Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of...

50
1 Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause: “Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service” 1 A Member of the Group Design Design Improvement by Diagnostics Improvement by Diagnostics of of Transformers Transformers still in Operation still in Operation and of and of Apparatuses taken Apparatuses taken out of Service out of Service Christoph Krause Christoph Krause Weidmann Weidmann Transformerboard Transformerboard Systems, Systems, Switzerland Switzerland Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006 "New Diagnostic Concepts for Better Asset Management"

description

Improvement of transformer designs through diagnosis of transformer in service and transformers out of service

Transcript of Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of...

Page 1: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

1

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

1A Member of the Group

DesignDesign Improvement by DiagnosticsImprovement by Diagnostics ofofTransformersTransformers still in Operationstill in Operationand ofand of Apparatuses takenApparatuses taken out of Serviceout of Service

Christoph KrauseChristoph Krause

Weidmann Weidmann TransformerboardTransformerboardSystems, Systems, SwitzerlandSwitzerland

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006"New Diagnostic Concepts for Better Asset Management"

Page 2: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

2

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Contents1. Power rating enhancement by elimination of the limitation set by induced tank

heating through a complex, three-dimensional electromagnetic-thermal study of a transformer still in operation, and subsequent design adaptation.

2. In-depth diagnostics of aged transformers by forensic investigations after having been taken out of service before being scrapped

provides accurate information about the cooling efficiency of the apparatus.

enables better assessment of the status of similar transformers in the grid

Page 3: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

3

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Contents1. Power rating enhancement by elimination of the limitation set by induced tank

heating through a complex, three-dimensional electromagnetic-thermal study of a transformer still in operation, and subsequent design adaptation.

2. In-depth diagnostics of aged transformers by forensic investigations after having been taken out of service before being scrapped

provides accurate information about the cooling efficiency of the apparatus.

enables better assessment of the status of similar transformers in the grid

Page 4: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

4

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

3D case study: Electromagnetic re-design to prevent tank overheating

185 MVA 1ph GSU Transformer

Target:Upgrade MVA-performance by > 20% of name plate rating

Problem:Tank flange hot spot = 96°C at 190 MVAThe enhanced oil cooling could not cope with the local tank hot spot

Page 5: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

5

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Thermal scan at 190 MVA

Page 6: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

6

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Inspection on site

Shorting plate disassembled

185 MVA 1ph GSU Transformer

Bushing

No MagSteel Cover

¾”

Page 7: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

7

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Page 8: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

8

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Flux Tangential Boundary Condition

Plane of symmetry

Technical challenges:• Aluminum shields inside the tank• Mild steel tank wall• Non-magnetic steel cover parts• 3-dimensional modeling

Modeling the zone of interest

Page 9: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

9

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Creating the FEM mesh: 269‘000 (number of tetraedra)

Page 10: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

10

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

3-D calculation of losses

Infrared scan

Page 11: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

11

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Original Design

Improved Design

Acting together with the manufacturer of the current bus enclosures, a different

design was developed with significantly lower losses in the critical area of the tank

Page 12: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

12

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Creating the FEM mesh

Detail view

659‘000 (number of tetraedra)

The mesh was generated using only standard mesh controls, i.e. no special methods were needed.

Page 13: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

13

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Original ModelModified Model

Design

Improvements

Losses in the zone of interest

scale: from 0 to 2.5x105 W/m3

Loss distribution

Page 14: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

14

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

3D case study: Electromagnetic re-design to prevent tank overheating

at 190 MVA, tank flange hot spot = 96°C

at 228 MVA, tank flange hot spot = 72°C Re-Design

Original Design

Page 15: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

15

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

3D case study: Electromagnetic re-design to prevent tank overheating

Summary:Localized tank cover flange heating detected by infrared scanDiagnosis technical challenge: aluminum shields inside the tank,mild steel tank wall, non-magnetic steel cover parts – 3D modeling The simulation provided excellent match with the measured tank temperaturesThe solution consisted in moving the crossover shorting plate to shift flux induced currents from the tank cover flange to themiddle of the tank coverRedesigned busbar enclosure permits transformer upgrade from 185 MVA to 228 MVA.

Page 16: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

16

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Other types of simulations / calculations being performed• Losses (with/without harmonic currents) and impedance of:

• Windings (including foil windings and complex circuit arrangements)• 3D bus bars arrangements• Reactors (with/without core, with/without magnetic shielding)

• Current distribution in high current windings as occur in industrial applications (arc furnace AC & DC, rectifiers)

• (3D): Losses in tanks, electromagnetic shields and conductive structures• Temperature distribution on tanks (3D)• Short circuit: computation of (transient) currents and peak forces on windings• Switch-on: computation of transient currents forces on primary winding• Electric field studies

Page 17: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

17

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Today, we are performing magneto-thermal calculations regularly – local overheating is a problem that occurs frequently.Here another example of such calculation of a GSU transformer. The results are shown on left hand side and the thermal scan is shown on right hand side.

Page 18: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

18

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Reference listABB Cordoba, Spain ABB Industrial Transformer Legnano, Italy and Bad Honnef, Germany ABB Rectifiers, Turgi, SwitzerlandABB Research Center, Baden, SwitzerlandABB Varennes, CanadaAREVA T&D, Stafford, UKAREVA, Dubai, U.A. EmiratesASA Trafobau GmbH, Bad Arolsen, GermanyCrompton Greaves Ltd, Mumbai, IndiaDUBAL, Dubai, U.A. Emirates Dynegy, Houston, TX, USAFRIEM Rectifiers, Segrate, ItalyFrance Transfo, Metz, FranceMatelec Group, LebanonPioneer Transformers Ltd, CanadaPII GE, UKPortland GE Company, Oregon, USASTEM Transformers, Trento, ItalyTamini Group, Melegnano, ItalyTranspower, New ZealandWilson Transformer Company, Victoria, Australia

(some of our customers)

Page 19: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

19

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Contents1. Power rating enhancement by elimination of the limitation set by induced tank

heating through a complex, three-dimensional electromagnetic-thermal study of a transformer still in operation, and subsequent design adaptation.

2. In-depth diagnostics of aged transformers by forensic investigations after having been taken out of service before being scrapped

provides accurate information about the cooling efficiency of the apparatus.

enables better assessment of the status of similar transformers in the grid

Page 20: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

20

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Motivation for in-depth diagnostics of aged transformers by forensic investigations:

Compare real aging with laboratory accelerated aging experiments(DP, water and acid content, tensile and bending strength, dissipation factor tan δ, resistivity)

Verify the cooling performance of the transformer active part

Assess the initial DP values of different solid insulation components (when the transformer was put in service)

Identify the location of the true hot spot(s)

Detect unintended, hot spot areas / design flaws

Appraise of the aging condition of similar transformers still in operation

Page 21: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

21

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Equipment and toolsWork clothesWork safety

Page 22: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

22

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Equipment and toolsKnivesScissors for cutting paper samples

Page 23: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

23

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Equipment and toolsCuttingSawing

Page 24: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

24

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Equipment and toolsPincers of any kind

Page 25: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

25

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Equipment and toolsPlastic bags Paper tagsPens (oil and water resistant)

Page 26: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

26

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Equipment and toolsOil container Plastic foilBoxes and crates

Page 27: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

27

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Determination of the aging status by measuring the DP (Degree of Polymerization) of cellulose samples

In operation, the cellulose degrades continuously with timeThis degradation alters (shortens) the cellulose moleculesThe DP is a good measure of the aging status, because it is proportional to the average length of the cellulose moleculesThe DP of new Kraft pressboard and -paper is about 1200, that of completely aged (end of life) about 200.

time (years)

DP (t)500

1000

DP

Page 28: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

28

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Transformer AVoltage: 110 / 63 kVRating: 31.5 MVAPhases: 3Cooling: ONAFManufacturer: Siemens Schuckert, Berlin, GermanyOperating utility: E.ON, GermanyIn service: 1955 - 2003

Transformer BVoltage: 220 / 110 kVRating: 140 MVAPhases: 3Cooling: OFAFManufacturer: TRO, Berlin, GermanyOperating utility: Vattenfall, GermanyIn service: 1974 - 2004

Transformer CVoltage: 380 / 220 kVRating: 600 MVA / 3Phases: 1Cooling: OFAFManufacturer: MFO, Zurich, SwitzerlandOperating utility: NOK, SwitzerlandIn service: 1962 - 2005

Measurements of the aging status of cellulosic insulation samples taken from three power transformers

region of sample taking (top to bottom along axial height)

one phase

Page 29: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

29

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Transformer AVoltage: 110 / 63 kVRating: 31.5 MVAPhases: 3Cooling: ONAFManufacturer: Siemens Schuckert, Berlin,

GermanyOperating utility: E.ON, GermanyIn service: 1955 - 2003

Page 30: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

30

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Page 31: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

31

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

401-500

601-700701-800801-900

Windings

< 200201-300301-400

LV HV Tap

501-600

> 900

Cor

e

0

200

400

600

800

1000

1200

Deg

ree

of P

olym

eriz

atio

n

bottommiddletop

LV HV Tap

Transformer AVoltage: 110 / 63 kVRating: 31.5 MVAPhases: 3Cooling: ONAFManufacturer: Siemens Schuckert, Berlin,

GermanyOperating utility: E.ON, GermanyIn service: 1955 - 2003

Page 32: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

32

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Transformer BVoltage: 220 / 110 kVRating: 140 MVAPhases: 3Cooling: OFAFManufacturer: TRO, Berlin, GermanyOperating utility: Vattenfall, GermanyIn service: 1974 - 2004

Page 33: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

33

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Page 34: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

34

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Cor

e

DPTert LV HV Tap

Windings

> 900

501-600601-700701-800801-900

< 200201-300301-400

401-500

0

200

400

600

800

1000

1200

Deg

ree

of P

olym

eriz

atio

n

bottommiddletop

LV HV Tap

Transformer BVoltage: 220 / 110 kVRating: 140 MVAPhases: 3Cooling: OFAFManufacturer: TRO, Berlin, GermanyOperating utility: Vattenfall, GermanyIn service: 1974 - 2004

Page 35: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

35

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Transformer CVoltage: 380 / 220 kVRating: 600 MVA / 3Phases: 1Cooling: OFAFManufacturer: MFO, Zurich, SwitzerlandOperating utility: NOK, SwitzerlandIn service: 1962 - 2005

Page 36: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

36

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Page 37: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

37

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

0

200

400

600

800

1000

1200

Deg

ree

of P

olym

eriz

atio

n

bottommiddletop

LV HVTertiary

> 900801-900

Windings

701-800601-700501-600401-500301-400201-300< 200

DP

Tertiary LV HV

Cor

e

laminated strips

cylindersTransformer CVoltage: 380 / 220 kVRating: 600 MVA / 3Phases: 1Cooling: OFAFManufacturer: MFO, Zurich, SwitzerlandOperating utility: NOK, SwitzerlandIn service: 1962 - 2005

Page 38: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

38

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

02468

10121416

0 250 500 750 1000Degree of Polymerization

Freq

uenc

y B C

A

Page 39: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

39

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

0

200

400

600

800

1000

1200

0 10 20 30 40 50

Aging time (years)

Deg

ree

of p

olym

eriz

atio

n

90°C

80°C

70°C60°C

100°C110°C

0

200

400

600

800

1000

1200

0 10 20 30 40 50

Aging time (years)

Deg

ree

of P

olym

eriz

atio

n

90°C 80°C70°C

60°C

50°C

40°C

Influence of water on the ageing rate

teADP

1)t(DP

1 TRE

0

A

⋅⋅=− ⋅−

Aging kinetic equation:Due to the moisture increase during transformer life, the determination of the operational temperature, at different locations in the transformer, is not precise.

2% water content <0.5% water content

Page 40: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

40

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

SummaryThe DP profiles matched the expectation: lower DP-values at the winding top and around the conductors, higher values at the bottom and of the inter-winding insulation.

The insulation of transformers A (50 years) and C (40 years) was still in relatively good condition.

The youngest transformer B (30 years) had reached its end of life - continuing operation would have been associated with catastrophic failure hazard.

• The moisture content was high, perhaps right from the beginning?• The DP of paper at the beginning of life time was lower, due to overheating

during drying? • The cooling design was insufficient?• The transformer was operated beyond name plate?

Page 41: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

41

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

RemarksIt takes relatively little effort to collect solid insulation samples, when power transformers are scrapped. The findings may be of high value.

For a comprehensive aging replica, it is necessary to take samples systematically throughout the transformer.

With the water content information of the samples, it is possible to assess the operating insulation temperatures with better precision. Yet, measuring the moisture of the samples requires quick handling on-site, due to inevitable water absorption when exposed to the (humid) air.

Page 42: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

42

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Preconditions for valuable forensic analysis of power transformersAcceptance of project and orientation of the transformer scrapping staff, surplus time is about 1 dayTransformer drawings for determination of sampling; transformer design & calculation documents

Page 43: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

43

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Preconditions for valuable forensic analysis of power transformersAcceptance of project and orientation of the transformer scrapping staff, surplus time is about 1 dayTransformer drawings for determination of sampling; transformer design & calculation documentsPlan (sequence of dismantling): winding, top to bottom, radial orientation, inter-winding insulation, different phases

Page 44: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

44

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Preconditions for valuable forensic analysis of power transformersAcceptance of project and orientation of the transformer scrapping staff, surplus time is about 1 dayTransformer drawings for determination of sampling; transformer design & calculation documentsPlan (sequence of dismantling): winding, top to bottom, radial orientation, inter-winding insulation, different phasesAssigned responsibilities on site: who is doing what Experts shall take the samples

Page 45: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

45

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Preconditions for valuable forensic analysis of power transformersAcceptance of project and orientation of the transformer scrapping staff, surplus time is about 1 dayTransformer drawings for determination of sampling; transformer design & calculation documentsPlan (sequence of dismantling): winding, top to bottom, radial orientation, inter-winding insulation, different phasesAssigned responsibilities on site: who is doing what Experts shall take the samples(local) Work safety instruction and strict adherence to

Page 46: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

46

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Preconditions for valuable forensic analysis of power transformersAcceptance of project and orientation of the transformer scrapping staff, surplus time is about 1 dayTransformer drawings for determination of sampling; transformer design & calculation documentsPlan (sequence of dismantling): winding, top to bottom, radial orientation, inter-winding insulation, different phasesAssigned responsibilities on site: who is doing what Experts shall take the samples(local) Work safety instruction and strict adherence toTime (patience). Envision unforeseen difficulties and effects. Teamwork!

Page 47: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

47

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Preconditions for valuable forensic analysis of power transformersAcceptance of project and orientation of the transformer scrapping staff, surplus time is about 1 dayTransformer drawings for determination of sampling; transformer design & calculation documentsPlan (sequence of dismantling): winding, top to bottom, radial orientation, inter-winding insulation, different phasesAssigned responsibilities on site: who is doing what Experts shall take the samples(local) Work safety instruction and strict adherence toTime (patience). Envision unforeseen difficulties and effects. Teamwork!Transformer operation records: temperatures, oil moisture, maintenance (oil reclaiming etc.), power flowCo-operate with transformer manufacturer - difficulty: old apparatusesRespect (local) working hours (unions!)

Page 48: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

48

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Preconditions for valuable forensic analysis of power transformersAcceptance of project and orientation of the transformer scrapping staff, surplus time is about 1 dayTransformer drawings for determination of sampling; transformer design & calculation documentsPlan (sequence of dismantling): winding, top to bottom, radial orientation, inter-winding insulation, different phasesAssigned responsibilities on site: who is doing what Experts shall take the samples(local) Work safety instruction and strict adherence toTime (patience). Envision unforeseen difficulties and effects. Teamwork!Transformer operation records: temperatures, oil moisture, maintenance (oil reclaiming etc.), power flowCo-operate with transformer manufacturer - difficulty: old apparatusesRespect (local) working hours (unions!)

Page 49: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

49

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”

Page 50: Design Improvement by Diagnostics of Transformers Still in Operation and of Apparatus Taken Out of Service

50

Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006; Christoph Krause:“Design improvement by diagnostics of transformers still in operation and of apparatuses taken out of service”