Jamesville-DeWitt High School, DeWitt, NY Pinnacle Skylight with Solera Glazing.
DeWitt
-
Upload
davedewitt -
Category
Real Estate
-
view
102 -
download
1
description
Transcript of DeWitt
DeWitt-Wooddale
AttributeAge (approximate)
Area (approximate)
Building type Single family, tri-level
Single family, two story
aaaa Single family, ranch
See comments
Construction Not applicable
Frame
Brick
aaaa Modular, steel frame
Name
Address
Phone(s) E-mail
Buyer's agent
Phone(s) E-mail
Seller's agent
Phone(s) E-mail
Lockbox/Other
Temperature Start Time
77° Fahrenheit 14:30
Notes/ Special Instructions
©1999-2009 MSI International, Inc. BestInspectors.Net™
Partly sunny
Mike DeWitt
Note: red boxes throughout this report indicating damage or items marked as needing repair may result in further damage or may present a health or safety hazard if not repaired.
very much like a stone foundation but this is purely asthetics in nature.
Eagle Eye Inspection LLCGeneral Information
2850 square feet
10-15 years 140 Wooddale
Vine Grove, Kentucky, 40175
Description / Type Address / Comments
home rests on concrete blocks, not a permanenet foundation. There is decorative stone around the bottom of the home which looks
Building Description
Date of Inspection: 9-26-2012
MLS discibes home as "triplewide home with approx.2816 sq ft.on permanent foundation". This is factually inaccurate, the mobile
I am proud of my service, and trust that you will be happy with the quality of my report. I have made every effort to provideyou with an accurate assessment of the condition of the property and its components and to alert you to any significant defects or adverse conditions. However, I may not have tested every outlet, and opened every window and door, or identified every problem. Also because my inspection is essentiallyvisual, latent defects could exist. I cannot see behind walls. Therefore, you should not regard my inspection as a guarantee or warranty. It is simply a report on the general condition of a property at a given point in time. As a homeowner you should expect problems to occur. Roofs will leak, basements may have water problems, and systems fail without warning. I cannot predict future events. For these reasons, you should keep a comprehensive insurance policy current. This report is only supplemental to a seller's disclosure.
Additional Building Description/ Comments
Client Information
General Conditions
Weather at time of inspection
DeWitt-Wooddale
Item ItemI NI NP R D Commentsaaaa Electric Public utility
aaaa Natural gas Public utility
aaaa Back-up gas Public utility
aaaa Propane Public utility
aaaa Water Public utility
aaaa Deep well Private Utility
aaaa Point well Private Utility
aaaa Generator Private Utility
aaaa Solar Private Utility
aaaa Septic Private Utility
©1999-2009 MSI International Best I nspectors . N et™
This has not been cleaned out in 4 yrs according to the disclosure, I would highly recommend having this cleaned out prior to moving in.
Photos and Additional Comments
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
Eagle Eye Inspection LLCUtilities
DeWitt-Wooddale
Item ConditionI NI NP R D Commentsaaaa Driveway and sidewalks
aaaa Front yard
aaaa Front porch and rear porch
aaaa Side yards
aaaa Back yard
aaaa Trees and shrubs
aaaa Grade
aaaa Drainage and sewers
©1999-2009 Best I nspectors . N et™
Photos and Additional Comments
Back yard grade leads toward the garage, there is evidence of flooding on the walls. The day of the inspection there were puddles in the garage. A swale should be dug to divert water.
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
Eagle Eye Inspection LLCGrounds
DeWitt-Wooddale
Item ConditionI NI NP R D Commentsaaaa aaaa aaaa Shingles
aaaa Underlayment
aaaa aaaa aaaa Roof deck
aaaa Flashing
aaaa Ventilation
aaaa Drip and rake edges
aaaa Gutters, downspouts
aaaa Age/ remaining life
Eagle Eye Inspection LLCRoof
The shingles installed are dimensional shingles. Th is is probably not the best choice for the 2/12 slo pe. There is a missing shingle and deterioration in the valleys. And the o verall installation appears shoddy, further evaluat ion by a professional roofer is highly recommended.
Roof deck is sagging is several areas and appears t hat it is only 1/2". The sattelite dish mounted to the roof should be removed and the holes repaired, these are known to cause leaks in the roofing system.
Covering and StructureI = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
At least TWO years remaining life can be reasonably expected based on normal life expectancy and condition at the time of the inspection.
Photos and Additional Comments
©1999-2009 MSI International Best I nspectors . N et™
DeWitt-Wooddale
Item ConditionI NI NP R D Commentsaaaa Siding
aaaa Fascia, soffits, trim
aaaa aaaa Doors
aaaa Windows
aaaa Lintels
aaaa Building wrap
aaaa Water faucets
aaaa Window wells, crawl space vents
©1999-2009 MSI International, Inc. Best I nspectors . N et™
Photos and Additional Comments
and ExteriorI = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
There is no screen in the front/storm door, this door does not latch correctly either.
Eagle Eye Inspection LLCStructure
DeWitt-Wooddale
ItemI NI NP R D Commentsaaaa aaaa Siding
aaaa aaaa Fascia, soffits, trim
aaaa Service Door(s)
aaaa Window(s)
aaaa Overhead door(s)
aaaa Safety eye(s)
aaaa aaaa Roof
aaaa aaaa aaaa Electrical
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
Eagle Eye Inspection LLCGarage
Photos and Additional Comments
On the garage there are a few pcs of siding that are not attached properly, and there is a gap in the jchannel near the shed that could allow moisture intrusions
There is no fascia cover and missing soffet on the rear of the garage. Some of the wood (peak of fascia) has been replaced by diriving screw through the shingles.
There is a dramatic difference between the 2 sections, Several shingles are missing on the decking and the ridge cap. Shingles are nearing the end of their life cycle and will need to be replaced soon.
There are several open j boxes in the garage which are safety hazards. The furnace has romex wire nutt ed to a cord, (not fused disconnect or switch). There is also no propane tank, the funa ce states that it is for NG, and there is no sedime nt trap installed.Further evaluation by a professional electrician/HVAC tech should be done b efore using this furnace.
©1999-2009 MSI International Best I nspectors . N et™
DeWitt-Wooddale
ItemI NI NP R D Commentsaaaa Foundation walls
aaaa Support beam
aaaa Floor joists
aaaa Beam pockets
aaaa Support posts
aaaa Rim joist(s)
aaaa Sump pump
aaaa Lintels
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
Eagle Eye Inspection LLCFoundation
Photos and Additional Comments
Unlike the MLS listing, there is no permanent foundation. The home rests on concrete blocks.
©1999-2009 MSI International Best I nspectors . N et™
DeWitt-Wooddale
ItemI NI NP R D Commentsaaaa Location
aaaa Clearance
aaaa Firebox
aaaa Flue damper
aaaa Flue
aaaa aaaa Gas supply
aaaa Heatilator
aaaa Hearth (firebox floor)
aaaa Doors
aaaa Mantle
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
©1999-2009 MSI International Best I nspectors . N et™
There is no source of gas for the use of the fireplace.
Photos and Additional Comments
Eagle Eye Inspection LLCFireplace
DeWitt-Wooddale
Item ItemI NI NP R D Commentsaaaa Master bedroom Doors and windows
aaaa Master bedroom Floor
aaaa Master bedroom Walls and ceiling
aaaa Master bedroom Closet
aaaa Master bedroom Electrical and lighting
aaaa aaaa Bedroom 2 Doors and windows
aaaa Bedroom 2 Floor
aaaa Bedroom 2 Walls and ceiling
aaaa Bedroom 2 Closet
aaaa Bedroom 2 Electrical and lighting
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
Eagle Eye Inspection LLCBedrooms
There is no return air duct or vent, this could lead to the room not being properly heated or cooled.
©1999-2009 MSI International Best I nspectors . N et™
Photos and Additional Comments
DeWitt-Wooddale
Item ItemI NI NP R D Commentsaaaa Bedroom 3 Doors and windows
aaaa Bedroom 3 Floor
aaaa Bedroom 3 Walls and ceiling
aaaa Bedroom 3 Closet
aaaa Bedroom 3 Electrical and lighting
aaaa Bedroom 4 Doors and windows
aaaa Bedroom 4 Floor
aaaa Bedroom 4 Walls and ceiling
aaaa Bedroom 4 Closet
aaaa Bedroom 4 Electrical and lighting
Photos and Additional Comments
Eagle Eye Inspection LLCBedrooms
©1999-2009 MSI International Best I nspectors . N et™
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
There is no return air duct or vent, this could lead to the room not being properly heated or cooled.
DeWitt-Wooddale
Item ItemI NI NP R D Commentsaaaa Interior living spaces Doors
aaaa Interior living spaces Windows
aaaa Interior living spaces Walls
aaaa Interior living spaces Ceilings
aaaa Interior living spaces Floors
aaaa Interior living spaces Electrical and lighting
aaaa Interior living spaces Attachments
aaaa Interior living spaces Cabinets and Trim
aaaa Interior living spaces Window treatments
aaaa Interior living spaces Locks
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
Eagle Eye Inspection LLCInterior
©1999-2009 MSI International Best I nspectors . N et™
Photos and Additional Comments
DeWitt-Wooddale
Item ItemI NI NP R D Commentsaaaa Master bathroom Toilet
aaaa Master bathroom Shower and bathtub
aaaa Master bathroom Plumbing
aaaa Master bathroom Electrical and lighting
aaaa Master bathroom Windows, walls, doors, floor, ceiling
aaaa Bathroom 2 Toilet
aaaa Bathroom 2 Shower and bathtub
aaaa Bathroom 2 Plumbing
aaaa Bathroom 2 Electrical and lighting
aaaa Bathroom 2 Windows, walls, doors, floor, ceiling
Photos and Additional Comments
Eagle Eye Inspection LLCBathrooms
©1999-2009 MSI International Best I nspectors . N et™
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
DeWitt-Wooddale
Item ItemI NI NP R D Commentsaaaa aaaa Kitchen Cabinets
aaaa Kitchen Counter tops and sink
aaaa Kitchen Plumbing
aaaa aaaa Kitchen Electrical and lighting
aaaa Kitchen Windows and doors
aaaa Kitchen Walls and ceiling
aaaa Kitchen Floor
aaaa aaaa Kitchen Stove/oven
aaaa Kitchen Dishwasher
aaaa Kitchen Refrigerator
There is an icemaker but no waterline run, This may indicate that there is a problem with the ice maker.
Photos and Additional Comments
One of the flourescent lighting fixtures in the kitchen is not working.
Eagle Eye Inspection LLCKitchen
©1999-2009 MSI International Best I nspectors . N et™
There are no racks in the oven, these could be costly and/or hard to find.
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
Many of the kitchen cabinet hinges are failing and will need to be replaced.
DeWitt-Wooddale
Item ItemI NI NP R D Comments
aaaa Utility room Cabinets
aaaa Utility room Counter tops and sink
aaaa Utility room Plumbing
aaaa Utility room Electrical and lighting
aaaa Utility room Windows and doors
aaaa Utility room Floor
aaaa Utility room Walls and ceiling
aaaa Utility room
aaaa Utility room
aaaa Utility room
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
Eagle Eye Inspection LLCUtility Room
©1999-2009 MSI International Best I nspectors . N et™
Photos and Additional Comments
DeWitt-Wooddale
ItemI NI NP R D Commentsaaaa Meter and Main shut-off valve(s)
aaaa Gas meter
aaaa Vents
aaaa aaaa aaaa Drainage
aaaa Distribution piping
aaaa Fittings
aaaa Valves
aaaa Whole house filter
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
Eagle Eye Inspection LLCPlumbing
Photos and Additional Comments
The drain leading from the masterbath is tied up wi th romex, some of which has come loose causing the drain line to sag in different areas. This could cause slow drainage or backups. A profes sional plumber should further evaluate this situati on.
©1999-2009 MSI International Best I nspectors . N et™
DeWitt-Wooddale
ItemI NI NP R D Commentsaaaa Water piping, valves, and fittings
aaaa Gas piping, valves, and fittings
aaaa Temperature/Pressure Relief Valve
aaaa Drain
aaaa Enclosure and pan
aaaa Controls
aaaa Age Unknown
aaaa Capacity 40 US Gallons
©1999-2009 MSI International Best I nspectors . N et™
Photos and Additional Comments
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
Eagle Eye Inspection LLCWater Heater
DeWitt-Wooddale
ItemI NI NP R D Comments
aaaa Gas piping, valves, and fittings
aaaa Heat exchanger
aaaa Blower
aaaa Controls
aaaa Humidifier
aaaa Flue
aaaa Age 2002
aaaa Output Capacity Unknown
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
Eagle Eye Inspection LLCHeating
Photos and Additional Comments
MLS also lists the heater as a heat pump, this is also inaccurate the home has an electric furnace and a split system central air conditioning system.
©1999-2009 MSI International Best I nspectors . N et™
DeWitt-Wooddale
ItemI NI NP R D Commentsaaaa Condenser coil/ housing
aaaa Evaporator coil
aaaa Fan
aaaa Controls
aaaa Refrigerant lines
aaaa Output Capacity 4 ton
aaaa Age 2002
aaaa General condition/ comments
Ac unit was working fine the day of the inspection
©1999-2009 MSI International Best I nspectors . N et™
Photos and Additional Comments
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
Eagle Eye Inspection LLCCooling
The AC unit is oversized for the home, this will lead to short cycling and will not properly reduce the humidity in the home.
DeWitt-Wooddale
ItemI NI NP R D Commentsaaaa Service entrance cable/conduit
aaaa Main panel
aaaa Main breaker/disconnect 200 amp
aaaa Made electrode - Water line
aaaa Made electrode - Ground rod
aaaa Branch circuits
aaaa GFCI breakers
aaaa AFCI breakers
I = Inspected NI = Not Inspected NP = Not Prese nt R = Repair Needed D = Defective
Eagle Eye Inspection LLCElectrical
Photos and Additional Comments
©1999-2009 MSI International Best I nspectors . N et™
Eagle Eye Inspection LLCSummaryMLS discibes home as "triplewide home with approx.2816 sq ft.on permanent foundation". This is factually
inaccurate, the mobile home rests on concrete blocks, not a permanenet foundation. There is decorative
stone around the bottom of the home which looks very much like a stone foundation but is merely skirting on
The shingles installed are dimensional shingles. This is probably not the best choice for the 2/12 slope. There
is a missing shingle and deterioration in the valleys. And the overall installation appears shoddy, further
evaluation by a professional roofer is highly recommended.
Roof deck is sagging is several areas and appears that it is only 1/2".
There is no screen in the front/storm door, this door does not latch correctly either.
There are several open j boxes in the garage which are safety hazards. The furnace has romex wire nutted to
a cord, (not fused disconnect or switch). There is also no propane tank, the funace states that it is for NG,
and there is no sediment trap installed.Further evaluation by a professional electrician/HVAC tech should be
There is a dramatic difference between the 2 roof sections on the garage, Several shingles are missing on the
decking and the ridge cap. Shingles are nearing the end of their life cycle and will need to be replaced soon.
On the garage there are a few pcs of siding that are not attached properly, and there is a gap in the jchannel
near the shed that could allow moisture intrusions
There is no fascia cover and missing soffet on the rear of the garage. Some of the wood (peak of fascia) has
been replaced by diriving screw through the shingles.
There is no source of gas for the use of the fireplace.
One of the flourescent lighting fixtures in the kitchen is not working.
There are no racks in the oven, these could be costly and/or hard to find.
There is an icemaker but no waterline run, This may indicate that there is a problem with the ice maker.
The drain leading from the masterbath is tied up with romex, some of which has come loose causing the
drain line to sag in different areas. This could cause slow drainage or backups. A professional plumber should
MLS also lists the heater as a heat pump, this is also inaccurate the home has an electric furnace and a split
system central air conditioning system.
The AC unit is oversized for the home, this will lead to short cycling and will not properly reduce the humidity
There is no return air duct or vent in the non master bedrooms, this could lead to the room not being
properly heated or cooled.
You are advised to seek two professional opinions and acquire estimates of repair as to any defects,
comments, improvements or recommendations mentioned in this report. I recommend that the professional
making any repairs inspect the property further, in order to discover and repair problems that were not
identified in the report. I recommend that all repairs, corrections, and cost estimates be completed and
documented prior to closing or purchasing the property. Feel free to hire other professionals to inspect the