Department of Electrical Engineering The Graduate College
Transcript of Department of Electrical Engineering The Graduate College
Al-Nileain University
Department of Electrical Engineering
The Graduate College
Generators Protection of Haggling Power Plant
Station
A thesis Submitted for Partial Fulfillment of the
Requirement for the master Degree in Electrical
Engineering
Prepared by:
Mohammed NourUlhudaAhammed
Supervisor:
Dr. Abdelrahim Ate
August 2018
1
ةـــــــــالآي
:قال تعالى
(وَقُمِ اعْمَهُواْ فَسَيَرَى انهّهُ عَمَهَكُمْ وَرَسوُنُهُ وَانْمُؤْمِنُونَ)
105
2
Dedication
This thesis is dedicated to :The sake of Allah , my creator and my
Master .
My great teacher and messenger , Mohammed (May Allah bless and
grant him ), who taught us the purpose of life.
My homeland Sudan .
Al neelainuniversity : my second magnificent home: My great
parents and my wives, I have to thank my parents for their love
and support
throughout my life .
Thanks you both for Dr.Alategiving me strength to reach for the stars
and chase
My dreams.
My beloved brothers and sisters .
My friends who encourage and support me , All the people in my life
who touch my heart , I dedicate this research .
3
Acknowledgment
In the Name of Allah . The Most Merciful , the most
compassionate all praise be to Allah , the Lord of the worlds : and
prayers be upon Mohamed His servant and messenger .
We would like to express our gratitude for everyone helped us
duringthe graduation project .
Starting with endless thanks for our supervisor Dr .Altewho
never stop encouraging us to do a great job .
Providing our group with valuable information and advice to be
better each time , Thanks for the continuous support and kind
communication witch had a great effect regarding to feel interesting
about what we are working on.
Also , we would like to say many thanks our neelain for their
endless support and their huge effort in contacting and providing us
with all what WE need for our graduation project . Also , we would
like to thank teachers that help us very much specially elate .
4
Abstract:
The Problem Statement an electrical generator can be subjected
either internal faults or external faults or both, hence any fault occurred in
the power system should be cleared in the power from the generator as
soon as possible otherwise it may create permanent damage in the
generator , the number and variety of fault occur in the generator are huge.
That is why generator is protected with several protection schemes so in
this thesis are working to protect the expensive equipment. The object of
this project is to design generators protection of flegglig power plant by
using ETAP program. so as an electrical generator can be subjected either
internal faults or external faults or both, hence any fault occurred in the
power system should be cleared in the power from the generator as soon
as possible otherwise it may create permanent damage in the generator ,
the number and variety of fault occur in the aenerator are huge. That is
why generator is protected with several protection schemes. In this thesis
the one line diagram of Hegglig generation grid was simulated by using
ETAP program and we run load flow analysis to calculate the steady state
current (Is) and to choose suitable current transformers (CTs) ratio
connected with relays. After that we run short circuit analysis in all system
to calculate the short circuit current and determine the size of protection
devices. Then we used these values to calculate the value of T.M.S (Time
Multiplier Setting), or time operation and pick up current of protective
relays that used to protect the system. Finally we run star protective device
coordination in ETAP and test the protection device coordination. The
objectives of this study are: Study the protection techniques as a general.
Design optimum generators protection methods of Hegglig power plant
substation by using ETAP program. The Methodology A one line diagram
of Hegglig generation grid was simulated by using ETAP program and we
run load flow analysis to calculate the steady state current (Is) and to
5
choose suitable current transformers (CTs) ratio connected with relays.
After that in this thesis run short circuit analysis in all system to calculate
the short circuit current and determine the size of protection devices.
The Result is summarized in four chapters, in chapter one is about
background of generator protection, thesis problems and objectives when
chapter two is studied general of the generator while chapter three is
discussed protection and faults that occur in the generator so that chapter
four is the case study in the system model by using ETAP and chapter five
is given the thesis conclusion and recommendations. We may say that the
objective of this project successfully achieved.
6
مستخلص
.
7
.
.
.
8
Table of Contents
CHAPTER ONE: INTRODUCTION
Dedication 2
Acknowledgement 3
Abstract English 4
Abstract Arabic 6
Table of Contents 8
List of Table 10
List of Figures 11
1.1 Background of Generator Protection 13
1.2 Objective 13
1.3 Problem Statement 13
1.4 Methodology 14
1.5 Thesis layout 14
CHAPTER TWO:ELECTRIC NETWORK SUPPLIES
2.1 History of generators 16
2.2 Generator working 18
2.3 Fleming's Right hand Rule 21
2.4 Types of Generator 23
2.5 Types and construction of rotors 24
2.5.1 Squirrel-Cage Rotor 25
2.5.2 Wound Rotor 26
2.5.3 Salient Pole Rotors 26
2.5.4 Cylindrical Rotors 27
2.5.5 Electrical 27
2.5.6 Uses for a Generator 27
2.5.7 Generators for Business, Commercial and Contractors 28
CHAPTER THREE: GENERATOR PROTECTION
3.1 Introduction 31
3.2 Internal Faults 31
3.3 Stator Windings Faults 31
9
3.4 Stator Differential protection for generators 32
3.5 Modified differential protection 33
3.6 Biased circulating current protection (percentage
differential relay protection)
33
3.7 Self-balance protection system 34
3.8 Stator ground fault protection 35
3.9 Stator inter turn fault protection 36
3.10 Stator over heating protection 37
3.11 Protection of Generator Rotor Earth Fault 38
3.12 Under/Over Frequency Protection 40
3.13 Under/ Voltage Protection \ Over 41
3.14 Under voltage protection 42
3.15 Protection of the Generator Due to Unbalance Loading 42
3.16 Over current fault of a generator 43
3.17 Alternator Prime Mover failure fault or reverse power
fault
43
CHAPTER FOUR: PROPOSED PROTECTION TECHNIQUES
THROUGH DIFFERENT CASES
4.1 The System Model 46
4.2 The system data are shown below 48
4.3 System Analysis 49
4.4 Protection system coordination test 52
4.4.1 Protect the fault that occur near the generator 53
4.4.2 Sequence-of-Operation Event Summary Report 54
CHAPTER FIVE: CONCLUSION & RECOMMUNDATOINS
5.1 Conclusion 56
5.2 Recommendation 56
5.3 Result 57
5.4 References 58
10
11
List of Tables
Table (4.1) Bus input Data 48
Table (4.2) 2-Winding Transformer Grounding Input Data
Grounding
48
Table (4.3) Synchronous Generator Input Data 49
Table (4.4) This data shows suitable coefficient value of the current
transformer in each point of the system model
50
Table (4.5) The slope of the time/current curve sets is determined by
the constant α and β as follow
52
Table (4.6) Symmetrical 3-phase Fault at Bus395 54
12
List of figures
Figure (2.1) Represent Generator Construction 21
Figure (2.2) Represent Generator Operation 23
Figure (2.3) Represent Fleming's Right hand Rule 24
Figure (2.4) Represent salient pole rotor 23
Figure (2.5) Represent cylindrical rotor 24
Figure (2.6) Represent Squirrel Cage rotor 25
Figure (2.7) Represent wound rotor 26
Figure (2.8) Represent cylindrical rotor 27
Figure (3.1) Differential protection for generators 32
Figure (3.2) Modified differential protection for generators 33
Figure (3.3) Biased circulating current protection for generators 34
Figure (3.4) self-biasing protection of the stator windings 35
Figure (3.5) Inter turn protection of the stator winding 37
Figure (3.6) protection against unbalance loading 43
Figure (4.1) One line diagram of Hegglig power plant
generation station
46
Figure (4.2) Testing System of Protection 54
13
CHAPTER ONE
INTRODUCTION
14
INTRODUCTION
1.1 Background of Generator Protection
Under Electrical Protection a generator is subjected to electrical traces
imposed on the insulation of the machine, mechanical forces acting on the
various parts of the machine, and temperature rises. These are the main
factors which make protection necessary for the generator or alternator.
Even when properly used, a machine in its perfect running condition does
not only maintain its specified rated performance for many years, but it does
also repeatedly withstand certain excess of over load. Hence, preventive
measures must be taken against overloads and abnormal conditions of the
machine so that it can serve safely.
Despite of sound, efficient design, construction, operation, and
preventive means of protection, the risk of that fault cannot be completely
eliminated from any machine. The devices used in generator protection,
ensure the fault, made dead as quickly as possible. The generator protection
is of both discriminative and non-discriminative type. Great care is to be
taken in coordinating the systems used and the settings adopted, so that the
sensitive, selective and discriminative generator protection scheme is
achieved.
1.2 Problem Statement
An electrical generator can be subjected either internal faults or external
faults or both, hence any fault occurred in the power system should be
cleared in the power from the generator as soon as possible otherwise it may
create permanent damage in the generator , the number and variety of fault
occur in the generator are huge. That is why generator is protected with
several protection schemesSoin this thesis are working to protect the
expensive equipment.
1.3 Objectives
The objectives of this study are:
1- Study the protection techniques as a general.
15
2- Design optimum generators protection methods of Hegglig power plant
substation by using ETAP program.
3- Analysis the overall performance of the proposed methods through
simulation results.
1.4 Methodology
A one line diagram of Hegglig generation grid was simulated by using
ETAP program and we run load flow analysis to calculate the steady state
current (Is) and to choose suitable current transformers (CTs) ratio
connected with relays.
After that in this thesis run short circuit analysis in all system to
calculate the short circuit current and determine the size of protection
devices.
in this thesis used these values to calculate the value of T.M.S (Time
Multiplier Setting), or time operation and pick up current of protective
relays that used to protect the system.
Finally we run star protective device coordination in ETAP and test the
protection device coordination.
1.5 Thesis layout
The thesis is summarized in five chapters, in chapter one is about
background of generator protection, thesis problems and objectives when
chapter two is studied general of the generator while chapter three is
discussed protection and faults that occur in the generator so that chapter
four is the case study in the system model by using ETAP and chapter five
is given the thesis conclusion and recommendations.
16
CHAPTER TWO
ELECTRIC NETWORK SUPPLIES
17
Electric Network Supplies
In electricity generation, a generator is a device that converts
mechanical energy to electrical energy for use in an external circuit. The
source of mechanical energy may vary widely from a hand crank to an
internal combustion engine. Generators provide nearly all of the power for
electric power grids.
The reverse conversion of electrical energy into mechanical energy is
done by an electric motor, and motors and generators have many
similarities. Many motors can be mechanically driven to generate electricity
and frequently make acceptable generators.
2.1 History of generators
As its name suggests, a generator generates electricity. Michael
Faraday‟s discovery of electromagnetic induction demonstrated a way to
construct a simple generator, but there was little need for such a device until
commercial technologies that used electricity, such as lights, appeared. The
earliest commercial uses of electricity, such as telegraphy, arc, and metal
electroplating used batteries as their power source. This was a very
expensive way of generating electricity.
In the 1860s and 1870s many inventors sought ways of using Faraday‟s
induction principle to generate electricity mechanically. Two kinds of
generators emerged. The first type was a generator of direct current (DC)
electricity. The second type was a generator of alternating current (AC)
electricity. In truth, a DC generator could generate AC current, but it
contains a simple device called a commutator to turn AC into DC.
A commutator reroutes the flow of electrons inside the DC generator, so
that the energy that appears at the output is a pulsing direct flow. An AC
generator does not need a commutator and generates AC directly.
18
One of the most important inventors of generators was German Werner
von Siemens, who designed improved DC generators and called them
dynamos. An even better generator was introduced by French
ZénobeThéophileGramme in 1867, which produced substantially higher
voltages than previous attempts. In 1871 he demonstrated a working model,
and with Hippolyta Fontaine began manufacturing them. Gramme‟s
dynamos
generated AC current and were widely used in arc lighting systems. In 1872,
however, von Siemens reemerged and invented what is essentially the
modern type of dynamo, referred to as the drum armature type of machine,
which was a more efficient design.
AC and DC generators were both used from the 1870s on. For
example, AC generators were used in a type of outdoor arc lighting known
as the Jablochkoff Candle. However, in the late 1870s when Thomas Edison
devised his highly successful electric lighting system, he used DC
generators. A major reason for this choice was that Edison wanted to use
electric power both for lighting (for which AC was fine) and for running
electric motors. At the time, there was no good AC electric motor available,
so DC was the only option. In 1882 Edison installed DC generators at the
Pearl Street station facilities in New York City, one of the earliest
commercial power generating plants.
As electric lighting and centrally distributed power began to achieve
commercial success in the 1880s, inventors began looking for ways to
distribute central-station power over longer distances.
Edison‟s DC system was poorly adapted to this, because he had
chosen to use 120-volt bulbs and motors. A much higher voltage would
have been easier to transmit down long wires, because at a low voltage
much energy is lost as heat. Edison stations, such as that at Pearl Street,
could be no more than about a mile from the customer. AC offered an
19
alternative: a way to generate at a low voltage, “step up” the voltage for
transmission using a simple device called a transformer, and then “step
down” the voltage at the customer premises. The only remaining problem,
though, was the lack of a suitable AC motor design.
Nikola Tesla, a Serbian immigrant to the United States, devised an
improved AC generator as well as a practical AC motor. Tesla‟s system
used polyphase AC, in which the generator generated several different AC
flows that were combined or superimposed onto one another to create a
single polyphase AC output, with the component currents “out of phase”
with one another. The Tesla motor, introduced in 1887, was designed so that
the peaks of this polyphase current supplied power at just the right moment
in the rotation of the motor, and the resulting induction motor as he called it,
ran smoothly. With a practical AC motor and generator in hand, along with
transformers to raise and lower voltage, Tesla‟s system could be used by
power companies to create ever-larger networks of power distribution using
massive power plants, such as the Niagara Falls hydroelectric plant built in
the 1890s. Larger power systems helped lower costs, which stimulated
demand for electricity, especially in homes.
Figure (2-1) Represent Generator Construction
2.2 Generator working
In the case when the coil is rotating in anticlock-wise direction without
commutator. As the coil assumes successive positions in the field, the flux
20
linked with it changes. Hence, an e.m.f is induced in it which is proportional
to the rate of change of flux linkages (e=-N dΦ/dt). When the plane of the
coil is at right angles to lines of flux then flux linked with the coil is
maximum but rate of change of flux linkages is minimum.
It is so because in this position, the coil sides do not cut or shear the flux,
rather they slide along them i.e. they move parallel to them. Hence, there is
no induced e.m.f in the coil. Generally this no e.m.f is taken as the starting
position i.e. zero degrees position. The angle of rotation or time will be
measured from this position.
As the coil continues rotating further, the rate of change of flux
linkages (and hence induced e.m.f in it) increases till the coil rotates 90°
from its starting position. Here the coil plane is vertical (see in fig) i.e.
parallel to the lines of flux. As seen, the flux linked with the coil is
minimum but rate of change of flux linkages is maximum. Hence, maximum
e.m.f is induced in the coil when in this position. In the next quarter
revolution i.e. from 90° to 180°, the flux linked with the coil gradually
increases but the rate of change of flux linkages decreases. Hence, induced
e.m.f decreases gradually till it becomes zero.
So, in this thesis find that in the first half revolution of the coil, no
e.m.f is induced in it at 0°, maximum when the coil is at 90° position anno
e.m.f when coil is at 180°.The direction of this induced e.m.f can be found
by applying Fleming's Right hand rule.
In the next half revolution i.e. from 180° to 360°, the variations in the
magnitude of e.m.f are similar to those in the first half revolution. Its value
is maximum when coil is at 270° and minimum when the coil is at
360°position.But it will be found that th direction of induced current is
reverse of the previous direction of flow.
21
Therefore, in this thesis find that the current which we obtain from such
a simple generator reverses its direction after every half revolution. Such a
current undergoing periodic reversals is known as alternating current. It
should be noted that alternating current not only reverses its direction, it
does not even keep its magnitude constant while flowing in any one
direction. The two half- cycles may be called positive and negative half-
cycles respectively.
Now see when the coil is rotating with commutator. In this case the slip
rings are replaced by split rings.
The split rings are made out of a conducting cylinder which is cut into
two halves or segments insulated from each other by a thin sheet of mica or
some other insulating material (you can see in fig). As before, the coil ends
are joined to these segments on which rest the carbon or copper brushes.
In case of split rings, the positions of the segments of split rings have
also reversed when the current induced in the coil reverses i.e when the
current direction reverses the brushes also comes in contact with reverse
segments as that of positive half-cycle.
Hence, this current is unidirectional. It should be noted that the
position of the brushes is so arranged that the changeover of segments from
one brush to other takes place when the plane of the rotating coil is at right
angles to the plane of the lines of flux. It is so because in that position, the
induced e.m.f in the coil is zero.
You can observe this in two cases by pausing the waveform. Another
important point is that now the current induced in the coil is alternating as
before. It is only due to the rectifying action of the split-rings (also called
commutator) that it becomes unidirectional in the external circuit.
22
Figure (2.2) Represent Generator Operation
2.3 Fleming's Right hand Rule
Fleming's right hand rule (for generators) shows the direction of
induced current flow when a conductor moves in a magnetic field.
Figure (2.3) represent Fleming's Right hand Rule
The right hand is held with the thumb, first finger and second finger
mutually at right angles, as shown in the diagram.
• The Thumb represents the direction of Motion of the conductor.
• The First finger represents the direction of the Field.
• The Second finger represents the direction of the induced or
generated Current (in the classical direction, from positive to
negative).
23
Electromagnetic generators fall into one of two broad categories, dynamos
and alternators.
• Dynamos generate direct current, usually with voltage or current
fluctuations, usually through the use of a commutator
• Alternators generate alternating current, which may be rectified by
another (external or directly incorporated) system.
A dynamo is an electrical generator that produces direct current with
the use of a commutator. Dynamos were the first electrical generators
capable of delivering power for industry, and the foundation upon which
many other later electric-power conversion devices were based, including
the electrical motor, the alternating-current alternator, and the rotary
converter. Today, the simpler alternator dominates large scale power
generation, for efficiency, reliability and cost reasons. A dynamo has the
disadvantages of a mechanical commutator. Also, converting alternating to
direct current using power rectification devices (vacuum tube or more
recently solid state) is effective and usually economical.
An alternator is an electrical generator that converts mechanical
energy to electrical energy in the form of alternator current for reasons of
cost and simplicity, most alternator use a rotating magnetic field with
stationary armature Occasionally, a linear alternator or a rotating armature
with a stationary magnetic field is used. In principle, any ac electrical
generator can be called an alternator, but usually the term refers to small
rotating machines driven by automotive and other internal combustion
engines. An alternator that uses a permanent magnetic for its magnetic field
is called a magneto. Alternators in power station driven by steam turbines
are called turbo-alternators. Large 50 or 60 Hz three alternators in power
plants generate most of the world's electric power, which is distributed by
electric power grid.
24
2.4 Types of Generator
Alternators or synchronous generators can be classified in many ways
depending upon their application and design. According to application these
machines are classified as:
1. Automotive type - used in modern automobile.
2. Diesel electric locomotive type - used in diesel electric multiple unit.
3. Marine type - used in marine.
4. Brush less type - used in electrical power generation plant as main
source of power.
5. Radio alternators - used for low brand radio frequency transmission.
These ac generators can be divided in many ways but we will discuss
now two main types of alternator categorized according to their
design. These are:
1.Salient pole type it is used as low and medium speed alternator. It has a
large number of projecting poles having their cores bolted or dovetailed
onto a heavy magnetic wheel of cast iron or steel of good magnetic
quality. Such generators are characterized by their large diameters and
short axial lengths. These generator are look like big wheel. These are
mainly used for low speed turbine such as in hydra power plant.
Figure (2.4) Represent salient pole rotor
2.Smooth cylindrical type it is used for steam turbine driven alternator. The
rotor of this generator rotates in very high speed. The rotor consists of a
smooth solid forged steel cylinder having a number of slots milled out at
intervals along the outer periphery for accommodation of field coils.
25
These rotors are designed mostly for 2 pole or 4 pole turbo generator
running at 36000 rpm or 1800 rpm respectively.
Cylindrical rotor cross sectional view
Figure (2.5) Represent cylindrical rotor
Mechanical
• Rotor: The rotating part of an electrical machine
• Stator: The stationary part of an electrical machine
The rotor is a moving component of an electromagnetic system in the
electric motor , electric generator or alternator. Its rotation is due to the
interaction between the windings and magnetic fields which produces a
torque around the rotor's axis.
2.5 Types and construction of rotors
Induction (asynchronous) motors, generators and alternators
(synchronous) have an electromagnetic system consisting of a stator and
rotor.
There are two designs for the rotor in an induction motor: squirrel
cage and wound. In generators and alternators, the rotor designs are salient
pole or cylindrical
2.5.1 Squirrel-Cage Rotor
The squirrel cage rotor consists of laminated steel in the core with
evenly space bars of copper or aluminum placed axially around the
periphery, permanently shorted at the ends by the end rings. This simple and
rugged construction makes it the favorite for most applications. The
26
assembly has a twist: the bars are slanted, or skewed, to reduce magnetic
hum and slot harmonics and to reduce the tendency of locking. Housed in
the stator, the rotor and stator teeth can lock when they are in equal number
and the magnets position themselves equally apart, opposing rotation in both
directions. Bearings at each end mount the rotor in its housing, with one end
of the shaft protruding to allow the attachment of the load. In some motors,
there is an extension at the non-driving end for speed sensors or other
electronic controls. The generated torque forces motion through the rotor to
the load.
Figure (2.6) represent Squirrel - Cage rotor
2.5.2 Wound Rotor
The rotor is a cylindrical core made of steel lamination with slots to
hold the wires for its 3-phase windings which are evenly spaced at 120
electrical degrees apart and connected in a 'Y' configuration. The rotor
winding terminals are brought out and attached to the three slips rings with
brushes, on the shaft of the rotor. Brushes on the slip rings allow for external
three-phase resistors to be connected in series to the rotor windings for
providing speed control. The external resistances become a part of the rotor
circuit to produce a large torque when starting the motor. As the motor
speeds up, the resistances can be reduced to zero.
27
Figure (2.7) represent wound rotor
2.5.3 Salient Pole Rotors
The rotor is a large magnet with poles constructed of steel lamination
projecting out of the rotor‟s core. The poles are supplied by direct current or
magnetized by permanent magnets. The armature with a three-phase
winding is attached to three slip rings with brushes riding on them and
mounted on the shaft.
The field winding is wound on the rotor which produces the magnetic
field and the armature winding is on the stator where voltage is induced.
Direct current (DC), from an external exciter or from a diode bridge
mounted on the rotor shaft, produces a magnetic field and energizes the
rotating field windings and alternating current energizes the armature
windings simultaneously
2.5.4 Cylindrical Rotors
The cylindrical shaped rotor is made of a solid steel shaft with slots
running along the outside length of the cylinder for holding the field
windings of the rotor which are laminated copper bars inserted into the slots
and is secured by wedges. The slots are insulated from the windings and are
held at the end of the rotor by slip rings. An external direct current (DC)
source is connected to the concentrically mounted slip rings with brushes
running along the rings. The brushes make electrical contact with the
28
rotating slip rings. DC current is also supplied through brushless excitation
from a rectifier mounted on the machine shaft that converts alternating
current to direct current.
Figure (2.8) represent cylindrical rotor
The stator is the stationary part of a rotary system, found in electric
generators, electric motors, sirens, or biological rotors. The main use of a
stator is to keep the field aligned. The stator is the stationary part of a rotary
system, found in electric generators, electric motors, sirens, or biological
rotors. The main use of a stator is to keep the field aligned.
2.5.5 Electrical Rotors
• Armature: The power-producing component of an electrical machine. In
a generator, alternator, or dynamo the armature windings generate the
electric current. The armature can be on either the rotor or the stator.
• Field: The magnetic field component of an electrical machine. The
magnetic field of the dynamo or alternator can be provided by either
electromagnets or permanent magnets mounted on either the rotor or the
stator.
2.5.6 Uses for a Generator
Portable Electric Generators for Outdoor Recreational Activities
With portable generators, camping has become more convenient and safe.
The conveniences of modern living like having a refrigerator for safe
storage of food and perishables and having a coffee maker to brew your
29
favorite drink in the morning are now possible to enjoy at a rustic campsite,
thanks to a portable generator. With a portable generator, you can bring
along and use appliances like an electric fan and microwave oven while in
the woods. You can also protect yourself and your family even better with
low voltage lights powered by a compact electric generator.
2.5.7 Generators for Business, Commercial and Contractors
This is particularly important for contractors and workers working on
construction sites without available electricity. With portable generators,
construction workers would be able to operate their tools, including spray
gun systems and roofing guns. Of course, they‟ll also have lighting to work
indoors and during the night. Small entrepreneurs would also be wise to
invest in a generator, especially if their business would be affected by a mid
or long-term power outage. For example, markets, butcher shops, and
restaurants could suffer from tremendous loss during a power outage as the
perishables stored in refrigerators and freezers may become spoiled. The
same goes for companies that provide Internet-based services, as a power
outage can affect their operations even if power is out for only a few hours.
Backup electricity source is also essential healthcare providers like small
clinics and hospitals.
Generators for Backyard Use: Aside from providing backup power
during outages, a generator can also offer auxiliary electricity for home
improvement projects. Portable generators can give backup power for
electric powered equipment like saws and drills. These generators can also
be used for sanders and grinders as well as work lights and fans. Hence,
there is no need to string extension cords out of the back door. Portable
generators offer an alternative source of energy for home improvement
projects so you can complete the tasks in a shorter amount of time. Backup
Generators for Extreme Weather Conditions: A backup generator is a good
investment for people who live in areas where severe climate or weather
conditions are a threat.
30
For instance, a generator is a must have for an individual who lives in
an extremely cold climate where a power failure could be lethal, as heaters
and home furnace won‟t be able to run. With a portable or standby
generator, families would be able to use these heat-producing appliances
even during a power outage. Families who reside in coastal areas, where
storms and tornadoes frequently occur, should invest in a generator. Power
outages are often caused by storms. Hence, a generator can provide backup
energy during emergency situations. Having a backup generator would also
enable families living in storm-ravaged areas to monitor the latest news and
weather updates, since they would have access to information through
television and radio.
Comfort, Convenience for Family Members: Perhaps the most
compelling reason why people invest in generators is the motivation to
provide comfort and convenience to their loved ones, especially their
children or elderly parents. It is no secret that power outages can be very
stressful. By investing in a generator families would be able to avoid any
unnecessary inconveniences.
31
CHAPTER THREE
GENERATOR PROTECTION
32
GENERATOR PROTECTION
3.1 Introduction
Generator protection and control are interdependent problems. A
generator has to be protected not only from electrical faults (stator and
rotor faults) and mechanical problems (e.g. Related to turbine, boilers
etc.), but it also has to be protected from adverse system interaction arising
if generator going on out of step with the rest of system, loss of field
winding etc. Under certain situations like internal faults, the generator has
to be quickly isolated (shut down), while problems like loss of field
problem requires an „alarm‟ to alert the operator. Following is a
descriptive list of internal faults and abnormal operating conditions.
3.2 Internal Faults
1. Phase and /or ground faults in the stator and associated protection zone
2. Ground faults in the rotor (field winding)
3.3 Abnormal Operating Conditions
1. Loss of field.
2. Overload.
3. Overvoltage.
4. Under and over frequency
5. Unbalanced Operation e.g. single phasing.
6. Loss motoring i.e. loss of prime mover.
7. Loss of synchronization (out of step).
8. Sub synchronous oscillation.
3.4Stator Windings Faults
Stator winding faults: These types of faults occur due to the insulation
breakdown of the Stator coils. Different types of stator windings faults are:
1. Phase to earth fault
2. Phase to phase fault
3. Intertern fault
33
Phase to earth fault are limited by resistance of the neutral
grounding resistor. There are fewer chances for the occurrence of the
phase to phase and Interturn faults. The insulation between the two phases
is at least twice as thick as the insulation between one coil and the iron
core, so phase to phase fault is less likely to occur. Inter turn fault occurs
due the incoming current surges with steep wave front.
3.5 Stator Differential Protection for Generators
Differential protection is used for Protection of the generator against
phase to earth and phase to phase fault. Differential Protection is based on
the circulating current principle.
Figure (3.1): Differential protection for generators
In this type of protection scheme currents at two ends of the
protection system are compared. Under normal conditions, currents at two
ends will be same. But when the Fault occurs, current at one end will be
different from the current at the end and this difference of current is made
to flow through relay operating coils. The relays then closes its contacts
and makes the circuit breaker to trip, thus isolate the faulty section. This
type of protection is called the merz price circulating current system.
34
3.5 Modified Differential Protection
In modified differential protection setting of the Earth faults can be
reduced without any effect on the stability.
Figure (3.2): Modified differential protection for generators
In this method two relays are used for the phase to phase fault and
one relay is used for the protection of earth fault. In this method the two
relays and the balancing resistance are connected in star and the phase
fault relay is connected between the star point and the Neutral pilot wire.
The star connected circuit is symmetrical in terms of impedance. So
when the fault current occurs due to the phase to phase fault, it cancels at
the star point Due to the equal impedance. Thus it is possible with this
scheme to operate with the Sensitive earth fault relays. Thus this scheme
provides protection to the greater Percentage of the stator winding.
3.6 Biased Circulating Current Protection (percentage
differential relay protection)
With the differential protection relaying, the CTs at both end of the
stator windings must be same. If there is any difference in the accuracy of
the CTs the mal-operation of the relay will occurs. To overcome this
35
difficulty, biased circulating current protection is used. In this protection
system we can automatically increase the relay setting in Proportion to the
fault current. By suitable proportioning of the ratio of the relay Restraining
coil to the relay operating coil any biased can be achieved.
Figure (3.3) Biased circulating current protection for generators
Under normal operating condition current in secondary of the line
CTs will be same as the current in the secondary of the CTs at the neutral
end. Hence there are balanced current flows in the restraining coils and no
current flows in the operating coil. If there is any phase to phase or phase
to earth fault occurs then it causes the differences in the Secondary current
of the two CTs. Thus the current flows through the operating coil and
Make the circuit breaker to trip.
3.7 Self balance protection system
This type of protection is employed for earth fault and also for the
phase to phase fault.
36
Figure (3.4): self-biasing protection of the stator windings
In this type of protection two cables are required which is connected
to the two ends of the each phase. These two cables are passed through the
circular aperture of the ring type CTs.
Under normal conditions the current flowing in the two leads of the
cable will be in the same direction and no magnetization occurs in the ring
type CTs. When the earth fault occurs in any phase the fault current occurs
only once through the CTs and thus magnetic flux induced, this induces
the emf in the relay circuit causes the circuit breaker to trip.
This is very sensitive type earth fault protection but it also have some
limitations:
a) A different design of the cable lead is required in this scheme.
b) Large electromagnetic forces are develop in the CT ring under the
condition of heavy short circuit.
3.8 Stator Ground Fault Protection
The method of grounding effect the degree of protection which is
employed by the differential protection. High impedance reduces the fault
current and thus it is very difficult to detect the high impedance faults. So
37
the differential protection does not work for the high impedance
grounding. The separate relay to the ground neutral provides the sensitive
protection. But ground relay can also detect the fault beyond the generator,
it the time co-ordination is necessary to overcome this difficulty.
3.9 Stator Inter Turn Fault Protection
Differential protection for stator does not provide protection against
the inter-turn faults on the same phase winding of the stator. The reason is
that the current produced by the turn to turn fault flows in the local circuit
between the turns involved and thus it does not create any difference
between the current entering and leaving the windings at its two ends
where the CTs are mounted.
The coils of the modern turbo generator are single- turn, so there is
no need to provide inter –turn fault protection for the turbo generator. But
the inter turn protection is necessary for the multi turn generator like hydro
electric generator. Sometimes stator windings are duplicated to carry
heavy current. In this case stator winding have two different paths. In this
type of protection primaries of the CTs are inserted in the parallel paths
and secondary‟s are inter connected. Under the normal condition current
flowing through the two parallel paths of the stator winding will be same
and no current flowing through the relay operating coil. Under the inter
turn fault, current flowing through the two parallel path will be different
and this difference in current flowing through the operating coil and thus
causes the circuit breaker to trip and disconnect the faulty section. This
type of protection is very sensitive. The coils of the modern turbo
generator are single- turn, so there is no need to provide inter –turn fault
protection for the turbo generator. But the inter turn protection is necessary
for the multi turn generator like hydro electric generator. Sometimes stator.
Windings are duplicated to carry heavy current. In this case stator
winding have two different paths. In this type of protection primaries of
38
the CTs are inserted in the parallel paths and secondary‟s are inter
connected. Under the normal condition current flowing through the two
parallel paths of the stator winding will be same and no current flowing
through the relay operating coil. Under the inter turn fault, current flowing
through the two parallel path will be different and this difference in current
flowing through the operating coil and thus causes the circuit breaker to
trip and disconnect the faulty section.
This type of protection is very sensitive.
Figure (3.5) Inter turn protection of the stator winding
3.10 Stator Over Heating Protection
Stator over heating is caused due to the overloads and failure in
cooling system. It is very difficult to detect the overheating due to the short
circuiting of the lamination before any serious damage is caused.
Temperature rise depend upon I^2Rt and also on the cooling. Over current
relays cannot detect the winding temperature because electrical protection
cannot detect the failure of the cooling system. So to protect the stator
against overheating, embed resistance temperature detector or
39
thermocouples are used in the slots below the stator coils. These detectors
are located on the different places in the windings so that to detect the
temperature throughout the stator. Detectors which provide the indication
of temperature change are arranged to operate the temperature relay to
sound an alarm.
3.11 Protection of Generator Rotor Earth Fault
The rotor of a generator is wound by field winding. Any single earth
fault occurring on the field winding or in the exciter circuit is not a big
problem for the machine. But if more than one earth fault occur, there may
be a chance of short circuiting between the faulty points on the winding.
This short circuited portion of the winding may cause unbalance magnetic
field and subsequently mechanical damage may occur in the bearing of the
machine due to unbalanced rotation. Hence it is always essential to detect
the earth fault occurred on the rotor field winding circuit and to rectify it
for normal operation of the machine.
There are various methods available for detecting rotor earth fault of
alternator or generator. But basic principle of all the methods is same and
that is closing a relay circuit through the earth fault path. There are mainly
three types of rotor earth fault protection scheme used for this purpose. 1.
Potentiometer method 2. AC injection method 3. DC injection method let
us discuss the methods one by one.
Potentiometer Method of Rotor Earth Fault Protection in Alternator
The scheme is very simple. Here, one resistor of suitable value is
connected across the field winding as well as exciter. The resistor is
centrally tapped and connected to the ground via a voltage sensitive relay.
As it is seen in the figure below, any earth fault in the field winding as
well as exciter circuit closes the relay circuit through earthed path. At the
same time the voltage appears across the relay due to potentiometer action
of the resistor.
40
This simple method of rotor earth fault protection of alternator has a
big disadvantage. This arrangement can only sense the earth fault occurred
in the any point except the center of the field winding.
From the circuit it is also clear that in the case of earth fault on the
centre of the field circuit will not cause any voltage to be appeared across
the relay. That means simple potentiometer methods of rotor earth fault
protection, is blind to the faults at the centre of the field winding. This
difficulty can be minimized by using another tap on the resistor
somewhere else from the centre of the resistor via a push button. If this
pushbutton is pressed, the centre tap is shift and the voltage will appear
across the relay even in the event of central arc fault occurs on the field
winding.
AC Injection Method of Rotor Earth Fault Protection in Alternator
Here, one voltage sensitive relay is connected at any point of the field and
exciter circuit. Other terminal of the voltage sensitive relay is connected to
the ground by a capacitor and secondary of one auxiliary transformer as
shown in the figure below.
Here, if any earth fault occurs in the field winding or in the exciter circuit,
the relay circuit gets closed via earthed path and hence secondary voltage
of the auxiliary transformer will appear across the voltage sensitive relay
and the relay will be operated. The main disadvantage of this system is,
there would always be a chance of leakage current through the capacitors
to the exciter and field circuit. This may cause unbalancing in magnetic
field and hence mechanical tresses in the machine bearings. Another
disadvantage of this scheme is that as there is different source of voltage
for operation of the relay, the protection of rotor is inactive when there is a
failure of supply in the AC circuit of the scheme.
41
DC Injection Method of Rotor Earth Fault Protection in Alternator
The drawback of leakage current of AC injection method can be
eliminated in DC Injection Method.
Here one terminal of DC voltage sensitive relay is connected with positive
terminal of the exciter and another terminal of the relay is connected with
the negative terminal of an external DC source. The external DC source is
obtained by an auxiliary transformer with bridge rectifier. Here the
positive terminal of bridge rectifier is grounded.
It is also seen from the figure below that at the event of any field
earth fault or exciter earth fault, the positive potential of the external DC
source will appear to the terminal of the relay which was connected to the
positive terminal of the exciter. In this way the rectifier output voltage
appears across the voltage relay and hence it is operated.
3.12 Under/Over Frequency Protection
Over frequency results from the excess generation and it can easily be
corrected by reduction in the power outputs with the help of the governor
or manual control.
Under frequency operation: Under frequency occurs due to the excess.
During an overload, generation capability of the generator increases and
reduction in frequency occurs. The power system survives only if we drop
the load so that the generator output becomes equal or greater than the
connected load. If the load increases the generation, then frequency will
drop and load need to shed down to create the balance between the
generator and the connected load. The rate at which frequency drops
depend on the time, amount of overload and also on the load and generator
variations as the frequency changes. Frequency decay occurs within the
seconds so we cannot correct it manually. Therefore automatic load
shedding facility needs to be applied.
42
These schemes drops load in steps as the frequency decays. Generally
Load shedding drops 20 to 50% of load in four to six frequency steps.
Load shedding scheme works by tripping the substation feeders to
decrease the system load. Generally automatic load shedding schemes are
designed to maintain the balance between the load connected and the
generator.
The present practice is to use the under frequency relays at various load
Points so as to drop the load in steps until the declined frequency return to
normal. Non-essential load is removed first when decline in frequency
occurs. The setting of the under frequency relays based on the most
probable condition occurs and also depend upon the worst case
possibilities.
During the overload conditions, load shedding must occur before the
operation of the under frequency relays. In other words load must be shed
before the generators are tripped.
3.13 Under/ Voltage Protection / Over
Over voltage occurs because of the increase in the speed of the prime
mover due to sudden loss in the load on the generator. Generator over
voltage does not occur in the turbo generator because the control
governors of the turbo generators are very sensitive to the speed variation.
But the over voltage protection is required for the hydro generator or gas
turbine generators. The over voltage protection is provided by two over
voltage relays have two units – one is the instantaneous relays which is set
to pick up at 130 to 150% of the rated voltage and another unit is IDMT
which is set to pick up at 110% of rated voltage. Over voltage may occur
due to the defective voltage regulator and also due to manual control
errors.
43
3.14 Under voltage protection
If more than one generators supply the load and due to some reason
one generator is suddenly trip, then another generators try to supply the
load. Each of these generators will experience a sudden increase in current
and thus decreases the terminal voltage. Automatic voltage regulator
connected to the system try to restore the voltage. And under voltage relay
type-27 is also used for the under voltage protection.
3.15 Protection of the Generator Due to Unbalance Loading
Due to fault there is an imbalance in the three phase stator currents
and due to these imbalance currents, double frequency currents are
induced in the rotor core. This causes the overheating of the rotor and thus
the rotor damage. Unbalanced stator currents also damage the stator.
Negative sequence filter provided with the over current relay is
used for the Protection against unbalance loading. From the theory of the
symmetrical components, we know that an unbalanced three phase
currents contain the negative sequence component. This negative phase
sequence current causes heating of the stator. The negative heating follows
the resistance law so it is proportional to the square of the current. The
heating time constant usually depend upon the cooling system used and is
equal to I²t=k where I is the negative sequence current and t is the current
duration in seconds and k is the constant usually lies between 3 and 20. Its
general practice to use negative current relays which matches with the
above heating characteristics of the generator. In this type of protection
three CTs are Connected to three phases and the output from the
secondary‟s of the CTs is fed to the coil of over current relay through
negative sequence filter.
Negative sequence circuit consists of the resistors and capacitors
and these are connected in such way that negative sequence currents flows
through the relay coil. The relay can be set to operate at any particular
44
value of the unbalance currents or the negative sequence component
current.
Figure(3.6) protection against unbalance loading
3.16 Over current fault of a generator
Causes of over current fault on a generator is the Partial breakdown
of internal winding insulation, Overload on the supply system. Overcurrent
protection for generator is unnecessary because of high internal impedance
of generator, Modern design concept of generator is to set high internal
impedance of generator. Thus if over current fault occurs, due to high
internal impedance generator can withstand short circuit for a while. It can
manually disconnect from the bus. False tripping on an generator by over
current protection relay is need to be considered as this might disconnect
generator from bus for some fault outside of plant. This will cause
interruption of continuous operation, so over current relay used must have
time delay.
3.17 Alternator Prime Mover failure fault or reverse power
fault
What is prime mover in generator -We know about prime mover.
It‟s the mechanical system that rotates the rotor in alternator or just in
simple word runs the alternator. Typical prime movers are diesel or gas
engines, steam turbine, wind tidal force, water flow static force in
45
hydroelectric plant with dam etc. Now that we understand about prime
mover, it is clearly understandable that any time a prime mover might fail
to keep the alternator running. The root causes are so simple like fuel flow
shut up in gas /diesel engine, inadequate water flow in hydroelectric plants
etc.
The effect of prime mover failure in an alternator– we can imagine
the situation, an alternator is coupled with prime mover running, and it is
directly connected to the grid or some parallel electrical bus supplying
power. When the prime mover fails, it is still connected to the live electric
bus. Then the alternator fails to supply power but starts receiving power
from live electric bus. This time the synchronous alternator takes power
acts as a synchronous motor and run the engines or turbine in uncontrolled
high speed. This is called reverse power.
Severity of reverse power: For gas turbine and any hydroelectric
system the turbine installed is capable of running in very high speeds, so
when high speed occurs due to reverse power, any technician can decouple
the circuit breaker. But for diesel/ engine system, the reverse power is so
dangerous, as the over speed limit of engines re nominal like 120% of
rated speed. As example our plant‟s Wasilla engines rated speed was 750
RPM, and its high speed limit was 840/880 RPM.
Remedy -A reverse power relay is recommended. But this relay
should have time delay to avoid false trip in case of short time system
disturbance, phase swinging and fluctuation in synchronization.
Thus when a reverse power problem occurs, the first thing is to
decouple the corresponding circuit breaker to disconnect the alternator
from live line. If it is stuck, then shut down the whole bus, if that too is not
possible then shut the whole power plant for engine based power plant
only.
46
CHAPTER FOUR
PROPOSED PROTECTION TECHNIQUES THROUGH
DIFFERENT CASES
47
Proposed Protection Techniques through different Cases
4.1 The System Model
Heggligpower plant generation station consists of 4 phases The system each
phase contains two generators.
- Phase four contains two generators and their capacity is 3.5MW one of
them in the case of standby.
- Phase three contains two generators and their capacity is 3.6MW one of
them in the case of standby.
- Phase two contains two generators and their capacity is 3.5MW one of
them in the case of standby.
- Phase one contains two generators and their capacity is 3.5MW one of
them in the case of standby.
The capacity of the station in completely within 14.1MW.
The station contains in six transformers.
Figure (4.1): One line diagram of Hegglig power plant generation station
In network operation, stability plays a major role in the energy saving of the
Higgling station. This network shows that any disturbances must be resolved
quickly to ensure the stability of the power system network. The protective
equipment must be chosen in a suitable manner that can be obtained by short
48
circuit analysis.
Through this network, we study the short circuit of the Heglig 14.1 MW
using the ETAP program. Short circuit analysis was performed based on the
standards of the American National Institute (ANSI) -38 and the
International Electrotechnical Commission (IEC) -60909 and IEC 61363-1.
Short circuit responses of the Heglig 14.1 MW were obtained for different
types of symmetric and asymmetric faults at different locations.
49
4.2 The system data are shown below:-
Table (4.1) Bus input Data
Bus initial Voltage
ID Type Nom kv Base kv Sub-sys %Mag Ang
Bus 3 SWNG 6.6 6.6 3 100 00 0.00
Bus 2 SWNG 6.6 6.6 3 100 00 0.00
Bus 1 SWNG 6.6 6.6 3 100 00 0.00
The table (4-1) represents Bus input Data, the table shows the Bus
identification Nominal voltage Base voltage, initial voltage and angle .
Table (4.2) 2-Winding Transformer Input Data of Grounding
Trans former Rating conn
ID MVA PrimKV Sec KV Type
T200 30.000 6.6 0.4 D/Y
T204 30.000 6.6 33 D/Y
The table (4-2) Shows the r-winding transformer connection identification,
rating in MVA, primary voltage, secondary voltage and connection type.
50
Table (4. 3) Transformer Input Data
Transformer Rating Z-Variation % Tap Setting Adjusted Phase shift
ID MVA Prim KV
Sec KV %Z X/R +5% % Tol Prim Sec %Z Type Angle
T211 30.000 311.000 110.000 10.00 23.70 0 0 0 0 10.0000 Std Post. Seq 30.000
T212 30.000 11.000 110.000 10.00 23.70 0 0 0 0 10.0000 Std Post. Seq 30.000
T213 100.000 11.000 110.000 12.00 34.10 0 0 0 0 10.0000 Std Post. Seq 30.000
T214 100.000 11.000 110.000 12.00 34.10 0 0 0 0 10.0000 Std Post. Seq 30.000
T215 60.000 11.000 110.000 11.00 34.10 0 0 0 0 10.0000 Std Post. Seq 30.000
T216 60.000 11.000 110.000 11.00 34.10 0 0 0 0 10.0000 Std Post. Seq 30.000
* The table (4.2) shows the transformer input Data. This table
represent the Rating ,primary voltage, secondary voltage ,Z-variation ,
Tap settings and phase shift and connection type.
4.3 System Analysis and Result
First:- In this thesis run the load flow study in the system model
analysis of the system under.
The purpose of current calculated in the steady state to choose the
suitable current transformer ratio to the current transformer and use
these values in equation to set the relay as shown below.
The figure (4-2) represent the one line diagram of Hegglig power
plant station load flow analysis to calculate the steady state current and
choose suitable current transformer ratio.
51
Table (4.4):- This data shows suitable coefficient value of the current transformer in
each point of the system model.
Bus-Bars Current Transformer
Bus4 1458.B A
Bus3 145.9 A
Bus2 3174 A
The table (4.4) shows the suitable coefficient value of current
transformer in each point of the system model and this value used to
choose suitable current transformer ratio in each point , whereas choose
values very important to set the protection device.
The figure (4.3) shows the current transformer CT editor in ETAP-7,
represent the rating of the current transformer ,use choose CT-5 as example.
Second:- we run short circuit analysis in all bus bars to calculate
short circuit faults in each data to calculate the value of short circuit to
52
choose the suitable capacity in each circuit breaker and to use this value
to set relay.
The figure (4.4) shows short current circuit analysis of Khartoum north
power generation station to calculate of short circuit current and this
value very important to choose suitable protective device capacity.
We run the coefficients of equation as follows below to set the relays
this equation relates the values of steady state currents (Iss) and short circuit
(Isc) as follows below:
The relay current:
sc
f
II
C T R A T IO (1)
Where:
Isc = short circuit current
ss
s
II
C T R A T IO (2)
If = fault current of relay
Is = steady state current of relay Iss = steady state current
The pickup phase current=
s1 ,2 IC T R A T IO (3)
The pickup Ground current =
s0 ,3 IC T R A T IO
(4)
o p n + 10 .0 2o p
0 ,1 4 T .M .ST T 0 .0 4 m s
P S M 1
@ (5)
Where
TOPn = operation of the zone n
T.M.S = time multiple setting of relay
53
s
t ,= I 1 TI
*
(6)
t im eA = C o n stan t o f c u rre n t
t im eB = C o n stan t o f c u rre n t
Table (4.5):- The slope of the time/current curve sets is determined by
the constant α and β as follow:
The Table (4.5) shows the slope of the time current of the relay represent
standard measure, inverse, very inverse, extremely inverse.
Slope of time / current curve set Α Time Β Current
IEC Standard inverse 0.02 0.14
IEC Very inverse 1.0 13.5
IEC Extremely inverse 2.0 80
Therefore, all trip time calculations of over current relay were performed
according to above The International Electro-technical Commission (IEC)
standard formula.
4.4 Protection system coordination test
It was analyzed for simulation in electrical faults in three different positions
located at the station of Hegglig power plant .
The first location is the Generator (3.5MW) at bus bar4 near the
Generator H The second location is the Transformer (33KVA) as the
fault occur near the Transformer (T204)
system. Example when a fault occur in near the generator Hat bus bar 4
and the fault isn‟t line to ground and will be short circuit phase.
Note that the circuit breaker of the generator is tripped because the relay 1
gives the order to the circuit breaker and immediately feared to.
54
4.4.1 Protect the fault that occur near the generator
The figure (4.5) shows 3-phase fault sequence when fault occur near
the generator , and we notice that the circuit breaker near the generator
open quickly as much as possible to protect the generator we choose
fault near the generator H .
When fault occurs near the generator the simulation of the
three phase at the guarantor (Gen-H) at bus bar 4 we find
result as shown in finger 4.2 and the table 4.6 the circuit
breaker CB-H1 is tripped at the time 154 sec the relay 1 and
the fault current.
In this line program we run load flow study in thesis system model
analysis of the system under the purpose of current calculated in the
study state to choose the suitable current transform ratio to the
current transformer.
55
Figure (4.2) Testing System of Protection
4.4.2 Sequence-of-Operation Event Summary Report
Table (4.6):- Symmetrical 3-phase Fault at Bus395
Time(ms) ID if (KA) T1 (ms) T2 (ms) Condition
154 Relay1 3.054 154 OC1-51
204 CB-H 00 50 Tripped by relay1 Phase OC1-51
The table (4.6) shows sequence of operation of symmetrical 3-phase
fault at bus 4 , this table contains the fault current (IF) in KA ,firing time
and condition of sequence of operation.
When fault occurs near the transformer 204 and the fault is not line to
ground it is short circuit three phase.
Note that the circuit break of the transformer will immediately
disconnected very short time .
Result :
When fault occurs near the generator the simulation of the three
phase at the guarantor (Gen-H) at bus bar 4 we find result as shown in
finger 4.2 and the table 4.6 the circuit breaker CB-H1 is tripped at the
time 154 sec the relay 1 and the fault current.
56
CHAPTER FIVE
CONCLUSION ، RECOMMENDATIONS& Result
57
CONCLUSION ، RECOMMENDATIONS & Result
5.1 CONCLUSION
This project objective was to design generators protection of Hegglig
power plant by using ETAP program. so as an electrical generator can be
subjected either internal faults or external faults or both, hence any fault
occurred in the power system should be cleared in the power from the
generator as soon as possible otherwise it may create permanent damage in
the generator , the number and variety of fault occur in the generator are
huge. That is why generator is protected with several protection schemes.
In this thesis the one line diagram of Hegglig power plant generation
grid was simulated by using ETAP program and we run load flow analysis
to calculate the steady state current (Is) and to choose suitable current
transformers (CTs) ratio connected with relays. After that we run short
circuit analysis in all system to calculate the short circuit current and
determine the size of protection devices. Then we used these values to
calculate the value of T.M.S (Time Multiplier Setting), or time operation
and pick up current of protective relays that used to protect the system.
Finally we run star protective device coordination in ETAP and test the
protection device coordination.
The proposed methods were given good results which indicate that
the objectives of this study were successfully achieved.
5.2 RECOMMENDATIONS
1- In this thesis recommend that to protect the generators from any fault that
may occur due to external and internal faults.
2-Also we recommend to use suitable CT ratio with relays, and avoid the
current transformer from saturation.
3- In this thesis recommend to test the protection devices coordination to be
sure that the power system protection coordination well.
58
Result:
In this thesis run the load flow study in the system model analysis of
the system under.
The purpose of current calculated in the steady state to choose the
suitable current transformer ratio to the current transformer and use
these values in equation to set the relay as shown below.
The figure (4-2) represent the one line diagram of Hegglig power
plant station load flow analysis to calculate the steady state current
and choose suitable current transformer ratio.
The suitable coefficient value of current transformer in each point of
the system model and this value used to choose suitable current
transformer ratio in each point , whereas choose values very important
to set the protection device.
Bus-Bars Current Transformer
Bus4 1458.B A
Bus3 145.9 A
Bust2 3174 A
Bus4
Bus3 Bust2
Indicators of the stability number of minutes lost to thecurrent.Indicates the number of times a typical
power outage of a power outage occurs within a predetermined time period (unit measured in
number).
The equation: the average value of the frequency of power outages = the sum of
the wrong current / on the state of the current.
59
References
1. Raman deep kaurAujla "Generator stator protection over /under
voltage over/under frequency and unbalanced loading ", (May 5
2008)
2. Y.G.Paithankar and S.R.Bhide “Fundamentals of Power System
Protection” (2003).
3. The book reflects many years of experience of the authors in
teaching this subject matter to undergraduate electrical engineering
students.
4. The book, now in its second edition, continues to provide the
most relevant concepts and techniques in power
5. Laboratory setup for teaching and research in computer-based
power system protection, conference paper, Dec. 1995.
6. T.S. Sidhu M.S. Sachdev M.S. Sachdev View show abstract.
7. Development of power system protection laboratory through
senior design projects article, jun 2005 IEEE TO POWER SYST.
8. Mason, C. Russell. "The Art and Science of Protective Relaying"
(PDF). General Electric. Retrieved 2009-01-26.
9. "Coordinated Power Systems Protection". Army Corps of
Engineers. 1991-02-25. Archived from the original on 2008-01-13.
Retrieved 2009-01-26.
10. "How Do Protection Relays Work?".Littelfuse. Retrieved 2011-
12-31.
11. "What is SCADA?". Rose India Technologies. Retrieved 2011-
12-31.
12. "Introduction to Practical Power System Protection" (PDF).
University of Idaho. Retrieved 2011-12-31.
60
13. AbdelmoumeneAbdelkader, and Hamid Bentarzi. "A review on
protective relays' developments and trends." Journal of Energy in
Southern Africa 25.2 (2014): 91-95.
14. http://www.scielo.org.za/pdf/jesa/v25n2/10.pdf
15. http://www.scielo.org.za/scielo.php?pid=S1021-
447X2014000200010&script=sci_arttext&tlng=pt
16. http://perso.numericable.fr/michlami protection and
monitoring of the electrical energy transmission network
17. http://www.electrical4u.com/13/1/2018:5:58 pm
18. https://www.wikipedia.com/13/1/2018 :3:22 am
19. https://www.electricalengineeringschool.org/14/1/2018:3:54
20. https://www.pacificelectrical.com/14/1/2018:5:30
21. https://www.electricalsafrtyfirst.org.uk/15/1/2018:1:00
22. https://www.electricalwebsolution.com/20/3/2018:2:54