    DECS-250 and DECS-250N

    Digital Excitation Control System

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    2/60

    Presentation Outline

    Introduction Product features Protection Metering Communications

    NEW Environmental / Agency / Testing

    Software Ordering DECS-200 compatibility Sales

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    3/60

    Presentation Outline

    Introduction Product features

    Protection

    Metering

    CommunicationsNEW

    Environmental / Agency / Testing

    Software

    Ordering DECS-200 compatibil ity

    Sales

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    4/60

    Introduction

    The DECS-250 and DECS-250Nare Basler Electrics newest

    high performance digital

    excitation control systems.

    High performance,feature packed design

    Exceptional regulation performanceand transient response

    Complete system solution in a reliable,cost effective package

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    5/60

    Presentation Outline

    Introduction Product features Protection Metering

    Communications NEW Environmental / Agency / Testing

    Software

    Ordering DECS-200 compatibility Sales

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    6/60

    Standard Features

    Feature loaded microprocessor design Two power stage options available:

    15A PWM DECS-250

    20A Negative forcing SCR DECS-250N

    Abundant communications Extremely flexible

    Extensive microprocessor and memory capabili ties

    Expandable I/O capabil ity

    Compatible with BESTCOMSPlus PC software

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    7/60

    More Standard Features

    AVR/FCR/FVR/VAR control/PF control On-Line/Off-Line Over Excitation Limiters (OEL)

    OEL with temperature compensation(via a transducer input or AEM-2020 module)

    Stator Current Limiter (SCL) Temperature compensated SCL(via a transducer input or AEM-2020 module)

    Under Excitation Limiter (UEL) with plottable points

    VAR limiter Voltage matching

    Internal tracking between operating modes

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    8/60

    More Standard Features

    Real t ime monitor (str ip chart recorder) Oscillography (wave form capture)

    Sequence of Events Recording

    IRIG-B (time sync function)

    Soft start

    Generator protection

    Generator metering

    Large amount of contact I/O Expandable I/O via J1939 CANbus

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    9/60

    More Standard Features

    Auxiliary input (10Vdc or 4-20mA)

    Front Panel HMI via LCD and pushbuttons

    Communications

    USB for PC programming RS-485 (Modbus protocol)

    Ethernet (100 baseT)

    Output Power Stages:

    PWM based 15 Adc rated (DECS-250) SCR based 20 Adc rated with negative forcing

    (DECS-250N)

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    10/60

    Sensing Options

    Single and three phase selectable voltagesensing on both bus and generator

    120V / 240V / 480V or 600V nominal sensing

    Single or three phase selectable

    current sensing 1A or 5A nominal inputs

    4 CT inputs

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    11/60

    Inputs/Outputs (I/O)

    Contact I/O (16) Contact inputs

    (12) Contact outputs (7Adc)

    Expandable Contact I/O (Optional)

    CEM-2020 (10) inputs, (12) 1A gold, (12) 7A

    CEM-2020H (10) inputs, (12) 2A gold, (6) 10A

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    12/60

    Inputs/Outputs

    CEM-2020

    All Additional I/O can be programmed throughBESTCOMSPlus

    Single Module may eliminate addit ional controlrelaying or PLC

    Communicate via CANbus for remote mounting

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    13/60

    Analog Inputs/Outputs

    Expandable Analog I/O AEM-2020 (Optional) (8) Inputs, programmable for 4-20mA

    or 0-10Vdc

    (8) RTD Inputs 10 or 100 Ohm

    (2) K Type thermocouple inputs (4) Outputs, programmable for 4-20mA

    or 0-10Vdc

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    14/60

    Analog Inputs/Outputs

    Expandable Analog I/O AEM-2020Allows additional monitoring and protection

    to be implemented within the DECS-250 logic

    Temperature monitoring

    Limiter scaling

    Winding and bearing temperature

    Analog inputs

    Vibration / pressure transducers

    System monitoring

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    15/60

    Auto-Tuning Software

    PC software automatically selects PID values Reduces test/setup time

    Maximizes generator performance

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    16/60

    Auto-Tuning Software

    Auto tuning allows for unit to retrieveexcitation parameters and calculate system

    gains.

    Auto tune works by implementing a series

    of step responses and adjusting gainsaccordingly

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    17/60

    Auto Tune

    PID Design Mode:a) Pole Zero Cancellation

    b) Pole Placement

    Power Input Mode:

    a) PMG External

    b) Shunt

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    18/60

    Auto Tuning Screen

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    19/60

    PID Gain

    Now all gains are in PU to make the parameterseasier to integrate into math models

    Ka is the new loop gain, which is nowreferred to as the voltage regulator gain

    (Kg is no longer used)

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    20/60

    Generator Protection

    Loss of sensing Over/Under voltage

    Over/Under frequency

    Reverse power

    Reverse Vars

    Sync check

    Two settings groups for all settings

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    21/60

    Field over voltage Field over/under current

    Loss of PMG voltage

    Rotating diode monitor

    Crowbar activated (DECS-250N)

    Watchdog

    Softstart Limiter

    V/Hz Limiting

    More Generator Protection

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    22/60

    Configurable Protection

    Allows the user to add custom protectionfunctions

    Adds four thresholds per function

    Adds arming and activation delays to each

    configurable element Any monitored analog parameter can be used

    as function.

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    23/60

    More Configurable Protection

    Up to eight configurable protection elementscan be added.

    Includes inputs from the AEM-2020 AnalogExpansion Module:

    (8) Aux Inputs (4-20mA or 0-10Vdc)(8) RTDs (10 or 100 Ohm)

    (2) Thermocouples (K Type)

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    24/60

    Protection Screen

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    25/60

    Metering, Generator

    Three Phase GeneratorVoltage

    Generator Frequency

    Power Factor

    Three Phase Generator

    Current KVAR per Phase and Total

    KW per Phase and Total

    KVA Per Phase and Total

    KWH

    KVAH

    KVARH

    Phase Angle between GenVoltage and Current

    Auxiliary Input Voltage orCurrent

    Tracking Error

    Set point Position Indication

    Excitation Current and Voltage

    Exciter Diode Ripple Level

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    26/60

    Metering, Bus

    Sync Angle

    Slip Frequency

    Three Phase Bus Voltage

    Bus Frequency

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    27/60

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    28/60

    New Features

    Integrated PSS (Optional)

    Auto tuning

    Reactive load sharing via Ethernet

    Automatic synchronizing (Optional)

    BESTCOMSPlus(Programmable Logic/Configurable Protection)

    Increased I/O

    Expandable I/O

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    29/60

    More New Features

    Three phase stator current limit

    Auxiliary input from 10Vdc or 4-20mA

    On-Line/Off-Line Over Excitation Limiter

    J1939 CANbus for expansion modules

    Ethernet 100 Base T or F(includes load sharing via ENET)

    Profibus communication

    USB communications

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    30/60

    Environmental

    -40 to 70 C (DECS-250 operating)

    -40 to 60 C (DECS-250N operating)

    -40 to 85 C (storage)

    5Gs, 18-2000 Hz vibration

    15Gs shock

    Moisture resistance per MIL-STD-705B,Method 711-1C

    Salt Fog per MIL-STD-810E Method 509.3

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    31/60

    Agency Approvals

    UL 508

    CSA

    CE

    DNV (Det Norske Veritas)

    BV (Bureau Veritas) - pending

    GL (Germanischer-Lloyd) - pending

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    32/60

    HALT Testing

    Highly Accelerated Life Testing Identifies design areas to re-evaluate

    Accelerated simultaneous shock/vibe

    Elevated temperature testing

    6 axis simultaneous vibration

    60C/Min change in temperature possible

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    33/60

    HALT Testing

    Temperature extremes: -100C to 130C Multiple cycles of a rapid rate of change

    from -80C to 90C and from 90C to -80C

    with a dwell of roughly 15 minutes at

    each extreme Vibration extremes: 50 Grms

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    34/60

    HALT Testing

    Vibration duration: 10 Grms steps,increasing to 50 Gs for 9 hours

    Combined vibration and temperature

    Ramp from -80 to 90C in 10 minutes,

    every hour Ramp vibration to 50 Gs every hour

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    35/60

    HALT Testing

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    36/60

    HALT Testing

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    37/60

    Presentation Outline

    Introduction

    Product featuresProtection

    Metering

    Communications

    NEW

    Environmental / Agency / Testing

    Software Ordering

    DECS-200 compatibil ity

    Sales

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    38/60

    BESTCOMSPlus

    Latest Basler PC software format Enhanced metering

    Faster, more intuitive setup

    More sophisticated event recording,oscillography, SER

    Programmable logic

    Remote I/O configurations

    Auto-Tuning software

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    39/60

    BESTCOMSPlus, Control Panel

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    40/60

    BESTCOMSPlus, System Status

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    41/60

    BESTCOMSPlus,AVR/FCR/FVR

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    42/60

    BESTCOMSPlus, Logic

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    43/60

    Optional Features

    Ethernet 100 Base F External tracking between dual units

    Integrated power system stabil izer

    Profibus Auto synchronizing

    Compression or spring type terminals(removable)

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    44/60

    Presentation Outline

    Introduction

    Product featuresProtection

    Metering

    Communications

    NEW

    Environmental / Agency / Testing

    Software

    Ordering DECS-200 compatibil ity Sales

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    45/60

    Style Chart, DECS-250

    DECS-250

    MODEL NUMBER STYLE NUMBER

    Power Supply

    L) 24/48 Vdc

    C)120 Vac/125 Vdc

    Terminals

    S) Spring type

    C) Compression type

    Synchronizer

    N) None

    A) Auto synchronizer

    1 Communication ProtocolST

    1) 100Base-T Ethernet

    2) 100Base-F Ethernet

    2 Communication ProtocolN D

    N) None

    P) PROFIBUS

    Autotracking

    1) Internal

    autotracking only

    2) Internal/external

    autotracking

    PSS

    N) None

    P) Power system stabilizer

    NOTE

    Compression type terminals are available for the current

    sensing (CT) inputs, operating power input, and power output

    connections only.

    1

    1

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    46/60

    Style Chart, DECS-250N

    DECS-250N

    MODEL NUMBER STYLE NUMBER

    Terminals

    S)Spring type

    C)Compression type

    Synchronizer

    N)None

    A)Auto synchronizer

    2 Communication ProtocolND

    N)None

    P)PROFIBUS

    Input Power Frequency

    1)Low (50 to 150 Hz)

    2)High (151 to 420 Hz)

    3)High Voltage (480 Vac

    at 50/60 Hz)

    PSS

    N)None

    P)Power systemstabilizer

    1

    1 Communication ProtocolST

    1)100Base-T Ethernet

    2)100Base-F Ethernet

    Power Supply

    L)24/48 Vdc

    C)120 Vac/125 Vdc

    NOTES

    2

    A DECS-250N with style XX3XXXX accepts 480 Vac operating

    power at 50/60 Hz to provide a 250 Vdc nominal power output.

    Compression type terminals are available for the current

    sensing (CT) inputs, operating power input, and power output

    connections only.

    1

    2

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    47/60

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    48/60

    DECS-200/DECS-200N Compatibility

    Same dimensions as DECS-200Front panel

    Rear panel dri lling

    Cutout and drilling

    Escutcheon Plate available forDECS-200N dimensions

    Terminal locations in similar locations

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    49/60

    DECS-200/DECS-200N Compatibility

    External Tracking compatible DECS-200 = DECS-250

    DECS-200N = DECS-250N

    Same as DECS-200

    Default logic Legacy Modbus registers

    Application Note available

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    50/60

    Presentation Outline

    Introduction

    Product featuresProtection

    Metering

    Communications

    NEW

    Environmental / Agency / Testing

    Software

    Ordering

    DECS-200 compatibil ity

    Sales

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    51/60

    Competition

    ABB Unitrol 1020

    Unitrol 1000-15

    Brush

    Prismic

    Leroy Somer

    Kutai

    Rievax

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    52/60

    Competitive Advantages

    Basler Electrics acceptancein the market - DECS-200

    Ease of use BESTCOMSPlus

    Flexibility BESTlogic

    Configurable protection

    Configurable elements Configurable alarms

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    53/60

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    54/60

    Competitive Advantages

    Auto tuning

    Automatically sets PID gains for optimalperformance

    Makes tuning easier for the user

    Pole placement or pole zero calculations Reduces commissioning time

    Saves on cost during commissioning

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    55/60

    Competitive Advantages

    Reactive Load Sharing over Ethernet

    Eliminates the need for cross current(reactive differential)

    Zero voltage droop with exceptional VAR sharing

    Reduces wiring errors Limits problems with cross current connections

    Long wire runs

    Non-equal CT ratios

    Contact and wiring errors

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    56/60

    Competitive Advantages

    Environmental Advantages

    Extended temperature range

    HALT tested

    Extreme vibration and shock ratings

    EMI/RFI immunity

    Tolerant of high total harmonic distortion

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    57/60

    Competitive Advantages

    Agency approvals

    UL

    CSA

    CE

    Marine Approvals

    BV

    GL

    DNV

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    58/60

    Target Markets

    Utilities Independent Power Producers

    Industrials

    Marine

    OEMs

    Assemblers

    Repair and Service

    Consultants / Engineering Services

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    59/60

    Sales and Promotion Tools

    Product Bulletin

    Feature / Function / Benefit Table

    Guide form Specification

    Product Comparisons

    Target Market

    Application Notes DECS-200 / DECS-200N Retrofit

    Auto-tuning Implementation and operation of VAR limiter

  • 8/10/2019 decs_250_Basler_Excitation_Systems

    60/60