DESIGN GUIDELINES Division 26 - ELECTRICAL

80
DESIGN GUIDELINES Division 26 - ELECTRICAL Release 1.0 April, 2011 Released by: Cleveland Clinic Facilities and Construction 9500 Euclid Ave. Cleveland OH 44195 All information within this Document is considered CONFIDENTIAL and PROPRIETARY. By receipt and use of this Document, the recipient agrees not to divulge any of the information herein and attached hereto to persons other than those within the recipients’ organization that have specific need to know for the purposes of reviewing and referencing this information. Recipient also agrees not to use this information in any manner detrimental to the interests of Cleveland Clinic.

Transcript of DESIGN GUIDELINES Division 26 - ELECTRICAL

Page 1: DESIGN GUIDELINES Division 26 - ELECTRICAL

DESIGN GUIDELINES

Division 26 - ELECTRICAL

Release 1.0 April, 2011 Released by: Cleveland Clinic Facilities and Construction 9500 Euclid Ave. Cleveland OH 44195

All information within this Document is considered CONFIDENTIAL and PROPRIETARY. By receipt and use of this Document, the recipient agrees not to divulge any of the information herein and attached hereto to persons other than those within the recipients’ organization that have specific need to know for the purposes of reviewing and referencing this information. Recipient also agrees not to use this information in any manner detrimental to the interests of Cleveland Clinic.

Page 2: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Guidelines Copyright © 2011

By the Cleveland Clinic These Specifications, or parts thereof, may not be reproduced in any form without the permission of the Cleveland Clinic.

Page 3: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic

Cleveland Clinic Design Guidelines: Division 26 - Electrical

The following pages contain guidelines for the design and construction of new and renovated facilities at all domestic Cleveland Clinic locations. They shall be used by A/E firms in the preparation of drawings and specifications for construction of facilities. The general purpose of each Design Guideline is to provide minimal criteria for design, materials, and equipment at Cleveland Clinic facilities regarding Codes and FM Global compliance, warranty, approved products, execution and uniformity. The Guidelines are not Contract Specifications, but used to prepare more detailed, project specific specifications. The Guidelines are intended to be used to address system design aspects of equipment that Cleveland Clinic desires to standardize among facilities, and identify prohibited materials and construction practices. The use of these Guidelines is mandatory for all design or maintenance projects. Deviations are discouraged. If project conditions arise which require a deviation, it shall be thoroughly documented by the user and submitted to Cleveland Clinic for review and approval using the Design Standards Revision Request document. Additionally, all Cleveland Clinic staff, architects, engineers, and contractors are encouraged to participate in the ongoing development of these guidelines by communicating any suggestions by use of the Revision Request document.

*****

Page 4: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic DESIGN GUIDELINES: DIVISION 26 – ELECTRICAL

1. MEDIUM VOLTAGE POWER CABLES (up to 35kV) 2. LOW VOLTAGE POWER CABLES 3. GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 4. RACEWAYS, BOXES AND ENCLOSURES FOR ELECTRICAL SYSTEMS 5. OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDIES 6. ELECTRICAL POWER MONITORING AND CONTROL 7. LIGHTING CONTROL DEVICES 8. NETWORK LIGHTING CONTROLS 9. SECONDARY UNIT SUBSTATIONS 10. MEDIUM VOLTAGE POWER TRANSFORMERS 11. MEDIUM VOLTAGE SWITCHGEAR 12. LOW VOLTAGE DRY TYPE TRANSFORMERS 13. LOW VOLTAGE SWITCHGEAR 14. PARALLELING LOW VOLTAGE SWITCHGEAR 15. LOW VOLTAGE SWITCHBOARDS 16. BRANCH CIRCUIT AND DISTRIBUTION PANELBOARDS 17. MOTOR CONTROL CENTERS AND MOTOR CONTROLS 18. ENCLOSED BUS ASSEMBLIES 19. WIRING DEVICES 20. LOW VOLTAGE FUSES 21. ENCLOSED SWITCHES AND CIRCUIT BREAKERS 22. VARIABLE FREQUENCY CONTROLLERS 23. ENGINE GENERATOR SYSTEMS 24. CENTRAL BATTERY EQUIPMENT 25. UNINTERRUPTIBLE POWER SUPPLY (UPS) 26. TRANSFER SWITCHES 27. LIGHTNING PROTECTION FOR STRUCTURES 28. SURGE PROTECTION DEVICES FOR LOW VOLTAGE ELECTRICAL

POWER CIRCUITS 29. INTERIOR LIGHTING 30. EXTERIOR LIGHTING

** End of List **

Page 5: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES MEDIUM VOLTAGE POWER CABLES

PART I - GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for Medium Voltage (5 to 35 kV) Cables and accessories. Refer to Specification Section 260513 for detailed requirements.

1.2 MEDIUM VOLTAGE CABLE REQUIREMENTS

A. Includes the following:

1. Cable. 2. Splices. 3. Terminations. 4. Separable connectors.

1.3 MEDIUM VOLTAGE CABLES

A. Voltage Rating: 1. 5000 V for 4160 V distribution systems. 2. 15000 V for 11.4, 13.2, 13.8 kV distribution systems. 3. 15001 to 35000 V: per project requirements.

B. Cables shall be UL type MV-105 and consist of compact stranded Copper conductors with 133 percent level Ethylene Propylene Rubber insulation. Strand and insulation screen shall be black extruded semi-conducting thermoset. Shielding shall be helical wound copper tape or six copper drain wires and outer jacket of Chlorinated Polyethylene (CPE).

1.4 SPLICE KITS

A. Specify heat shrinkable or modular types that comply with IEEE 404.

1.5 TERMINATIONS

A. Specify long barrel, 2 – hole, compression type termination lugs.

B. Specify Class 1 or 2, heat shrinkable or modular type.

1.6 SEPARABLE CONNECTORS

A. Dead-Break cable terminators: Elbow type, current rating and voltage class per project requirements.

APRIL 2011 Page - 1

Page 6: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES MEDIUM VOLTAGE POWER CABLES

APRIL 2011 Page - 2

B. Load-Break cable terminators: Elbow type, current rating and voltage class per project requirements.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification 260513.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with current edition in effect of the National Electrical Code.

B. Cable identification requirements: refer to Specification Section 260553.

C. Testing and acceptance requirements: refer to Specification Section 260513.

*****

Page 7: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES MEDIUM VOLTAGE POWER TRANSFORMERS

PART I - GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for medium voltage transformers for sizes from 75 – 5000 kVA, with primary from 2400 V to 25000 V. Refer to Specification Section 261200 for detailed requirements.

B. Coordinate with Specification Section 261116 for transformers provided as part of a unit substation.

1.2 TRANSFORMER REQUIREMENTS

A. All transformers shall be UL listed and FM labeled.

B. Transformer includes:

1. Primary switching. 2. Transformers. 3. Accessories.

C. Provide pad-mount type transformers for stand alone applications.

D. Provide distribution style transformers when part of an indoor/outdoor unit substation application.

E. Size transformers for anticipated peak load plus fifteen percent spare capacity for future growth.

1.3 PRIMARY SWITCHING

A. 5/15/27 kV class, metal enclosed, fused interrupter switchgear when part of a unit substation assembly.

B. Pad-mount type: Outdoor, non-walk-in, free-standing, 5/15/27 kV class, metal enclosed, fused interrupter switchgear.

1.4 TRANSFORMERS

A. Liquid filled type, silicon fluid, meeting FM Global flammability requirements.

B. Distribution type transformers shall be self cooled and specified with cooling fans and controls.

C. Pad-mounted transformers shall be self cooled, compartmental type with barriered high and low voltage sections and individual full height doors.

D. All transformers shall comply with the latest DOE energy efficiency requirements.

APRIL 2011 Page - 1

Page 8: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES MEDIUM VOLTAGE POWER TRANSFORMERS

APRIL 2011 Page - 2

E. All windings shall be Copper.

F. NEMA standard accessories.

G. High voltage, delta primary, voltage depending on project requirements.

H. Low voltage, wye secondary, 480/277 V or 208/120 V, depending on project requirements.

1.5 SURGE PROTECTIVE DEVICES

A. Provide a listed surge/lightning arrestor device for each phase on transformer primary for pad-mount types.

1.6 METERING and COMMUNICATIONS

A. Communications link shall be via Cleveland Clinic’s energy management software. See section 260913 “Electrical Power Monitoring and Control”.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 261200.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with current edition in effect of the National Electrical Code and all applicable federal, state and local requirements, referenced standards and conform to codes and ordinances of Authorities Having Jurisdiction.

B. All indoor transformers shall be installed on four inch high concrete housekeeping pads, typically in a locked, dedicated, and ventilated electrical room complying with FM Global requirements.

C. All outdoor transformers shall be mounted on concrete pads designed by Structural Engineer.

D. All equipment shall be grounded in accordance with Specification Section 260526.

E. Testing and acceptance requirements: refer to Specification Section 261200.

*****

Page 9: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES MEDIUM VOLTAGE SWITCHGEAR

PART I - GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for Medium Voltage Switchgear Assemblies which shall typically be the primary service entrance equipment. Refer to Specification Section 261300 for detailed requirements.

1.2 MEDIUM VOLTAGE SWITCHGEAR (MVS) REQUIREMENTS

A. MVS includes:

1. Switchgear assembly. 2. Battery systems. 3. Surge Protective Devices. 4. Metering and Communications. 5. Primary disconnect devices. 6. Main and Tie devices. 7. Feeder devices.

B. The Primary Source of normal electrical power shall be obtained from the local public utility, usually at 11.4 kV, 13.2 kV, or other medium distribution voltage.

1. The Utility’s representative shall be invited to all utility coordination meetings.

C. Provide double-ended switchgear with two main and one tie devices where two distinct Utility feeds are available. Each utility feed shall be capable of carrying the entire facility load.

D. Provide single-ended switchgear where only a single Utility feed is available.

E. Size substations for anticipated peak load plus fifteen percent spare capacity for future growth.

F. Comply with the applicable sections of the following Codes and Standards: 1. NEC 70. 2. NFPA 99. 3. FM Global.

1.3 MEDIUM VOLTAGE SWITCHGEAR

A. (5/15/27/38) kV class, metal enclosed, fused, load interrupter switchgear shall be specified for primary overcurrent protection and switching of unit substation transformers.

B. (5/15/27/38) kV class, metal-clad, draw-out, vacuum circuit breakers shall be specified for distribution of high voltage service from the Utility. 1. The switchgear shall consist of a factory assembled line up of breakers and auxiliary

compartments to form a self supporting rigid structure. 2. Typical arrangement shall be Main-Tie-Main with Feeder devices. 3. Bussing shall be silver plated copper, fully insulated and enclosed.

APRIL 2011 Page - 1

Page 10: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES MEDIUM VOLTAGE SWITCHGEAR

4. Outdoor enclosures shall be non-walk in (aisle-less), rain-tight type.

D. Provide separate cubicles for Utility metering equipment. Obtain the Utility's approval of the cubicle arrangements prior to fabrication of the switchgear.

E. Provide at least one fully provisioned spare cubicle in the line up to allow for future growth.

1.4 BATTERY SYSTEMS

A. Batteries shall be high discharge rate type nickel-cadmium batteries. Battery voltage shall be 125 VDC nominal.

B. Battery chargers shall be solid state, full wave rectifier type utilizing silicon controlled rectifiers as the power-control elements.

1.5 SURGE PROTECTIVE DEVICES

A. Provide UL listed distribution/intermediate/station class surge arrestors connected to the incoming service leads. Arrestors shall be integrally mounted in the switchgear enclosure.

1.6 METERING and COMMUNICATIONS

A. Provide manufacturer’s standard digital multi-function metering on mains/feeders.

B. Communications link shall be via Cleveland Clinic’s energy management software. See Section 260913 “Electrical Power Metering and Control”.

C. The manufacturer defined communications bus shall be extended from main, tie and feeder breaker relays to an externally mounted hinged pull box containing a manufacturer provided gateway for connection to Cleveland Clinic’s monitoring system via Ethernet. System shall be configured for monitoring only.

D. Utility Metering Compartments: Coordinate with serving Utility requirements for Utility furnished and installed metering.

1.7 MAIN and TIE DEVICES

A. All main and tie devices shall be drawout power vacuum circuit breakers, rated to safely interrupt the available fault current.

B. Provide key interlocking between main and tie devices so that all three devices cannot be closed at the same time. Throw-over will be done manually.

C. Protective Devices - Protective relays for circuit breakers shall be GE/MULTILIN relays or equal by Cutler-Hammer as indicated below and shall be fully electronic RMS sensing type and provide the following functions: 1. Time and ground (51, 51G). 2. Instantaneous and ground (50, 50G).

APRIL 2011 Page - 2

Page 11: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES MEDIUM VOLTAGE SWITCHGEAR

APRIL 2011 Page - 3

3. Lockout (86).

1.8 FEEDER DEVICES

A. All feeder devices shall be drawout vacuum circuit breakers, rated to safely interrupt the available fault current.

B. Protective Devices - Protective relays for circuit breakers shall be GE/MULTILIN relays or equal by Cutler-Hammer as indicated below and shall be fully electronic RMS sensing type and provide the following functions: 1. Time and ground (51, 51G). 2. Instantaneous and ground (50, 50G).

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 261300.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with current edition in effect of the National Electrical Code, FM Global requirements, all applicable federal, state and local requirements, referenced standards, and conform to codes and ordinances of Authorities Having Jurisdiction.

B. All Switchgear Assemblies installed indoors shall be located in locked, dedicated rooms, ensure adequate ventilation and cooling. Allow for front and rear access. Provide four inch high concrete housekeeping pads for equipment.

C. Outdoor installations shall be reviewed with the Cleveland Clinic Office of Facilities. All Switchgear Assemblies installed outdoors shall be located above the 100 year floodplain and mounted on concrete pads designed by Structural Engineer.

D. All equipment shall be grounded in accordance with Specification Section 260526.

E. Testing and acceptance requirements: refer to Specification Section 261300.

*****

Page 12: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LOW VOLTAGE DRY TYPE TRANSFORMERS

PART I - GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for dry type, air cooled distribution transformers rated 600V and less, with capacities up to 1000 kVA. Refer to Specification Section 262200 for detailed requirements.

1.2 LOW VOLTAGE TRANSFORMER REQUIREMENTS

A. Capacity: Transformer size shall be based on known loads, with 15% capacity for future load increase.

B. Coils: Coil material shall be copper.

C. Transformers shall comply with NEMA ST 20 UL 1561.

D. Enclosures shall be suitable for the intended location.

E. Taps: specify with 2 above and 2 below for transformers over 25 kVA.

F. Specified Insulation Class: 220 deg C, UL-component-recognized insulation system with a maximum of 115 deg C rises above 40 deg C ambient temperature.

G. Specify Energy Efficient Transformers. Units rated 15 kVA and larger shall comply with NEMA TP 1, Class 1 efficiency levels.

H. Provide K – rated transformers for non-linear loads as follows: Transformers serving discharge lighting loads shall have a K-4 rating, K-13 for UPS and telecommunications equipment, and K-20 for Data Centers, VFC’s, and receptacles in critical care areas.

I. For shielded transformers each winding shall have an independent, single, full-width copper electrostatic shield.

J. Specify transformers with reduced sound levels if transformer is to be installed in a location where audible sound may be objectionable.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 262200.

APRIL 2011 Page - 1

Page 13: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LOW VOLTAGE DRY TYPE TRANSFORMERS

APRIL 2011 Page - 2

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with current edition in effect of the National Electrical Code.

B. Transformers shall be located in a locked room dedicated for electrical equipment. Ensure adequate clearance around all equipment as well as ventilation. Coordinate the fire rating requirements of the room with the NEC and the Fire Protection Engineer. Locate transformers in areas where audible sound is not offensive to building inhabitants.

C. All floor-mounted transformers shall be installed on four inch high concrete housekeeping pads. Transformers rated 45 kVA or less may be wall mounted.

D. Ground equipment according to Division 26 Section "Grounding and Bonding for Electrical Systems."

E. Testing and acceptance requirements: refer to Specification Section 262200.

*****

Page 14: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR

PART I - GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for Low Voltage Switchgear. Refer to Specification Section 262300 for detailed requirements.

1.2 LOW VOLTAGE SWITCHGEAR (LVS) REQUIREMENTS

A. LVS includes:

1. Switchgear. 2. Surge Protective Devices. 3. Metering and Communications. 4. Main and Tie devices. 5. Distribution devices.

B. Provide double-ended switchgear with two main and one tie where two distinct feeds are available.

C. Provide single-ended switchgear where only a single feed is available.

D. Switchgear shall be UL Service Entrance labeled where necessary.

E. Size switchgear for anticipated peak load plus twenty-five percent spare capacity for future growth.

F. Comply with the applicable requirements of FM Global.

G. Switchgear shall comply with UL 1558.

1.3 LOW VOLTAGE SWITCHGEAR

A. 600V class, draw-out, 100% rated for continuous duty circuit breakers.

B. The switchgear shall consist of a factory assembled line up of breaker/switch and auxiliary compartments and instrumentation to form a self supporting rigid structure.

1. Bussing shall be silver plated copper, fully insulated and enclosed.

2. Neutral bussing shall be 100% rated.

3. An un-insulated ground bus shall extend the length of the switchgear.

D. Provide separate cubicles for metering equipment.

E. Provide at least one fully provisioned spare cubicle in the line up to allow for future growth. APRIL 2011 Page - 1

Page 15: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR

F. Minimum feeder breaker frame size shall be 600 A, with minimum sensor size of 600A which can be set at 50% of breaker rating.

G. Circuit breakers shall be manually operated. Breakers for main-tie-main arrangements shall be electrically operated.

H. Power for operating the trip units shall be obtained from within the individual circuit breaker assembly.

1.4 SURGE PROTECTIVE DEVICES

A. Provide UL listed surge protective devices (SPD) connected to the incoming service leads. SPD’s shall be integrally mounted in a barriered compartment in the switchgear. See Specification Section 264313 for detailed requirements.

1.5 METERING and COMMUNICATIONS

A. Provide manufacturer’s standard digital multi-function metering on mains/feeders.

B. Communications link shall be via Cleveland Clinic’s energy management software. See Specification Section 260913 “Electrical Power Monitoring and Control”.

C. The manufacturer defined communications bus shall be extended from main, tie and feeder breakers to an externally mounted hinged pull box containing a manufacturer provided gateway for connection to the Cleveland Clinic’s monitoring system via Ethernet. System shall be configured for monitoring only.

1.6 MAIN and TIE DEVICES

A. All main and tie devices shall be 100% rated for continuous duty, drawout power circuit breakers rated to safely interrupt the available fault current.

B. Provide key interlocking between main and tie devices so that all three devices cannot be closed at the same time. Throw-over will be done manually.

C. Protective Devices – Solid state, true RMS sensing electronic trip units with adjustable trip settings: 1. Long time. 2. Short time. 3. Ground fault. 4. Zone selective interlocking.

1.7 DISTRIBUTION DEVICES

A. All feeder devices shall be 100% rated for continuous duty, drawout circuit breakers rated to safely interrupt the available fault current.

APRIL 2011 Page - 2

Page 16: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR

APRIL 2011 Page - 3

B. Minimum frame size shall be 800 A.

C. Protective Devices - Solid state, true RMS sensing electronic trip units with adjustable trip settings: 1. Long time. 2. Short time. 3. Instantaneous. 4. Ground fault (Healthcare facilities). 5. Zone selective interlocking.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 262300.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with current edition in effect of the National Electrical Code.

B. Switchgear Assemblies typically shall be installed indoors in a locked, dedicated room, provided with adequate ventilation and cooling. Provide rear access for all switchgear with working clearance according to NEC requirements. Provide four inch high concrete housekeeping pads.

C. All equipment shall be grounded in accordance with Specification Section 260526.

D. Testing and acceptance requirements: refer to Specification Section 262300.

*****

Page 17: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES PARALLELING LOW-VOLTAGE SWITCHGEAR

PART I - GENERAL

1.1 SUMMARY

A. This Guideline describes the general requirements of control systems for paralleling generators on an isolated bus and for distributing power in AC systems.

B. Paralleling is the operation in which two or more generators are started, synchronized and then connected to a common bus. Paralleling multiple generators increases reliability, flexibility in load control, and maintenance.

C. Paralleling Switchgear is a combination of protective relaying, metering, control and switching components integrated to manage emergency power distribution. Paralleling Switchgear shall be provided where two or more generators are supplying a common load. Typical installations would include hospitals, acute care facilities, ambulatory surgery centers, research/lab facilities, and data centers.

D. Refer to Specification Section 262313 - Paralleling Low Voltage Switchgear for detailed requirements.

1. Related specifications include Section 262300 “Low Voltage Switchgear”, Section 263600 "Transfer Switches”, and Section 262312 "Engine Generators".

1.2 GENERATOR PARALLELING MONITOR AND CONTROL SYSTEM

A. The Paralleling Switchgear shall be furnished with a dedicated microprocessor based controller that provides supervisory and power transfer functions that works in conjunction with digital generator controls to provide a fully automatic system for use in unattended applications.

B. The Controller shall have the following minimum features:

1. Generator management. 2. Load management. 3. Individual generator start/stop. 4. System test/exercise. 5. Electrical metering. 6. Mechanical metering. 7. Alarm/event logging. 8. Remote communications and ability to interface with Cleveland Clinic’s Power

Monitoring and Control System.

C. Paralleling and monitoring equipment, components, and accessories shall be mounted in the switchgear control section of the switchgear lineup. An Operator Control Panel with graphical display shall be specified.

APRIL 2011 Page - 1

Page 18: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES PARALLELING LOW-VOLTAGE SWITCHGEAR

APRIL 2011 Page - 2

D. Paralleling shall be accomplished with UL listed power circuit breakers with integral stored-energy closing mechanisms. Circuit breakers shall be of draw-out design for interchangeability and ease of maintenance.

E. Communications link shall be via Cleveland Clinic’s energy management software. Refer to Specification Section 260913 for requirements.

1.3 DESCRIPTION OF SYSTEM OPERATIONS

A. Upon loss of normal power all generators start and achieve rated voltage and frequency. The generators are sequentially synchronized and closed on to the paralleling bus. If the bus becomes overloaded the loads are shed until normal frequency is restored. If the load is below preset limits for 15 minutes the controller shuts down generator sets in predetermined order until minimum number of sets are operating.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 262313.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. The installation shall comply with the current edition in effect of the National Electrical Code. Where generators are installed indoors, the equipment shall be installed in the same room as the generators. Where generators are installed outdoors, paralleling equipment shall be located in a locked, dedicated and ventilated room; coordinate installation to allow front and rear access to equipment.

B. See Specification Section 262313 for testing and installation requirements.

*****

Page 19: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LOW VOLTAGE SWITCHBOARDS

APRIL 2011 Page - 1

PART I - GENERAL

1.1 SUMMARY

A. This Guideline specifies the general requirements for Low Voltage Switchboards. Refer to Specification Section 262413 for detailed requirements.

1.2 LOW VOLTAGE SWITCHBOARD REQUIREMENTS

A. LVS includes:

1. Switchboard. 2. Surge Protective Devices. 3. Metering and Communications. 4. Main devices. 5. Distribution devices.

B. Switchboards designated as Service Equipment shall have a single main device for disconnecting the incoming service. Multiple main disconnects shall not be used.

C. Switchboards shall be UL Service Entrance labeled where necessary.

D. Distribution switchboards shall be served by a dedicated circuit beaker within the distribution section of the Low Voltage Switchgear or Unit Substation.

E. Size switchgear for anticipated peak load plus twenty-five percent spare capacity for future growth, split between spare breakers and breaker spaces.

F. The Engineer shall specify the short circuit rating of the equipment.

1.3 LOW VOLTAGE SWITCHBOARD

A. All equipment shall be 600 V class, 100% rated for continuous duty circuit breakers, series rated equipment is not acceptable.

B. Switchboard construction shall comply with UL 891, all line and load connections shall be accessible from the front.

C. Continuous current rating of switchboards shall not exceed 2500 A, above this use low voltage switchgear in accordance with Section 262300.

D. The switchboard shall consist of a factory assembled line up of breaker and auxiliary compartments and instrumentation to form a self supporting rigid structure.

1. Bussing shall be silver plated copper.

2. Neutral bussing shall be 100% rated.

Page 20: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LOW VOLTAGE SWITCHBOARDS

APRIL 2011 Page - 2

3. A ground bus shall extend the length of the switchgear.

4. Provide Neutral – Ground link for switchboards used as service equipment.

D. Provide separate cubicles for metering equipment.

E. Spaces for future devices shall be fully provisioned to accept circuit breakers without modification.

F. Minimum feeder breaker frame size shall be 250 A, with minimum sensor size of 250A which can be set at 50% of breaker rating.

G. Circuit breakers 1600 A or less shall be manually operated breakers larger than 1600 A shall be electrically operated.

H. All circuit breakers shall have provisions to be padlocked in the open or closed position.

1.4 SURGE PROTECTIVE DEVICES

A. Provide UL listed surge protective devices (SPD) connected to the incoming leads or the line side of the main device for switchboards used as service entrance equipment or those serving sensitive loads. SPD’s shall be externally mounted immediately adjacent to the switchboard enclosure. See specification section 264313 for detailed requirements.

1.5 METERING and COMMUNICATIONS

A. Provide manufacturer’s standard digital multi-function metering on mains.

B. Communications link shall be via Cleveland Clinic’s energy management software. See section 260913 “Electrical Power Monitoring and Control”.

C. The manufacturer defined communications bus shall be extended from main breakers to an externally mounted hinged pull box containing a manufacturer provided gateway for connection to Cleveland Clinic’s monitoring system via Ethernet. System shall be configured for monitoring only.

1.6 MAIN DEVICES

A. All main devices shall be 100% rated for continuous duty, circuit breakers, rated to safely interrupt the available fault current.

1. In general, all main devices less than 1600 A may be individually mounted molded case power circuit breakers. 1600 A and above use draw-out power circuit breakers.

B. Protective Devices – Solid state, true RMS sensing electronic trip units with adjustable trip settings: 1. Long time. 2. Short time. 3. Ground fault (above 1000A, 480 V service).

Page 21: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LOW VOLTAGE SWITCHBOARDS

APRIL 2011 Page - 3

1.7 DISTRIBUTION DEVICES

A. All feeder devices shall be 100% rated for continuous duty, molded case circuit breakers, rated to safely interrupt the available fault current.

B. All feeder devices 800 A or less may be panel mounted, above 800 A devices shall be individually mounted.

C. Protective Devices - Solid state, true RMS sensing electronic trip units with adjustable trip settings: 1. Long time. 2. Short time. 3. Instantaneous. 4. Ground fault (Healthcare facilities where provided on main device).

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Eaton Corporation (Cutler – Hammer). Acceptable manufacturers are provided in Specification Section 262413.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with current edition in effect of the National Electrical Code.

B. Typically switchboards shall be located indoors in a locked, dedicated room, provide with adequate ventilation and cooling. Switchboards shall be front only accessible. Front and rear accessible construction may be used where space permits. Where rear access is provided allow for working clearance according to NEC requirements. Provide four inch high concrete housekeeping pads for all switchboards.

C. All equipment shall be grounded in accordance with Specification Section 260526.

D. Testing and acceptance requirements: refer to Specification Section 262413.

*****

Page 22: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES BRANCH CIRCUIT AND DISTRIBUTION PANELBOARDS

PART I – GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for panelboards, including the following up to 1200A and 600V. Refer to Specification Section 262416 for detailed requirements. 1. Distribution Panels. 2. Branch Circuit Panels. 3. Electronic Grade Panels. 4. Isolated Power Panels.

1.2 GENERAL REQUIREMENTS FOR PANELBOARDS

A. Description: Panelboards shall comply with NEMA, UL and NFPA requirements.

B. Enclosures: Provide door-in-door construction with lockable latch fasteners on all doors. Locks shall conform to Cleveland Clinic standard locking scheme. Specify enclosures suitable for the environment.

C. Incoming Mains and Buses: Main over current devices, where installed, shall be circuit breakers in accordance with Section 262816 “Switches and Circuit Breakers”. All bus bars and terminations shall be copper. Panelboards shall be 100% neutral rated, except where used on the secondary of K-rated transformers they shall be 200% neutral rated. Fully rated ground busses shall be provided in all panelboards.

D. Ratings: Service shall be three -phase, four-wire, use of single phase panels is not permitted. Existing buildings with three phase service shall have only three phase panels provided. 1. All panelboards shall be fully rated to interrupt symmetrical short-circuit current

available at terminals. Series rated panelboards are not acceptable. Minimum AIC symmetrical ratings shall be 10K at 208V and 14K at 480V.

E. Load center type panelboards shall not be specified.

F. Sub-Feed breakers shall not be used.

G. Use of panels with more than 42 poles is discouraged. If more than 42 poles are required, it is preferred to provide an additional panelboard and divide the load.

H. Branch Overcurrent Protective Devices shall be bolt-on thermal-magnetic circuit breakers.

I. Do not provide main devices or feeders less than the panel bus rating.

J. New panels shall be minimum 200 A for 208/120 V receptacle/small power service and 100 A for 480/277 V lighting panels.

K. Size and Capacity: Panelboards shall be sized for the load plus 30% spare capacity, including 10% spare breakers and 20% spaces.

APRIL 2011 Page - 1

Page 23: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES BRANCH CIRCUIT AND DISTRIBUTION PANELBOARDS

APRIL 2011 Page - 2

L. Provide Surge Protective Devices for panelboards in accordance with Section 264313.

M. All operating suites shall be provided with two - 10 kVA isolated power panels, selected procedure rooms shall be provided with one panel. Coordinate with Project requirements. The panels shall serve no other rooms. All isolated power panels shall have a main breaker, sixteen 20 A – 2P branch breakers, integral Line Isolation Monitor (LIM), and non-ventilated stainless steel front. Panels are typically ten inches deep; coordinate proposed locations of panels with Architect. Refer to Specification Section 262011 for detailed requirements.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 262416.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR INSTALLATION

A. Comply with the edition in effect of the National Electrical Code and NFPA 99.

B. Panels shall only serve devices that are located on the same floor as the panel; emergency panels may serve devices on the floor above and floor below.

C. Panelboard loads shall be separated based on type. Motor loads and sensitive electronic loads shall not be served from the same panelboard. The Engineer shall review the load types to verify such conflicts are avoided.

D. Locate panels such that branch circuits will not exceed 100 feet in length.

E. In high density electrical utilization areas where circuit requirements exceed 12 poles, provide a dedicated panel for that area.

F. Panelboards should generally be located in locked electrical rooms with a 1-hour fire rating, do not install panelboards in corridors.

G. Flush mount panelboards in finished spaces, surface mount in utility spaces. 1. Do not mount panelboards in fire-rated walls.

H. Provide at least four 1” empty conduits stubbed above ceiling in finished spaces with flush mounted panels.

I. Branch circuits shall not share neutral conductors.

J. Testing, adjusting and acceptance requirements: refer to Specification Section 262416.

*****

Page 24: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES MOTOR CONTROL CENTERS and MOTOR CONTROLS

PART I - GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for motor control centers, including arrangement of components, starters, overcurrent protection and auxiliary devices. Refer to Specification Sections 262419 and 262913 for detailed requirements.

1.2 GENERAL REQUIREMENTS FOR MOTOR CONTROL CENTERS

A. Motor Control Centers (MCC’s) shall be provided in Mechanical Rooms where more than six motors are installed or other areas where motors are grouped reasonably close together. Avoid feeding motors from lighting or receptacle panels.

B. Motor control centers shall be of the freestanding type complying with the design and function requirements of the Project. MCC’s shall be factory-assembled, dead front, self-supporting motor control centers consisting of required vertical sections bolted together to form one rigid assembly.

C. Enclosures shall be NEMA Type 1. Wiring shall be Class I, Type B.

D. All Bussing shall be copper. Specify half capacity Neutral bus in all MCC’s. Bus shall be braced for maximum available fault current, Engineer shall specify bracing.

E. Provide energy metering for MCC breakers or starters that will interface with Cleveland Clinic’s Energy Management System or to comply with LEED requirements.

F. Install power factor correction capacitors on all motors 50 HP and larger. Do not install capacitors on any installation where the motor is controlled by a solid state device such as a VFC. Correct power factor to 95%.

1.3 MOTOR STARTERS

A. Motor starters shall be minimum NEMA Size One for uniformity and maximum interchangeability and shall be combination type equipped with circuit breakers or fusible switches.

B. For motors 50 HP and larger, use reduced voltage starting if VFC not provided.

C. Motor starters shall be as specified in Specification Section 262913 Enclosed Controllers.

D. Do not specify IEC rated components.

E. Provide communication modules for designated motor starters in accordance with Specification Section 260913 “Electrical Power Monitoring and Control”.

APRIL 2011 Page - 1

Page 25: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES MOTOR CONTROL CENTERS and MOTOR CONTROLS

APRIL 2011 Page - 2

1.4 VARIABLE FREQUENCY CONTROLLERS (VFC)

A. Refer to Mechanical Specification Section 232923 for requirements for VFC’s to be provided in Motor Control Centers.

1.5 OVERCURRENT PROTECTION

A. Overcurrent protection and disconnecting means shall be thermal-magnetic MCCB with interrupting capacity to comply with available fault currents or fusible switch with Class R fuses.

B. Provide overload protection in all three phases for three-phase motors, and in all “hot” legs for single phase motors.

1.6 CONTROL DEVICES

A. Magnetic motor starters shall have rotary selector switch “Hand – Off – Auto” controls. For motors without automatic control, the Auto position shall be left open.

B. Provide a red “ON” and a green “OFF” pilot light (LED) for each starter.

C. Control circuits shall operate at 120V. 480V starters shall have internal control transformers.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 262419.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR INSTALLATION

A. MCC’s shall be located away from high ambient temperatures and radiant heat sources.

B. MCC’s shall be installed on 4” high concrete housekeeping pads.

C. Identification nameplates for MCC and each cubicle shall be provided per Specification Section 260553.

D. For testing, adjusting and acceptance requirements refer to Specification Section 262419.

*****

Page 26: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES ENCLOSED BUS ASSEMBLIES

PART I - GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for low voltage enclosed bus duct and associated plug-in devices. Refer to Specification Section 262500 for detailed requirements.

1.2 GENERAL REQUIREMENTS FOR ENCLOSED BUS ASSEMBLIES

A. The use of Feeder busways shall be considered for all feeders greater than 1200 Amperes.

B. The use of Plug-In busways shall be considered for Vertical power distribution in buildings more than four stories in height.

C. The use of short runs of feeder busway shall be considered to connect switchgear line ups or switchgear to transformers in electrical rooms.

D. Existing low voltage busways are either to be extended and/or additional plug-in units are to be installed. The new material shall match existing type, capacity and manufacturer, and the installation method shall match existing.

E. Bus Assemblies shall be low-impedance, in non-ventilated housing using single-bolt joints; current/voltage ratings per project requirements.

F. Bus shall be copper with silver plated contact surfaces and fully insulated except at joints. The bus bar shall be braced to withstand a short current of maximum RMS symmetrical rating as determined by the Engineer.

G. Housings shall be aluminum, totally enclosed and non-ventilated.

H. Provide integral copper ground bus through the length of the busway and fittings.

1.3 PLUG-IN UNITS

A. Use only interchangeable plug-in units on busways. Units shall be circuit breaker type. Circuit breakers shall comply with Specification Section 262816.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 262500.

APRIL 2011 Page - 1

Page 27: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES ENCLOSED BUS ASSEMBLIES

APRIL 2011 Page - 2

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR INSTALLATION

A. Comply with the edition in effect of the National Electrical Code and all applicable federal, state and local requirements, referenced standards and conform to codes and ordinances of authorities having jurisdiction.

B. Bus assemblies shall be fully accessible at joints and fittings.

C. Allow for expansion fittings at locations where bus assemblies cross building expansion joints and where run exceeds 200 feet in length. Provide at other locations so distance between expansion fittings does not exceed manufacturer's recommended distance between fittings.

D. Identification nameplates for busway and each plug-in unit shall be per Specification Section 260553.

E. For testing, adjusting and acceptance requirements refer to Specification Section 262500.

*****

Page 28: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES WIRING DEVICES

PART 1 - GENERAL

1.1 SUMMARY

A. This Guideline includes requirements for the following:

1. Receptacles, receptacles with integral GFCI, and associated device plates. 2. Twist-locking receptacles. 3. Isolated-ground receptacles. 4. Hospital-grade receptacles. 5. Tamper-resistant receptacles. 6. Weather-resistant receptacles. 7. Snap switches and wall-box dimmers. 8. Wall-switch occupancy sensors. 9. Floor service outlets, poke-through assemblies, and multi-outlet assemblies.

B. Refer to Specification Section 262726 for detailed requirements.

1.2 GENERAL REQUIREMENTS

A. Wiring Devices shall be provided where required by the Building Program and as follows:

1. Office and Administrative areas, Corridors: heavy duty, specification grade. 2. Mechanical and Electrical rooms, warehouse, toilet rooms (staff, public): heavy duty,

specification grade. 3. Toilet rooms (patient care areas): hospital grade. 4. Surgical, procedure, patient care, recovery, diagnostic, imaging and similar: hospital

grade. 5. MRI Suites: hospital grade with non-magnetic strap, screws, etc. 6. Pediatric areas: tamper resistant, hospital grade.

B. Wiring device requirements: 1. Type, quantity and locations of receptacles, switches, etc. shall be as described in the

“Room Specific Design Guidelines” in the Cleveland Clinic Design Standards Manual. 2. Comply with National Electrical Code. 3. Comply with NFPA 99.

1.3 PROHIBITIED MATERIALS

A. Residential grade devices.

B. Power service poles.

APRIL 2011 Page - 1

Page 29: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES WIRING DEVICES PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 262726.

2.2 GENERAL WIRING-DEVICE REQUIREMENTS

A. All wiring Devices, Components, and Accessories shall be listed and labeled as defined in NFPA 70, by Underwriters’ Laboratories, and marked for intended location and application.

B. Specify devices UL listed for use with stranded building wire.

2.3 STRAIGHT-BLADE RECEPTACLES

A. Hospital Grade, Isolated Ground, and Convenience Duplex Receptacles: 125 V, 20 A, Configuration NEMA 5-20R.

B. Tamper-Resistant Convenience Receptacles: 125 V, 20 A, NEMA Configuration 5-20R. Comply with UL 498, Supplement SD.

1. Description: Label shall comply with NFPA 70, "Health Care Facilities" Article, and “Pediatric Locations" Section.

2.4 GFCI RECEPTACLES

A. General Description:

1. Non-feed-through type.

2. NEMA Configuration 5-20R, 125 V, 20 A.

2.5 HAZARDOUS (CLASSIFIED) LOCATION RECEPTACLES

A. Wiring Devices for Hazardous (Classified) Locations shall comply with Building Program requirements.

2.6 TWIST-LOCKING RECEPTACLES

A. Single Convenience Receptacles: configuration shall comply with Building Program requirements.

2.7 WALL –SWITCH OCCUPANCY SENSORS

A. See “Lighting Controls” Design Guide for requirements.

APRIL 2011 Page - 2

Page 30: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES WIRING DEVICES 2.8 TOGGLE SWITCHES

A. Switches, Pilot-Light Switches, Key-Operated Switches: 120/277 V, 20 A.

2.9 WALL-BOX DIMMERS and OCCUPANCY SENSORS

A. See “Lighting Controls” Design Guide for requirements.

2.10 WALL PLATES

A. Single and combination types. 1. Material for Finished Public Spaces (FHC): Smooth, high-impact, commercial grade

nylon or Noryl. Color by Architect. 2. Material for Imaging, Surgical, Diagnostic, Laboratories, Patient Care, and Treatment

areas (ASC), satin-finished Type 302 stainless steel. 3. MRI suites: non-magnetic plates and screws. 4. Material for Unfinished Spaces: satin-finished Type 302 Stainless steel.

B. Wet-Location, Weatherproof Cover Plates: weatherproof in use, die-cast aluminum with lockable cover.

2.11 FLOOR SERVICE FITTINGS

A. Type: for floor boxes, coordinate with requirements of Section 260533 Raceways and Boxes.

B. Power Receptacle: comply with Building Program requirements.

C. Voice and Data Communication Outlet: coordinate with requirements in Division 27 Section "Communications Horizontal Cabling."

D. Comply with UL 514 scrub water exclusion requirements.

2.12 POKE-THROUGH ASSEMBLIES

A. Description:

1. Dual service for power/data. Provide outlets to match Building Program requirements. 2. Comply with UL 514 scrub water exclusion requirements. 3. Fire Rating: Unit is listed and labeled for fire rating of floor-ceiling assembly.

2.13 MULTI-OUTLET ASSEMBLIES

A. Assemblies with prewired 20A/120V receptacles spaced 12 to 24 inch on centers, metal or plastic housing, with snap on covers.

APRIL 2011 Page - 3

Page 31: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES WIRING DEVICES

APRIL 2011 Page - 4

B. Use in new construction is discouraged, may be used in renovation type projects or laboratories where Building Program requirements call for accessibility to power in locations such as benchtops.

2.14 FINISHES

A. Device Color:

1. Wiring Devices Connected to Normal Power System: As selected by Architect. 2. Wiring Devices Connected to Emergency Power System: Red. 3. Isolated-Ground Receptacles: Orange.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Installation of wiring devices shall comply with NEC and NFPA 99.

B. Circuiting guidelines: 1. Convenience receptacles – 6 unassigned receptacles per circuit. 2. Computer/data – 3 dedicated receptacles per circuit. 3. Equipment – dedicated circuit. 4. Three circuits per homerun conduit. 5. Neutrals shall not be shared. 6. Corridor receptacles shall not be circuited to adjacent room circuits.

C. Comply with Division 26 Section "Identification for Electrical Systems"; receptacles shall be identified with panelboard identification and circuit number.

3.2 FIELD QUALITY CONTROL

A. Tests and inspections for wiring devices shall be accordance with Section 262726.

1. In healthcare facilities, reports that comply with recommendations in NFPA 99 shall be provided by the Contractor and reviewed by the Engineer.

*****

Page 32: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LOW VOLTAGE POWER CABLES

PART I - GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for Low Voltage (600 V and less) Cables and accessories. Refer to Specification Section 260519 for detailed requirements.

1.2 LOW VOLTAGE CABLE REQUIREMENTS

A. Includes the following:

1. Cable. 2. Splices. 3. Terminations.

1.3 LOW VOLTAGE CABLES

A. Voltage Rating: 1. 600 V for 480/277 V and 208/120 V distribution systems.

B. Conductor: Soft, annealed copper, stranded, Class B compressed for #14 and larger.

C. Minimum #12 awg for power and lighting circuits, #14 for control circuits.

D. Insulation: XHHW for service conductors and feeders #2 awg and larger. THHN/THWN may be specified for feeders up to 600 kcmil. THHN/THWN shall be specified for branch circuits, except for Isolated Power Systems where XHHW-2 with dielectric constant of 3.5 or less shall be used.

E. Secondary service, feeder and branch circuit cables shall be color coded.

1.4 TERMINATIONS

A. Only terminations UL486A listed for 90 deg C shall be specified.

B. Cable termination lugs shall be long barrel, 2 – hole, compression type for 250 kcmil and above, 1 – hole for less than 250 kcmil.

1.5 MATERIALS NOT PERMITTED

A. Aluminum conductors shall not be specified.

B. Type MC Cable shall not be specified under any circumstances unless specifically approved in writing by the Senior Director of Facilities.

APRIL 2011 Page - 1

Page 33: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LOW VOLTAGE POWER CABLES

APRIL 2011 Page - 2

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 260519.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. No conductor smaller than No. 12 wire shall be used for branch circuit wiring. For “homeruns” over 50 feet in length (100 feet for 277 volt), no conductor smaller than a No. 10 wire shall be used. The tap conductor from the J-box to the outlet may be No. 12. Each 120-volt phase conductor shall have a neutral conductor of the same size. All feeder and branch circuits shall be sized by conforming to the following provisions. Only lighting circuits shall share grounding conductors. All lighting circuits with shared grounding conductors shall be #10 AWG minimum. 1. 480 Volt Branch Circuits: The voltage drop in the case of 480/277 volt circuits shall not

exceed 1.0 percent at maximum load and 70.0 percent power factor. 2. 208/120 Volt Branch Circuits: The voltage drop in the case of 208/120 volt circuits shall

not exceed 2.0 percent at maximum load and 70.0 percent power factor.

B. Splices in feeder circuits shall be avoided unless necessitated by the length of the run.

C. Do not use conductors larger than 600 kcmil. If necessary due to project conditions, use paralleled conductors for sizes 250 kcmil up to and including 600 kcmil.

D. Comply with current edition in effect of the National Electrical Code.

E. All cables shall be identified in accordance with Specification Section 260553.

F. Testing and acceptance requirements: refer to Specification Section 260519.

*****

Page 34: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LOW VOLTAGE FUSES

PART 1 - GENERAL

1.1 SUMMARY

A. This Guideline includes:

1. Requirements for use of cartridge type fuses rated 600-VAC and less. 2. Refer to Specification Section 262813 for detailed requirements.

1.2 GENERAL REQUIREMENTS

A. Fuses shall be permitted for the following type circuits only:

1. Motor circuits.

a. In combination starters located in Motor Control Centers. b. In separately mounted combination motor starters. c. In switches used as local disconnects for motors or hermetic compressors.

2. Control circuits or for protection of control power transformers. 3. Elevator feeders and elevator disconnect switches. 4. Class J fuses shall not be specified for motor protection.

B. Fuse applications: 1. Motor circuits: Class RK-1, time delay. 2. Control circuits: Class CC, fast acting.

1.3 QUALITY ASSURANCE

A. Fuses shall comply with NEMA FU 1 for cartridge fuses and NFPA 70.

1.4 COORDINATION

A. Coordinate fuse ratings with system short-circuit current levels as defined in the “Overcurrent Device and Short Circuit Study” (Section 260573).

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 262813.

APRIL 2011 Page - 1

Page 35: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LOW VOLTAGE FUSES

APRIL 2011 Page - 2

PART 3 - EXECUTION

3.1 GENERAL

A. Comply with the edition in effect of the National Electrical Code.

B. Testing and acceptance requirements: refer to Specification Section 262813.

******

Page 36: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES ENCLOSED SWITCHES AND CIRCUIT BREAKERS

PART I - GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for enclosed switches, separately mounted molded case circuit breakers, and shunt trip switches for elevators. Refer to Specification Section 262816 for detailed requirements.

1.2 SWITCHES – GENERAL REQUIREMENTS

A. All Switches shall be Heavy Duty type, horsepower rated, with number of poles and ampere rating determined by the load. General duty switches shall not be specified.

B. Switches shall be specified with rejection type fuse clips.

C. Specify enclosures suitable for the intended location.

D. All motors and mechanical equipment shall have local disconnect switches. Fusible switches shall be used where required for overcurrent protection of the motor or equipment.

1.3 MOLDED-CASE CIRCUIT BREAKERS – GENERAL REQUIREMENTS

A. For frame sizes up to 1600 A molded case breakers shall be used.

B. Specify thermal magnetic circuit breakers up to 250 A.

C. Circuit Breakers 250 amp and larger shall have adjustable electronic trip units.

D. Circuit breakers used for specific applications shall have the appropriate application listing.

E. Specify enclosures suitable for the intended location.

1.4 SHUNT TRIP SWITCHES FOR ELEVATORS

A. When sprinklers are installed in elevator hoistways or machine rooms, power must be switched off prior to activating these sprinklers. This can be accomplished by providing a shunt trip device on the elevator power circuit disconnecting means. It is recommended a fusible shunt trip power module be specified for this purpose.

B. Fusible shunt trip power modules for elevators shall contain power switch, fuse block, shunt trip mechanism, integral control power transformer and auxiliary contacts for alarm and tripping functions, fire alarm voltage monitoring relay, and fire safety interface relay.

C. Fusible shunt trip power modules shall comply with the following: 1. ANSI/ASME. 2. NFPA 70. 3. NFPA 72.

APRIL 2011 Page - 1

Page 37: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES ENCLOSED SWITCHES AND CIRCUIT BREAKERS

APRIL 2011 Page - 2

4. UL listed package.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 262816.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with current edition in effect of the National Electrical Code.

B. Ensure labeling and acceptance procedures are per Specification Section 262816.

*****

Page 38: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES VARIABLE FREQUENCY CONTROLLERS (VFC)

PART I - GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for Variable Frequency Controllers (VFC). VFCs shall be furnished under Division 23 and installed by Division 26. For exact requirements refer to Specification Section 232923.

1.2 GENERAL REQUIREMENTS VFD CONTROLLERS

A. Description: Variable Frequency Controllers (VFCs) may be used to vary the flow of air and water. VFCs shall be factory packaged in an enclosure, with integral disconnecting means and overcurrent and overload protection; listed and labeled by an NRTL as a complete unit; arranged to provide self-protection, protection, and variable-speed control of one or more three-phase induction motors by adjusting output voltage and frequency.

B. VFCs shall be locally mounted near the motor to limit the distance from the drive to motor to no more than 75 feet.

C. Manual bypass starters for VFCs should be considered on a case by case basis where life safety or risks of extensive losses are an issue.

D. A dry common trouble alarm contact shall be provided for input to the BAS.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 232923.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR INSTALLATION

A. Comply with the edition in effect of the National Electrical Code.

B. Testing, adjusting and acceptance requirements: refer to Specification Section 232923.

*****

APRIL 2011 Page - 1

Page 39: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES ENGINE-GENERATOR SYSTEMS

PART 1 - GENERAL

1.1 SUMMARY

A. This Section includes requirements for engine-generator sets for Level 1 emergency power supply.

B. Related Sections include the following:

1. Coordinate requirements of this section with those of Section 263600 "Transfer Switches" and Section 262313 “Paralleling Low Voltage Switchgear”.

1.2 GENERAL REQUIREMENTS

A. Emergency generator(s) shall typically be provided as the Alternate Power Source for the following facilities where the interruption of electric power to a building would result in hazard to life or property, or major loss of research or equipment:

1. Acute care hospital. 2. Research and laboratory buildings. 3. Data processing facilities. 4. Ambulatory surgery centers. 5. Central plants.

B. The alternate source of power shall be one or more diesel-engine-driven-generator sets. Provide physical space for one additional generator; paralleling switchgear shall be appropriately provisioned.

C. Emergency generator(s) may be provided as the Alternate Power Source for the following facilities:

1. Family health centers. 2. Office/administrative facilities. 3. Storage/warehouse. 4. Outpatient clinics.

D. Emergency generators are not mandatory for non-patient care facilities since battery packs can adequately handle the Life Safety requirements of NFPA No. 101 and the lowering of elevators in case of a power outage. If there are unusual emergency loads, cost considerations shall determine whether an emergency generator would be cost effective.

APRIL 2011 Page - 1

Page 40: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES ENGINE-GENERATOR SYSTEMS 1.3 QUALITY ASSURANCE

A. Prepare and submit calculations that justify the size of each generator or paralleled fleet of generators, including but not limited all downstream loads of the generator set(s) and capacity reserved for future loads. If applicable under NEC Article 517, demand factors and historical data used to justify generator set(s) sizing shall be submitted.

1. Oversizing the generator compared with the rated power output of the engine is permissible to meet specified performance for Sensitive Loads.

2. Typically size generator(s) for 125% of projected peak load.

3. Emergency generator(s) shall not be used for load shaving.

B. Electrical Components, Devices, and Accessories: Listed and labeled by Underwriters’ Laboratories.

C. Comply with ASME B15.1.

D. Comply with NFPA 37.

E. Comply with NFPA 70.

F. Comply with NFPA 99.

G. Comply with NFPA 110 requirements for Level 1 emergency power supply system.

H. Comply with FM Global requirements.

I. Comply with latest EPA Tier requirements.

J. Engine Exhaust Emissions: Comply with applicable state and local government requirements.

K. Noise Emission: Comply with applicable state and local government requirements for maximum noise levels.

L. Coordinate mechanical engineering elements of the generator system design with the A/E’s Mechanical Engineer and Cleveland Clinic Mechanical Design Guidelines.

1. Including but not limited to exhaust piping, fuel storage, pumping, and piping.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 263213.

APRIL 2011 Page - 2

Page 41: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES ENGINE-GENERATOR SYSTEMS 2.2 ENGINE-GENERATOR SET

A. Engine: Four-stroke, 1800 rpm, diesel fueled. Natural gas/LP fueled units are not acceptable.

1. Start Time: Comply with NFPA 110, Type 10, system requirements, generator system shall accept full load in one step.

2. Engine-generators shall be rated for “Stand-By Duty”.

B. Adjustable isochronous governors shall be specified.

C. Cooling System: Prefer liquid cooled, with radiator factory mounted on engine-generator-set.

1. Use of remote mounted radiators is discouraged.

D. Muffler/Silencers shall be hospital grade, critical type.

E. Starting System shall be 12-V electric, with negative ground for units up to 250 kW. Above 250 kW, system shall be 24-V. 1. Units 1000 kW and above: provide dual cranking motors, battery banks and chargers for

reliability.

F. Fuel Oil System: Comply with UL 142, NFPA 30 and NFPA 37, and provide the following features:

1. For each generator set specify a sub-base day tank of eight (8) hours fuel supply at 100% load.

a. Provide direct fuel oil supply and return piping between the day tank and on-site storage tank.

b. If so dictated by critical project needs, provide a remote fuel fill station to replenish the day tank directly from a fuel truck/trailer.

2. On-Site Storage Tank Capacity: As recommended by engine manufacturer for an uninterrupted period of minimum 96 hours' operation at 100 percent of rated power output of engine-generator system without being refilled.

3. Single generator installations of 500 kW or less may have only a sub-base main fuel tank with minimum capacity of 24 hours at 100% load, or as determined by project requirements.

4. If oil fired boilers are specified, fuel oil piping for the generator system shall not be connected into the boiler transfer fuel delivery loop.

5. Main storage tank to day tank pumps shall be duplex arrangement. Provide a manually operated transfer pump connected in parallel with electric pumps to allow oil to be pumped to day tank in event the electric driven pumps are in-operable.

APRIL 2011 Page - 3

Page 42: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES ENGINE-GENERATOR SYSTEMS 2.3 CONTROL AND MONITORING

A. Indicating and Protective Devices and Controls: As required by NFPA 110 for Level 1 system.

B. Generators shall be provided with Communications capabilities: A communication gateway, discrete I/O module, for each alarm and status indication for data-link transmission of indications to remote data terminals and control network. Generator shall be capable of communicating with Cleveland Clinic’s data collection and control network.

C. Remote Alarm Annunciators shall comply with NFPA 99 and be installed in a location where it can be monitored 24 hours /day, such as the Security office or Building Manager’s office.

2.4 GENERATOR OVERCURRENT AND FAULT PROTECTION

A. Generator Circuit Breaker: Molded case (up to 800 A.) or insulated-case (above 800 A), electronic-trip type; 100 percent rated; complying with UL 489.

B. Ground-Fault Indication shall be provided per NFPA 70, "Emergency System" signals for ground-fault.

2.5 GENERATOR LOAD BANK

A. Generator installations shall be designed with provisions for a portable load bank connection.

1. A circuit breaker rated at 100% of generator output shall be provided in the Generator paralleling switchgear or generator distribution switchboard and wired to a roll up termination cabinet similar to an Eaton type “RUGTC”. This cabinet shall be typically located outdoors. Refer to Specification 262417.

2. This connection may also be used to provide temporary generator connection to building load in event of installed generator failure.

2.6 OUTDOOR ENCLOSURES

A. Where provided, specify vandal-resistant, weatherproof, walk-in type, steel housing, wind resistant up to 100 mph (160 km/h). All instruments and controls shall be mounted within enclosure. Specify an acoustical rating of Level 2 (75dBa @ 23 feet). 1. Mufflers shall be located within the enclosure. 2. Walk-in enclosures shall be provided with a factory installed and wired 208/120V

loadcenter with sufficient breakers to power all required auxiliary equipment. 3. Where non-walk-in enclosures are specified, an elevated work platform extending around

the entire enclosure shall be provided to permit total access to all generator components.

APRIL 2011 Page - 4

Page 43: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES ENGINE-GENERATOR SYSTEMS

APRIL 2011 Page - 5

PART 3 - EXECUTION

3.1 INSTALLATION

A. Emergency Generator installations shall comply with NFPA 99 and 110, FM Global, and NEC 70E.

B. Preferably emergency generators shall be installed indoors on the ground floor, above the 100 year floodplain, in a locked dedicated room with adequate ventilation and access to at least one outside wall. Locate away from occupied spaces. Provide reinforced concrete housekeeping pads for generator equipment. Walls should preferably be CMU and extended from floor to structural deck. Fire rating of walls and doors shall be determined by the Fire Protection Engineer.

1. Generators should be installed at least 100 feet from communications frame equipment to avoid RF interference. Coordinate with Cleveland Clinic ITD staff.

C. Route exhaust piping to avoid re-entraining exhaust gases into building or adjoining building(s) ventilation systems.

D. Outdoor installations shall be reviewed and approved by the Cleveland Clinic Facilities Group.

E. Outdoor installations shall be within a locked masonry enclosure, with adequate working clearance around the entire generator housing. Provide raised reinforced concrete housekeeping pads. Security lighting and convenience power shall be provided.

F. Coordinate location, design and specification of remote fuel oil storage, piping, and pumping systems with Mechanical Engineer and Division 23 Sections.

3.2 TESTING AND ACCEPTANCE

A. Refer to Division 26 Section 263213 "Engine Generators" for requirements.

*****

Page 44: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES CENTRAL BATTERY EQUIPMENT

PART I - GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for Central Battery Equipment (CBE) used for emergency lighting systems. Refer to Specification 263323 for detailed requirements. For Uninterruptible Power Supplies see Section 263353 Uninterruptible Power Supplies (UPS).

1.2 DESIGN REQUIREMENTS FOR CENTRAL BATTERY SYSTEMS

A. Where the use of an emergency generator cannot be financially justified to provide power for emergency/egress lighting, consideration shall be given to the use of a Central Battery Inverter System. Application would typically be for stand alone Administrative /Support facilities.

1. Critical care areas in hospital or acute healthcare facilities (i.e. operating suites, LDR’s) that cannot tolerate loss of illumination shall be considered for use of a CBE to back up the room illumination provided by selected fixtures. This should be coordinated during the initial design phase.

B. Provide Slow-Transfer Central Battery Inverters that will automatically sense loss of normal ac supply and use an electromechanical switch to transfer loads. The unit should automatically transfer load from normal source to internal battery/inverter source in one second or less.

C. Inverters shall be solid-state type sized to carry 125% of the connected load for 10 minutes.

D. Inverters shall be compatible with all fixture types. Fixture types include, but are not limited to, fluorescent ballasts, incandescent lamps, electronic and high power factor fluorescent ballasts, LED, and HID fixtures.

E. Batteries shall be Valve regulated, sealed lead calcium, maintenance free batteries capable of sustaining full-capacity output for a minimum of 90 minutes. Ni-Cad batteries shall not be specified.

F. Distribution to emergency circuits should be through panelboards complying with Section 262416, except they can be integral to the equipment cabinet.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 263323.

APRIL 2011 Page 1

Page 45: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES CENTRAL BATTERY EQUIPMENT

APRIL 2011 Page 2

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with current edition in effect of the National Electrical Code.

B. Equipment shall be installed in a locked room dedicated for electrical equipment. Ensure adequate clearance around all equipment as well as sufficient ventilation.

C. Testing and acceptance requirements: refer to Specification Section 263323.

*****

Page 46: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES UNINTERRUPTIBLE POWER SUPPLY

PART 1 - GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for modular Uninterruptible Power Supplies (UPS) 10 kVA and larger. Refer to Specification Section 263353 for detailed requirements.

1.2 GENERAL REQUIREMENTS

A. The equipment described herein will generally include free standing, modular type UPS systems. These are typically provided in facility MDF rooms, server or IT equipment rooms.

B. UPS includes the following components:

1. Three-phase, on-line, double-conversion, static-type, UPS units with:

a. Surge suppression on input. b. Input circuit breaker. c. Rectifier-charger. d. Inverter. e. Static bypass transfer switch. f. Battery Cabinet and battery disconnect device. g. Maintenance bypass/isolation switches cabinet. h. Output circuit breaker (depending on project requirements). i. Output step down transformer (depending on project requirements). j. Output distribution panelboard (depending on project requirements). k. Remote UPS monitoring provisions. l. Battery monitoring.

1.3 PERFORMANCE REQUIREMENTS

A. Minimum Duration of Supply: If battery is sole energy source supplying rated full UPS load current at 80 percent power factor, duration of supply shall be a minimum of 10 minutes.

1. Coordinate exact requirements with the Cleveland Clinic ITD Department.

1.4 POWER SOURCE

A. Typically the UPS(s) shall receive power from a dedicated Closed Transition Transfer Switch fed from the facility emergency generator. The Maintenance Bypass source shall be a feeder from the Critical Branch transfer switch.

APRIL 2011 Page - 1

Page 47: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES UNINTERRUPTIBLE POWER SUPPLY

APRIL 2011 Page - 2

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 263353.

2.2 BATTERY

A. Batteries shall be valve-regulated, recombinant, lead-calcium units factory assembled in an isolated cabinet with battery disconnect switch.

2.3 CONTROLS

A. An “Emergency Power Off” Switch shall be provided in the room at the door to shut off all power to the UPS(s).

2.4 MONITORING BY REMOTE COMPUTER

A. A “Liebert Site Scan” communication module shall be specified for capability of remote monitoring of UPS(s). The remote computer and the connecting signal wiring are not included in this Section. Include the following features: 1. Software and Hardware: Compatible with that specified in Division 26 Section

"Electrical Power Monitoring and Control."

2.5 BASIC BATTERY MONITORING

A. Battery monitoring shall be specified, the Albercorp system shall be used.

PART 3 - EXECUTION

3.1 INSTALLATION

A. UPS shall be located in locked, dedicated, climate controlled rooms, or in the main server or distribution frame room. Location shall be coordinated with the Cleveland Clinic ITD group.

3.2 PERFORMANCE TESTING

A. Performance and acceptance testing shall be in accordance with Section 263353 requirements.

*****

Page 48: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES TRANSFER SWITCHES

PART 1 - GENERAL

1.1 SUMMARY

A. This Guideline provides requirements for automatic transfer switches rated 600 V and less, including the following:

1. Automatic Transfer Switches (ATS). 2. Closed Transition Transfer Switches (CTTS). 3. Bypass/isolation switches.

B. Refer to Specification Section 263600 for detailed requirements.

C. Related Specification Sections: 1. Section 263213 - Engine Generators. 2. Section 260913 - Electrical Power Monitoring and Control.

1.2 TRANSFER SWITCH REQUIREMENTS

A. Provide transfer switches for loads connected the emergency power systems as defined in NFPA 70 for critical, life safety, equipment and delayed equipment branches.

B. Consideration shall be given to the quantity of transfer switches and respective loads to allow for load shedding in circumstances of emergency power system diminished capacity.

C. In general, it is desired that transfer switches be limited to 800 amperes maximum size and located to provide the highest practicable reliability in service to the load.

D. For three phase four wire systems, switches shall be true four pole switches, with all four poles mounted on a common shaft.

E. Transfer switch control panels shall be provided with communications package to allow real time monitoring. Transfer switches shall be monitored via the electrical power monitoring and control system (Section 260913). Ethernet communications shall be MODBUS protocol and use Cleveland Clinic’s energy management software.

F. Switching Arrangement: Single motor for Life Safety and Critical Branch switches, dual motor for delayed Equipment Branch switches, and Closed Transition for UPS loads or other loads that automatically reboot after restoration of power.

G. Bypass/isolation switches: Provide a bypass/isolation switch to electrically bypass and isolate each ATS or CTTS. The switch must be capable of bypassing to whichever source the ATS/CTTS is connected to.

APRIL 2011 Page - 1

Page 49: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES TRANSFER SWITCHES

APRIL 2011 Page - 2

1.3 QUALITY ASSURANCE

A. Comply with NEMA ICS 1.

B. Comply with NFPA 70.

C. Comply with NFPA 99.

D. Comply with NFPA 110 Level 1 requirements.

E. Comply with UL 1008.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 263600.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Comply with current edition in effect of the National Electrical Code.

B. Generally, transfer switches shall be located in an electrical room dedicated for emergency system equipment.

1. Install on 4 inch high concrete base with chamfered edges, front edge shall be painted yellow.

C. All equipment shall be grounded in accordance with Specification Section 260526.

D. Components shall be identified according to Specification Section 260553.

E. Tests and inspections shall be in accordance with Specification Section 263600.

*****

Page 50: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LIGHTNING PROTECTION FOR STRUCTURES

PART 1 - GENERAL

1.1 SUMMARY

A. This Guideline includes lightning protection for new structures. Refer to Specification Section 264113 for detailed requirements.

1.2 GENERAL REQUIREMENTS

A. Early in the design phase of a new building, if the structure will be taller than surrounding buildings and structures, the Engineer shall provide a Lightning Risk Analysis in accordance with NFPA 780. The Project Team will review the Risk Analysis and determine if a lightning protection system should be provided.

B. If it is determined that a lightning protection system should be provided, provide a traditional Franklin type of system in accordance with the appropriate chapter of NFPA 780.

C. If it is decided a lightning protection system is not required, this decision shall documented and made a matter of record along with the Risk Analysis.

1.3 QUALITY ASSURANCE

A. Applicable Codes and Standards:

1. UL 96A. 2. NFPA 780. 3. NFPA 70. 4. FM Global Data Sheets.

1.4 COORDINATION

A. Coordinate design of lightning protection with other building systems and components, including electrical wiring, supporting structures and building materials, metal bodies requiring bonding to lightning protection components, roofing, and building finishes.

PART 2 - PRODUCTS

2.1 LIGHTNING PROTECTION SYSTEM COMPONENTS

A. Specify products that comply with UL 96 and NFPA 780.

APRIL 2011 Page - 1

Page 51: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LIGHTNING PROTECTION FOR STRUCTURES

APRIL 2011 Page - 2

PART 3 - EXECUTION

3.1 INSTALLATION

A. At the completion of the Project the Engineer shall insure a UL Master Label certificate is delivered to Cleveland Clinic.

*****

Page 52: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES SURGE PROTECTIVE DEVICES FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

PART 1 - GENERAL

1.1 SUMMARY

A. Section includes requirements for Surge Protective Devices (SPD) for low-voltage (120 to 600 V) power distribution equipment. See Specification Section 264313 for detailed requirements.

B. The latest edition of UL 1449 has eliminated “Transient Voltage Surge Suppressors” and replaced them with “Surge Suppression Devices”. The new standard categories are as follows: 1. Service Entrance: Old: Class B – new: Type 1. 2. Sub-distribution Switchboards and Panelboards: Old: Class C – new: Type 2.

C. Related Sections:

1. Division 26 Section 264113 "Lightning Protection for Structures". 2. Division 26 Section 260526 "Grounding and Bonding".

1.2 DEFINITIONS

A. SPD: Surge Protective Device.

B. TVSS: Transient voltage surge suppressor(s).

1.3 GENERAL REQUIREMENTS

A. SPD’s offer protection against either externally induced surges caused by lightning or utility switching, or internally generate switching surges caused by starting/stopping of compressors, air conditioners, elevators or fuse/circuit breaker operations.

B. Surge Protective Devices shall be provided at service entrance equipment of all facilities.

C. Use of integrated, cascaded SPD is required at all acute care and data processing facilities, at the highest secondary voltage (“service entrance”) level, at downstream panelboards that serve sensitive electronic equipment, and for other critical branch and life safety loads.

D. Surge Protective Devices installation shall be coordinated with lightning protection system in buildings so equipped.

E. SPD’s shall use heavy duty MOV technology and serviceable, replaceable modules.

F. Surge current capability per phase shall be:

March 2011 Page - 1

Page 53: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES SURGE PROTECTIVE DEVICES FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

Service Entrance or Transfer Switch 300 kA Type 1

Distribution Panelboards and MCC’s 200 kA Type 2

Branch Circuit Panelboards 100 kA Type 2

1. For facilities in areas of high lightning incidence, increase ratings to 400 kA, 250 kA, and 120 kA respectively.

2. The SPD shall provide surge current paths for all modes; L – N, L – G, and N – G.

1.4 QUALITY ASSURANCE

A. Surge Protective Devices shall comply with the following:

1. Comply with IEEE C62.41.2 and test devices according to IEEE C62.45.

2. Comply with UL 1449, 3rd edition.

3. Comply with NFPA 70.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 264313.

PART 3 - EXECUTION

3.1 INSTALLATION

A. SPD devices shall be specified at service entrance LV Switchgear on line side of the main device, with ground lead bonded to service entrance ground. 1. SPD devices shall be internally mounted in switchgear in a barriered compartment. 2. A dedicated, separately mounted disconnect device shall be provided in the switchgear

for the SPD.

B. SPD devices for Switchboards, Distribution panelboards and Branch circuit panelboards shall be specified with conductors or buses between suppressor and points of attachment as short and straight as possible. The neutral and ground shall not be bonded.

1. SPD devices shall be externally mounted for switchboards, distribution and branch circuit panelboards.

March 2011 Page - 2

Page 54: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES SURGE PROTECTIVE DEVICES FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS

March 2011 Page - 3

2. Insure sufficient wall space for mounting of SPD immediately adjacent to panelboard to minimize lead lengths.

3. A dedicated disconnect device shall be specified for the SPD.

C. Coordinate the location of field-mounted SPD devices to allow adequate clearances for maintenance.

D. Tests and Inspections:

1. Refer to Specification Section 264313 for testing and acceptance requirements.

*****

Page 55: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES INTERIOR LIGHTING

PART I - GENERAL

1.1 SUMMARY

A. This Section specifies the general requirements for Interior Lighting. This is a design standard and is not to be used as a Specification. Refer to Specification 265100 for detailed requirements.

1.2 GENERAL REQUIREMENTS FOR INTERIOR LIGHTING

A. Interior Lighting 1. Perform all lighting calculations based on IES Lighting Handbook Latest Edition and the

lighting power density criteria of the latest edition of ANSI/ASHRAE/IESNA 90.1. Calculations shall be performed with industry leading software; Visual, AGI, etc.

2. Refer to IESNA Recommended Practice (RP-29-6) for further Healthcare Lighting criteria.

3. Provide individual luminaire details in a Luminaire Schedule on the Drawings and not as part of the Specification.

4. Show switch and switchleg control for all luminaires. 5. Emergency luminaires in corridors, stairwells and exit signs shall be connected to an

unswitched circuit. 6. Emergency paths of egress shall be illuminated at a minimum of one (1) foot candle. Ten

(10) footcandles at exit discharge. Engineer to provide calculations identifying required illumination along all paths of egress.

7. Incandescent lamps including halogen types shall not be used unless approval has been obtained from CCF Facilities Engineering Department.

8. Linear and compact fluorescent dimming is acceptable. 9. Provide occupancy sensors and/or low voltage master lighting control system to comply

with latest edition of ANSI/ASHRAE/IESNA 90.1 requirements as conditions warrant. 10. Luminaires in equipment rooms, telecommunication rooms and utility rooms shall be

mounted such that the luminaire bottom is not lass that 8’-6” above finished floor. Coordinate final location with equipment layout.

11. Equipment rooms, telecommunication rooms and mechanical rooms shall have at least one (1) overhead light on emergency power. When only two (2) luminaires are in a room, both may be on one switch on emergency power. Elevator machine room lighting shall be on a dedicated circuit.

12. Lensed fluorescent luminaires shall have 0.125” thick acrylic lens material. 13. Undercabinet and systems furniture task lights shall be 120 volt, LED type, solid front

with integral occupancy sensor(s). 14. All linear luminaires shall have T8 or T5 high performance lamps up to 4’ in length only

and electronic ballasts. Lamps shall be standardized for respective project. 15. Fluorescent 2’x4’ luminaires shall be the standard. 2’x2’ luminaires will be LED type

with evenly lighted diffuse panel and no visible LED modules. 16. Electronic ballasts shall be high power factor (.90 minimum), have a total harmonic

distortion of <10% and have a crest factor less than 1.7 so as not to depreciate lumen output and lamp life.

APRIL 2011 Page - 1

Page 56: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES INTERIOR LIGHTING

17. Fluorescent luminaires shall be provided with internal fusing for ballasts. This shall be in addition to the thermal fuses integral to the ballasts.

18. Fluorescent luminaires with linear lamps shall be provided with ballast disconnecting means per NEC. In areas of renovation, existing fluorescent luminaires to remain shall be provided with ballasts disconnects for each ballast.

19. Existing interior incandescent downlights shall be re-lamped with LED replacement lamps or Edison based self ballasted compact fluorescent lamps as a value engineering option.

20. New interior downlights shall be compact fluorescent type, vertical lamp unless ceiling restrictions dictate otherwise. LED downlights shall be considered and proposed to CCF Facilities Engineering Department for acceptance.

21. Downlight reflectors shall be clear alzak with integral white trim ring unless noted otherwise.

22. Recessed fluorescent downlights shall have open reflectors with 7” minimum diameter aperture.

23. Downlights installed outdoors or over food handling areas shall be lensed. 24. Downlights installed in shower locations shall be provided with flush type reflector with

opal lens. 25. Parabolic luminaires shall have low iridescent diffuse silver finish with 3” deep 18 cell

louvers. 2’x’4 parabolic luminaires shall have two (2) ballast covers. 26. Luminaire frames shall be flush or regressed aluminum, steel hinged and equipped with

spring loaded cam latches. 27. Clean room type luminaires shall be provided in specific areas as required and shall be

triple gasketed with sealed cam latches. 28. Warning signs (In-Use, Beam-On, X-Ray In Use, etc.) shall be LED type with housing

and face color as specified or electroluminescent. 29. Luminaires in Operating rooms, Pre and Post Op, ICU, CCU, PCU, NICU and other

similar Critical Care Areas and other areas where electronic equipment is used that is sensitive to RF interference, as determined by the CCF Facilities Engineering Department shall be provided with an RFI shielded lens and an RFI suppressor for each ballast.

30. Surgical troffers in Operating rooms shall have closed cell neoprene gasket with antimicrobial finish, with a high CRI and match the color temperature of adjacent sources. Luminaires shall be equipped with .156” asymmetric-symmetric lens to diffuse the light and to prevent glare. Door shall have captive screws. Luminaire shall be provided with three (3), two (2) lamp electronic Class P ballasts for multi-level control.

31. Operating Rooms, Procedure Rooms, etc., shall have supplemental recessed downlighting around perimeter of room controlled separately from surgical troffers.

32. Careful consideration shall be given when selecting luminaires. Proper lamp/ballast combinations shall be provided to meet the allowed lighting power density (LPD) noted in ASHRAE 90.1-2007. Engineer shall decide if the “space-by-space” or “whole building” method should be utilized.

33. MRI suites shall have 0-10VDC LED dimmable 6” aperture downlights, 4100ºK with 1,050 lumen package minimum, non-ferrous mounting bracket, integral thermal management and remote LED driver. Maximum depth 8”. All lighting in MRI suites shall be thoroughly coordinated with obstructions above ceiling to avoid conflict.

34. Luminaires shall be wired as parallel lamp circuits to maintain full light output on surviving lamps if one or more lamps fail.

35. Fluorescent lamps and ballasts shall be recycled per EPA approved methods. 36. All fluorescent lamps for use on dimming circuits shall be burned in for 100 hours

minimum. APRIL 2011 Page - 2

Page 57: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES INTERIOR LIGHTING

37. Luminaires in daylight areas shall be on at all times. When adequate daylight is present, luminaires shall dim down to 10% minimum output.

38. Luminaires shall be fully accessible for relamping and servicing from below ceiling plane.

B. Exit Signs 1. Provide exit signs in accordance with NFPA 101, Life Safety Code. 2. Indicate quantity of faces and directional arrows on the Drawings, where required. 3. Exit signs shall be provided push to test switch or self diagnostics where available. 4. Exit signs shall be green electroluminescent edgelit type with mirror finish in new or

renovated areas. New supplemental exit signs in existing areas to remain shall match adjacent signs. If LED exit signs are utilized, individual LED’s shall not be visible. Red and green shall not be mixed in the same areas.

5. Exit signs shall meet NEMA EM 1-2010, Exit Sign Visibility Testing Requirements.

C. Interstitial Spaces 1. Provide fluorescent industrial strip luminaires with open top reflectors providing 20%

uplight. Provide with wire guard where subject to physical damage.

D. LEED Goals 1. All projects shall be designed to attain LEED certification. Certification level goals shall

be coordinated with CCF Facilities Engineering Department at the beginning of each Project.

2. For Interior Lighting, at a minimum, Indoor Environmental Quality Credit 6.1 (EQ 6.1) Controllability of Systems - Lighting shall be addressed.

E. Deviation 1. Whenever deviations from Cleveland Clinic Standards and/or Design Guidelines may be

required, the Engineer shall submit a “Guideline Revision Request Form” applicable to that specific Project fully describing the requested deviation.

2. Request approval from CCF Facilities Engineering Department for the implementation of any new or improved Interior Lighting products and/or systems that are energy efficient or result in cost savings through submission of a “Guideline Revision Request Form”.

PART 2 - PRODUCTS

A. MANUFACTURERS: Refer to “Cleveland Clinic Master Lighting Fixture Schedule” for acceptable manufacturers.

B. Fluorescent lamps shall have a color temperature of 3000ºK in public spaces. Four foot T8 lamps shall be 25 watt high efficiency type with mercury content 1.7mg or less. Philips F25T8/ADV835/ALTO or equal be GE shall be the standard lamp. Other Color temperatures shall not be used unless approval has been obtained from CCF. All Clinical spaces, i.e., CCF Operating Rooms and adjacent support areas, such as, Pre and Post OP, Sub Sterile Rooms, Clean Storage Rooms, Corridors and Nursing Stations shall utilize 4100°K. Kelvin temperatures shall not be mixed within the same visible area.

APRIL 2011 Page - 3

Page 58: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES INTERIOR LIGHTING

APRIL 2011 Page - 4

C. Standard metal halide lamp color shall be 3500ºK. When providing metal halide luminaires at interior locations, Engineer shall select a lamp with a color temperature of 3200ºK. Verify selection with CCF Facilities Engineering Department prior to specifying.

D. Standard fluorescent luminaire for general lighting applications shall be 2’x4’ lay-in type with three (3) T8 lamps and electronic ballast(s). Ballast quantity as required by switching arrangement.

E. 2’x2’ fluorescent luminaires shall not be specified unless approval has been obtained from CCF Facilities Engineering Department.

F. Compact fluorescent lamps shall be 3500ºK, triple tube, 4 pin. Edison base type for replacement applications.

G. Eight (8) foot lamps are not acceptable.

H. High and Low pressure sodium or mercury vapor lamps are not acceptable.

I. Lamps shall have a minimum CRI of 85 with 90 of higher preferred.

J. Metal halide lamps shall be mogul or medium base. Specialty metal halide lamps may be PAR type with medium base.

K. Two, three and four foot linear lamps, compact fluorescent lamps and HID lamps shall be TCLP compliant with mercury content of 1.7mg or less.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR INTERIOR LIGHTING INSTALLATION

A. Comply with the edition in effect of the National Electrical Code and all applicable federal, state and local requirements, referenced standards and conform to codes and ordinances of Authorities Having Jurisdiction.

*****

Page 59: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

PART 1 - GENERAL

1.1 SUMMARY

A. This Guideline includes the requirements for grounding and bonding of electrical power and lighting systems and equipment. This Guideline shall not be regarded as a Specification. Refer to Specification 260526 for detailed requirements.

B. The main purpose of the grounding system is to maintain a low potential difference between metallic parts to protect personnel from electric shocks and to provide an effective system for the flow of ground fault currents and lightning strikes.

C. Drawings shall show ground systems, grounding and bonding cable sizes, and relative locations. Cleveland Clinic Standard Detail drawings shall be utilized. Specifications shall include detailed requirements of the grounding system. It is required that the Engineer specify all applicable requirements. Specifying requirements by the use of NEC references only is prohibited.

D. If changes to an existing grounding system are needed, they shall be done in accordance with Cleveland Clinic standards, and as described in Specification 260526.

1.2 RELATED DOCUMENTS

A. Coordinate the requirements of this design guide with the general provisions of the “Lightning Protection” Guide.

B. Grounding of Low Voltage and Telecommunications systems shall be in accordance with the Cleveland Clinic ITD Standards. Coordinate with the Systems Engineer all grounding and bonding requirements for the project.

1.3 QUALITY ASSURANCE

A. Comply with NFPA 70 and NFPA 99 requirements.

B. Comply with FM Global requirements.

C. Comply with IEEE 142 requirements.

PART 2 - PRODUCTS

2.1 CONDUCTORS

A. Conductors for indoor applications shall be tinned-copper, stranded wire or cable with 600 V green insulation, sized per NEC requirements.

APRIL 2011 Page - 1

Page 60: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

B. Conductors for outdoor direct buried applications shall be bare, tinned, stranded Copper conductors, minimum #4/0 awg.

C. Grounding Busses shall be predrilled rectangular bars of annealed copper mounted on stand-off insulators.

2.2 CONNECTIONS

A. Specify exothermically welded type connections such as “Cadweld” for underground and connections to structural steel.

B. Specify clamp type connectors for connection to piping.

C. Where connections need to be undone such as at a test well, bolted type connectors shall be specified.

D. Where terminating on ground bus bars, long barrel, compression type lugs shall be specified.

2.3 GROUNDING ELECTRODES

A. Ground Rods shall be Copper-clad steel, 3/4 inch by 10 feet (19 mm by 3 m) in diameter.

PART 3 - EXECUTION

3.1 GROUNDING SYSTEM REQUIREMENTS

A. For all new buildings, a below grade ground loop around the building shall be specified with connections to building steel columns and foundation rebar (Ufer system). The lightning protection system shall be bonded to this loop in accordance with NFPA 70 and 780. Ground rods shall be placed at each corner and every 60 feet around the building. 1. A ground test well shall be provided at a point closet to the service equipment. 2. Maximum specified grounding system resistance values for new buildings shall five (5)

ohms; for sensitive electronic equipment systems, three (3) ohms.

B. Where the Utility Company is the building power source, coordinate grounding and bonding of the utility metering equipment in accordance with Utility Company’s requirements.

C. Health care facilities: receptacle grounding, equipment grounding, ground fault protection, panelboard grounding, isolated power system (where used) grounding, wet locations grounding, and grounding of non current-carrying conductive surfaces of fixed electric equipment likely to become energized that are subject to personal contact, etc. shall be in accordance with NEC 517. Details shall be shown on drawings.

D. Insulated equipment grounding conductors shall be provided with all feeders and branch circuits.

E. Raceways shall not be used as grounding conductors.

APRIL 2011 Page - 2

Page 61: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

APRIL 2011 Page - 3

F. Grounding Bus Bars shall be provided in electrical and telephone equipment rooms, in rooms housing service equipment, and elsewhere as required. Provide ground risers of not less than #2/0 Copper to bond all ground busses to the main electrical ground point.

G. Grounding of specific communication, instrument, medical, computer, etc. equipment or systems shall be provided as recommended by system vendor.

1. Low voltage systems grounding shall be designed in accordance with the latest edition of the Cleveland Clinic ITD Standards.

2. Providing of separate grounding systems for computers that are completely isolated from the building ground systems is prohibited.

H. All exterior metal sheathing of buildings, such as metal curtain wall, shall be grounded to help ensure personnel are not exposed to electrical shock hazards.

I. Grounding of Secondary Neutrals and Transformer Enclosures: refer to Standard Detail Drawing.

J. Grounding of underground distribution system components shall comply with IEEE C2 requirements.

K. Manholes and Handholes shall be provided with a driven ground rod through manhole or handhole floor, refer to Standard Detail Drawing.

L. Pad-Mounted Transformers and Outdoor Switchgear shall be provided with a ground ring around the equipment pad and at least two ground rods at opposite corners.

M. All metal poles supporting outdoor lighting fixtures shall have a ground rod and a separate insulated equipment grounding conductor in addition to grounding conductor installed with branch-circuit conductors, refer to Standard Detail Drawing.

3.2 FIELD QUALITY CONTROL

A. Testing and Inspections of grounding systems: refer to Specification 260526 for requirements.

1. Comply with NEC, IEEE, NFPA 99 and NEIS requirements. 2. The Engineer shall require the Contractor to perform all testing and witness such testing.

******

Page 62: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES EXTERIOR LIGHTING

PART I - GENERAL

1.1 SUMMARY

A. This Section specifies the general requirements for Exterior Lighting. This is a design standard and is not to be used as a Specification. Refer to Master Specification 265600 for detailed requirements.

1.2 GENERAL REQUIREMENTS FOR EXTERIOR LIGHTING

A. Exterior Lighting 1. Perform all lighting calculations based on IES Lighting Handbook Latest Edition and the

lighting power density criteria of the latest edition of ANSI/ASHRAE/IESNA 90.1. Calculations shall be performed with industry leading software; Visual, AGI, etc.

2. Area site lighting shall comply with the Commercial Building Energy Alliances (CBEA) high efficiency LED parking lot performance specifications.

3. Provide individual luminaire details in a Luminaire Schedule on the Drawings and not as part of the Specification.

4. Site lighting poles shall be anodized or polyester powder coated aluminum. Color and shape of poles shall be coordinated with CCF Facilities Engineering Department and Architect. Height as required for specific application.

5. Luminaires shall be (Metal Halide) (LED). (3500º/4100º Kelvin). IP-66 rated. 6. Illuminate large parking lots with pole mounted full cut-off luminaires, utilizing alternate

circuiting. High wattage pole or building mounted luminaires are discouraged. The maximum height of a pole shall be a minimum of 12 feet, not to exceed 30 feet. Coordinate locations with snow removal means, hardscape and landscape features, etc. A combination of exterior wall mounted and pole mounted luminaires may be used for illumination of small parking lots.

7. Provide minimum maintained illumination levels for pedestrian pathways, vehicle routes, parking lots, way finding, signage, pedestrian entrances and building surrounds and services which will provide safety and security.

8. Preferred pole locations are islands and landscaped areas beyond the reach of vehicle bumpers. When not practical, extend concrete base 30” above finished grade. Refer to standard pole base detail.

9. Automatic controls shall be capable of turning off exterior lighting when sufficient daylight is available or when the lighting is not required during night time hours. Lighting not designated for dusk-to-dawn operation shall be controlled by an astronomical time clock or relay system.

10. Refer to ASHRAE 90.1 Building Exterior Lighting Power Density Table for further information.

11. For security facilitate facial recognition through vertical illumination and careful selection of color temperature and CRI of light sources.

12. Control light distribution to prevent direct glare to motorists, pedestrians and occupants of adjacent buildings, light pollution and light trespass.

13. Locate luminaires to emphasize specific building components and site features, i.e., entrances, columns, pedestrian/vehicular gateways, etc. Locate luminaires symmetrically at building entrances. Maintain symmetrical pattern along walkways.

APRIL 2011 Page - 1

Page 63: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES EXTERIOR LIGHTING

14. Provide dual source illumination at exterior exit discharge where necessary to meet Life Safety Code requirements.

15. Exterior lighting shall be controlled by a Building Automation System (BAS). Provide local control only if BAS control is not available. Do not provide time clock or an individual photocell in each light unless approved by CCF Facilities Engineering Department.

16. Stub out a spare 1 1/4" conduit from every fourth pole base for new poles and at every corner or intersection for expansion of lighting circuit in the future.

17. Avoid locating in ground junction boxes in sidewalks or driveways. Conceal them when possible in landscaping.

B. Parking garage lighting shall be LED, mounting configuration as necessary on a site by site basis. Top level and perimeter luminaires shall be controlled via photocell, all other luminaires shall be controlled via a switching relay panel.

C. Existing Sites 1. At existing sites, new poles, luminaires and lamp sources shall match existing exterior

luminaires. If existing luminaires cannot be matched, provide details, manufacturers name and catalog number for review by CCF Facilities Engineering Department.

D. Obstruction Lighting 1. Where required, refer to obstruction lighting advisory per Federal Aviation

Administration (FAA) Advisory Circular AC 70/7460-1K, Obstruction Marking and Lighting, latest edition. This is an advisory only and does not establish required practices.

E. Helipads 1. Refer to helipad lighting advisory per FAA Advisory Circular 150/5390-2B. This is an

advisory only and does not establish required practices. Flush or semi-flush LED marker lights shall not be utilized.

F. Deviations 1. Whenever deviations from Cleveland Clinic Standards and/or Design Guidelines may be

required, the Engineer shall submit a “Guideline Revision Request Form” applicable to that specific Project fully describing the requested deviation.

2. Request approval from CCF Facilities Engineering Department for the implementation of any new or improved Exterior Lighting products and/or systems that are energy efficient or result in cost savings through submission of a “Guideline Revision Request Form”.

G. LED Backlight/Uplight/Glare (BUG) Ratings. 1. If LED site luminaires are proposed, luminaires shall be rated with IES technical

memorandum TM-15-07.

H. LEED Goals 1. All projects shall be designed to attain LEED certification. Certification level goals shall

be coordinated with CCF Facilities Engineering Department at the beginning of each Project.

APRIL 2011 Page - 2

Page 64: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES EXTERIOR LIGHTING

APRIL 2011 Page - 3

2. For Exterior Lighting, at a minimum, Sustainable Sites Credit 8 (SS 8) Light Pollution Reduction shall be addressed.

PART 2 - PRODUCTS

A. MANUFACTURERS: Refer to “Cleveland Clinic Master Lighting Fixture Schedule” for acceptable manufacturers.

B. HID ballasts shall be electronic type, -30ºC starting, constant discharge (HID) wattage autotransformer, fused 120,208,277 or 480 volt input as required by application. Match ANSI ballast type to lamp specified. Potted magnetic ballasts are not acceptable.

C. LED drivers shall be 120, 277 or 480 volt input, -40ºC starting, UL listed for application. 350mA.

D. LED’s shall be tested and approved under the approved methods LM-79 and LM-80.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR EXTERIOR LIGHTING INSTALLATION

A. Comply with the edition in effect of the National Electrical Code and all applicable federal, state and local requirements, referenced standards and conform to codes and ordinances of Authorities Having Jurisdiction.

*****

Page 65: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES RACEWAYS, BOXES AND ENCLOSURES

PART I - GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for raceways, boxes and enclosures. Refer to Specification Sections 260533 and 260543 for detailed requirements.

1.2 QUALITY ASSURANCE

A. Comply with the following Codes and Standards: 1. FM Global. 2. NFPA 70. 3. NFPA 99. 4. NEMA. 5. ANSI. 6. UL.

1.3 GENERAL REQUIREMENTS

A. The following are acceptable raceway methods:

1. Rigid galvanized steel (RGS). 2. Electrical metallic tubing (EMT). 3. Rigid polyvinyl chloride conduit (PVC). 4. Flexible metal conduit (FMC). 5. Liquid-tight flexible metal conduit (LFMC). 6. Surface metal raceways. 7. Surface non-metallic raceways.

B. Prohibited materials. 1. Electrical non-metallic tubing (ENT) sometimes referred to as “blue tube” or “smurf

tube”. 2. Liquid-tight flexible non-metallic conduit (LFNC).

C. The following shall be used only where specific project requirements dictate use of such: 1. Rigid aluminum conduit. 2. PVC coated rigid steel conduit.

D. Non-metallic or non-ferrous raceways, boxes, fittings, etc. shall be specified for use in MRI scan rooms.

E. RGS conduit shall be specified for all circuits rated greater than 600 VAC routed inside buildings.

APRIL 2011 Page - 1

Page 66: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES RACEWAYS, BOXES AND ENCLOSURES

F. FMC shall be used for connection to recessed and semi-recessed light fixtures, for final primary and secondary connections to Low Voltage transformers, and final connections to motors or other vibrating equipment

G. Use of surface raceways (e.g. Wiremold) in finished spaces shall be coordinated with the Architect.

H. Non-metallic surface raceways shall not be used in patient care areas such as patient rooms, exam rooms, therapy rooms, recreational areas, solaria, and certain patient corridors.

I. Minimum conduit size: 1. Interior: ¾ inch. 2. Exterior: below grade: one (1) inch.

1.4 FITTINGS

A. Specify the following: 1. RGS: threaded fittings. 2. EMT: set screw type. 3. PVC: plastic with low VOC solvent cement.

1.5 FLOOR BOXES

A. Floor boxes shall be flush, rectangular, sheet metal type.

1.6 UNDERGROUND/EXTERIOR

A. Underground raceways shall generally consist of Schedule 40 PVC conduit encased in reinforced concrete. Conduit separation shall be maintained by spacers. Red dye shall be added to the top of the concrete after the pour. 1. Transitions from underground to above ground shall be made with rigid galvanized steel

elbows. 2. For ductbanks containing circuits greater than 600 V, a separate grounding conductor

shall be run with the ductbank.

B. Site lighting circuits shall be permitted to be run in direct buried PVC with appropriate cover.

C. Exposed aboveground raceways shall be RGS or Schedule 80 PVC.

D. Handholes shall be polymer concrete type. Traffic rating of lid shall be appropriate for the location.

E. Power and communications manholes shall be precast concrete type.

1.7 IDENTIFICATION OF RACEWAYS AND BOXES

A. Comply with Specification Section 260553.

APRIL 2011 Page - 2

Page 67: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES RACEWAYS, BOXES AND ENCLOSURES

APRIL 2011 Page - 3

B. Conduits and boxes shall be factory color coded to identify electrical systems as follows: 1. Life safety branch: purple. 2. Critical branch: yellow. 3. Emergency equipment branch: orange. 4. Normal branch: green. 5. Communications systems: blue. 6. Low voltage systems: black. 7. Fire alarm system: red.

PART 2 - PRODUCTS

2.1 MANUFACTURERS: Acceptable manufacturers are:

A. See Specification Sections 260533 and 260543 for approved manufacturers.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR ELECTRICAL INSTALLATIONS

A. Comply with current edition in effect of the National Electrical Code and NFPA 99.

B. Refer to Standard Electrical Detail Drawings for installation requirements.

*****

Page 68: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

APRIL 2011 Page - 1

PART 1 - GENERAL

1.1 SUMMARY

A. This Guideline includes computer-based, fault-current, overcurrent protective device coordination and arc flash studies. Protective devices shall be set based on results of the protective device coordination study. Refer to Specification Section 260573 for detailed requirements.

1.2 GENERAL REQUIREMENTS

A. On projects providing a new or replacing an existing power system or service greater than 1200 Amps, provide a fault current, device coordination and arc flash studies. 1. This study shall be part of the design services and shall not be supplied by a Contractor or

Vendor. 2. Use of series-rated devices is not permitted.

1.3 QUALITY ASSURANCE

A. Studies shall be performed using computer software programs that are distributed nationally and are in wide use. Hand calculated studies are not acceptable.

B. Coordination-Study Specialist Qualifications: A Professional Engineer, licensed in the state where Project is located, shall be responsible for the study. All elements of the study shall be performed under the direct supervision and control of the engineer. The final submittal shall be signed and sealed by the Professional Engineer responsible for the work.

PART 2 - PRODUCTS

2.1 COMPUTER SOFTWARE PROGRAM REQUIREMENTS

A. Acceptable Software programs are provided in Specification Section 2626057.

PART 3 - EXECUTION

3.1 EXECUTION

A. Perform a preliminary power systems study in order to specify equipment ratings.

B. Submit study for review at the end of Design Development.

C. The approved final study shall be submitted prior to any equipment energization and shall be used for final settings of devices for job closeout and commissioning.

*****

Page 69: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES ELECTRICAL POWER MONITORING AND CONTROL

PART 1 - GENERAL

1.1 SUMMARY

A. This Guideline includes PC-based computer and software for monitoring and control of electrical power systems and includes a complete Power Management Communications System (PMCS) to be shown on the drawings and shall be described in the specifications. Refer to Specification Section 260913 for detailed requirements. The PMCS is defined to include, but not to be limited to, remote devices for monitoring, control and protection, device communication interface hardware, intercommunication wiring, master control unit including UPS, software, ancillary equipment, startup and training services, and ongoing technical support.

1. PCMS shall be specified for all new acute care facilities, ambulatory facilities, clinical, research, administrative buildings, family health centers and central utility plants.

2. If feasible, renovation projects should install power monitoring equipment on any major electrical equipment directly affected or modified by the work.

3. Power monitoring and metering are in addition to utility metering.

B. Power Management Communications System (PMCS):

1. At a minimum, power monitoring and metering equipment should be provided for medium-voltage switchgear on each main and distribution feeder circuit breaker, unit substation transformer secondary low-voltage main and feeder circuit breakers, generators and generator switchboards and paralleling switchboards, low-voltage switchboards, major distribution panelboards, for both normal and essential electrical systems, large motors ( >100 hp) and Central UPS systems. The power monitoring and metering system shall have the capability of communication with the CCF centralized remote metering station via a high speed Ethernet network.

2. At a minimum, power monitoring and metering equipment shall record, store, and trend voltage, current, kW, kWh, kVA, kVAR, power factor, and voltage and current total harmonic distortion.

C. PMCS shall be capable of communicating with the following devices to be shown on the drawings or specified to be included in assembled equipment: 1. Electronic Trip Units. 2. Breaker Interface Modules. 3. Breaker Controllers. 4. Analog and Digital Input Modules. 5. Energy Sub-meters. 6. Motor Starters. 7. VFC’s.

D. Drawings for power monitoring and control equipment shall show system layout and connection diagrams for interfacing with electrical equipment.

APRIL 2011 Page- 1

Page 70: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES ELECTRICAL POWER MONITORING AND CONTROL

APRIL 2011 Page- 2

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 260913.

2.2 SYSTEM REQUIREMENTS

A. Specify factory-installed hardware and software to enable the Cleveland Clinic’s existing system to monitor, display, and record data for use in processing reports.

B. Software shall be specified to run on a single PC, with capability for accessing multiple devices simultaneously. Modbus TCP/IP, RS-232, and RS-485 digital communications.

C. Network Configuration shall be high-speed, multi-access, open non-proprietary, industry standard communication protocol; LANs complying with EIA 485, 100 Base-T Ethernet, and Modbus TCP/IP.

PART 3 - EXECUTION

3.1 COORDINATION

A. Coordinate features of distribution equipment and power monitoring and control components to form an integrated interconnection of compatible components.

1. Coordinate the PMCS specification with the specifications of equipment that is monitored or controlled by power monitoring and control equipment.

2. The supplier of the PCMS shall be the same as the supplier of the electrical distribution equipment.

*****

Page 71: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LIGHTING CONTROL DEVICES

PART I - GENERAL

1.1 SUMMARY

A. This Section specifies the general requirements for Lighting Control Devices. This is a design standard and is not to be used as a Specification. Refer to Specification 260923 for detailed requirements.

1.2 GENERAL REQUIREMENTS FOR LIGHTING CONTROL DEVICES

A. Lighting Control Devices 1. Luminaires with three, four or more lamps, switch the lamps symmetrically for two or

three levels of light. 2. For day lighting areas in new or existing facilities, provide variable control for luminaires

located within 15 feet from perimeter windows. Provide photo sensor control for either step or continuous dimming or bi-level switching. (In-board/Outboard). Remaining luminaires within these areas shall be controlled separately.

3. Where multiple room entrances are not immediately adjacent to each other, provide three-way or four-way switching.

4. Provide dual technology occupancy sensor (ultrasonic/PIR) controls in public toilet rooms, conference rooms, examination rooms, offices and similar spaces. Occupancy sensors shall be considered for all non-emergency egress luminaires in non-patient care corridors. Occupancy sensors shall have an isolated relay output for connection to mechanical systems when necessary.

5. Patient room bed ward corridors shall be controlled from Nurse Stations. 6. Infrequently used rooms such as crawl spaces, pipe spaces, interstitial spaces, attics, etc,

provide a pilot light outside the areas to indicate when lights are on. 7. Electrical and Mechanical Rooms shall not be controlled by occupancy sensors. 8. Low voltage lighting control panels shall be provided in all areas in which lighting is not

required to be on 24/7. Low voltage switches shall be provided for over ride of programmed control of luminaires.

9. Exterior site pole luminaires shall be controlled via a central photocell control. Refer to ASHRAE 90.1 Exterior Lighting Control requirements for further information.

10. Exterior wall pack luminaires shall be controlled via a photocell integral to the luminaire. Refer to ASHRAE 90.1 Exterior Lighting Control requirements for further information.

11. Dimmers shall be slide type with on/off control, single-pole or three-way as shown on Plans. Faceplate color shall be coordinated with Architect and match device color.

12. Manual dimming controls shall be fully compatible with electronic dimming ballasts and approved by the ballast manufacturer, shall operate over full specified dimming range and shall not degrade the performance or rated life of the electronic dimming ballast and lamp(s).

13. Lighting (including emergency lighting) in auditoriums, lecture halls, large conference rooms, laboratories, etc., shall be capable of being shut off. Provide generator transfer device to turn emergency lights on up to full brightness when power fails.

14. Provide photo-sensor controls to control luminaires in skylights or atrium ceiling areas to turn the luminaires off if sufficient daylight is available.

APRIL 2011 Page - 1

Page 72: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES LIGHTING CONTROL DEVICES

APRIL 2011 Page - 2

B. Deviations 1. Whenever deviations from Cleveland Clinic Standards and/or Design Guidelines may be

required, the Engineer shall submit a “Guideline Revision Request Form” applicable to that specific Project fully describing the requested deviation.

2. Request approval from CCF Facilities Engineering Department for the implementation of any new or improved Lighting Control Devices products and/or systems that are energy efficient or result in cost savings through submission of a “Guideline Revision Request Form”.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 260923.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR LIGHTING CONTROL DEVICES INSTALLATION

A. Comply with the edition in effect of the National Electrical Code and all applicable federal, state and local requirements, referenced standards and conform to codes and ordinances of Authorities Having Jurisdiction.

*****

Page 73: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES NETWORK LIGHTING CONTROLS

PART I - GENERAL

1.1 SUMMARY

A. This Section specifies the general requirements for Network Lighting Controls and Modular Lighting Controls. This is a design standard and is not to be used as a Specification. Refer to Specification Section 260943 for detailed requirements.

B. The Cleveland Clinic intends to obtain LEED ratings for all new facilities. LEED criteria shall be followed for the design and specification of lighting control systems. The Engineer shall be responsible for the following items to ensure new facilities achieve LEED certification:

a. Sustainable Sites - SS Credit 8 b. Indoor Environmental Quality - IEQ Credit 6.1

1.2 NETWORK LIGHTING CONTROLS

Definitions: A. System shall be an open architecture system with the ability of complete monitoring and

control by a building management system and shall consist of networkable dimming panels, switching panels, digital controls and shading systems tied to a central PC for total lighting management. a. Central PC

1) Shall enable management of entire lighting system from central location. Software shall have capabilities to configure, maintain, and monitor all systems.

2) Time clock events, load shed capabilities, and seamless integration to BMS via native BacNet IP protocol functions.

b. Lighting Management Panels

1) Shall tie independent lighting systems such as dimming panels, switching panels, daylight harvesting digital controls, and low voltage roller shades to the central PC.

2) Shall have capacity for configurable links that each can be configured for digital controls, addressable wallstations, low voltage control interfaces, shade power panels, dimming/switching panels, and preset lighting controllers.

c. Architectural Dimming Panels

1) Shall be specification grade dimming panels with main lugs and secondary branch breakers.

2) Offer universal 16A continuous dimming outputs. 3) Be capable of 16A non-dim loads. 4) Shall tie to lighting management panel using a link configured for panels.

d. Light Duty Commercial Dimming Panels 1) Flush or surface mounted containing 16A dimming or switching modules

with capability of multiple outputs from one 16A circuit.

APRIL 2011 Page - 1

Page 74: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES NETWORK LIGHTING CONTROLS

2) Ties to lighting management panel using a link configured for panels.

e. Relay Switching Panel 1) Flush or surface mounted relay cabinet with 20 amp rated relays. 2) Shall be feed-thru or main lug. 3) Fully rated for continuous duty for inductive, capacitive, or resistive loads. 4) Ties to lighting management panel using a link configured for panels.

f. Modular Lighting Controller (refer to Modular Lighting Controls Section 1.3 Items e, f, & g) 1) Ties to lighting management panel using a configurable link.

g. Addressable Wallstations 1) Programmable to operate lights and/or shades as scenes, raise lower, or

toggle operation. 2) Modular faceplate kits available to change wallstation configuration. 3) Backlit and engraved buttons with red buttons identifying switched

emergency loads. 4) Ties to lighting management panel using a configurable link.

h. Shade Power Panel 1) Provides power for up to 10 low voltage roller shades. 2) Establishes communication between shades for grouping. 3) Ties to lighting management panel using a configurable link.

B. All panels shall have a permanently affixed brass nameplate identifying where fed from and loads served.

1.3 MODULAR LIGHTING CONTROLS

Definitions: A. System shall consist of independent switching/dimming panels, digital controls (daylight

harvesting) and shading systems. Some systems shall have built-in capability to be networked to each other or to a lighting management panel.

a. Preset Lighting Controls Modular Based

1) Controls all load types via modular power panels. 2) Capable of controlling digital addressable ballasts (up to 64). 3) Have integral time clock. 4) Capable of future networking via link to lighting management panel.

b. Preset Lighting Controls Panel Based 1) Shall control all load types via architectural dimming panels, light duty

commercial dimming panel or DC dimming panel.

c. Relay Panel with Integral Timeclock

APRIL 2011 Page - 2

Page 75: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES NETWORK LIGHTING CONTROLS

1) Flush or Surface mounted relay cabinet with 20 amp rated relays. 2) May be feed-thru or main lug. 3) Fully rated for continuous duty for inductive, capacitive, or resistive loads.

d. Dimming Panel with Integral Timeclock 1) Flush or surface mounted containing 16A dimming or switching modules

with capability of multiple outputs from one 20A circuit.

e. Modular Switching Controller 1) Switch outputs rated for 20A. 2) Occupancy sensors, daylight sensors, and wallstations wire directly to

modular controller. 3) Programmable by sequence of button presses or external controller. 4) Capable of networking with other modular controllers. 5) Capable of future networking via link to lighting management panel.

f. Lighting Control 0-10v Modular Controller 1) 0-10v outputs, and switch outputs rated for 20A. 2) Occupancy sensors, daylight sensors, and wallstations wire directly to

modular controller. 3) Programmable by sequence of button presses or external controller. 4) Capable of networking with other modular controllers. 5) Capable of future networking via link to lighting management panel.

g. Lighting Control Digital Modular Controller 1) 1 or 2 Digital Links capable of controlling up to 64 digital addressable

ballasts, LED drivers, or modules. 2) Occupancy sensors, daylight sensors, and wallstations wire directly to

modular controller or ballast. 3) Programmable by external controller. 4) Capable of networking with other modular controllers. 5) Capable of future networking via configurable link to lighting management

panel.

h. Low Voltage Roller Shades 1) For control of natural light to optimize daylight harvesting, reduce glare and

heat gains. 2) Up to 10 shades shall be powered by a shade power panel. 3) Addressable wallstations control as open/close, presets, or fine adjustment

up/down. 4) Capable of future networking via configurable link to lighting management

panel.

1.4 LIGHTING CONTROL IMPLEMENTATION PER AREA

A. Public Areas

a. Daylight harvesting via digital controls where sufficient natural light is available.

APRIL 2011 Page - 3

Page 76: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES NETWORK LIGHTING CONTROLS

b. Automatic roller shades to optimize daylight harvesting, control glare and heat gain.

c. Switching relays for interior locations via time clock, photocell, and/or manual overrides.

B. Patient Rooms

a. Integrate lighting and shades into bedside controls via modular lighting controls. b. Incorporate low voltage wallstations to control both lights and shades with scene

capabilities and toggle override.

C. Nurse Stations a. Utilize addressable wallstations to control designated light levels in corridor

immediate to nurse stations using switching. 1) If corridor is utilizing dimmed fixtures, time clock events can be

configured to simulate natural circadian rhythms for interior corridor areas.

D. Conference Rooms

a. Preset addressable wallstations control lights and shades via preset dimming controllers and/or digital controls.

b. A/V integration via contact closure, RS232, or Ethernet.

E. Procedure Rooms a. Preset addressable wallstations to control lights via switching/dimming/digital

controls.

F. Exam Rooms a. Local occupancy control utilizing dual technology devices.

G. MRI Rooms a. Local 0-10VDC slide dimmer located at control room/desk to control luminaires

from 100% to 5% of rated lumen output with dimmable remote power supply.

H. Private Offices a. Daylight harvesting via digital control photosensors where sufficient natural light

is available. b. Automatic roller shades to optimize daylight harvesting, control glare and heat

gain. c. Modular controller where no usable daylight is available. d. Local occupancy control utilizing dual technology devices.

I. Small Restrooms; Utility Rooms; Storage Rooms a. Local occupancy control utilizing dual technology devices.

J. Exterior Controls a. Automatic controls shall be capable of turning off exterior lighting when sufficient

daylight is available or when the lighting is not required during night time hours. Lighting not designated for dusk-to-dawn operation shall be controlled by an astronomical time clock or relay system.

APRIL 2011 Page - 4

Page 77: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES NETWORK LIGHTING CONTROLS

APRIL 2011 Page - 5

1.5 DEVIATIONS

A. Whenever deviations from Cleveland Clinic Standards and/or Design Guidelines may be

required, the Engineer shall submit a “Guideline Revision Request Form” applicable to that specific Project fully describing the requested deviation.

B. Request approval from CCF Facilities Engineering Department for the implementation of any new or improved Network/Modular Lighting Controls products and/or systems that are energy efficient or result in cost savings through submission of a “Guideline Revision Request Form”.

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 260943.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR NETWORK LIGHTING CONTROLS INSTALLATION

A. Comply with the edition in effect of the National Electrical Code and all applicable

federal, state and local requirements, referenced standards and conform to codes and ordinances of Authorities Having Jurisdiction.

*****

Page 78: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES SECONDARY UNIT SUBSTATIONS

PART I - GENERAL

1.1 SUMMARY

A. This Guideline provides the general requirements for secondary unit substations. Refer to Specification Section 261116 for detailed requirements.

1.2 UNIT SUBSTATION REQUIREMENTS

A. Unit Substation includes:

1. Primary switching. 2. Transformers. 3. Surge Protective Devices. 4. Metering and Communications. 5. Main and Tie devices. 6. Distribution devices.

B. Provide double-ended substations with two main and one tie secondary circuit breakers for acute care facilities, ambulatory surgery centers, research buildings, data centers, and central utility plants.

C. Provide single-ended substations with main secondary circuit breaker for family health centers, administrative and office buildings.

D. Size substations for anticipated peak load plus fifteen percent spare capacity for future growth.

1.3 PRIMARY SWITCHING

A. 15 kV class, metal enclosed, fused interrupter switchgear.

B. Where only one Utility feeder is available, a single switch shall be provided on each primary. When two Utility feeders are available, duplex or sectionalizing-loop feed switches shall be specified.

C. Primary surge arrestors.

1.4 TRANSFORMERS

A. Liquid filled type, silicon fluid, meeting FM Global flammability requirements.

B. All transformers shall be self-cooled and specified with factory installed cooling fans.

C. All transformers shall comply with TP-1 energy efficiency requirements.

D. All windings shall be Copper.

APRIL 2011 Page -1

Page 79: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES SECONDARY UNIT SUBSTATIONS

E. NEMA standard accessories.

F. High voltage, delta primary, voltage depending on project requirements.

G. Low voltage, wye secondary, 480/277 V or 208/120 V, depending on project requirements.

1.5 SURGE PROTECTIVE DEVICES

A. Provide a UL1449 listed surge protective device (SPD) between transformer secondary and each main device. SPD’s shall be integrally mounted in a barriered compartment and provided with a disconnect device.

B. Service entrance SPD’s shall be UL labeled as Type 1 devices.

C. Refer to Specification Section 264313 for additional requirements.

1.6 METERING and COMMUNICATIONS

A. Provide manufacturer’s standard digital multi-function metering on mains and feeders.

B. Communications link shall be via Cleveland Clinic’s energy management software. See section “Electrical Power Monitoring and Control”.

C. The manufacturer defined communications bus shall be extended from main, tie and feeder breakers to an externally mounted hinged pull box containing a manufacturer provided gateway for connection to Cleveland Clinic’s monitoring system via Ethernet. System shall be configured for monitoring only.

1.7 MAIN and TIE DEVICES

A. All main and tie devices shall be drawout power air circuit breakers, 100% rated to safely interrupt the available fault current.

1. Refer to Design Guide for Low Voltage Switchgear for additional requirements.

B. All devices shall be manually charged, electrically charged for main-tie-main arrangements.

C. Provide key interlocking between main and tie devices so that all three breakers cannot be closed at the same time. Throw-over will be done manually.

D. Trip units shall be fully electronic RMS sensing type and provide the following functions: 1. Long time. 2. Short time. 3. Ground fault. (All Main’s over 1200 A. on 480 V systems).

APRIL 2011 Page -2

Page 80: DESIGN GUIDELINES Division 26 - ELECTRICAL

Cleveland Clinic Design Standards ELECTRICAL DESIGN GUIDELINES SECONDARY UNIT SUBSTATIONS

APRIL 2011 Page -3

1.8 DISTRIBUTION DEVICES

A. All feeder devices shall be drawout power air circuit breakers, 100% rated to safely interrupt the available fault current. 1. Feeder circuit breakers shall be 800 Amp frame minimum. 2. Refer to Design Guide for Low Voltage Switchgear for additional requirements.

B. Trip units shall be fully electronic RMS sensing type and provide the following functions: 1. Long time. 2. Short time. 3. Instantaneous. 3. Ground fault. (All feeders for healthcare facilities)

PART 2 - PRODUCTS

2.1 MANUFACTURERS:

A. Acceptable manufacturers are provided in Specification Section 261116.

PART 3 - EXECUTION

3.1 REQUIREMENTS FOR ELECTRICAL INSTALLATION

A. Comply with current edition in effect of the National Electrical Code, FM Global requirements, and all applicable federal, state and local requirements, referenced standards and conform to codes and ordinances of Authorities Having Jurisdiction.

B. All Unit Substations shall be indoor construction, located in ventilated and cooled, locked, dedicated rooms. Allow for front and rear access. Provide four inch high concrete housekeeping pads.

C. All equipment shall be grounded in accordance with Specification Section 260526.

D. Testing and acceptance requirements: refer to Specification Section 261116.

******