Chiller Plant Design

Julian R. de BulletPresident

deBullet Consulting703-483-0179

[email protected]

Page 2: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

ASHRAE WILL GIVE YOU

THE WORLD

This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer

Committee

Page 3: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

BECOME A FUTURE LEADER IN ASHRAE – WRITE THE NEXT CHAPTER IN YOUR CAREER

YOU ARE NEEDED FOR:

Membership Promotion

Research Promotion

Student Activities

Chapter Technology Transfer Technical Committees

Find your Place in ASHRAE! Visit www.ashrae.org

ASHRAE Members who attend their monthly chapter meetings become

leaders and bring information and technology back to their job.

Page 4: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Complete the Distinguished Lecturer Event Summary Critique

CTTC needs your feedback to continue to improve the DL Program

Distribute the DL Evaluation Form to all attendeesCollect at the end of the meetingCompile the attendee rating on the Event Summary

CritiqueSend the completed Event Summary Critique to your

CTTC RVC and ASHRAE Headquarters

Forms are available at:

www.ashrae.org/distinguishedlecturers

Page 5: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

What is a Chiller Plant?

•Major components:• Building or Process cooling load

• Water cooled chiller- (this can be air-cooled)

• Cooling Tower

• Pumps and piping• Controls

Page 6: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Why use chilled water?

• Chilled Water Is A Great Way To Move Energy Around A Building

• A 2” Pipe Moves As Much Energy As A 42” Duct

• A Chilled Water Coil W/ Valve Can Offer Excellent Control

• Dehumidification

• Chiller Plants Can Be Very Efficient

• Locate Equipment Away From Occupants

• Service

• Sound

• Safety

Page 7: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Buildings

72%

Other

28%

Industry

30%

Residential

22%

Transportation

29%

Commercial

19%

Energy Usage

Source: Energy Information Administration 2009

Energy Use by Sector Electricity Use by Sector

Page 8: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Talking about

Green?

Sustainability?

and High Performance!

Green:More efficient equipment

Sustainable:Design considers the big

picture, how is equipment made, where it is installed, how long it lasts….

High Performance:High Efficient equipment,

sized, installed and maintained correctly for maximum impact

Page 9: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Base Load

Lighting

Fans

Pumps

Cooling

0

200

400

600

800

1000

1200

1400

1600

k

W

Conventional Cooling Profile

6 AM 12 PM 6 PM

avg. electric load

Page 10: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Full load on “Design Day”

Design Performance

Chiller

58%

Tower

5%

Fans

24%Pumps

13%

Page 11: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Question: What is a cooling “Design Day”

a. The day the building load calculation was begun?

b. The first day the HVAC System is turned on?

c. The hottest day of the year?

d. The coldest day of the year?

Page 12: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Question: What is a cooling “Design Day”

a. The day the building load calculation was begun?

b. The first day the HVAC System is turned on?

c. The hottest day of the year?

d. The coldest day of the year?

ANSWER: c

Page 13: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Basic system

•Chiller

•Cooling Tower

•Building Cooling Load

•Pumps and Piping

Page 14: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Annual Energy Usage

Annual Energy Usage

Pumps

22%

Tower

2%

Chiller

33%Fans

43%

Page 15: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Chiller Basics

•Air, Water Or Evaporatively Cooled

•Reciprocating, Scroll, Screw Or Centrifugal Compressors

•DX or Flooded Evaporators

Page 16: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Single Chiller

Air Handling Unit

ChilledWater Pump

Water-CooledChiller

CondenserWater Pump

CoolingTower

Section 7 – System Piping Arrangements

CoolingTower

Page 17: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Typical Air-Cooled Chiller Piping Detail

Thermometer(Typical)

Section 6 – Typical Piping Details at Equipment

Drain Valve

Shutoff Valve (Typical)

Pressure Gauge (Typical)

Supply

Return

Air-Cooled Chiller

Page 18: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Typical Water-Cooled Chiller Piping Detail

Water-CooledChiller

Drain ValveFlange (Typical)

Pressure Gauge (Typical)Strainer (if pump is on return side of chiller)

Drain Valve

Supply Return

Thermometer(Typical)

CondenserWater

ChilledWater

Shutoff Valves

Section 6 – Typical Piping Details at Equipment

Supply Return

Page 19: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Typical Cooling Towers

Section 4 – Cooling Towers

Cooling towers are heat rejecters. They do not condense refrigerant so they are not considered condensers.

Page 20: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Cooling Tower

Basic Cooling Tower Operating Characteristics

95° F db78° F wb

From Water-CooledCondenser

85° F Back to Condenser

95° F

Approximately 90° F Saturated Air

Section 4 – Cooling Towers

Page 21: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Closed-Loop System

Coil

Expansion Tank

Chiller

Two-Way ValvePump

Includes:

• A chiller and/or a boiler

• Coils that produce cooling or heating

• Two or three-way valves to control the coils

• Piping and pump to circulate water

• An expansion tank (insignificant water contact with air)

Section 2 – Types of Piping Systems

Three-Way Valve

Piping 45° F

55° F

Page 22: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Open-Loop System

• The water-cooled condenser is typically part of a water-cooled chiller or water-cooled package unit

• A cooling tower rejects the condenser heat to the atmosphere

• Flow rates and temperatures are industry standards for North America

• Piping and pumps circulate water

• Water is reused and exposed to the ambient conditionsin the cooling tower

Water-Cooled Condenser

94 to 95° F

Chiller

Cooling Tower85° F

Condenser Water Pump

3 gpm/ton

Section 2 – Types of Piping Systems

Page 23: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Once-Thru Water System

• Much less common due to environmental concerns

• Water is sent to waste or returned back to source

• Large consumption of water

• Source example: river, lake, well

Water to waste or source

Piping

Pump

Source of water (river)

Chiller with Condenser

Once-ThruOptional

Valve

Section 2 – Types of Piping Systems

Page 24: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Question: What is a Closed Loop?

a. The pipe is capped

b. It is not open to the atmosphere

c. The chilled water piping is a closed loop

Page 25: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Question: What is a Closed Loop

a. The pipe is capped

b. It is not open to the atmosphere

c. The chilled water piping is a closed loop

ANSWER: b and c

Page 26: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Closed loop and Open loop- Recap!

• Closed Loop• The chilled water piping is usually a closed loop• A closed loop is not open to the atmosphere• The pump needs only to overcome the friction loss in the piping and the

components• The pump does not need to lift” the water to the top of the loop

• Open Loop• When open cooling towers are used in the condenser piping• The condenser pump must overcome the friction of the system and “lift”

the water from the sump to the top of the tower

Page 27: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Flow and Capacity

Q = W x Cp x deltaTWhere

• Q = Quantity Of Heat Exchanged (Btu/hr)

• W = Flow Rate Of Fluid (US gpm)

• Cp = Specific Heat Of Fluid

• deltaT = Temperature Change Of Fluid (°F)

For Water• Q (Tons) = US gpm x (°Fin - °Fout) x 500

• Q (Btu/hr) = US gpm x (°Fin - °Fout)/24

Page 28: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Load Basics

•Chilled Water Coils Transfer Heat From Building Air To Chilled Water

•Process Loads• Cooling Jackets

Page 29: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Typical Heating

Terminal

1-Pipe Distribution System

Main Piping LoopSupply and Return(1 size throughout)

Monoflow®

Fitting

Typical Heating-Only

System

Boiler

System Pump

Section 3 – Water Distribution Systems

Page 30: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Supply Piping

2-Pipe Distribution System

ReturnPiping

Boiler

Summer Mode

System Pump

Chiller

Section 3 – Water Distribution Systems

Typical Heating and

Cooling Terminal

Page 31: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

3-Pipe Distribution System

Section 3 – Water Distribution Systems

Special 3-pipe Water Control

ChilledWaterSupply

Common Return Pipingwith Mixed Hot and

Cold Water

Chiller

Boiler

Hot Water Supply

System Pumps

Distributes hot and cold water simultaneouslyTypical

Heating and Cooling

Terminal

Page 32: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

4-Pipe Distribution System

ChillerSystem Pumps

Distributes hot and cold water simultaneously

Hot Water Supply

Boiler

Section 3 – Water Distribution Systems

ChilledWaterSupply

4-Pipe Heating and

Cooling Terminal

Page 33: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Direct and Reverse Return Systems

Page 34: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Return

Reverse Return Horizontal Distribution

Supply

• Return header flow is same direction as supply flow

• Water leaves Unit-1 and goes all the way around inreturning to source

• The first unit supplied is the last returned

• Circuit pressure drop through Unit-1 = Unit-2 = Unit-3 = Unit-4 = Unit-5

• Balancing valves may be eliminated

Unit-5Unit-1 Unit-2 Unit-3 Unit-4

Section 4 – Direct and Reverse Return Systems

Page 35: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Direct Return Horizontal Distribution

• Water enters Unit-1 from supply

• Water leaves Unit-1 and returns directly to source

• The first unit supplied is the first returned

• Unequal circuit pressure drops result

• Circuit pressure drop through Unit-1 < Unit-2 < Unit-3 < Unit-4 < Unit-5

• Balancing valves are a necessity

Balancing Valves

Return

Supply

Unit-5Unit-1 Unit-2 Unit-3 Unit-4

Section 4 – Direct and Reverse Return Systems

Page 36: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Piping MaterialsTypical Materials:

> 2 ½- in. Schedule 40 black steel

< 2- in. Schedule 40 black steel or Type L copper

Section 5 – Water Piping Componentsand Accessories

Page 37: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Control Valves

Valve Actuator

2-Way Modulating

3-Way Diverting2 outlets 1 inlet

3-Way Mixing2 inlets 1 outlet

Section 5 – Water Piping Componentsand Accessories

Page 38: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Expansion Tanks

Open Tank

• Open to air

• Air-water interface

Closed Tank

• Very popular

• Captured air space

• Air-water interface

Closed Diaphragm Tank

• Flexible membrane

• No air-water interface

• Very popular

Drain

Air Space

Overflow

Compressed Air

DiaphragmOpen to

atmosphere

Section 5 – Water Piping Componentsand Accessories

Page 39: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Piping Example

Page 40: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Piping Example

Given The Following Pressure Drops in Feet

• Coil 3.0 ft• Pipe

• Try To Be Around 4ft P.D. Per 100 Ft Piping• 2” Pipe= 3.1ft/100ft• 10.7 ft

• Gate Valve 0.04 ft• Balancing Valve 2.0 ft

• 4 Elbows 0.91 ft

• 2 Tees 0.64 ft• Control Valve 8.2 ft

• Total 25.35 ft

Page 41: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Air Vents

Locate at high points

Typical Locations:• Risers

• Coils

• Terminals

4 Pipe Diameters

Service Valve

Manual or Automatic Air Vent

To Return Main

From Terminal Coil

Section 5 – Water Piping Componentsand Accessories

Page 42: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Thermometers, Gauges and Pete’s Plug

Locate thermometers and gauges at inlets and outlets of equipment

Pete’s Plugs:Temperature and Pressure Ports

Section 5 – Water Piping Componentsand Accessories

Page 43: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Pipe Hangers and Anchors

How many pipe hangers are needed and what is their support distance?

• Distance between hangers is 14 ft

• Number of hangers = (100/14) = 7

100 ft of 4-Inch Schedule 40 Black Steel Pipe

Recommended Support Spacing for

Schedule 40 Pipe

Nominal Pipe Size

(in.)

Distance Between

Supports (ft)

¾ - 1¼ 8

1½ - 2½ 10

3 – 3½ 12

4 – 6 14

8 - 12 16

14 - 24 20

Section 5 – Water Piping Componentsand Accessories

Page 44: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Check for Volume Tank Requirements

Rule of thumb for chilled-water systems:

• 3 gallons per nominal ton of chiller for normal air-conditioning duty

• 6 to 10 gallons per nominal ton of chiller for process duty or low ambient unit operation

Suggested volume tank designs

Section 5 – Water Piping Componentsand Accessories

Page 45: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

In-Line Pump

Motor

PumpAssembly

Small capacity design

Section 8 – Pump Basics and Types of Pumps

Page 46: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Close-Coupled Pump

Internal Self-Flushing Seal

Section 8 – Pump Basics and Types of Pumps

Page 47: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Base-Mounted End Suction Pump

Discharge

Short ShaftCoupling Guard Motor

Suction

Welded Steel Frame provides support and installation ease

Section 8 – Pump Basics and Types of Pumps

Page 48: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Double-Suction Vertical Split Case Pump

Vertical Suctionand Discharge

Large-capacity designs for chillers and cooling towers

Section 8 – Pump Basics and Types of Pumps

Page 49: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Double-Suction Horizontal Split Case Pump

PumpCoupling

Guard Motor

Large-capacity design for chillers and cooling towers

Section 8 – Pump Basics and Types of Pumps

Page 50: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Pump Type Comparison

Pump Type

CostFlow & Head

CapabilitySpace

RequiredEase of Service

In Line Least 1 200 gpm @ 55 ft Least 1 Poor 5

Close-

Coupled2 2,300 gpm @ 400 ft 2 4

End

Suction3 4,000 gpm @ 500 ft 3 1

Vertical

Split Case4 9,000 gpm @ 400 ft 4 2

Horizontal

Split CaseHighest 5 40,000 gpm @ 600 ft Most 5 Good 3

Section 8 – Pump Basics and Types of Pumps

Page 51: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Single Chiller

Air Handling Unit

ChilledWater Pump

Water-CooledChiller

CondenserWater Pump

CoolingTower

Section 7 – System Piping Arrangements

CoolingTower

REMEMBER THIS? ARE YOU READY TO PLAY IN THE WATER?

Page 52: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Parallel Flow Systems

Hydraulic Decoupler

(Bridge)

Production Loop (primary) Building System Loop (secondary)

Alternate Bypass Line minimum chiller flow

233 Ton

400 gpm

400 gpm

400 gpm

233 Ton

233 Ton

Page 53: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

3 x 267 Ton, Primary/Secondary

Section 7 – System Piping Arrangements

Hydraulic Decoupler

(Bridge)

Production Loop (primary) Building System Loop (secondary)

Alternate Bypass Line minimum chiller flow

233 Ton

400 gpm

400 gpm

400 gpm

233 Ton

233 Ton

Building Load 100% (700 Tons)

700 tons / 3 chillers = 233 tons per chiller

When building 100% loaded, entering condenser water = 85F

Page 54: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Variable Primary

Flow Meter

Control Valve, sized for minimum chiller flow

Automatic Isolation Valves

Variable Speed Primary Pumps

Bypass

350 Ton 350 Ton

1050 gpm

Page 55: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Variable Speed Chillers

Series Counter Flow – Lift Reduction

58F

50F

42F

83F

90.5F98F

Both chillers designed to operate at 42F/83F.

Downstream screw chiller cools from 50F – 42F

Upstream centrifugal chiller cools from 58F – 50F.

Reduced Lift = Reduced Speed = Reduced KW

Lift Reduced by 7.5°F

Page 56: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Variable Flow vs. Constant Flow

0

50000

100000

150000

200000

250000

300000

350000

400000

450000

500000

Chillers Pumps Towers Fans

kW

h

Variable Primary Flow 2 Chiller Primary/Secondary Flow 2 Chiller Parallel Flow

Pump Work Cut

In Half

Page 57: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Summary

• Lift = SCT – SST

• CS vs VS Centrifugal Chillers

• VFDs take advantage of Part Lift & Part Load with Speed Control

•Variable Speed Screw Technology

• Series Counter Flow Systems Reduce Lift & Lower KW

• Chiller Plant Analysis

Page 58: deBullet - ASHRAE- BASIC CHILLER PLANT DESIGN-ASHRAE4 ...

Fire detection

and alarm

systems

Fire fighting and

suppression

systems

Service, maintenance and

inspection

Access control,

intrusion monitoring

and video surveillance

HVAC & Electronic Security Fire Safety

Electronic locks,

and energy management

systems

Chillers and

controls

Air handling, fan

coils

and refrigeration

Building Automation

System

Integration of Systems

Building

Systems