Design and development of a two-phase closed loop
thermosyphon for CPU cooling
Miguel Andrade Pereira Barata Moura
IN+ - Instituto Superior Técnico, Universidade de Lisboa, Av. Rovisco Pais, 1049-001 Lisbon, Portugal
ABSTRACT The present work comprises the design and development of a benchmark facility based on a two-phase closed
loop thermosyphon. This study aims at inferring on the feasibility of pool boiling of dielectric fluids to be used as a
CPU cooling technique.
The devised system acts as a modular benchmark facility, allowing a detailed analysis of the various parameters
that influence its performance, which were investigated for steady state and transient working conditions.
Regarding the use of micro-structured surfaces, the micro-patterns consist of arrays of laser etched cavities, with
fixed shape and dimensions, so the sole varying parameter is the distance between cavities. The results show
that the overall thermal resistance is reduced 21% using the surface with cavities distance of 300μm, when
compared to the performance evaluated for a smooth surface. In transient power steps, the onset of nucleate
boiling was identified as the critical parameter influencing the system performance, due to the overshoot in the
temperature above steady-state values.
The tilt angle affects the overall performance of the system: a 10º inclination, compared to the horizontal position
lead to a decrease in 5% of the overall thermal resistance.
Concerning the orientation of the evaporator, the cooling system has a lower performance for the evaporator
mounted in the vertical position. However, this outcome is balanced by the benefits arising from more application
oriented implementation.
Based on this analysis, the geometry of the final system was optimized. The final thermal resistance achieved
was 𝑅𝑗𝑎=0.29 ºC/W for a heat load Q=130W.
Keywords
Pool boiling, closed loop thermosiphon, CPU cooling system, overall thermal resistance, micro-structured
surfaces
INTRODUCTION
Moore’s law states that the number of transistors in an integrated circuit (IC) approximately doubles every two
years [1]. In fact, half-century later this prediction is held true, in such a way that it has become a mandatory
target in every major computer-chip manufacturers. The exponential increase in the number of transistors
associated to larger clock frequencies and subsequently smaller packaging led to a significant increase of the
heat power dissipated. Such increase has been possible until 2004, when the Intel Pentium 4 processor appears
and becomes widely known due to severe thermal management failures. Single-core architecture was replaced
by multi-core architectures along with multi-thread software optimization, distributing the computational load
2
across multiple and less powerful processors [3]. However, a decrease in the performance slope is notorious after
the multi-tread implementation when considering numerical simulations or computer gaming applications [4].
Hennessy and Patterson [2] state that thermal management of electronic devices is the major limitation in the
development of new processors in the near future. [5] state that the conventional air cooled systems have trouble
accompanying the heat flux generated by constant increase of clock frequency and number of transistors. In line
with this, the development of new CPU cooling techniques has been broadly studied. Liquid single-phase cooling
or two-phase heat-pipe heatsinks are the most efficient technologies available on the market, although in spite of
that, they are still widely studied in the literature [e.g. 6-7]. Phase-change technologies are considered as the
most promising heat transfer techniques owing to the latent heat of vaporization, which is associated to typical
heat transfer coefficients of 104 W/m2K, much higher that the value of 102 W/m2K, typical obtained from air-forced
convection. In this context, forced convection two-phase micro-channels, spray-cooling or pool boiling, among
others are widely studied [e.g. 8-10]. Considering the later, in spite of being characterized with a typical lower heat
transfer coefficient, when compared to other two, it is in fact considered as the most promising solution in the field
of electronic cooling, due to its inherent lower level of complexity, the higher reliability, ease of manufacturing and
implementation. However despite flourishing literature review exist in the optimization process of this device [11-
12], from the literature reviewed only few studies investigated the possibility of implementing a cooling solution for
CPU, based on two phase thermosyphons [13-16]. In any case, the authors who performed this kind of analysis
all agreed that there is in fact the convenience of using such a device as a CPU cooling technique.
In this context, the present work addresses the investigation, design and development of a bench mark
experimental facility based on a two-phase closed loop thermosyphon to address the feasibility of pool boiling as
a cooling technique for the replacement of conventional ones and implementation on desktop computers for
dedicated use.
CONTROL AND VALIDATION OF A TRANSISTOR AS A CPU SIMULATOR
Controlling circuit
Although in a different scale, a transistor is in fact the fundamental building element of a processor’s core
integrated circuit. The experimental setup shown in Figure 1 was used to understand and to optimize all the
parameters in order to precisely control the power dissipate by a transistor.
a) b)
Figure 1 - a) Electronic control circuit diagram; b) Experimental setup
In order to simulate an extremely demanding CPU a Pentium 4 like configuration was chosen, due to the fact that
it has a single-core architecture which means that the dissipated heat flux through the die is much higher than that
in recent multi-core technologies. The selected transistor is a IRFP450 N-channel power MOSFET with a TO-247
package. Relevant characteristics are the maximum dissipated power of 190W and its Integrated Heat Spreader -
3
IHS which has a contact area of 172mm2. Thus, this device can simulate the thermal behavior of the
aforementioned processor, with a maximum heat flux dissipation of 110.47W/cm2. Maximum junction temperature
is 150ºC, much higher than in any CPU, to allow a safe margin in the operating temperature of the system.
Furthermore, its considerably high on-state internal resistance allows higher voltage for the same current and
dissipated power, thus allowing the power supply to work in a more stable condition. Figure 2 depicts a visual
comparison between an actual die size of a 2005 Intel Pentium 4 CPU and the transistor chosen. CPU die size is
200mm2 and the transistor IHS is 172mm2.
Figure 2 – Intel Pentium 4 IHS bottom view (left), processor die top view (centre) and selected transistor bottom view (right).
The developed electronic circuit imposes constant current in the transistor, so the user can control the dissipated
power by means of the DC power supply frontal voltage controls. However, the integrated potentiometer does not
provide precise control of the resulting dissipated power. This means that, to allow a full and more precise
simulation the CPU thermal behavior, automation of the power supply is also required. Due to the
abovementioned reason, a control system has to be developed, comprising a user interface panel.
The resulting circuit and user interface panel comprise the following features: manual control of voltage output;
automatic control via programed micro-controller; trigger of a pre-programed sequence by means of micro-
controller programing.
Finally, the transistor CPU simulated system must be integrated in a functional way with the cooling device to be
developed. In this scope, the entire package is surrounded by a PTFE 2cm thickness block and 10cm in diameter,
to minimize heat losses to the environment. The only open boundary is the top of the IHS to interact with the
cooling system. Four compression springs hold the simulated package together and contact pressure
reproducibility is assured due to known spring deflection, in order to reproduce the same contact resistance
between the transistor, thermal grease and IHS in every experiment. Concerning junction temperature acquisition,
a 0.6mm hole was drilled in the side base of the transistor up to the mid-section to accommodate a 0.5mm K-
Type insulated probe thermocouple. Insulated probes have lower response time but, reminding that the drilled
section of the transistor is in electrical contact with the Emitter, a voltage difference above ground is expected,
which would compromise temperature readings
Validation
In the present work, efforts were conducted in order to accurately replicate a CPU thermal behavior, namely the
power density, the die size and the materials. Although the IHS has the exact same material and dimensions, and
the simulated die dimensions are similar to those of s real CPU, the thermal response of this CPU simulator must
be validated under steady-state and transient power loads. Infrared thermography was used to infer on the
temperature distribution and peak temperature of the transistor and of the CPU, respectively. An example of
obtained temperature profile of the two devices in reported in Figure 3.
4
ºC
a) b)
Figure 3 - IR image of CPU and transistor assembly at PD=15W. a) Intel Pentium 4; b) Simulator of the CPU thermal behaviour. Dashed lines indicate acquisition region.
The dashed line in the figures indicates the pixel region where temperature values were acquired. These are
quantitatively reported in Figure 4. From the plot depicted in this figure, it can be clearly inferred that the
temperature distribution and the maximum temperature of the two tested electronic devices is very similar. This
confirms that the chosen transistor can properly simulate the thermal behaviour of the CPU under investigation, in
the present study.
Figure 4 - Temperature profile a) and maximum temperature b) measured by IR thermography
FINAL EXPERIMENTAL FACILITY DESIGN
Evaporator design
Given the importance of the evaporator to the overall thermal performance of the cooler, particular attention was
given to the design of this element. The major conditions to be satisfied in the design of the evaporator are listed
as follows:
- Possibility to interchange the evaporator surface.
- Material compatibility with the fluid and resistance to the operational temperature.
- Possibility to change the size of the pool.
- Presence of Vapour line and Liquid line connections
- Possibility to accommodate pressure and temperature sensors
- Possibility to operate in vertical and horizontal positions.
- Minimum size compatible with thermal requirement of the fluid (critical heat flux 18 𝑊/𝑐𝑚2 ).
PD
5
Due to structural stiffness and ease of manufacturing, an acrylic cylindrical based evaporator was selected, with
an inner diameter of 42 mm. The cylindrical evaporator was machined with two grooves for Viton O-rings, a liquid
return line and a slot to accommodate the thermocouple measuring the liquid saturation temperature. The cover
comprises the pressure transducer and the vapour outlet.
The final design of the evaporator is schematically represented in Figure 5.
1. Liquid inlet line;
2. Vapour outlet line;
3. Aluminum interface surface;
4. Pressure tap;
5. Pressure taps for differential
measurement;
6. Thermocouples;
7. Fill / exhaust valve;
8. CPU simulated heat source;
Figure 5 - Final design of the evaporator
Condenser design
The selected condenser consists radiator-like geometry comprising flat tubes with plain serpentine fins. Due to the
particular geometry of the system, no corresponding correlations were found in literature. Hence, a numerical
CFD simulation using a commercial code (COMSOL Multiphysics 4.3b) was carried out in order to infer on the
heat transfer performance of the abovementioned geometry. Figure 6 identifies the simulated domains and the
boundary conditions used in the simulation.
a) b) c)
Figure 6 - a) CAD model; b) fluid and solid domain mesh; c) Qualitative temperature distribution in both domains for ReDh = 280 in a single element of the plain serpentine fins.
The performed simulation allowed evaluating the heat transfer of the entire condenser. The resulting value was
equal to 217 𝑊 at atmospheric pressure, which is an acceptable value. The simulation shows that a single row of
22 mm flat tubes with a frontal area of 120 𝑚𝑚 x 120 𝑚𝑚 is sufficient to remove the heat generated in the process
and consequently condense the fluid.
8
6
Figure 7 - Overview of the final condenser
Final experimental facility design
The thermosyphon developed here was then tested in a modular benchmark facility, which was assembled to
address the effect of several parameters on the performance of the devised cooling system. In this context, the
effect of the surface structure, condenser positioning and arrangement, evaporator orientation and dimensions
was investigated for both steady and transient operating conditions.
Figure 8 - Overview of the complete two phase closed loop thermosyphon
The following measurement instrumentation was use during the test:
- A GEFRAN -1..2bar gauge pressure is flush-mounted into the vapour line, connecting the evaporator to
the condenser inlet. Error in the pressure reading according to the manufacturer were of 0.05%FSO
acquired by a NI USB-6008 board from National Instruments, with 12-bit resolution and acquisition
frequency to 1.0 𝑘𝐻𝑧.
- 6 K-type thermocouples by Omega, with an uncertainty of ±1ºC. The thermocouples were positioned
respectively, inside the IHS of the transistor, inside the evaporator, at the inlet and outlet of the
evaporator and of the condenser. The output signal of the thermocouples is acquired with a Data
Translation DT9828 12-bit ADC cold-junction compensated.
7
RESULTS AND DISCUSSION
Effect of surface microstructure
The parametric study developed in this work focused on the distance between cavities and, as a result, the
number of cavities in each aluminum surface. Hence, the surfaces are micro-structured with regular arrays of
cavities, with fixed size and shape. The distance between cavities is 800µm, 600µm, 400µm and 300µm.
In Figure 9a, analyzing the evolution of the thermal resistance vs the imposed heat load, under steady-state
conditions, the thermal resistance shows a clear decreasing trend as the thermal load increases. The surface
having the smallest distance between cavities and therefore the largest cavity density provided the best
performance of the system, which can be attributed to the increased number of nucleation sites, with
corresponding higher heat removal.
Tests were also performed under transient conditions, to infer on the response of the system to a steep increase
of the heat load. The plot reported in Figure 9b evidences the appearance of an overshoot, occurring due to the
fast transition from the natural convection to the nucleate boiling regime. Considering these transient power steps
and also a benchmark power load of a typical CPU, the onset of nucleate boiling was identified as the critical
parameter influencing the system performance, due to the overshoot in temperature above steady-state values.
However, due to stochastic nature of the phenomena, little conclusions can be withdrawn, exception made to the
fact that higher cavity density minimizes the overshoot. Furthermore, maximum overshoot recorded across the
entire power range tested with the surfaces of 400m and 300m was lower than 4ºC and the peak temperature
at overshoot was always lower the steady-state settled temperature, as summarized in Table 1.
a) b)
Figure 9 – a) Evolution of the thermal resistance versus the applied heat load and cavity distance; b) Typical step response in junction temperature.
Table 1 - Values of overshoot for transient conditions (power steps) obtained with the various micro-structured surfaces analysed in the present work
40 W 60 W 80 W 100 W 125 W 150 W
Smooth 0.7 1.9 2.4 5.4 4.6 7.9
𝐒 = 𝟖𝟎𝟎µ𝐦 5.0 5.5 4.3 4.5 4.0 4.8
𝐒 = 𝟔𝟎𝟎µ𝐦 4.4 4.0 4.1 3.1 4.1 2.1
𝐒 = 𝟒𝟎𝟎µ𝐦 1.7 2.2 3.8 2.2 1.0 1.0
𝐒 = 𝟑𝟎𝟎µ𝐦 1.5 2.5 3.4 3.8 1.7 0.3
8
Effect of condenser tilt angle
Regarding the effect of the tilt angle of the condenser, the results clearly show the existence of an optimum angle.
This trend is particularly clear with increasing heat loads. A polynomial fit to the resulting data allows a rough
estimative of the optimum angle, as function of the power dissipated by the cooling system. These results are
depicted in Figure 10. In the design process of a thermosyphon for CPU cooling, the optimum tilt angle could be
chosen according to the abovementioned results. Looking towards a practical application of the devised system
and considering, for instance the CPU as an Intel i7 with a Thermal Design Point TDP=95W, it is recommended to
use a tilt angle between 9º and 13º degrees facing downward. Fortunately, the resulting optimum angle also
benefits the implementation inside the highly restricted space that is available inside a modern desktop.
Figure 10- Effect of the condenser tilt angle on the overall thermal resistance
Effect of evaporator orientation
Considering the usual vertical orientation of common processors inside a tower PC, the effect of the evaporator
orientation was investigated. The tests reported in Figure 11 show, as expected, a small decrease in the
performance of the system, when comparing to that obtained when the evaporation is mounted in the horizontal
position. However, this outcome is balanced by the benefits arising from a more application oriented
implementation.
Figure 11 - Effect of the evaporator orientation on the performance of the system
9
FINAL REMARKS
The present work comprises the design and development of a bench mark facility, which is based on a two-phase
closed loop thermosyphon. This study aims at demonstrating the feasibility of pool boiling of dielectric fluids to be
used as a CPU cooling technique.
The devised system acts as a modular benchmark facility, allowing a detailed analysis of the various parameters
that may affect its performance, which were investigated for steady state and transient working conditions.
Based on this detailed analysis, the geometry of the final system was optimized. The final thermal resistance
achieved was 𝑅𝑗𝑎=0.29 ºC/W for a heat load Q=130W.
NOMENCLATURE
Acronyms
ADC Analog to Digital Converter
CFD Computational Fluid Dynamics
CPU Central Processor Unit
IC Integrated Circuit
IHS Integrated Heat Spreader
IR Infra-Red
Latin Letters
𝐼 electrical current 𝐴
𝑞′′ heat flux 𝑊 𝑐𝑚2⁄
𝑄 heat rate 𝑊
𝑅𝑗𝑎 junction to ambient thermal resistance ℃ 𝑊⁄
𝑆 cavity distance 𝜇𝑚
𝑇 temperature ℃
𝑈 electrical voltage 𝑉
Subscripts
amb ambient
j junction
max maximum
sat at saturation conditions
ACKNOWLEDGEMENTS The authors are grateful to Fundação para a Ciência e a Tecnologia (FCT) for partially financing the research under the framework of the project RECI/EMS-SIS/0147/2012 and for supporting M. Moura with a research fellowship.
10
REFERENCES
[1] G. E. Moore, "Cramming more components onto integrated circuits," Electronics, vol. 38, no. 8, pp. 114-117,
1965.
[2] J. Hennesy and D. A. Patterson, Computer Architecture: A Quantitative Approach, Morgan Kaufmann, 2003.
[3] A. Kumar, L. Shang, L.-S. Peh and N. K. Jha, "A coordinated hardware-software approach for dynamic thermal
management," in 43rd Design Automation Conference ACM/IEEE, San Francisco, CA, 2006.
[4] D. Brooks and M. Martonosi, "Dynamic thermal management for high-performance microprocessors," in
Seventh International Symposium on High-Performance Computer Architecture, Washington, DC, 2001.
[5] T. Cader, L. J. Westra and R. C. Eden, "Spray Cooling Thermal Management for increased Device Reliability,"
IEEE Transactions on Device and Materials Reliability, 2004.
[6] P. Naphon , S Wiriyasart “Liquid cooling in the mini-rectangular fin heat sink with and without thermoelectric
for CPU” International Communications in Heat and Mass Transfer 36 (2009) 166–171
[7] K. S. Kim, M. H. Won, J. W. Kim and B. J. Back. Heat pipe cooling technology for desktop PC CPU, Applied
Thermal Engineering, 23, pp. 1137- 1144, 2003.
[8] L. Jiang, J. M. Koo, S. Zeng, J. C. Mikkelsen, L. Zhang, P. Zhou, J. G. Santiago, T. W. Kenny, K. E. Goodson,
J. G. Maveety and Q. A. Tran, “Two-Phase Microchannel Heat Sinks for an Electrokinetic VLSI Chip Cooling
System” , Proc. of the 17th IEEE SEMI-THERM Symposium, 2001, San Jose, CA, pp. 153–157.
[9] H. Bostanci, D. Rini, J. Kizito, Chow and Louis, “Spray Cooling with Ammonia on microstructured Surfaces:
Performance Enhancement and Hysteresis Effect,” Journal of Heat Transfer, vol. 131, 2009
[10] A. Franco and S. Filippeschi “Experimental analysis of heat and mass transfer in small dimension, two-phase
loop thermosyphons” Heat Pipe Science and Technology, An International Journal, 1(2):163–182, 2010
[11] J. Yeo, S. Yamashita, M. Hayashida, S. Koyama, “A Loop Thermosyphon Type Cooling System for High Heat
Flux” Journal of Electronics Cooling and Thermal Control, 2014, 4, 128-137
[12] W. T. Kim, K. S. Song and Y. Lee “Design of a Two-Phase Loop Thermosyphon for Telecommunications
System - Experiments and Visualization” KSME International Journal, Vol. 12, No. 5, pp. 926-941, 1998
[13] R. L. Webb, S. Yamauchi, S. Denko, and K. K. Tochigi, “Remote Heat Sink Concept for High Power Heat
Rejection” IEEE Transactions on Components and Packaging Technologies, 25, 608-614,2002
[14] A. Pal, Y Joshi, M. H. Beitelmal, C. D. Patel and T. Wenger,”Design and performance evaluation of a
compact thermosyphon", IEEE Transactions on Components and Packaging Technologies, 25(4), pp. 601-
607. 2002
[15] P. E. Tuma” Evaporator/Boiler Design for Thermosyphons Utilizing Segregated Hydrofluoroether Working
Fluids," Proceedings 22nd IEEE SEMI-THERM Symposium, 2006.