descargadores ABB selección

8
Insulation withstand and clearances with EXLIM and PEXLIM surge arresters Technical information In order to reduce the risk of insulation failure to an economically and opera- tionally acceptable level, the insulation withstand of substation equipment is selected with regard to expected over-voltages, taking into account the protective characteristics of the surge arresters. This technical information discusses the different aspects of insulation withstand and provides guidelines for positioning EXLIM and PEXLIM surge arresters in outdoor substations.   The insu lati on co-o rdin atio n o f a surg e ar reste r in the netw ork needs to consider its own dimensioning according to protec- tive characteristics as well as its positioning relative to other equipment and grounded objects so as not to increase the total risk for insulation failure. The insulation withstand proper- ties of surge arresters in a substation can be divided into:  insulation withstand of the surge arrester itself, including the insulation between flanges and grading rings, etc. insulation withstand between the sur ge arrester and groun- ded objects  insulation withstand between the sur ge arrester and other equipment connected to the same phase, e.g. bushings.  insulation withstand between surge arr ester s in adjacent phases.  The i nsulat ion withst and is the o nly co nstrai nt wh en sel ecting suitable clearances for EXLIM and PEXLIM surge arresters. Any effects various phase-to-ground and phase-to-phase clearan- ces may have on the voltage distribution along the ZnO block column have been accounted for in the design of EXLIM and PEXLIM arresters, e.g. by the use of optimized grading rings.  The i nsulat ion withst and o f the surge arrester itsel f has been thoroughly considered in the design of EXLIM and PEXLIM sur- ge arresters. Spacings between metal anges as well as spa- cings between anges and grading rings, are sufciently large to withstand overvoltages appearing during current discharges.  The insulation with stan d o f EX LIM and PEXL IM arresters has been verified by tests according to international standards, and the values obtained exceed the minimum requirements, generally by a good margin. PEXLIM surge arresters permit close placement to give the best protection.

Transcript of descargadores ABB selección

Page 1: descargadores ABB selección

7/27/2019 descargadores ABB selección

http://slidepdf.com/reader/full/descargadores-abb-seleccion 1/8

Insulation withstand and clearances withEXLIM and PEXLIM surge arresters

Technical information

In order to reduce the risk of insulation

failure to an economically and opera-

tionally acceptable level, the insulation

withstand of substation equipment

is selected with regard to expected

over-voltages, taking into account the

protective characteristics of the surge

arresters. This technical information

discusses the different aspects ofinsulation withstand and provides

guidelines for positioning EXLIM and

PEXLIM surge arresters in outdoor

substations.

 

 The insu lation co-ordination of a surge ar rester in the network

needs to consider its own dimensioning according to protec-

tive characteristics as well as its positioning relative to other

equipment and grounded objects so as not to increase the

total risk for insulation failure. The insulation withstand proper-ties of surge arresters in a substation can be divided into:

 − insulation withstand of the surge arrester itself, including

the insulation between flanges and grading rings, etc.

− insulation withstand between the surge arrester and groun-

ded objects

 − insulation withstand between the surge arrester and other

equipment connected to the same phase, e.g. bushings.

 − insulation withstand between surge arresters in adjacent

phases.

 The insulat ion withstand is the only constraint when selecting

suitable clearances for EXLIM and PEXLIM surge arresters. Any

effects various phase-to-ground and phase-to-phase clearan-

ces may have on the voltage distribution along the ZnO block

column have been accounted for in the design of EXLIM andPEXLIM arresters, e.g. by the use of optimized grading rings.

 The insulat ion withstand of the surge arrester itsel f has been

thoroughly considered in the design of EXLIM and PEXLIM sur-

ge arresters. Spacings between metal flanges as well as spa-

cings between flanges and grading rings, are sufficiently large

to withstand overvoltages appearing during current discharges.

 The insulat ion withstand of EXLIM and PEXLIM arresters has

been verified by tests according to international standards,

and the values obtained exceed the minimum requirements,

generally by a good margin.

PEXLIM surge arresters permit close placement to give the best protection.

Page 2: descargadores ABB selección

7/27/2019 descargadores ABB selección

http://slidepdf.com/reader/full/descargadores-abb-seleccion 2/82 Technical information | ABB Surge Arresters

Phase-to-ground clearance

 The phase-to-ground clearance in substations is usual lybased on the selected standard rated lightning and switching

impulse withstand voltages. International standards, e.g.

IEC 60071-1, recommend minimum clearances.

In general, the clearance between a grounded object and an

EXLIM or PEXLIM surge arrester should be the same as the

phase-to-ground clearance selected for other high voltage

equipment in a substation. If it is not possible to use the

normal phase-to-ground clearance in special applications of

EXLIM or PEXLIM arresters, a smaller clearance may be cho-

sen, considering the protective characteristics of the arrester.

The Adjusted Protective Level to be used in Figure 2,

is defined as:

For lightning impulse:

Upl x 1.15 x em(H/8150)

For switching impulse:

Ups x 1.10 x em(H/8150)

Where H is the altitude in meters above sea level.

Upl and Ups are the lightning and switching impulse pro-

tective levels for the selected EXLIM and PEXLIM surge

arresters at the respective co-ordinating currents.Table 1 suggests appropriate co-ordinating currents for

different system voltage levels.

Co-ordinating currents

Lightning impulse Switching impulse

up to 420 kV 10 kA below 145 kV 0.5 kA  

550 kV 15 kA 145-362 kV 1.0 kA  

800 kV 20 kA 420-800 kV 2.0 kA  

> 800 kV 20 kA > 800 kV 2.0 kA  

Table 1

Exponent ¨m¨ depends on various parameters includingminimum discharge path. For insulation co-ordination

purposes, with reference to IEC 60071-2, exponent m may

be conservatively taken to be as per Table 2.

 This is possible because there is usually a fa irly large marginbetween the standard rated withstand voltage for a substa-

tion and the protective level of EXLIM or PEXLIM arresters.

Furthermore, distance effects by fast transients do not exist in

the immediate vicinity of the surge arrester.

 Thus, the recommended minimum phase-to-ground clearance

for EXLIM and PEXLIM surge arresters, with regard to light-

ning and switching overvoltages, are presented in Figure 2.

 These clearances are based on IEC 60071-1, Tables A.1 and

 A.2, and on the protective characterist ics of the surge arres-

ter. They include safety margins and altitude correction.

Exponent m

System

voltage

Lightning

impulse

Switching

impulse

≤ 800 kV 1.0 1.0

> 800 kV 1.0 As per Fig. 1

Table 2

Figure 1: Dependence of exponent m on the co-ordination switching im-

pulse withstand voltage.

Where Ucw = 1.1 x Ups for phase to ground. For phase-to-

phase, Ucw is equivalent to the rated switching impulse

withstand voltage phase-to-phase.

The minimum clearance is determined either by lightning

or switching impulse withstand, whichever renders a lar-

ger value. In case the clearance requirements for arres-

ters on systems greater than 800 kV calculated from the

above are higher than selected for the protected equip-ment, the same clearance requirements as for the equip-

ment should also apply for the arresters.

0.0

1000 2000 Ucw [kV]

0.5

1.0

m

Phase-to-phase

Phase-to-ground

Page 3: descargadores ABB selección

7/27/2019 descargadores ABB selección

http://slidepdf.com/reader/full/descargadores-abb-seleccion 3/8 ABB Surge Ar resters | Technical information 3

Other equipmentin the same phase

 The clearance between an EXLIM or PEXLIM surge ar resterand other high-voltage equipment connected to the same

phase, e.g. bushings or post insulators, is usually not of

importance during normal operating conditions. In polluted

conditions, however, the transient voltage distribution on

the insulator surfaces may become extremely uneven. This

creates high voltage stresses between the surge arrester

housing and any high-voltage insulator positioned nearby.

It is recommended therefore to choose half the phase-to-

ground clearance determined in the previous section for the

spacing between the upper (energized) end of the EXLIM or

PEXLIM surge arrester, and the top (energized) end of otherhigh-voltage equipment.

Furthermore, for the case of an inclined high-voltage equip-

ment e.g. a bushing, it is recommended to use the phase-

to-ground clearance selected for the surge arrester also for

the spacing between the lower (grounded) end of the surge

arrester, and the bottom (grounded) end of other high-volta-

ge equipment.

Figure 3 shows these recommendations, where D is the

selected phase-to-ground clearance for the selected EXLIM

or PEXLIM surge arrester. For the case with a verticallymounted bushing and if a PEXLIM arrester is used with a

better pollution performance than a porcelain type EXLIM

arrester the suggested required distance D at the lower end

may be omitted.

6

5

4

3

2

2

1

1

0

0

2

1

0

6

5

4

3

2

1

0

0

0

500

500

1000

1000

1500 2000

Phase-to-ground Clearance [m]

Switching impulse

Switching impulse

Lightning impulse

Lightning impulse

 Adjusted Protective Level [kV]

Figure 2 Figure 3: Clearance to other high-voltage equipment in the same phase

Recommended minimum phase-to-ground clearance

D

D  / 2 

Page 4: descargadores ABB selección

7/27/2019 descargadores ABB selección

http://slidepdf.com/reader/full/descargadores-abb-seleccion 4/84 Technical information | ABB Surge Arresters

Phase-to-phase clearance

 The phase-to-phase clearance for high-voltage equipment ina substation is normally based on the selected standard rated

lightning and switching impulse phase-to-phase withstand

voltages. International standards, e.g. IEC 60071-1 recom-

mend minimum phase-to-phase clearances. Note that the

normal selection of surge arrester protective levels does not

directly protect the phase-to-phase insulation since two arres-

ters in series must be considered.

In general, the clearance between EXLIM and PEXLIM surge

arresters in adjacent phases should be the same as the

phase-to-phase clearance selected for other high-voltage

equipment in the substation. If it is not possible to use thenormal phase-to-phase clearance in a special application of

EXLIM or PEXLIM surge arresters, the minimum clearance

with regards to lightning overvoltages can be derived from Fi-

gure 4. The electrode configuration established by the grading

rings on two adjacent EXLIM or PEXLIM surge arresters which

are equipped with grading rings is more favourable compared

to arresters without grading rings. Therefore separate curves

are given in Figure 4 for EXLIM or PEXLIM arresters with or

without grading rings.

 The clearances shown in F igure 4 are based on the assump-

tion that one phase is subjected to a lightning overvoltage,while the voltage on the adjacent phase is at the peak of the

maximum power frequency operating voltage (opposite pola-

rity). Obviously, these clearances will also cover the case of

lightning overvoltages of the same polarity appearing simulta-

neously on two or three phases.

 − The Adjusted Protective Level shown in Figure 4 isbased on the lightning protective characteristics of the

selected EXLIM or PEXLIM surge arrester. It includes

safety margin and altitude correction factor. and is

defined as:

Upl x 1.15 x eH/8150

+ Um x √2/ √3

where

− Um is according to IEC 60071-1 the highest voltage for

equipment, which is usually equal to the highest systemvoltage.

 − Upl is the lightning impulse protective level for the se-

lected EXLIM or PEXLIM arrester at the recommended

co-ordination current (see Table 1).

− H is the altitude in meters above sea level.

 The minimum phase-to-phase clearance for EXLIM or PEX-

LIM arresters with respect to switching overvoltages should

always be based on the selected standard rated switching

impulse phase-to-phase withstand voltage for the substation.Consequently the clearances specified in IEC 60071-1, Table

 A.3, are valid for most applications of EXLIM and PEXLIM

arresters. If a special application requires a minimized phase

spacing, the favourable electrode configuration established by

the grading rings on EXLIM and PEXLIM surge arresters may

permit a further reduction of the phase-to-phase clearance.

Figure 5 shows recommended phase- to-phase clearances

for EXLIM and PEXLIM surge arresters equipped with grading

rings with regard to switching overvoltages. These clearances

are derived from the Transmission Line Reference Book,

345 kV and above, Second Edition, Figure 11.8.10, with anadequate safety margin applied. The necessary altitude cor-

rection should, by definition, be included in the standard rated

switching impulse phase-to-phase withstand voltage selected

for the substation.

 The minimum phase-to-phase clearance is determined eit-

her by the lightning or by the switching impulse withstand,

whichever renders the larger value.

PEXLIM surge arresters offer flexibility for the mounting arrangement to

allow optimum placement.

Page 5: descargadores ABB selección

7/27/2019 descargadores ABB selección

http://slidepdf.com/reader/full/descargadores-abb-seleccion 5/8 ABB Surge Ar resters | Technical information 5

Figure 4

Figure 5

Note. Rated switching impulse withstand voltage shall include altitude

correction if applicable.

Recommended minimum phase-to-phase clearancefor lightning overvoltages

Recommended minimum phase-to-phase clearancefor switching overvoltages

2

1

0

5

4

3

2

1

0

5

4

3

2

1

0

0

0 500 1000

2000 2500 300015001000500

Phase-to-phase Clearance [m]

With grading ring

With grading ring

Without

grading

ring

Without grading ring

 Adjusted Protective Level [kV]

0

00 500 1000

1

2

0

1

2

0

2

4

6

8

10

0

2

4

6

8

10

0 500 1000 1500 2000 2500 3000

Phase-to-phase Clearance [m]

Rated Switching Impulse Phase-to-Phase Withstand Voltage [kV]

With grading ring

Page 6: descargadores ABB selección

7/27/2019 descargadores ABB selección

http://slidepdf.com/reader/full/descargadores-abb-seleccion 6/86 Technical information | ABB Surge Arresters

Example

 The following example shows theapplication of the presented guidelines

for selecting minimum clearances for

EXLIM and PEXLIM surge arresters in a

420 kV substation.

 The substat ion is s ituated at an alti tude of 200 m above sea

level and equipped with arresters type EXLIM P360-GM420. The basic insulation withstand data for the substation is:

 − Rated lighting impulse withstand voltage:

1425 kV phase-to-ground

− Rated switching impulse withstand voltage:

1050 kV phase-to-ground

1575 kV phase-to-phase

 According to IEC 60071-1, Tables A.1 and A.2, the minimum

recommended phase-to-ground clearance is 2.6 m. The

recommended minimum phase-to-phase clearance is 3.6 m,according to IEC 60071-1, Table A.3. We assume that these

clearances are not possible to achieve for the surge arresters

in this example. The minimum permissable values can be

determined as follows:

 According to Table 1 the appropria te co-ordinating dischar-

ge currents for a system voltage level of 420 kV are 10 kA

for lightning impulse and 2.0 kA for switching impulse. The

corresponding protective levels of the EXLIM P360-GM420

surge arrester used in this substation are 819 kV and 728 kV

respectively (see ABB Buyer’s Guide).

 The Adjusted Protective Level to be used in Figure 2 for deter-mination of the phase-to-ground clearance, is:

− For lightning impulse:

819 x 1.15 x e200/8150 = 965 kV

− For switching impulse:

728 x 1.10 x e200/8150 = 821 kV

 As seen in F igure 2, phase- to-ground clearances o f 2 .0 m

and 1.9 m are required. The minimum phase-to-ground clea-

rance is therefore the higher value of these two i.e. 2.0 m.

 The Adjusted Protective Level to be used in Figure 3 for deter-

mination of the phase-to-phase clearance is:

− For lightning impulse:

819 x 1.15 x e200/8150 + 420 x √2/ √3 = 1308 kV

The EXLIM P360-GM420 is fitted with grading rings.

 According to figure 4 a minimum clearance of 2.0 m is

required based on the lightning impulse strength.

− For switching impulse, the minimum phase-to-phase

clearance for the surge arrester is based on the rated

switching impulse withstand voltage of the substation,since the phase-to-phase clearance in a substation is

normally not protected by the arresters.

In this case, the selected rated switching impulse with-

stand voltage phase-to-phase is 1575 kV. As seen in

Figure 5, the required minimum phase-to-phase clea-

rance, taking into account the favourable electrode con-

figuration created by the grading rings, is 3.0 m.

 

Hence, the minimum permissable clearances for the EXLIM

P360-GM420 surge arresters in our example substation are

2.0 m phase-to-ground and 3.0 m phase-to-phase.

Page 7: descargadores ABB selección

7/27/2019 descargadores ABB selección

http://slidepdf.com/reader/full/descargadores-abb-seleccion 7/8 ABB Surge Ar resters | Technical information 7

Page 8: descargadores ABB selección

7/27/2019 descargadores ABB selección

http://slidepdf.com/reader/full/descargadores-abb-seleccion 8/8

   1   H   S   M    9

   5   4   3   1   6  -   0   1  e  n   E   d   i   t   i  o  n   1 ,

   2   0   1   2  -   0   6 ABB AB

High Voltage Products

Surge Arresters 

SE-771 80 Ludvika, Sweden

Phone: +46 (0)240 78 20 00

Fax: +46 (0)240 179 83

E-Mail: [email protected] 

www.abb.com/arrestersonline 

©Copyright 2011 ABB

 All r ights reserved

NOTE! ABB AB is working continuously to

improve the products. We therefore reserve the

right to change designs, dimensions and data

without prior notice.