Diesel Generator Set mtu 20V4000 DS3600
Transcript of Diesel Generator Set mtu 20V4000 DS3600
Diesel Generator Set
mtu 20V4000 DS3600
Product highlights
Optionalequipmentandfinishingshown.Standardmayvary.
Bene� ts— Lowfuelconsumption— Optimizedsystemintegrationability— Highreliability— Highavailabilityofpower— Longmaintenanceintervals
Support— Globalproductsupportoffered
Standards— Engine-generatorsetisdesignedandmanufacturedinfacilitiescertifiedtostandardsISO2008:9001andISO2004:14001
— GeneratorsetcompliestoISO8528— GeneratormeetsNEMAMG1,BS5000,ISO,DINENandIECstandards
— NFPA110
Power rating— Systemratings:3380kVA-3390kVA— AcceptsratedloadinonestepperNFPA110— GeneratorsetcompliestoG3accordingtoISO8528-5— GeneratorsetexceedsloadstepsaccordingtoISO8528-5
Performance assurance certi� cation (PAC)— Engine-generatorsettestedtoISO8528-5fortransientresponse— 100%loadfactor— Verifiedproductdesign,qualityandperformanceintegrity— Allenginesystemsareprototypeandfactorytested
Complete range of accessories available— Controlpanel— Powerpanel— Fuelsystem— Fuelconnectionswithshut-offvalvemountedtobaseframe— Starting/chargingsystem— Exhaustsystem— Electricaldrivenradiators— Mechanicaldrivenradiators— Mediumandoversizedvoltagealternators
Emissions— Fuelconsumptionoptimized
Certi� cations — CEcertificationoption— UnitconformityandcertificateaccordingtoAR-N-4110(GermanGrid-Code)onrequest
3.3-11kV/50Hz/primepower/fuelconsumptionoptimized20V4000G44F/waterchargeaircooling
Application data 1)
1 AlldatarefersonlytotheengineandisbasedonISOstandardconditions(25°Cand100mabovesealevel).2 ValuesreferencedareinaccordancewithISO3046-1.Conversioncalculatedwithfueldensityof0.83g/ml.Allfuelconsumptionvaluesrefertoratedenginepowerand areapproximatevalues.
Standardandoptionalfeatures
System ratings (kW/kVA)
Generator model Voltagefuel consumption optimized
without radiator
kWel kVA* AMPS
LeroySomerLSA54.2XL11 (Med.volt.LeroySomer)
11kV 2704 3380 177
Marathon1040FDH7103 (Mediumvolt.marathon)
11kV 2712 3390 178
LeroySomerLSA54.2ZL12 (MVLeroySomeroversized)
11kV 2704 3380 177
Marathon1040FDH7105 (MVmarathonoversized)
11kV 2712 3390 178
*cosphi=0.8
EngineManufacturer mtu Model 20V4000G44F Type 4-cycle Arrangement 20V Displacement:l 95.4 Bore:mm 170 Stroke:mm 210 Compressionratio 16.4 Ratedspeed:rpm 1500 Enginegovernor ECU9 Maxpower:kWm 2807 Aircleaner dry
Fuel systemMaximumfuellift:m 5 Totalfuelflow:l/min 27
Fuel consumption 2) l/hr g/kwh At100%ofpowerrating: 653 193 At75%ofpowerrating: 485 191 At50%ofpowerrating: 349 206
Liquid capacity (lubrication)Totaloilsystemcapacity:l 390 Enginejacketwatercapacity:l 260 Intercoolercoolantcapacity:l 50
Combustion air requirementsCombustionairvolume:m3/s 4.0 Max.airintakerestriction:mbar 30
Cooling/radiator systemCoolantflowrate(HTcircuit):m3/hr 80 Coolantflowrate(LTcircuit):m3/hr 44 Heatrejectiontocoolant:kW(100/110%) 945/1090 Heatradiatedtochargeaircooling:kW(100/110%) 700/795 Heatradiatedtoambient:kW 105 Fanpowerforelectr.radiator(40°C):kW 105
Exhaust systemExhaustgastemp.(afterengine,max.):°C 550 Exhaustgastemp.(beforeturbocharger):°C 605 Exhaustgasvolume:m3/s 9.6 Maximumallowablebackpressure:mbar 50 Minimumallowablebackpressure:mbar –
Cooling system
Jacketwaterpump Thermostat(s) Waterchargeaircooling
Electricaldrivenfront-endcooler Jacketwaterheater Pulleyforfandrive
Standard and optional features
Control panel
Representsstandardfeatures
Representsoptionalfeatures
Power panel
Availablein600x600mm Phasemonitoringrelay230V/400V
Supplyforbatterycharger Supplyforjacketwaterheater
Supplyforanticondensationheating Plugsocketcabinetfor230VcompatibleEuro/USA
Pre-wiredcontrolcabinetforeasyapplicationofcustomizedcontroller(V1+) Islandoperation(V2) Automaticmainsfailureoperationwith ATS(V3a) Automaticmainsfailureoperation incl.controlofgeneratorandmainsbreaker(V3b) Islandparalleloperationof multiplegensets(V4) Automaticmainsfailureoperationwithshort(<10s)mainsparalleloverlapsynchronization(V5)
Mainsparalleloperationofa singlegenset(V6) Mainsparalleloperationof multiplegensets(V7) Baslercontroller Deifcontroller Completesystemmetering Digitalmetering Engineparameters Generatorprotectionfunctions Engineprotection SAEJ1939engineECUcommunications Parametrizationsoftware
Multilingualcapability Multipleprogrammablecontactinputs Multiplecontactoutputs Eventrecording IP54frontpanelratingwith integratedgasket Remoteannunciator Daytankcontrol Generatorwinding-andbearing temperaturemonitoring ModbusTCP-IP
Generator
4polethree-phasesynchronous generator Brushless,self-excited,self-regulating,self-ventilated Digitalvoltageregulator Anticondensationheater StatorwindingY-connected,accessibleneutral(broughtout) ProtectionIP23
InsulationclassH,utilizationacc.toH RadiosuppressionEN55011,group1,cl.B Shortcircuitcapability3xInfor10sec WindingandbearingRTDs (withoutmonitoring) ExcitationbyAREP+PMI MountingofCT´s:3x2coreCT´s Windingpitch:5/6winding Voltagesetpointadjustment±5%
MeetsNEMAMG-1,BS5000,IEC60034-1,VDE0530,DINEN12601,AS1359and ISO8528requirements LeroySomermediumvoltagegenerator Marathonmediumvoltagegenerator Oversizedgenerator
Engine
4-cycle Standardsinglestageairfilter Oildrainextension&shut-offvalve
Closedcrankcaseventilation Governor-electronicisochronous Commonrailfuelinjection
Fuelconsumptionoptimizedengine
Standard and optional features
Representsstandardfeatures
Representsoptionalfeatures
Fuel system
Flexiblefuelconnectorsmountedto baseframe Fuelfilterwithwaterseparator Fuelfilterwithwaterseparatorheavy-duty
Switchablefuelfilterwithwaterseparator Switchablefuelfilterwithwaterseparatorheavy-duty Seperatefuelcooler
Fuelcoolerintegratedintocoolingequipment
Starting/charging system
24Vstarter Starterbatteries,cables,rack, disconnectswitch
Batterycharger Redundantstarter2x15kW
Mounting system
Weldedbaseframe Resilientengineandgeneratormounting Modularbaseframedesign
Exhaust system
Exhaustbellowswithconnectionflange Exhaustsilencerwith 10dB(A)soundattenuation
Exhaustsilencerwith 30dB(A)soundattenuation
Exhaustsilencerwith 40dB(A)soundattenuation Y-connection-pipe
Weights and dimensions
Drawing above for illustration purposes only, based on a standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design. See website for unit specific template drawings.
Emissionsdata
— Consultyourlocalmtudistributorforemissionsdata.
Sound data
— Consultyourlocalmtudistributorforsounddata.
Weightsanddimensionsarebasedonopenpowerunitsandareestimatesonly.Consultthefactoryforaccurateweightsanddimensionsforyourspecificengine-generatorset.
System Dimensions (LxWxH) Weight (dry/less tank)
Openpowerunit(OPU) 6249x1887x2412mm 18420kg
Rolls-Royce Groupwww.mtu-solutions.com/powergen
Subjecttochange.|32310661|Edition01/21|ESM2021-01.
Ratingdefinitionsandconditions
— Primepowerratingsapplytoinstallationswhereutilitypowerisunavailableorunreliable.Atvaryingload,thenumberofgeneratorsetoperatinghoursisunlimited.A10%overloadcapacityisavailableforonehourintwelve.RatingsareinaccordancewithISO8528-1,ISO3046-1,BS5514andAS2789. Averageloadfactor:≤100%.
— Consultyourlocalmtudistributorforderatinginformation.