Digital Compressor Controller Overview Presentation

download Digital Compressor Controller Overview Presentation

of 17

Transcript of Digital Compressor Controller Overview Presentation

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    1/17

    Digital Compressor ControllerDigital Compressor Controller

    *.ppt 11/2/2009 12:48 PM 1

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    2/17

    Co eland Scroll Di ital ControllerCo eland Scroll Di ital ControllerCo eland Scroll Di ital ControllerCo eland Scroll Di ital Controller Simple Controller That Enables OEMs To Use Digital Scrolls

    Relieves OEM From Develo in S ecial Controllers

    Faster Time To Market

    Copeland Controller Functions

    - Compressor Contactor

    - Capacity Modulation Solenoid

    Protection

    - Excessive Discharge Temperature

    - Low Flow Conditions

    -Diagnostics

    - 8 Codes Indicating Faults

    *.ppt 11/2/2009 12:48 PM 2

    Module Is Installed In System Cabinet

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    3/17

    Copeland ScrollCopeland Scroll Digital Digital

    Com ressor Dia nosticsCom ressor Dia nostics

    Copeland ScrollCopeland Scroll Digital Digital

    Com ressor Dia nosticsCom ressor Dia nosticsz Patented Copeland Diagnostics

    z Green POWER LED

    24VAC Indicator

    Flashes During Anti-Short

    z Yellow UNLOADER LED

    Indicates Solenoid IsEnergized

    z Red ALERT LED

    as o e n ca ng cALERT Code Is Active

    Code Interpreted By

    *.ppt 11/2/2009 12:48 PM 3

    oun ng um er Flashes (1-9)

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    4/17

    Co eland Di ital Scroll ControllerCo eland Di ital Scroll ControllerCo eland Di ital Scroll ControllerCo eland Di ital Scroll Controller

    OEM

    Alarm

    System Controller

    ompressor

    Capacity Request

    (0-5 VDC)

    Capacity

    Solenoid

    Capacity Signal

    CONTACTORCompressor

    Start / Stop

    z Capacity Solenoid Control

    Controller Modulates Solenoid Based On Ca acit Demand

    Demand Is Read Once Every 20 Seconds

    z Minor Alert Display Appropriate Alarm

    *.ppt 11/2/2009 12:48 PM 4

    z Major Alert De-energize Contactor To Lock Out Compressor

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    5/17

    Copeland Digital Scroll ControllerCopeland Digital Scroll Controller

    O tional Pressure Si nal FilterinO tional Pressure Si nal Filterin

    Copeland Digital Scroll ControllerCopeland Digital Scroll Controller

    O tional Pressure Si nal FilterinO tional Pressure Si nal Filterin

    Alarm

    Filtered Suction Pressure

    OEMSystem Controller

    Compressor

    Capacity Request CapacitySolenoid

    Capacity Signal

    Suction Pressure

    CONTACTORCompressor

    Start / Stop

    z Digital Controller Can Provide Suction Pressure Feedback

    5 VDC Suction Pressure Transducer Required

    *.ppt 11/2/2009 12:48 PM 5

    Algorithm Filters Suction Pressure Swings

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    6/17

    Copeland ScrollCopeland Scroll Digital Digital

    Demand Si nal vs. ModulationDemand Si nal vs. Modulation

    Copeland ScrollCopeland Scroll Digital Digital

    Demand Si nal vs. ModulationDemand Si nal vs. Modulation

    *.ppt 11/2/2009 12:48 PM 6

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    7/17

    Copeland Scroll Digital ControllerCopeland Scroll Digital Controller

    Ke S ecificationsKe S ecifications

    Copeland Scroll Digital ControllerCopeland Scroll Digital Controller

    Ke S ecificationsKe S ecifications Size

    - Depth 6 x Height 4 x Width 2

    - Designed To Minimize Footprint In System Electrical Panel

    Voltages- Controller Supply: 19-28VAC, 48-62Hz, 2VA Max

    - Pilot Voltage Capabil ity: AC Voltages 24, 120, 240

    Inputs- Minimum: Capacity Signal 1-5VDC, Discharge Thermistor (100K NTC)

    - Optional : Suct ion Pressure Sensor (Controller Wil l Source 5VDC To Sensor)

    Outputs- Minimum: Digital Solenoid, Compressor Contactor

    - Optional : Suction Pressure, Alarm, Vapor Injection

    Operator Interface- 3 LEDs : Green Indicating Module Health

    Amber Indicatin Di ital Solenoid O eration

    *.ppt 11/2/2009 12:48 PM 7

    Red - Up To 8 Flash Codes Indicating Operation Status

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    8/17

    Copeland Scroll Digital ControllerCopeland Scroll Digital Controller

    Ke O erational FeaturesKe O erational Features

    Copeland Scroll Digital ControllerCopeland Scroll Digital Controller

    Ke O erational FeaturesKe O erational FeaturesOperation RulesDigital duty cycle of 15 seconds

    Min Ca acit l imited to 10%

    Scrolls unloaded for 0.5 sec on start up

    Scrolls unloaded for 1 sec on shut down to prevent reverse rotation2 Min anti short cycle enforced on all shutdown

    30 minute no start enforced on all hi h tem erature shutdown

    Status Codes1 Future

    Digital solenoid turned OFF on protector trip

    2 High Discharge Temperature Td >268F,Reset Td

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    9/17

    Copeland ScrollCopeland Scroll Digital Digital

    Fault CodesFault Codes

    Copeland ScrollCopeland Scroll Digital Digital

    Fault CodesFault Codes Alert Light Blinks When Any Of 7 Harmful System Conditions Is

    Detected

    Diagnost ic Alert Light

    Blinks 2 Times

    Action

    Lockout

    Alert Code

    Code 2

    System Condition

    High Discharge Temp Trip

    Blinks 3 Times

    Blinks 4 Times

    Blinks 5 Times

    Lockout

    Lockout

    Lockout

    Code 3

    Code 4

    Code 5

    Compressor Protector Trip

    Locked Rotor

    Demand Signal Loss

    Blinks 6 Times

    N/A

    Reduce Capacity

    N/A

    Code 6

    Code 7

    Discharge Thermistor Fault

    Future

    Blinks 9 Times

    Trip Compressor

    Code 9

    Low Voltage

    *.ppt 11/2/2009 12:48 PM 9

    ro ec ve au s a equ re anua ese

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    10/17

    Code 2Code 2 Hi h Dischar e Tem erature TriHi h Dischar e Tem erature TriCode 2Code 2 Hi h Dischar e Tem erature TriHi h Dischar e Tem erature Triz Event Trigger

    Discharge temperature is above 268F OR discharge thermistoru u

    z Action

    Close alarm relay contacts Display Code 2 Alert Unloader solenoid deenergized

    z Event Reset For Restarting Compressor

    30 minute cool down timer AND discharge temperature below 250F

    z Flash Code Clear/Alarm Relay Contact Open

    Compressor must have 60 non-interrupted, ALERT free minutes of

    *.ppt 11/2/2009 12:48 PM 10

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    11/17

    z Event Trigger

    5 High Discharge Temperature trips within 4 hours

    z Action

    Deenergize compressor contactor Take Compressor Offl ine Close alarm relay contacts Display Code 2 Alert

    Unloader solenoid deenergized

    z Event Reset For Restarting Compressor

    Controller 24VAC power must be cycled on and off

    z as o e ear arm e ay on ac pen Controller 24VAC power must be cycled on and off

    *.ppt 11/2/2009 12:48 PM 11

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    12/17

    Code 3Code 3 Com ressor Protector TriCom ressor Protector TriCode 3Code 3 Com ressor Protector TriCom ressor Protector Triz Event Trigger

    Demand 1.4VDC or higher AND

    Compressor internal overload protector open OR

    Power disconnected to compressor (fuse, breaker, loose wire)

    z c on

    Deenergize compressor contactor Take Compressor Offl ine Close alarm rela contacts Dis la Code 3 Alert Unloader solenoid deenergized

    z Event Reset For Restarting Compressor

    Wait anti-short cycle timer delay (2 minutes)

    z Flash Code Clear/Alarm Relay Contact Open

    *.ppt 11/2/2009 12:48 PM 12

    Demand 1.4VDC or higher AND compressor current detected

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    13/17

    Code 4Code 4 Locked RotorLocked RotorCode 4Code 4 Locked RotorLocked Rotorz Event Trigger

    Controller senses a locked rotor condition in compressor

    z

    Action Deenergize compressor contactor Take Compressor Offl ine Close alarm relay contacts Display Code 4 Alert Unloader solenoid deenergized

    z

    Controller 24VAC power must be cycled on and off

    Controller 24VAC power must be cycled on and off

    *.ppt 11/2/2009 12:48 PM 13

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    14/17

    Code 5Code 5 Demand Si nal LossDemand Si nal LossCode 5Code 5 Demand Si nal LossDemand Si nal Lossz Event Trigger

    Demand signal below 0.5VDC

    z

    Action Deenergize compressor contactor Take Compressor Offl ine Close alarm relay contacts Display Code 5 Alert Unloader solenoid deenergized

    z

    Demand signal above 0.5VDC AND anti-short cycle timer complete

    Demand signal above 0.5VDC

    *.ppt 11/2/2009 12:48 PM 14

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    15/17

    Code 6Code 6 Dischar e Thermistor FaultDischar e Thermistor FaultCode 6Code 6 Dischar e Thermistor FaultDischar e Thermistor Faultz Event Trigger

    Discharge thermistor is not connected to CompressorController

    z Action

    m max mum capac y o compressor o un oa er modulation

    Close alarm relay contacts Display Code 6 Alertz Event Reset For Restarting Compressor

    Thermistor reconnected

    z Flash Code Clear/Alarm Relay Contact Open

    Thermistor reconnected

    *.ppt 11/2/2009 12:48 PM 15

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    16/17

    Code 8Code 8 Com ressor Contactor FaultCom ressor Contactor FaultCode 8Code 8 Com ressor Contactor FaultCom ressor Contactor Faultz Event Trigger

    Compressor current is detected when demand is below 1.4VDC

    z Action

    Reenergizes compressor contactor

    ose a arm re ay con ac s sp ays o e er Unloader solenoid energized

    Net effect is to run com ressor unloaded until demand risesabove 1.4VDC again

    z Event Reset For Restarting Compressor

    z Flash Code Clear/Alarm Relay Contact Open

    Demand above 1.4VDC OR no com ressor current detected

    *.ppt 11/2/2009 12:48 PM 16

  • 7/30/2019 Digital Compressor Controller Overview Presentation

    17/17

    Code 9Code 9 Low 24VAC Su lLow 24VAC Su lCode 9Code 9 Low 24VAC Su lLow 24VAC Su lz Event Trigger

    Compressor Controller 24VAC supply below 18.5VAC

    z Action

    Tri com ressor

    Close alarm relay contacts Display Code 9 Alertz Event Reset For Restartin Com ressor

    24VAC supply above 19.5VAC AND anti-short cycletimer complete

    z Flash Code Clear/Alarm Relay Contact Open

    24VAC supply above 19.5VAC AND anti-short cycle

    *.ppt 11/2/2009 12:48 PM 17

    mer comp e e