DE33E0 (LC Frame - Genelite

4
Engine Make & Model: Circuit Breaker Type: Fuel Tank Capacity: litres (US gal) Frequency: 50 Hz 60 Hz Fuel Consumption, Prime: l/hr (US gal/hr) Engine Speed: RPM Base Frame Type: Fuel Consumption, Standby : l/hr (US gal/hr) Heavy Duty Fabricated Steel Generator Model: Control Panel: EMCP 4.1 Output Ratings Generator Set Model - 3 Phase Standby* Prime* * Refer to ratings definitions on page 4. Ratings at power factor. Technical Data Image shown may not reflect actual package DIESEL GENERATOR SET LEHE0690-02 Cat® C3.3 3 Pole MCB / 3 Pole MCCB 161 (42.5) 7.0 (1.8) 8.1 (2.1) 1500 1800 7.7 (2.0) 9.0 (2.4) LC1514F 33.0 kVA 26.4 kW 30.0 kW 37.5 kVA 30.0 kVA 24.0 kW 27.0 kW 33.8 kVA 480V, 60 Hz 400/230 V, 50 Hz 0.8 DE33E0 (LC Frame)

Transcript of DE33E0 (LC Frame - Genelite

Engine Make & Model:

Circuit Breaker Type:

Fuel Tank Capacity: litres (US gal)

Frequency: 50 Hz 60 Hz

Fuel Consumption, Prime: l/hr (US gal/hr)

Engine Speed: RPM

Base Frame Type:

Fuel Consumption, Standby : l/hr (US gal/hr)

Heavy Duty Fabricated Steel

Generator Model:

Control Panel: EMCP 4.1

Output Ratings

Generator Set Model - 3 Phase Standby*Prime*

* Refer to ratings definitions on page 4.Ratings at power factor.

Technical Data

Image shown may not reflect actual package

DIESEL GENERATOR SET

LEHE0690-02

Cat® C3.3

3 Pole MCB / 3 Pole MCCB

161 (42.5)

7.0 (1.8) 8.1 (2.1)

1500 1800

7.7 (2.0) 9.0 (2.4)

LC1514F

33.0 kVA

26.4 kW

30.0 kW

37.5 kVA

30.0 kVA

24.0 kW

27.0 kW

33.8 kVA480V, 60 Hz

400/230 V, 50 Hz

0.8

DE33E0 (LC Frame)

Air Filter Type:

Combustion Air Flow:

m³/min (cfm) -Standby:

-Prime:

Max. Combustion Air Intake

Restriction: kPa (in H2O)

Radiator Cooling Air Flow:

m³/min (cfm)

External Restriction to

Cooling Air Flow: Pa (in H2O)

Air System 60 Hz50 Hz

Moment of Inertia: kg m² (lb. in²)

Governing Type:

Governing Class:

Compression Ratio:Displacement: l (cu.in)

Engine Electrical System:

-Voltage/Ground:

-Battery Charger Amps:

Weight: kg (lb) - Dry:

- Wet:

Cooling Method:

Bore/Stroke: mm (in)

Induction:

Manufacturer:

Model:

No. of Cylinders/Alignment:

Cycle:

Regenerative Power: kW-Prime:

-Standby:BMEP: kPa (psi)

-Prime:

-Standby:Gross Engine Power: kW (hp)Engine Speed: RPM

Oil Pan l (US gal):

Total Oil Capacity l (US gal):

Oil Filter Type:

Oil Type:

Cooling Method:

Prime

50 Hz

60 Hz

(based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)

Recommended Fuel:

Fuel Consumption: l/hr (US gal/hr)

110%Load

75%Load

50%Load

100%Load

Fuel Filter Type:

Standby

50 Hz

60 Hz

Level: dB

Silencer System: kPa (in Hg)

Pressure Drop Across

Silencer Noise Reduction

Silencer Type:

Pressure: kPa (in. Hg)

Max. Allowable Back

-Prime:

m³/min (cfm) -Standby:

Exhaust Gas Flow:

-Prime:

-Standby:

Exhaust Gas Temperature: °C (°F)

Silencer Model & Quantity:Cooling System Capacity: l (US gal)

Water Pump Type:

Heat Rejected to Water &

Lube Oil: kW (Btu/min)

-Standby:

-Prime:

-Prime:

kW (Btu/min) -Standby:Heat Radiation to Room: Heat radiated from engine and alternator

Radiator Fan Load: kW (hp)

Cooling system designed to operate in ambient conditions up to 50°C (122°F). Contact your local Cat dealer for power ratings at specific site conditions.

Cooling System 60 Hz50 Hz

Performance 60 Hz50 Hz

Fuel System

Exhaust System

Lubrication SystemPhysical Data

Engine Technical Data

LEHE0690-02

60 Hz50 Hz

Class A2 Diesel or BSEN590

DIESEL GENERATOR SET

6.5 (26.1)

62.6 (2211)

Replaceable Element

2.6 (91)2.2 (76)

2.6 (92)2.2 (76)

6.5 (26.1)

125 (0.5)125 (0.5)

84.8 (2995)

1.14 (3896)

Water Mechanical ISO 8528 G2

19.25:1

3.3 (201.4)

105.0 (4.1)/127.0 (5.0)

12/Negative

65412 (908)

430 (948)

Caterpillar

C3.33 / In Line

4 Stroke

Naturally Aspirated

9.07.0684.0 (99.2) 669.0 (97.0)

738.0 (107.0)752.0 (109.0)

33.1 (44.0)28.2 (38.0)31.0 (42.0) 36.5 (49.0)

18001500

Spin-On, Full Flow

8.3 (2.2)7.8 (2.1)

API CG4 / CH4 15W-40

Water

3.8 (1.0)4.7 (1.2)6.2 (1.6)8.1 (2.1)9.0 (2.4)

5.2 (1.4)7.0 (1.8)7.7 (2.0)

Replaceable Element

4.1 (1.1)5.7 (1.5)7.7 (2.0)5.0 (1.3)6.8 (1.8)9.0 (2.4)

EXSY1 (1)

2.00 (0.591)1.80 (0.532)

1920

10.0 (3.0)8.0 (2.4)

6.6 (233)5.8 (205)

6.4 (226)5.7 (201)

530 (986)520 (968)

520 (968)500 (932)

Industrial

18.0 (1024)

0.5 (0.7)

10.2 (2.7)10.2 (2.7)Centrifugal

22.0 (1251)

18.0 (1024)16.0 (910)

9.7 (552)9.3 (529)

8.2 (466)7.9 (449)

0.3 (0.4)

2

Data Item50 Hz 60 Hz

Motor Starting Capability* kVA

Reactances: Per Unit

Xd

X'd

X''d

Reactances shown are applicable to prime ratings. *Based on 30% voltage dip at 0.6 power factor.

Short Circuit Capacity %

Generator Performance Data

LC Frame

Model:

No. of Bearings:

Insulation Class:

Winding Pitch - Code:

Wires:

Ingress Protection Rating:

Excitation System:

AVR Model:

Overspeed: RPM

Voltage Regulation: (steady state)

Wave Form NEMA = TIF:

Wave Form IEC = THF:

Total Harmonic Content LL/LN:

Radio Interference:

Radiant Heat: kW (Btu/min)

-50 Hz:

-60 Hz:

Suppression is in line with European Standard EN61000-6

Physical Data Operating Data

Generator Technical Data

DIESEL GENERATOR SET

LEHE0690-02

72 68 63 78 78 55 63 69

2.298 2.474 2.741 2.045 2.323 3.706 3.092 2.764

0.143 0.153 0.170 0.127 0.144 0.230 0.192 0.171

0.071 0.077 0.085 0.063 0.072 0.115 0.096 0.086

415/240V 400/230V230/115V200/115V

380/220V220/110V

220/127V 480/277V240/139V

380/220V220/110V

240/120V208/120V

440/254V220/127V

- - - - - - - -

LC1514F

1

H

2/3 - 6

12

IP23

SHUNT

R220 3.7 (210)

3.3 (188)

5.0%

2.0%

50

+/- 1.0%

2250

3

kWkVAkWkVA

Technical Data

Voltage50 Hz Prime Standby

Standby Rating

Prime RatingOutput available with varying load for an unlimited time. Average power output is 70% of the prime power rating. Typical peak demand is 100% of prime rated ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12. Overload operation cannot exceed 25 hours per year.

.Standard Reference ConditionsNote: Standard reference conditions 25°C (77°F) air inlet temp,100m (328ft) A.S.L. 30% relative humidity. Fuel consumption dataat full load with diesel fuel with specific gravity of 0.85 andconforming to BS2869: 1998, Class A2.

Definitions

kWkVAkWkVA

Voltage60 Hz Prime Standby

Weights & Dimensions

Weights: kg (lb)

Net (+ lube oil)

Wet (+ lube oil & coolant)

Fuel, lube oil & coolant

Dimensions: mm (in)

Height

Width

Length

DocumentsA full set of operation and maintenance manuals and circuit wiring diagrams.

Quality StandardsThe equipment meets the following standards: IEC60034-1,IEC60034-22, ISO3046, ISO8528, NEMA MG 1-32, NEMA MG 1-33, 2004/108/EC, 2006/42/EC, 2006/95/EC.

General Data

Price Lists: C3.3PGABI, C3.3PGABT

Gen. Arr. Number:

LEHE0690-02 (04/16)

www.Cat-ElectricPower.com

© 2016 Caterpillar All rights reserved.

Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication.

CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow," the"Power Edge" trade dress, as well as corporate and product

identity used herein, are trademarks of Caterpillar and may not beused without permission.

Note: General configuration not to be usedfor installation. See general dimensiondrawings for detail.

DIESEL GENERATOR SET

26.433.0

26.433.0

26.433.0

26.433.0

26.433.0

26.433.0

26.433.0

24.0

24.0

24.0

24.030.0

30.0

30.0

30.0

24.030.0

30.0 24.0

200/115V

220/110V

220/127V

230/115V

380/220V

415/240V

400/230V

24.030.0

30.0

30.037.527.033.8208/120V

30.037.527.033.8220/110V

30.0

30.037.527.033.8380/220V

30.0

30.037.527.033.8480/277V

37.5

37.5

37.527.0

27.0

27.033.8

33.8

33.8

240/139V

240/120V

220/127V

976 (2153)

840 (1852)

827 (1823)

1361 (53.6)

970 (38.2)

1540 (60.6)