![Page 1: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/1.jpg)
Muhammad Ali
Design of District Cooling Distribution System for higher
Availability, Reliability, Maintainability and Capability
![Page 2: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/2.jpg)
Contents
1. The Components of Effectiveness2. Availability3. Reliability4. Maintainability5. Capability
![Page 3: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/3.jpg)
A,R,M, and C
Maintainability
Capability
Availability
Reliability
Effectiveness
Effectiveness = Availability * Reliability * Maintainability * Capability
![Page 4: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/4.jpg)
Raw Data from Operating LogsWall Clock Hours
Start End Elapsed Time for Up Time
Elapsed Time for Down Time
0 708.2 708.2 708.2 711.7 3.5711.7 754.1 42.4 754.1 754.7 0.6754.7 1867.5 1112.8
1867.5 1887.4 19.91887.4 2336.8 449.4 2336.8 2348.9 12.12348.9 4447.2 2098.3 4447.2 4452 4.84452 4559.6 107.6
4559.6 4561.1 1.54561.1 5443.9 882.8 5443.9 5450.1 6.25450.1 5629.4 179.3 5629.4 5658.1 28.75658.1 7108.7 1450.6 7108.7 7116.5 7.87116.5 7375.2 258.7 7375.2 7384.9 9.77384.9 7952.3 567.4 7952.3 7967.5 15.27967.5 8315.3 347.8 8315.3 8317.8 2.5
Total 8205.3 112.5MTBM 683.8 MTTR 9.4
MTBM = mean uptime; this is the time between two maintenance periods
MTTR= mean downtime due to maintenance; this is the time when system is down for repair
![Page 5: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/5.jpg)
• Deals with the duration of up-time for operations and is a measure of how often the system is alive and well.
Availability
Up-time ≡ not downtimeA = A hardware*A software*A humans*A interfaces*A process
Availability
![Page 6: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/6.jpg)
98% availability for a continuous process says to expect • up-time of 0.98 * 8760 hours = 8584.8 hrs/year
• down time of 0.02 * 8760 = 175.2 hrs/year, as
Availability + unavailability = 1
Availability
![Page 7: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/7.jpg)
• Design looped network
Availability
LOOP
![Page 8: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/8.jpg)
• Design looped network
Availability
DN 1200
DN 800
DN 1
200
LOOP
![Page 9: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/9.jpg)
• Multiple Supply/Return at Plant
Availability
PLANT-1
PLANT-2
12
1 2
![Page 10: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/10.jpg)
• When high availability is of special importance, install standby “duty assist” pumps. Higher availability might be requested for commercial use than for residential buildings.
• One control valve for each PHE• Multiple heat exchangers
Availability
![Page 11: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/11.jpg)
• Deals with reducing the frequency of failures over a time interval and is a measure of the probability of failure-free operation during a given
interval, i.e., it is a measure of success for a failure free operation
Reliability
![Page 12: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/12.jpg)
R(t)
(Mean Time Between Failures) is the time between system failuresR = R utilities*R feed-plant*R processing*R packaging*R shipping
• For a given mission time, to achieve high reliability, a long MTBF is required.
Reliability
![Page 13: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/13.jpg)
• MTBF = 638.8 hours• Mission time = 1 year = 8760 hoursReliability = R(t)
• MTBF = 30 years• Mission time = 1 year Reliability = R(t)
1
2
=12.8
Reliability
![Page 14: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/14.jpg)
DCP Wadi
DCP West
DCP North
DCP Marina
Cooling plant
• Four main plants : Total Market > 500,000 TR
Reliability
Multiple production sites around the city connected to DC grid
![Page 15: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/15.jpg)
Reliability
• Pre-insulated • Welded end • Direct buried
Eliminating flanges – a potential source of leaks
![Page 16: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/16.jpg)
Reliability
![Page 17: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/17.jpg)
• Deals with duration of maintenance outages or how long it takes to achieve the maintenance actions compared to a datum.
M(t)
MTTR is Mean Time To RepairMaintainability issue is to achieve short repair times for keeping availability high
Maintainability
![Page 18: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/18.jpg)
• Maximum Repair Time 24 hrs
• Maintenance Goal 99.9%
0 5 10 15 200%
10%20%30%40%50%60%70%80%90%
100%
1 25%2 44%3 58%4 68%5 76%6 82%7 87%
8 90%9 92%
10 94%11 96%12 97%
13 98%14 98%15 99%16 99%17 99%18 99%19 100%20 100%21 100%22 100%23 100%
24 100%
Hours
Prob
abili
ty
MTTR 3.48 Hours
Maintainability
![Page 19: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/19.jpg)
• MTTR = mean down time due to maintenance = 9.4 hours
• System Maintainability= ?
If allowed Maximum Repair Time is 10 hoursM(t) = 65.5%
Probability of maintaining the system in allowed time of 10 hours is 65.5%
Maintainability
![Page 20: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/20.jpg)
Maintainability
Minimize need for maintenance; manufacture utilizing high quality material and components
• Install leak detection system• Secure Joints: Do not let water/moisture enter
the HDPE Jacket• Design pipe, works and components for high
life-time; 40 years• 10 years warranty
![Page 21: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/21.jpg)
Maintainability Be Careful with Bends, Fittings and
Valves
![Page 22: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/22.jpg)
MaintainabilityCondensation
problems: LDS to monitor, detect and
locate faults
Building entry sealin concrete walls
and floors
![Page 23: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/23.jpg)
• Deals with productive output compared to inherent productive output which is a measure of how well the production activity is performed compared to the datum.
Capability = Efficiency * Utilization
Efficiency = Productive Work output/ work inputUtilization = Time spent on productive efforts / total time consumed
Capability
![Page 24: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/24.jpg)
• For example; System efficiency 80%Utilization 82.19% (300/365 days)
Capability = 0.8 * 0.8219 = 65.75%
Capability
![Page 25: Design of District Cooling Distribution System for Higher Availability, Reliability, Maintainability and Capability](https://reader038.fdocuments.in/reader038/viewer/2022102623/5885e18d1a28ab906d8b6225/html5/thumbnails/25.jpg)
Remember A,R,M, and C
Maintainability
Capability
Availability
Reliability
Effectiveness
Effectiveness = Availability * Reliability * Maintainability * Capability