Diesel Generator Set MTU 12V4000 DS1750 · VDE 0530, DIN EN 12601, AS1359 and ISO 8528 requirements...

5
Optional equipment and finishing shown. Standard may vary. MTU 12V4000 DS1750 Diesel Generator Set Product highlights 380V – 11 kV/50 Hz/grid stability power/ fuel consumption optimized/12V4000G14F/water charge air cooling Bene�ts Low fuel consumption Optimized system integration ability High reliability High availability of power Long maintenance intervals Support Global product support offered Standards Engine-generator set is designed and manufactured in facilities certified to standards ISO 2008:9001 and ISO 2004:14001 Generator set complies to ISO 8528 Generator meets NEMA MG1, BS5000, ISO, DIN EN and IEC standards NFPA 110 Power rating System ratings: 1590 kVA - 1700 kVA Accepts rated load in one step per NFPA 110 Generator set complies to G3 according to ISO 8528-5 Generator set exceeds load steps according to ISO 8528-5 Performance assurance certi�cation (PAC) Engine-generator set tested to ISO 8528-5 for transient response 100% load factor Verified product design, quality and performance integrity All engine systems are prototype and factory tested Complete range of accessories available Control panel Power panel Circuit breaker/power distribution Fuel system Fuel connections with shut-off valve mounted to base frame Starting/charging system Exhaust system Mechanical and electrical driven radiators Medium and oversized voltage alternators Emissions Fuel consumption optimized Certi�cations CE certification option Unit certificate acc. to BDEW (German Grid-Code)

Transcript of Diesel Generator Set MTU 12V4000 DS1750 · VDE 0530, DIN EN 12601, AS1359 and ISO 8528 requirements...

  • Optionalequipmentandfinishingshown.Standardmayvary.Optionalequipmentandfinishingshown.Standardmayvary.

    MTU 12V4000 DS1750DieselGeneratorSet

    Producthighlights

    380V–11kV/50Hz/gridstabilitypower/fuelconsumptionoptimized/12V4000G14F/waterchargeaircooling

    Bene� ts— Lowfuelconsumption— Optimizedsystemintegrationability— Highreliability— Highavailabilityofpower— Longmaintenanceintervals

    Support— Globalproductsupportoffered

    Standards— Engine-generatorsetisdesignedandmanufacturedinfacilitiescertifiedtostandardsISO2008:9001andISO2004:14001

    — GeneratorsetcompliestoISO8528— GeneratormeetsNEMAMG1,BS5000,ISO,DINENandIECstandards

    — NFPA110

    Power rating— Systemratings:1590kVA-1700kVA— AcceptsratedloadinonestepperNFPA110— GeneratorsetcompliestoG3accordingtoISO8528-5— GeneratorsetexceedsloadstepsaccordingtoISO8528-5

    Performance assurance certi� cation (PAC)— Engine-generatorsettestedtoISO8528-5fortransientresponse— 100%loadfactor— Verifiedproductdesign,qualityandperformanceintegrity— Allenginesystemsareprototypeandfactorytested

    Complete range of accessories available— Controlpanel— Powerpanel— Circuitbreaker/powerdistribution— Fuelsystem— Fuelconnectionswithshut-offvalvemountedtobaseframe— Starting/chargingsystem— Exhaustsystem— Mechanicalandelectricaldrivenradiators— Mediumandoversizedvoltagealternators

    Emissions— Fuelconsumptionoptimized

    Certi� cations— CEcertificationoption— Unitcertificateacc.toBDEW(GermanGrid-Code)

  • Application data 1)

    1 AlldatarefersonlytotheengineandisbasedonISOstandardconditions(25°Cand100mabovesealevel).2 ValuesreferencedareinaccordancewithISO3046-1.Conversioncalculatedwithfueldensityof0.83g/ml.Allfuelconsumptionvaluesrefertoratedenginepower.

    Standardandoptionalfeatures

    System ratings (kW/kVA)

    Generator model Voltage fuel consumption optimized

    without radiator with mechanical radiator

    kWel kVA* AMPS kWel kVA* AMPS

    LeroySomerLSA52.3S5(LowvoltageLeroySomerstandard)

    380V 1360 1700 2583 1320 1650 2507

    400V 1360 1700 2454 1320 1650 2382

    415V 1360 1700 2365 1320 1650 2295

    Marathon743RSL7090(LowvoltageMarathon)

    380V 1352 1690 2568 1312 1640 2492

    400V 1344 1680 2425 1312 1640 2367

    415V 1272 1590 2212 1272 1590 2212

    Marathon744RSL7091(LowvoltageMarathonoversized)

    380V 1352 1690 2568 1312 1640 2492

    400V 1344 1680 2425 1312 1640 2367

    415V 1272 1590 2212 1272 1590 2212

    Marathon1020FDH7095(Mediumvolt.marathon)

    11kV 1352 1690 89 1312 1640 86

    LeroySomerLSA53.2VL6(Mediumvolt.LeroySomer)

    11kV 1352 1690 89 1320 1650 87

    *cosphi=0.8

    EngineManufacturer MTUModel 12V4000G14FType 4-cycleArrangement 12VDisplacement:l 57.2Bore:mm 170Stroke:mm 210Compressionratio 16.4Ratedspeed:rpm 1500Enginegovernor ECU9Maxpower:kWm 1420Aircleaner dry

    Fuel systemMaximumfuellift:m 5Totalfuelflow:l/min 16

    Fuel consumption 2) l/hr g/kwhAt100%ofpowerrating: 323.3 189At75%ofpowerrating: 250.2 195At50%ofpowerrating: 173.7 203

    Liquid capacity (lubrication)Totaloilsystemcapacity:l 260Enginejacketwatercapacity:l 160Intercoolercoolantcapacity:l 40

    Combustion air requirementsCombustionairvolume:m3/s 1.6Max.airintakerestriction:mbar 50

    Cooling/radiator systemCoolantflowrate(HTcircuit):m3/hr 56Coolantflowrate(LTcircuit):m3/hr 30Heatrejectiontocoolant:kW 540Heatradiatedtochargeaircooling:kW 200Heatradiatedtoambient:kW 75Fanpowerforelectr.radiator(40°C):kW 38

    Exhaust systemExhaustgastemp.(afterturbocharger):°C 430Exhaustgasvolume:m3/s 4.0Maximumallowablebackpressure:mbar 85Minimumallowablebackpressure:mbar 30

  • Standard and optional features

    Representsstandardfeatures

    Representsoptionalfeatures

    Engine

    4-cycle Standardsinglestageairfilter Oildrainextension&shut-offvalve

    Closedcrankcaseventilationwithimprovedoilseperator Governor-electronicisochronous

    Commonrailfuelinjection Fuelconsumptionoptimizedengine Centrifugaloilfilter

    Generator

    4polethree-phasesynchronousgenerator Brushless,self-excited,self-regulating,self-ventilated Digitalvoltageregulator Anticondensationheater StatorwindingY-connected,accessibleneutral(broughtout) ProtectionIP23

    InsulationclassH,utilizationacc.toH RadiosuppressionEN55011,group1,cl.B Shortcircuitcapability3xInfor10sec WindingandbearingRTDs(withoutmonitoring) ExcitationbyAREP MountingofCT´s:2coreCT´s Windingpitch:2/3winding Voltagesetpointadjustment±10%

    MeetsNEMAMG-1,BS5000,IEC60034-1,VDE0530,DINEN12601,AS1359andISO8528requirements LeroySomerlowvoltagegenerator Marathonlowvoltagegenerator Oversizedgenerator Mediumvoltagegenerator

    Cooling system

    Jacketwaterpump Thermostat(s) Waterchargeaircooling

    Mechanicalradiator Electricaldrivenfront-endcooler Jacketwaterheater

    Control panel

    Pre-wiredcontrolcabinetforeasyapplicationofcustomizedcontroller(V1+) Islandoperation(V2) AutomaticmainsfailureoperationwithATS(V3a) Automaticmainsfailureoperationincl.controlofgeneratorandmainsbreaker(V3b) Islandparalleloperationofmultiplegensets(V4) Automaticmainsfailureoperationwithshort(<10s)mainsparalleloverlapsynchronization(V5) Mainsparalleloperationofasinglegenset(V6)

    Mainsparalleloperationofmultiplegensets(V7) Baslercontroller Deifcontroller Completesystemmetering Digitalmetering Engineparameters Generatorprotectionfunctions Engineprotection SAEJ1939engineECUcommunications Parametrizationsoftware Multilingualcapability Multipleprogrammablecontactinputs Multiplecontactoutputs Eventrecording

    IP54frontpanelratingwithintegratedgasket Differentexpansionmodules Remoteannunciator Daytankcontrol Generatorwindingtemperaturemonitoring Generatorbearingtemperaturemonitoring ModbusTCP-IP

    Power panel

    Availablein600x600and600x1000 Phasemonitoringrelay230V/400V Supplyforbatterycharger Supplyforjacketwaterheater

    Supplyforanticondensationheating Plugsocketcabinetfor230VcompatibleEuro/USA

    Supplyforelectricaldrivenradiatorfrom45kW–75kW(PP600x1000)

  • Standard and optional features

    Circuit breaker/power distribution

    3-polecircuitbreaker 4-polecircuitbreaker

    Manual-actuatedcircuitbreaker Electrical-actuatedcircuitbreaker

    Stand-alonesolutioninseperatecabinet

    Fuel system

    Flexiblefuelconnectorsmountedtobaseframe Fuelfilterwithwaterseparator Fuelfilterwithwaterseparatorheavy-duty

    Switchablefuelfilterwithwaterseparator Switchablefuelfilterwithwaterseparatorheavy-duty Seperatefuelcooler

    Fuelcoolerintegratedintocoolingequipment

    Starting/charging system

    24Vstarter Starterbatteries,cables,rack,disconnectswitch

    Batterycharger

    Mounting system

    Weldedbaseframe Resilientengineandgeneratormounting Modularbaseframedesign

    Representsstandardfeatures

    Representsoptionalfeatures

    Exhaust system

    Exhaustbellowswithconnectionflange Exhaustsilencerwith10dB(A)soundattenuation

    Exhaustsilencerwith30dB(A)soundattenuation

    Exhaustsilencerwith40dB(A)soundattenuation Y-connection-pipe

  • Rolls-Royce Groupwww.mtu-solutions.com/powergen

    Weights and dimensions

    Sound data

    — Consult your local MTU distributor for sound data.

    Emissions data

    — Consult your local MTU distributor for emissions data.

    Rating definitions and conditions

    — Grid Stability Power ratings apply to installations serving electric utility programs. At constant or varying load, the number of generator set operating hours is limited to 1000 hours per year with no more than 500 hours per year at 100% load without interruption. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO 8528-1, ISO 3046-1, BS 5514 and AS 2789. Average load factor: ≤ 100%.

    — Consult your local MTU distributor for derating information.

    Drawing above for illustration purposes only, based on a standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design. See website for unit specific template drawings.

    Sub

    ject

    to

    chan

    ge.

    | 32

    3847

    1 | E

    diti

    on 0

    1/20

    | ES

    M 2

    020

    -03.

    Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.

    System Dimensions (L x W x H) Weight (dry/less tank)

    Open power unit (OPU) 4059 x 1810 x 2330 mm 10654 kg