Design and Monitoring of borehole heat exchangers using distributed
temperature measurements
KTH Royal Institute of TechnologyJosé Acuña
www.svepinfo.sewww.pemtec.se
Fiber inne i borrhålen
TnTn‐1
T1 T2 T3 T4 ……….
Distributed Temperature Sensing
DTS Instrument
DTS Instrument
Measurement example: U-pipe BHEs
0
20
40
60
80
100
120
140
160
180
200
220
9 11 13 15 17 19 21 23 25
Djup
[m]
Temperatur [C]
0,5 l/s0,4 l/s0,2 l/s0,14 l/s
Dep
th[m
]
time[°C] 0
260
Measurement example: DTRT
Example of results from DTRT
10
30
50
70
90
110
130
150
170
190
210
230
250
2.5 3 3.5Djup
[m]
λberg [W/mK]
‐250
‐200
‐150
‐100
‐50
03 3,2 3,4 3,6 3,8 4
Djup [m]
Värmelednings förmåga [ W/mK]
0
50
100
150
200
250
300
9.0 11.0 13.0 15.0 17.0 19.0
Dju
p [
m]
Temperatur [°C]
Stockholms University
130 boreholes230 m deep
Winter: 1400 kW2,5 / 6,0 ºC
Summer: 2500 kW31 / 25 ºC
Hesselmannskastiftelsen
How to include DTS in design and monitoring of large bore fields ?
Installationsite
Optical fiber cables outside the BHE pipes
Some g-functions in zone 12
0
10
20
30
40
50
60
70
80
90
‐11 ‐9 ‐7 ‐5 ‐3 ‐1 1 3 5
g‐functio
n
ln (9FoH)
Single borehole
Two boreholes
Manifold 12
Whole Installation
Theory and practice
0
20
40
60
80
100
120
140
160
180
200
220
9 11 13 15 17 19 21 23 25
Djup
[m]
Temperatur [C]
0,5 l/s0,4 l/s0,2 l/s0,14 l/s
0
50
100
150
200
250
300
9.0 11.0 13.0 15.0 17.0 19.0
Dju
p [
m]
Temperatur [°C]
Measured data vs.models byPatricia Monzóand Alberto Lazzarotto
First DTRT: Frescati
Preliminary results
KTH team: FRESCATI PROJECT
KTH energiteknikKTH byggnadsteknik
KTHs team:Patricia Monzó, doktorandDavide Rolando, researcherAlberto Lazarotto, doktorand (PhD tomorrow !!)José Acuña, researcherProf. Björn PalmProf. Folke Björk
An example from USA
Borehole Thermal Energy Storage (BTES)
• Albany, GA• BTES• 306 boreholes• About 64 m deep
DTS at the BTES
DTS
X
X
Monitoring borehole, splice box
First DTS measurement (raw data)
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
0
200
400
600
800
1000
1200
1400
1600
1800
2000
0 500 1000 1500 2000 2500
Tempe
rature [ºC]
Signal strength
Measured length [m]
Stokes
anti‐Stokes
temperature (°C)
DTRT0
10
20
30
40
50
60
70
80
90
100
110
19 24 29 34 39 44
Depth [m
]
Temperature [ºC]
A DTRT has been recentlycarried out in order to get a better insight about the geology