dehumidifikasi ppt blm fix

19
SOAL DEHUMIDIFIKASI 1.Inget Yester Yunanda 2.Laila Kusmiati 3.Fitri Afriani 4.Nirmala Sari 5.Noferiyanli

Transcript of dehumidifikasi ppt blm fix

Page 1: dehumidifikasi ppt blm fix

SOAL DEHUMIDIFIKASI

1.Inget Yester Yunanda2.Laila Kusmiati3.Fitri Afriani4.Nirmala Sari5.Noferiyanli

Page 2: dehumidifikasi ppt blm fix

Catatan Penting :

• Satuan dalam Psycometry Chart

Soal menggunakan Psycometry Chart dari

HandBook Munters DH The Dehumidification Handbook second Edition

1 lb = 7000 grains

Page 3: dehumidifikasi ppt blm fix

SOAL 1

• Air having a dry bulb temperature of 37,8oC and wet bulb of 26,7oC is to be dried by first cooling to 15,6oC to condense water vapor and then heating to 23,9oC.

A. Calculate the initial humidity and percentage humidity

B. calculate the final humidity and percentage humidity.(hint: locate the initial point on the humidity chart. Then go horizontally (cooling) to the 100 % saturation line. Follow this line to 15,6oC. Then go horizontally).

Page 4: dehumidifikasi ppt blm fix

SOLUTION

Page 5: dehumidifikasi ppt blm fix

LANJUTAN

A. Initial humidity: 0,0397 kg

percentage humidity : 40 %

B. Final humidity : 0,0115 kg H2O/ kg dry air

percentage humidity : 60 %

Page 6: dehumidifikasi ppt blm fix

SOAL 2

• Air entering an adiabatic cooling chamber has a temperature of 32,2oC and a percentage humidity of 65%. It is cooled by a cold and heated to 23,9oC. The final air has a percentage humidity of 40%.

A. What initial humidity of the air

B. What is the final humidity after heating

Page 7: dehumidifikasi ppt blm fix

SOLUTION

Page 8: dehumidifikasi ppt blm fix

LANJUTAN

A. Initial humidity : 0, 0419 kg H2O/kg dry air

B. final humidity : 0,0187 kg H2O/kg dry air

Page 9: dehumidifikasi ppt blm fix

SOAL 3• Udara akan didinginkan dan didehumidifikasi melalui

kontak lawan-arah dengan air didalam menara isian. Menara tersebut dirancang sebagai berikut: suhu dry bulb udara masuk 28oC, suhu wet bulb udara masuk 25oC, laju alir udara masuk 7000 kg/jam udara kering, suhu air masuk 10oC, dan suhu air keluar 24oC. Persen humidity keluar 70 %

a. Untuk udara masuk tentukan kelembaban, persen kelembaban relatif,dan titik embun

b. Berapakah Wa ?

Page 10: dehumidifikasi ppt blm fix

SOLUTION

Page 11: dehumidifikasi ppt blm fix

LANJUTAN

A. Initial humidity : 0,05 kg H2O/ kg dry air

percentage humidity : 90%

dew point : 77F atau 10,7C

B. Final humidity : 0,0287 kg H2O/kg dry air

ΔHR= (0,05-0,0287) kg H2O/kg dry air

=0,0213 kg H2O/kg dry air

Page 12: dehumidifikasi ppt blm fix

LANJUTAN

Page 13: dehumidifikasi ppt blm fix

SOAL 4

• Moist air at 50°C dry bulb temperature and 32%relative humidity enters the cooling coil of a dehumidification kiln heat pump system and is cooled to a temperature of 18°C. If the drying rate of 6 m3 of red oak lumber is 4 kg/hour, determine the kW of refrigeration required.

Page 14: dehumidifikasi ppt blm fix

SOLUTION

Page 15: dehumidifikasi ppt blm fix

LANJUTAN

Page 16: dehumidifikasi ppt blm fix

LANJUTAN

Page 17: dehumidifikasi ppt blm fix

SOAL 5Udara dimasukkan dalam suatu proses mempunyai suhu bola kering 30 oC dan RH 40%. Proses terdiri dari pendinginan, dehumidifikasi, dan pemanasan kembali. Udara masuk pendinginan pada Tdb 35 oC dan RH 60% dengan laju alir 1 m3/s pada 1 atm.Tentukan laju panas yang dikeluarkan dalam pendinginan dan dehumidifikasi!

Page 18: dehumidifikasi ppt blm fix

SOLUTION

Page 19: dehumidifikasi ppt blm fix

LANJUTANEntalphy awal pemanasan (h1) = 58 kJ/kgEntalphy akhir pemanasan (h2) = 63 kJ/kgEntalphy awal pendinginan (h3) = 91 kJ/kgEntalphy akhir pendinginan (h4) = 85 kJ/kg

Volume spesifik akhir (V3) = 0,91 m3/kg. UK