Diesel Drive Controller Functions and Operation
- for -
F.M. Approvals- by -
James S. Nasby
Columbia Engineering
C.E. F.M. Approvals 2
Topics Covered Type of Controller
Manual Combined Automatic
Measurement Timing Remote Functions
C.E. F.M. Approvals 3
Type of Controller Manual Only Controller
Peerless "Mantrol" was U.L. Listed Most F.P. Engine Panels do this
Automatic Controller Must be both A Manual Controller -and- An Automatic Controller
C.E. F.M. Approvals 4
Timing Cranking
Six Cranks 15 Seconds Each 5 Rests 15 Seconds Each Total 165 Seconds (2-3/4 Minutes) Patern: 1-R-2-R-1-R-2-R-1-R-2-FTS (Alam) FM-1321/23 Modifies FTS Operation
• Hold Terminal #1 Active for One Hour• Then Disable Fuel and Water
Weekly Test, 30 Minutes Nominal Run
C.E. F.M. Approvals 5
Optional Timing Automatic Stop (Minimum Run) - Not per F.M. Delayed Starting: Which Demands?
Sequence Start: Static Demands• Pressure (Weekly Test)• Deluge• A.C. PF Start
Don’t Delay• Remote Momentary Switch (Push Button)
High Zone Start - Which Demands Static Demands -and- Remote Momentary (Don't Want to Start a Dry or
Cavitating Pump
C.E. F.M. Approvals 6
A.C. Line Margins Low Line Operation
Battery Charger 24 Hour Capability High Line Operation
Excess Power Dissipation
C.E. F.M. Approvals 7
D.C. Line Margins Single Battery Operation Low Battery Voltage
Starter Break-away (50%) Cranking (Undulating): 10Vdc, 9Vdc,
8Vdc? High Battery Voltage
Charger Equalizing Alternator High Rate Operation
C.E. F.M. Approvals 8
Operating Voltages Alternator High Rage: 15+ Vdc Alternator Maintaining: 14+ Vdc Charger Equalize: ~14 Vdc Charger Float: ~13.25 Vdc Ideal Alarm Voltage: ~12.5 Vdc Battery Full Charge Open Circuit: 12.5 Vdc Battery Discharged (Open Circuit): 11.75 Vdc Cranking: <10 Vdc Break-away: ~6 Vdc
C.E. F.M. Approvals 9