeofmodelstosatisfyapplicationrequirements.
DIMENSIONS (INCHES/MILLIMETERS)
WIRING
INPUT ThermocoupleJorKRTD
OPERATING VOLTAGE 100/240VAC,±10%,50/60Hz
POWER CONSUMPTION 2VA@120VAC
SETTING METHOD DialScale
CONTROL MODES ON/OFF/Proportional(Programmable)
OUTPUT RelaySPDT,2A@250VAC SSR12VDC±2V,20mA
MOUNTING FrontPanel(45mm2cutout)
TERMINATION 8-PinPlug-In
WEIGHT 4oz.Shipping:5oz.
SPECIfICATIONS
MODEL NUMBER TOS B 4
OUTPUT Relay R SSRelayDriver S
SENSOR JThermocouple J KThermocouple K RTD P
TEMPERATURE RANGE* 0-200°F 2F 0-400°F 4F 0-600°F 6F 0-800°F 8F 0-100°C 1C 0-300°C 3C 0-400°C 4C 0-800°C 8C
*OtherRangesAvailable—ConsultFactorySocketsforTOS:600-3-0011ForPanelMount,600-3-0013ForDINRailorBase.
•EconomicalControl
•1/16DIN,AnalogSetting
•Simple8-PinPlug-InInstallation
•FrontPanelLEDIndicatesOutput
STATUS
•JorKThermocoupleInput
•RelayorSSRDriverOutput
ORDERING CODE
DigiTec Division 800.727.5646 DigiTec Division 249DigiTec Division 800.727.5646 DigiTec Division
TEM
PERA
TURE
CON
TROL
LERS
T3S
Seri
es
1/16 DIN Analog Temperature Controller
•EconomicalDigitalControl
•1/16DIN,48mm2
•ON-OFForProportionalControl
•J,KThermocoupleorRTDInput
•Relay,SSRelayDriveror 4-20mAOutput
•BoldLEDTemperature Display
•SetValueVisibleOnSet Switches
•LEDOutputIndication
•UpscaleThermocoupleBreak
WIRING
MODEL NUMBER T3S B 4
OUTPUT Relay R SSRelayDriver S Current,4-20mA C
INPUT RTD;Pt100,0to199°C JThermocouple,0to399°F J4F JThermocouple,0to799°F J8F KThermocouple,0to799°F K8F
SampleOrderingModelNumber:T3S-B4RJ4FSocketsforT3S:600-3-0011ForFrontPanel,600-3-0013ForDINRailorBase.
ORDERING CODE
The T3S,1/16DINisapopulartemperaturecontrolbecauseitprovidesboldLEDtemperaturereadoutandsimpletosetbidirectionalpushbuttonswitches.
Operationof theT3Sissimplesinceallthatisrequiredistosetthebidi-rectionalswitchtotherequiredtemperatureandthecontrolprovidesanoutputuntilthetemperaturesettingisachieved.Outputcanbeorderedineitherrelaycontact(2A@250VAC,FormC),outputtodriveasolidstaterelay(12VDC,20mA),or4to20mA.Thisoutputflexibilityplusselectionof J,KthermocoupleorRTDinputprovidesarangeofmodelstosatisfyapplicationrequirements.
TheeconomicalT3Sisversatilewithfeatureslikeuniversalinputpower(100to240VAC,50/60Hz)andselectableON-OFForproportionalcontrolmodes.
OPERATION
SPECIfICATIONSINPUT ThermocoupleJorKRTD
OPERATING VOLTAGE 100/240VAC,50/60Hz
POWER CONSUMPTION 5VA
SETTING METHOD FrontPanelPush-buttonSwitches
CONTROL MODES ON/OFForProportional-Selectable
OUTPUT RelaySPDT,2A@250VAC SSR12VDC±2V,20mA Current4-20mA,600Max.
PROPORTIONAL Band 3%FullScaleFixedCONTROL Period 20SecondsFixed
RESET fUNCTION Adjustable±3%FullScale
DISPLAY LED
MOUNTING FrontPanelorSocketMount
TERMINATION 8-PinPlug-In
WEIGHT NET: 6.4oz.Shipping:8oz.
DIMENSIONS (INCHES/MILLIMETERS)
250 DigiTec Division 800.727.5646 DigiTec Division
TEM
PERA
TURE
INDI
CATO
RSfD
X Se
ries
Multi-Point Temperature Indicator
SAMPLING TIME 500milliseconds
THERMOCOUPLE 30commongroundCHANNELS
POWER SUPPLY FDX-II One9Vbattery,typeMN1604 orequivalent BatteryLife:50Hours FDX-SL 9to48VDC;12to30VAC
THERMOCOUPLES TypeJ,K,E,andTalloys(12to26A.W.G.)
RESOLUTION 1degree,FahrenheitorCentigrade
TEMPERATURE Range 32°Fto2502°F(0°Cto1372°C) Operating 32°Fto122°F(0°Cto50°C) Storage -40°Fto150°F(-40°Cto65°C)
TEMPERATURE SCALE FahrenheitorCentigrade
INPUT IMPEDANCE >100megohms
DISPLAY 6digitliquidcrystal0.5"(12.7mm)height
METER ACCURACY ±3°F(±2°C)
DIMENSIONS 6.5"H-5.85"W-3.75"D (165mm-149mm-95mm)
WEIGHT 2.5lbs.(1.1kg)
SPECIfICATIONS
WIRING
ORDERING CODE
The fDX-II isathermocoupleinputpyrometer.Theunitcanmeasureupto30inputs,basedonthermocouplealloysJ,K,T,orE.TheFDX-IIhasanaccuracyof ±3°F(±2°C).Itispoweredbya9Vbattery.Theopera-torselectsthechanneltoview,andusesthearrowstoscrollthroughtheadditionalchannels.TheFDX-IIisdesignedtofitthefootprintof theModelFDX,FA,orFAXforeasyreplacement.
The fDX-SLisascanningpyrometer.Itacceptsthermocoupleinputsforupto30channels.ItcanbesettoAutomaticorManualmodes.WhenintheManualmode,usetheUpandDownbuttonstoselectthechan-nelyouwouldliketoview.WhenintheAutomaticmode,theFDX-SLwillscrollbetweentheenabledchannels.Eachchannelhashighandlowalarmcapabilities.TheFDX-SLispoweredon9–48VDCor12-30VAC,andhasanaccuracyspecificationof ±3°F(±2°C).
FDX-II
• User-selectableglobalor individualalloytype
• Temperaturescale
• Adjustableon-time
• Multi-point,multi-alloy thermocouplecapability
• ULlistedasintrinsicallysafefor useinClass1,GroupsCandD, Division1environments
• Automaticshut-off forbattery conservation
• Paneltemplateincluded
• Accessories:9Vbatterytype MN604orequivalent
FDX-SL
• User-selectableglobalor individualalloytype
• Temperaturescale
• AdjustableScanDwell Time
• Multi-point,multi-alloy thermocouplecapability
• RS232Output
• Paneltemplateincluded
• AlarmRelayOutputwith SilenceFeature
NOTETighted screws to
hold TC wires.TCTerminals(1-15)
TCTerminals(16-30)
MODEL NUMBER DESCRIPTION
605-500-020 FDX-IITemperatureIndicator 605-500-030 FDX-SLTemperatureIndicator
DirectreplacementfortypesFA,FAX,FDX