DE CORRIENTE PRUEBAS A TRANSFORMADORES · enable fs/ %ec calculation security limiting factor 5a...

9
16/11/2015 1:1PM ENCAPSULADA ENTRADA °F 28 % 40 TRANFORMADOR TC1 FACE A ASSET ID HUMIDITY AMBIENT TEMP. JOB # DATE POSITION SUBSTATION SUB 115 KV EQUIPMENT LOCATION 27650, REVISED 31/08/2012 COPYRIGHT © 2002-2012 POWERDB, INC. www.powerdb.com MCT1605 TESTED BY: TEST EQUIPMENT USED: ING. ROGELIO RAMIREZ S. HITACHI NAMEPLATE DATA MANUFACTURER TYPE T12346E1 A PHASE WindowSolid FREQUENCY X STYLE 60Hz SATURATION STANDARD IEC 60044-1 SERIAL NO. ACCURACY CLASS ASSET ID 1 NUMBER OF TESTS 5 INSULATION RATING VOLTAGE RATING 123000 500V SECONDARY CURRENT 10P ENABLE FS/ %EC CALCULATION SECURITY LIMITING FACTOR 1A RATED OUTPUT (VA) SEC. BURDEN TEST AMPS 5 NAMEPLATE RATIO ACTUAL RATIO RESISTANCE Tap RATIO % ERROR PHASE DEV. (deg.) POLARITY X VOLTAGE (volts) X CURRENT (amps) CT RATIOS VOLTAGE (volts) CURRENT (amps) KNEE POINT (ohms) 600 601.575 0.26250 S1-S2 0.64 Correct 21.60 0.027 158.23 0.15172 5 5 : : 600 : 5 S1-S2 IEC 60044-1 INSULATION RESISTANCE Primary To Secondary BURDEN VA POWER FACTOR PHASE (Degree) COMMENTS: VALORES ACEPTABLES DE OPERACION. DEFICIENCIES: PRUEBAS A TRANSFORMADORES DE CORRIENTE

Transcript of DE CORRIENTE PRUEBAS A TRANSFORMADORES · enable fs/ %ec calculation security limiting factor 5a...

Page 1: DE CORRIENTE PRUEBAS A TRANSFORMADORES · enable fs/ %ec calculation security limiting factor 5a rated output (va) sec ... voltage (volts) current (amps) knee point (ohms) s1-s2 1,200:

16/11/2015 1:1PM

ENCAPSULADA

ENTRADA

°F28

%40

TRANFORMADOR TC1 FACE AASSET ID

HUMIDITY

AMBIENT TEMP.

JOB #

DATE

POSITION

SUBSTATION

SUB 115 KV EQUIPMENT LOCATION

27650, REVISED 31/08/2012COPYRIGHT © 2002-2012 POWERDB, INC. www.powerdb.com

MCT1605 TESTED BY:TEST EQUIPMENT USED: ING. ROGELIO RAMIREZ S.

HITACHI

NAMEPLATE DATA

MANUFACTURER

TYPE

T12346E1 A PHASE

WindowSolid FREQUENCY

X STYLE

60Hz

SATURATION STANDARD IEC 60044-1

SERIAL NO.

ACCURACY CLASS

ASSET ID

1NUMBER OF TESTS 5

INSULATION RATINGVOLTAGE RATING 123000 500V

SECONDARY CURRENT 10P

ENABLE FS/ %EC CALCULATION

SECURITY LIMITING FACTOR 1A

RATED OUTPUT (VA)

SEC. BURDEN TEST AMPS

5

NAMEPLATE RATIO

ACTUAL RATIO

RESISTANCE

Tap RATIO % ERROR

PHASE DEV. (deg.) POLARITY

X VOLTAGE (volts)

X CURRENT (amps)

CT RATIOS

VOLTAGE (volts)

CURRENT (amps)

KNEE POINT

(ohms)

600 601.575 0.26250S1-S2 0.64Correct 21.60 0.027 158.23 0.151725 5::

600 : 5 S1-S2

IEC 60044-1

INSULATION RESISTANCE

Primary To SecondaryBURDEN

VA POWER FACTOR PHASE (Degree)

COMMENTS: VALORES ACEPTABLES DE OPERACION.

DEFICIENCIES:

PRUEBAS A TRANSFORMADORES DE CORRIENTE

Page 2: DE CORRIENTE PRUEBAS A TRANSFORMADORES · enable fs/ %ec calculation security limiting factor 5a rated output (va) sec ... voltage (volts) current (amps) knee point (ohms) s1-s2 1,200:

16/11/2015 1:3PM

ENCAPSULADA

ENTRADA

°F28

%40

TRANSFORMADOR TC1 FASE B ASSET ID

HUMIDITY

AMBIENT TEMP.

JOB #

DATE

POSITION

SUBSTATION

SUB 115 KV EQUIPMENT LOCATION

27650, REVISED 31/08/2012COPYRIGHT © 2002-2012 POWERDB, INC. www.powerdb.com

MCT1605 TESTED BY:TEST EQUIPMENT USED: ING. ROGELIO RAMIREZ S.

HITACHI

NAMEPLATE DATA

MANUFACTURER

TYPE

T12346E2 B PHASE

WindowSolid FREQUENCY

X STYLE

60Hz

SATURATION STANDARD IEC 60044-1

SERIAL NO.

ACCURACY CLASS

ASSET ID

1NUMBER OF TESTS 5

INSULATION RATINGVOLTAGE RATING 123000 500V

SECONDARY CURRENT 10P

ENABLE FS/ %EC CALCULATION

SECURITY LIMITING FACTOR 1A

RATED OUTPUT (VA)

SEC. BURDEN TEST AMPS

5

NAMEPLATE RATIO

ACTUAL RATIO

RESISTANCE

Tap RATIO % ERROR

PHASE DEV. (deg.) POLARITY

X VOLTAGE (volts)

X CURRENT (amps)

CT RATIOS

VOLTAGE (volts)

CURRENT (amps)

KNEE POINT

(ohms)

600 601.575 0.26250S1-S2 0.64Correct 21.60 0.027 158.23 0.151725 5::

600 : 5 S1-S2

IEC 60044-1

INSULATION RESISTANCE

Primary To SecondaryBURDEN

VA POWER FACTOR PHASE (Degree)

COMMENTS: VALORES ACEPTABLES DE OPERACION.

DEFICIENCIES:

PRUEBAS A TRANSFORMADORES DE CORRIENTE

Page 3: DE CORRIENTE PRUEBAS A TRANSFORMADORES · enable fs/ %ec calculation security limiting factor 5a rated output (va) sec ... voltage (volts) current (amps) knee point (ohms) s1-s2 1,200:

16/11/2015 1:9PM

ENCAPSULADA

ENTRADA

°F28

%40

TRANSFORMADOR TC1 FASE CASSET ID

HUMIDITY

AMBIENT TEMP.

JOB #

DATE

POSITION

SUBSTATION

SUB 115 KV EQUIPMENT LOCATION

27650, REVISED 31/08/2012COPYRIGHT © 2002-2012 POWERDB, INC. www.powerdb.com

MCT1605 TESTED BY:TEST EQUIPMENT USED: ING. ROGELIO RAMIREZ S.

HITACHI

NAMEPLATE DATA

MANUFACTURER

TYPE

T12346E3 B PHASE

WindowSolid FREQUENCY

X STYLE

60Hz

SATURATION STANDARD IEC 60044-1

SERIAL NO.

ACCURACY CLASS

ASSET ID

1NUMBER OF TESTS 5

INSULATION RATINGVOLTAGE RATING 123000 500V

SECONDARY CURRENT 10P

ENABLE FS/ %EC CALCULATION

SECURITY LIMITING FACTOR 1A

RATED OUTPUT (VA)

SEC. BURDEN TEST AMPS

5

NAMEPLATE RATIO

ACTUAL RATIO

RESISTANCE

Tap RATIO % ERROR

PHASE DEV. (deg.) POLARITY

X VOLTAGE (volts)

X CURRENT (amps)

CT RATIOS

VOLTAGE (volts)

CURRENT (amps)

KNEE POINT

(ohms)

600 601.519 0.25317S1-S2 0.64Correct 21.60 0.028 157.96 0.156345 5::

600 : 5 S1-S2

IEC 60044-1

INSULATION RESISTANCE

Primary To SecondaryBURDEN

VA POWER FACTOR PHASE (Degree)

COMMENTS: VALORES ACEPTABLES DE OPERACION.

DEFICIENCIES:

PRUEBAS A TRANSFORMADORES DE CORRIENTE

Page 4: DE CORRIENTE PRUEBAS A TRANSFORMADORES · enable fs/ %ec calculation security limiting factor 5a rated output (va) sec ... voltage (volts) current (amps) knee point (ohms) s1-s2 1,200:

16/11/2015 3:56PM

SE PRINCIPAL

SALIDA

°F26

%43

TRANSFORMADOR TC2 FASE A ASSET ID

HUMIDITY

AMBIENT TEMP.

JOB #

DATE

POSITION

SUBSTATION

PIQ EQUIPMENT LOCATION

27650, REVISED 31/08/2012COPYRIGHT © 2002-2012 POWERDB, INC. www.powerdb.com

MCT1605 TESTED BY:TEST EQUIPMENT USED: ING. ROGELIO RAMIREZ S.

HITACHI

NAMEPLATE DATA

MANUFACTURER

TYPE

T12346E4 FA PHASE

BarType FREQUENCY

X STYLE

60Hz

SATURATION STANDARD IEC 60044-1

SERIAL NO.

ACCURACY CLASS

ASSET ID

1NUMBER OF TESTS 5

INSULATION RATINGVOLTAGE RATING 123000 500V

SECONDARY CURRENT 0.1

ENABLE FS/ %EC CALCULATION

SECURITY LIMITING FACTOR 1A

RATED OUTPUT (VA)

SEC. BURDEN TEST AMPS

5

NAMEPLATE RATIO

ACTUAL RATIO

RESISTANCE

Tap RATIO % ERROR

PHASE DEV. (deg.) POLARITY

X VOLTAGE (volts)

X CURRENT (amps)

CT RATIOS

VOLTAGE (volts)

CURRENT (amps)

KNEE POINT

(ohms)

1,200 1,202.61 0.21767S1-S2 0.91Correct 45.50 0.015 290.13 0.070385 5::

1200 : 5 S1-S2

IEC 60044-1

INSULATION RESISTANCE >1000M

Secondary To GroundBURDEN

VA POWER FACTOR PHASE (Degree)

COMMENTS: VALORES ACEPTABLES DE OPERACION.

DEFICIENCIES:

PRUEBAS A TRANSFORMADORES DE CORRIENTE

Page 5: DE CORRIENTE PRUEBAS A TRANSFORMADORES · enable fs/ %ec calculation security limiting factor 5a rated output (va) sec ... voltage (volts) current (amps) knee point (ohms) s1-s2 1,200:

16/11/2015 3:49PM

SE PRINCIPAL

SALIDA

°F26

%43

TRANSFORMADOR TC2 FASE B ASSET ID

HUMIDITY

AMBIENT TEMP.

JOB #

DATE

POSITION

SUBSTATION

PIQ EQUIPMENT LOCATION

27650, REVISED 31/08/2012COPYRIGHT © 2002-2012 POWERDB, INC. www.powerdb.com

MCT1506 TESTED BY:TEST EQUIPMENT USED: ING. ROGELIO RAMIREZ S.

HITACHI

NAMEPLATE DATA

MANUFACTURER

TYPE

T12345E5 FB PHASE

BarType FREQUENCY

X STYLE

60Hz

SATURATION STANDARD IEC 60044-1

SERIAL NO.

ACCURACY CLASS

ASSET ID

1NUMBER OF TESTS 5

INSULATION RATINGVOLTAGE RATING 123000 500V

SECONDARY CURRENT 0.1

ENABLE FS/ %EC CALCULATION

SECURITY LIMITING FACTOR 1A

RATED OUTPUT (VA)

SEC. BURDEN TEST AMPS

5

NAMEPLATE RATIO

ACTUAL RATIO

RESISTANCE

Tap RATIO % ERROR

PHASE DEV. (deg.) POLARITY

X VOLTAGE (volts)

X CURRENT (amps)

CT RATIOS

VOLTAGE (volts)

CURRENT (amps)

KNEE POINT

(ohms)

1,200 1,202.02 0.16808S1-S2 0.91Correct 45.40 0.015 291.90 0.069615 5::

1200 : 5 S1-S2

IEC 60044-1

INSULATION RESISTANCE >1000M

Secondary To GroundBURDEN

VA POWER FACTOR PHASE (Degree)

COMMENTS: VALORES ACEPTABLES DE OPERACION.

DEFICIENCIES:

PRUEBAS A TRANSFORMADORES DE CORRIENTE

Page 6: DE CORRIENTE PRUEBAS A TRANSFORMADORES · enable fs/ %ec calculation security limiting factor 5a rated output (va) sec ... voltage (volts) current (amps) knee point (ohms) s1-s2 1,200:

16/11/2015 3:34PM

SE PRINCIPAL

SALIDA

°F26

%43

TRANSFORMADOR TC2 FASE C ASSET ID

HUMIDITY

AMBIENT TEMP.

JOB #

DATE

POSITION

SUBSTATION

PIQ EQUIPMENT LOCATION

27650, REVISED 31/08/2012COPYRIGHT © 2002-2012 POWERDB, INC. www.powerdb.com

MCT1605 TESTED BY:TEST EQUIPMENT USED: ING. ROGELIO RAMIREZ S.

HITACHI

NAMEPLATE DATA

MANUFACTURER

TYPE

T12346E6 FC PHASE

WindowSolid FREQUENCY

X STYLE

60Hz

SATURATION STANDARD IEC 60044-1

SERIAL NO.

ACCURACY CLASS

ASSET ID

1NUMBER OF TESTS 5

INSULATION RATINGVOLTAGE RATING 123000 500V

SECONDARY CURRENT 10P

ENABLE FS/ %EC CALCULATION

SECURITY LIMITING FACTOR 5A

RATED OUTPUT (VA)

SEC. BURDEN TEST AMPS

5

NAMEPLATE RATIO

ACTUAL RATIO

RESISTANCE

Tap RATIO % ERROR

PHASE DEV. (deg.) POLARITY

X VOLTAGE (volts)

X CURRENT (amps)

CT RATIOS

VOLTAGE (volts)

CURRENT (amps)

KNEE POINT

(ohms)

1,200 1.55606e+006 129,571.3S1-S2 0.91Correct 311.20 0.249 294.37 0.072025 5::

1200 : 5 S1-S2

IEC 60044-1

INSULATION RESISTANCE >1000M

Secondary To GroundBURDEN

VA POWER FACTOR PHASE (Degree)

COMMENTS: VALORES ACEPTABLES DE OPERACION.

DEFICIENCIES:

PRUEBAS A TRANSFORMADORES DE CORRIENTE

Page 7: DE CORRIENTE PRUEBAS A TRANSFORMADORES · enable fs/ %ec calculation security limiting factor 5a rated output (va) sec ... voltage (volts) current (amps) knee point (ohms) s1-s2 1,200:

16/11/2015 4:0PM

SE PRINCIPAL

SALIDA

°F26

%43

TRANSFORMADOR TC3 FASE A ASSET ID

HUMIDITY

AMBIENT TEMP.

JOB #

DATE

POSITION

SUBSTATION

PIQ EQUIPMENT LOCATION

27650, REVISED 31/08/2012COPYRIGHT © 2002-2012 POWERDB, INC. www.powerdb.com

MCT1606 TESTED BY:TEST EQUIPMENT USED: ING. ROGELIO RAMIREZ S.

HITACHI

NAMEPLATE DATA

MANUFACTURER

TYPE

T12345E1 FA PHASE

BarType FREQUENCY

X STYLE

60Hz

SATURATION STANDARD IEC 60044-1

SERIAL NO.

ACCURACY CLASS

ASSET ID

1NUMBER OF TESTS 5

INSULATION RATINGVOLTAGE RATING 123000 500V

SECONDARY CURRENT 0.1

ENABLE FS/ %EC CALCULATION

SECURITY LIMITING FACTOR 1A

RATED OUTPUT (VA)

SEC. BURDEN TEST AMPS

5

NAMEPLATE RATIO

ACTUAL RATIO

RESISTANCE

Tap RATIO % ERROR

PHASE DEV. (deg.) POLARITY

X VOLTAGE (volts)

X CURRENT (amps)

CT RATIOS

VOLTAGE (volts)

CURRENT (amps)

KNEE POINT

(ohms)

1,200 1,202.85 0.23750S1-S2 0.98Correct 45.50 0.016 369.46 0.081155 5::

1200 : 5 S1-S2

IEC 60044-1

INSULATION RESISTANCE 993.00M

Secondary To GroundBURDEN

VA POWER FACTOR PHASE (Degree)

COMMENTS: VALORES ACEPTABLES DE OPERACION.

DEFICIENCIES:

PRUEBAS A TRANSFORMADORES DE CORRIENTE

Page 8: DE CORRIENTE PRUEBAS A TRANSFORMADORES · enable fs/ %ec calculation security limiting factor 5a rated output (va) sec ... voltage (volts) current (amps) knee point (ohms) s1-s2 1,200:

16/11/2015 3:46PM

SE PRINCIPAL

SALIDA

°F26

%43

TRANSFORMADOR TC3 FASE B ASSET ID

HUMIDITY

AMBIENT TEMP.

JOB #

DATE

POSITION

SUBSTATION

PIQ EQUIPMENT LOCATION

27650, REVISED 31/08/2012COPYRIGHT © 2002-2012 POWERDB, INC. www.powerdb.com

MCT1506 TESTED BY:TEST EQUIPMENT USED: ING. ROGELIO RAMIREZ S.

HITACHI

NAMEPLATE DATA

MANUFACTURER

TYPE

T12345E2 FB PHASE

WindowSolid FREQUENCY

X STYLE

60Hz

SATURATION STANDARD IEC 60044-1

SERIAL NO.

ACCURACY CLASS

ASSET ID

1NUMBER OF TESTS 5

INSULATION RATINGVOLTAGE RATING 123000 500V

SECONDARY CURRENT 10P

ENABLE FS/ %EC CALCULATION

SECURITY LIMITING FACTOR 5A

RATED OUTPUT (VA)

SEC. BURDEN TEST AMPS

5

NAMEPLATE RATIO

ACTUAL RATIO

RESISTANCE

Tap RATIO % ERROR

PHASE DEV. (deg.) POLARITY

X VOLTAGE (volts)

X CURRENT (amps)

CT RATIOS

VOLTAGE (volts)

CURRENT (amps)

KNEE POINT

(ohms)

1,200 1,202.78 0.23150S1-S2 0.97Correct 45.50 0.016 373.06 0.084035 5::

1200 : 5 S1-S2

IEC 60044-1

INSULATION RESISTANCE 746.00M

Secondary To GroundBURDEN

VA POWER FACTOR PHASE (Degree)

COMMENTS: VALORES ACEPTABLES DE OPERACION.

DEFICIENCIES:

PRUEBAS A TRANSFORMADORES DE CORRIENTE

Page 9: DE CORRIENTE PRUEBAS A TRANSFORMADORES · enable fs/ %ec calculation security limiting factor 5a rated output (va) sec ... voltage (volts) current (amps) knee point (ohms) s1-s2 1,200:

16/11/2015 3:40PM

SE PRINCIPAL

SALIDA

°F26

%43

TRANSFORMADOR TC3 FASE C ASSET ID

HUMIDITY

AMBIENT TEMP.

JOB #

DATE

POSITION

SUBSTATION

PIQ EQUIPMENT LOCATION

27650, REVISED 31/08/2012COPYRIGHT © 2002-2012 POWERDB, INC. www.powerdb.com

MCT1506 TESTED BY:TEST EQUIPMENT USED: ING. ROGELIO RAMIREZ S.

HITACHI

NAMEPLATE DATA

MANUFACTURER

TYPE

T12345E3 FC PHASE

WindowSolid FREQUENCY

X STYLE

60Hz

SATURATION STANDARD IEC 60044-1

SERIAL NO.

ACCURACY CLASS

ASSET ID

1NUMBER OF TESTS 5

INSULATION RATINGVOLTAGE RATING 123000 500V

SECONDARY CURRENT 10P

ENABLE FS/ %EC CALCULATION

SECURITY LIMITING FACTOR 5A

RATED OUTPUT (VA)

SEC. BURDEN TEST AMPS

5

NAMEPLATE RATIO

ACTUAL RATIO

RESISTANCE

Tap RATIO % ERROR

PHASE DEV. (deg.) POLARITY

X VOLTAGE (volts)

X CURRENT (amps)

CT RATIOS

VOLTAGE (volts)

CURRENT (amps)

KNEE POINT

(ohms)

1,200 1,202 0.16700S1-S2 0.98Correct 45.40 0.017 376.80 0.085425 5::

1200 : 5 S1-S2

IEC 60044-1

INSULATION RESISTANCE

Primary To SecondaryBURDEN

VA POWER FACTOR PHASE (Degree)

COMMENTS: VALORES ACEPTABLES DE OPERACION.

DEFICIENCIES:

PRUEBAS A TRANSFORMADORES DE CORRIENTE