DDNLH001 Holyrood Blackstart Diesel Units Application Page 1 of 1 Q. Please provide a complete copy of the contract to supply and lease the diesel units. 1  2  3 A. Please see DDNLH001 Attachment 1. 4 

Transcript of DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

Page 1: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

DD‐NLH‐001 Holyrood Blackstart Diesel Units Application 

Page 1 of 1 

Q.  Please provide a complete copy of the contract to supply and lease the diesel units. 1 

 2 

 3 

A.  Please see DD‐NLH‐001 Attachment 1. 4 

Page 2: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

Corqr n-ael

2c64' E6

NEWFOUNDLAND AND LABRADOR HYDRO

CONTRACT

FOR

Install Holyrood Blackstart Capability

2013-56865 AB

Seal of Engineer with Primary

Responsibility

Jet IN/

1,

i 1 s.Nt'i II P

t .

..04.....x0(fv., 04..........,

Electrical

Mechanical

Civil

Protection & Control ,r9 - , —

Transmission 8:15istribution

Telecontrol

System Planning

DD-NLH-001, Attachment 1 Page 1 of 88, Holyrood Blackstart Diesel Units Application

Page 3: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

DD-NLH-001, Attachment 1 Page 2 of 88, Holyrood Blackstart Diesel Units Application

Page 4: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

CONTRACT AGREEMENT CONTRACT 2013-56865AB

CONTRACT AGREEMENT

DD-NLH-001, Attachment 1 Page 3 of 88, Holyrood Blackstart Diesel Units Application

Page 5: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

CONTRACT AGREEMENT Page 11 CONTRACT: 2013-56865AB

PROJECT TITLE: Install Holyrood Blackstart Capability

CONTRACT

THIS CONTRACT made as of the 10 day of December, 2013

BETWEEN: NEWFOUNDLAND AND LABRADOR HYDRO, a corporation constituted by statute and an

agent of Her Majesty the Queen in right of the Province of Newfoundland and Labrador

and having its head office at Hydro Place, St. John's, in the said Province (hereinafter

called "Owner") of the one part;

AND Tormont CAT Power Systems (hereinafter called "Contractor") of the other part.

C 1 Contract Documents

.1 The following documents, sometimes referred to the Contract Documents, form part of this

Contract:

Schedule A — TENDER SUBMISSION

Schedule B — GENERAL CONDITIONS

Schedule C — SPECIAL CONDITIONS

Schedule D — PAYMENT

Schedule E —SPECIFICATIONS

.2 Execution by Owner and by Contractor of this Contract shall constitute acceptance and

approval by the parties of all the provisions, terms and conditions of all of the Contract

Documents as if each had been executed by both parties.

C2 Work

.1 The Contractor hereby undertakes to perform and complete the Work as described in this Contract.

.2 Contractor, for and in consideration of the payment to be made to Contractor as hereinafter

provided, agrees to furnish all labour, Material and Plant necessary or required for the

performance of the Work, unless specified elsewhere in the Contract.

C 3 Price and Payment

.1 Owner, in consideration of the performance of the Contract by Contractor, agrees to pay

Contractor in accordance with the rates and prices set forth in the Schedule A - TENDER

SUBMISSION, Schedule of Prices, subject to any additions or deductions provided for

elsewhere in the Contract Documents. Such payment shall be made in accordance with the

procedures set forth in Schedule D - PAYMENT.

Oct 2013 - Rev

DD-NLH-001, Attachment 1 Page 4 of 88, Holyrood Blackstart Diesel Units Application

Page 6: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

CONTRACT AGREEMENT Page 12 CONTRACT: 2013-56865AB

C 4 Interpretation

.1 The Contract embodies the entire agreement between the parties with respect to the

subject matter hereof. Reference should be made to the Definitions set out in Schedule B - GENERAL CONDITIONS.

.2 The Contract Documents are intended to be correlative and complementary and any Work

required by one document and not mentioned in another shall be executed as though required by all documents.

.3 The Contract is intended to cover all the Work to be done by Contractor; and, unless

expressly excluded in the Contract, any and all Material, Plant and labour not indicated

herein but which may be necessary or required to complete any part of the Work in a proper, substantial and workmanlike manner shall be furnished by Contractor.

.4 If Contractor, in the course of the Work, discovers any discrepancy between the

Specifications and the physical conditions of the Site or finds any error, omission or

ambiguity in the Contract Documents, Contractor shall immediately apply in writing to

Owner for clarification. Owner will promptly clarify such matters and so inform Contractor. Any part of the Work affected by any or all such discoveries which is performed by

Contractor prior to clarification by Owner shall be done at Contractor's risk and Contractor

shall be liable for any loss, damage or expense which Owner may incur, suffer or be put to

as a result of Contractor's failure to obtain such clarification.

.5 In case of conflict between the Contract Documents, the said documents shall be considered

in the following order of precedence, unless otherwise provided: the executed CONTRACT,

GENERAL CONDITIONS, SPECIAL CONDITIONS, SPECIFICATIONS (drawings of a larger scale

shall govern over a smaller scale), TENDER SUBMISSION,PAYMENT.

.6 In the Contract Documents all references to dollar amounts and all references to any other

money amounts are, unless specifically otherwise provided, expressed in terms of currency of Canada.

.7 Words in the Contract Documents importing the singular number shall include the plural

and vice versa and words importing the masculine gender shall include the feminine and neuter genders.

.8 Where a word is defined anywhere in the Contract Documents, other parts of speech and

tenses of the same word have a corresponding meaning.

.9 Wherever in the Contract Documents a number of days is prescribed for any purpose, the

days shall be reckoned exclusively of the first and inclusively of the last.

.10 Whenever the Contract Documents require either a notice to be given or a request to be

made, and the time within which any right will lapse or expire shall terminate on a Saturday,

Oct 2013 - Rev

DD-NLH-001, Attachment 1 Page 5 of 88, Holyrood Blackstart Diesel Units Application

Page 7: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

CONTRACT AGREEMENT Page 13 CONTRACT: 2013-56865AB

Sunday or legal holiday, such time will continue to run until the next succeeding normal

business day.

.11 In the Contract Documents the headings and any tables of contents and indexes attached

thereto are inserted for convenience of reference only and shall not affect the construction

or interpretation thereof.

.12 Any reference in any Contract Document to an article, a clause, a subclause, a paragraph or

a schedule shall, unless the context otherwise specifically requires, be taken as a reference

to an article, a clause, a subclause, a paragraph of or schedule to that Contract Document.

.13 This Agreement may be executed in two or more counterparts, each of which when so

executed shall be deemed to be an original, but all of such counterparts together shall

constitute one and the same instrument.

.14 The rights and recourses of Owner contained in the Contract Documents are cumulative and

not in the alternative. The exercise of any such rights or recourses shall not constitute a

waiver or renunciation of any other rights or recourses.

C 5 Assignment

.1 Neither Owner nor Contractor may assign or otherwise transfer any rights or interests

created under the Contract without the prior written consent of the other, provided always

that Owner may assign its rights and interests under the Contract to an Affiliate of Owner

without the consent of Contractor.

C 6 Waiver

.1 No act or failure to act or delay in the enforcement of any right by either party hereto

constitutes a waiver of any right under the Contract, and any such act, failure to act or delay

does not constitute an approval of or acquiescence in any breach or continuing breach

under the Contract except as expressly agreed to in writing and no waiver of any breach of

any provision of the Contract constitutes a waiver of any preceding or succeeding breach of

such provision or of any other provision of the Contract.

C 7 Severability

.1 In the event that any provision of the Contract, or part thereof, is determined to be invalid,

void or otherwise unenforceable, the remaining provisions of the Contract are to be

construed (provided the Contract remains capable of completion in all material respects as

contemplated hereunder) as if such invalid, void or unenforceable provision, or part thereof,

was omitted and the Contract continues in full force and effect without being impaired or

invalidated in any way, and the parties hereto agree to be bound by and perform the same

as thus modified.

Oct 2013 - Rev

DD-NLH-001, Attachment 1 Page 6 of 88, Holyrood Blackstart Diesel Units Application

Page 8: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

CONTRACT AGREEMENT Page 14 CONTRACT: 2013-56865AB

C 8 Law and Jurisdiction

.1 The Contract is governed by and is to be construed in accordance with the local domestic

laws of the Province of Newfoundland and Labrador, Canada (including the laws of Canada

applicable therein) without reference to its conflict of law rules. With respect to any action

or proceeding to which the parties do not consent to mediated negotiation or arbitration as

provided for in the Contract, the parties agree to and each of them do hereby exclusively

submit to the jurisdiction of the Courts of the Province of Newfoundland and Labrador,

Canada.

C 9 Notices

.1 Any written notice provided for herein to be given to one party by the other party shall be

deemed properly given and received if:

(a) delivered to the receiving party's designated representative at the Site; or

(b) either:

i. being mailed by prepaid registered mail; or

ii. transmitted by electronic methods;

to the receiving party's address as either stated in this Article or as changed through

written notice to the other party.

.2 Any notice which is sent by prepaid registered mail or transmitted by electronic methods

shall be deemed to be given and received forty-eight (48) hours after mailing or transmission,

as applicable; provided that if such time expires on a Saturday, Sunday or legal holiday, the

notice shall be deemed to be given and received on the next normal business day.

.3 Addresses of parties are:

Owner: NEWFOUNDLAND AND LABRADOR HYDRO P.O. Box 12400 Supply Chain Management 4th Level, Hydro Place St. John's, Newfoundland and Labrador A1B 4K7

Attention: Ashley Billiard Title: Supply Chain FAX: 709-737-4643

Contractor:

Oct 2013 - Rev

DD-NLH-001, Attachment 1 Page 7 of 88, Holyrood Blackstart Diesel Units Application

Page 9: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

CONTRACT AGREEMENT Page I CONTRACT: 2013-56865AB

Phone:

FAX:

C 10 Survival of Covenants

.1 All covenants, warranties, obligations, indemnities and provisions of the Contract which

expressly or by their nature require observance and/or performance by Contractor after the

expiration or other termination of the Contract, howsoever caused or arising, continue in

full force and effect subsequent to, and notwithstanding, such expiration or other

termination of the Contract until they are satisfied in full or by their nature expire.

C 11 Binding Effect

.1 The Contract enures to the benefit of and is binding upon the parties hereto and their

respective successors and permitted assigns.

Oct 2013 - Rev

DD-NLH-001, Attachment 1 Page 8 of 88, Holyrood Blackstart Diesel Units Application

Page 10: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

DA 1

(Title)

L,(41-1,k (Witness)

AND: v_py (Name

(Title)

CONTRACT AGREEMENT Page 16 CONTRACT: 2013-56865AB

IN WITNESS WHEREOF, the parties hereto have executed this Contract by the hands of their duly

authorized representatives as of the day and year first above written.

Signed and delivered in the presence of: NEWFOUNDLAND AND LABRADOR HYDRO

(Owner)

BY: f (Witness) (Name)

Signed and delivered in the presence of: Tormont CAT Power Systems

(Contractor)

BY:

etAA_e_te

(Name)

AND: (Name) (Witness)

(Title)

Oct 2013 - Rev

DD-NLH-001, Attachment 1 Page 9 of 88, Holyrood Blackstart Diesel Units Application

Page 11: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

L

DD-NLH-001, Attachment 1 Page 10 of 88, Holyrood Blackstart Diesel Units Application

Page 12: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

TOMMONT Power Systems

1

Toromont CAT Power Systems

82 Kenmount Road St. John's, NL Al B 3S2 709-722-5660 tel 709-722-2290 fax

December 17, 2013

Philip Holett Nalco Energy St John's, Newfoundland

Re: 16 MW — Holyrood Temporary Power Solution

Dear Phil;

We've reviewed the subject opportunity and timelines thoroughly. We can confirm that, on the strength of any resulting contract, Toromont is prepared to invest accordingly and hereby offer this solution. Please accept this letter as a basic summary of an analysis we've conducted to conclude this indicative proposal.

Option

Generators 25°C for a MWe (ISO

cAPPI::1 111111 8 Caterpillar XQ2000 Reciprocating Engine each stand-by rated 2.0 MW total installed capacity of 16 conditions) at each station.

i Item Recips 1. Make Caterpillar 2. Model XQ2000 3. Quantity 8

L

4. Output voltage 480 Volts Transformed to

4.16 kV 5. J Fuel LHV 42,780

DD-NLH-001, Attachment 1 Page 11 of 88, Holyrood Blackstart Diesel Units Application

Page 13: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

Item = Recips

, Running Capacity (N)

16.0 MWe @ -12C 16.0 MVVe @ -1.6C 16.0 MWe @ +15C 16.0 MWe @ +32C

7. Heat Rates SO conditions)

100% Load 9456 kJ/kWe-hr

8.

St ail times (@ ISO conditions) Purge

Ignition & warm-up Acceleration

Parallel

0 secs 10 secs 5 secs 30 secs

9. Load up time (ramp 0-100%) 30 secs. 10. No load run time limits 30 mins. 11. Load rejection limits No limit

Pricing Basis — Nalcor requested that we consider a rental term of six months with an option to extend to eighteen months.

Toromont Cat is pleased to quote you on the rental of equipment for the Holyrood project. Following are the monthly rental rates for the XQ2000's.

Rental Option: Standby rental rate for the 8 - XQ2000's based on 40 hours per month = $200,000/nnonth/40hrs.

Single Shift rental rate for 8 - XQ2000's based on 160 hours per month = $268,000/month/160hrs.

Shift-.rental rate for 8 - XQ2000's based on 320 hours per month = $400,000/month/320hrs.

Triple shift rental rate for 8 - XQ2000's based on 672 hours per month = $532,400/month/672hrs.

Transformer rental for 8 transformers is $40,000/month.

Low Voltage and High Voltage cable rental based on 60ft is $250,000

Freight is $350,000

Engineering and Field Service will be $175,000 Toromont CAT Power Systems

268 Orenda Road, Brampton, Ontario L6T 1E9 tel 905-488-2500 fax 905-488-2501

DD-NLH-001, Attachment 1 Page 12 of 88, Holyrood Blackstart Diesel Units Application

Page 14: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

$2,880,000,

te -

. .<'s for 8 units will be $80,000

Equipment Placement $15,000

PurchE•se Price for 1 - XC)2000, Transf:A iner E. Id Cable will be $1.2M. 80% of the rental rate per XC)2000 will be credited against the purchase price plus V/ interest per month.

As per contract # 2013-56865AR and assuming the project will be for 6 monti- : on standby. If in the event the units have to run for an outage the approrate will be char-ed. The standby rate for the XQ2000's will be for the 6 month period $200,000/month/40hrs. X 6 = $1,200,000.

The cable rental will f the low voltage cable and the high voltage cable based on 60ft runs. The cable will be installed by Toromont/ Hydro. The rate for the 6 months will be $250,000.

The 8 transformers for the 6 month period will be $240,000

The freight will be $350,000.

Engineering and Field Service will be $175,000.

Resistive and Reactive Load Bank Rentals for performing testing of system will be $50,000

NGR's will be $80,000

Equipment Placement $15,000

The total cost for thc. 6 rioeuRh rental will be $2,3130.603 +

To extend the contract for an additional 12 months will cost the following in addition to the 6 month contract.

The 8 - XQ2000's will cost $2,400,000.

The transformers will cost an extra $480,000.

The total cost for ,ndendin he contract for an additional 12 months will be

Toromont CAT Power Systems

268 Orenda Road, Brampton, Ontario L6T 1E9 tel 905-488-2500 fax 905-488-2501

DD-NLH-001, Attachment 1 Page 13 of 88, Holyrood Blackstart Diesel Units Application

Page 15: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

• The Customer will be responsible for insurance of the units while on rent If this is a problem for Hydro then Toromont could arrange for insurance but it would be an extra cost.

• Customer will be responsible for fuel. • Customer will be responsible for security on site. o The set up and tear down will be in conjunction with Hydro personal. o Hydro will be responsible for servicing of the units while on site ( ie: oil

and filter changes ) or arrangements can be made with Toromont to look after this at an extra cost. The units will come serviced and will not need oil/filter changes for 500 hours of usage.

o Shore power to power up things like Jacket Water Heaters and Battery Chargers will be Hydro. Control wiring between gensets will be Toromont/Hydro. Special cable ends for the High Voltage cable will be by Toromont/Hydro.

• The delivery times for the XQ2000's will be as per the contract.

If you have any questions please don't hesitate to call.

Yours Truly;

Darrell Lambert Toromont Cat Power Systems Direct: 709-722-5660 Cell: 709-682-1358

Toromont CAT Power Systems

268 Orenda Road, Brampton, Ontario L6T 1E9 tel 905-488-2500 fax 905-488-2501

DD-NLH-001, Attachment 1 Page 14 of 88, Holyrood Blackstart Diesel Units Application

Page 16: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS g e I 1 CONTRACT 2013-56865AB

SP 4 Transformer Specification

Each generating until will include a padmount transformer located outside and behind the diesel

unit. Pad mount transformers PAD1283-S and PAD1289-5 are acceptable solutions with the

following general specifications:

Configuration wye — wye

Primary Voltage: 480V

Secondary Voltage: 4160V

Impedance: 5% — 6%

Any other padmount transformer must be approved by the customer prior to acceptance.

Vendor will supply appropriately rated cables and terminations for cables leading from the

Diesel generators to the 480V side of the padmount transformers. Vendor will supply

appropriately rated cables to connect from the 4160V side of the transformer to the riser pole.

These cables must be a minimum of 60' long. Vendor to supply the connections from the cables

to the 4160V side of the transformer.

SP 5 Information to be Supplied With Bid

INFORMATION TO BE SUPPLIED WITH BID

E.1 TECHNICAL PARTICULARS Bidder shall submit Drawings and design data as per Article 8,2.1 of Appendix B — General Conditions with each copy of its Proposal. It shall also give details of the equipment it proposes to supply, including, but not limited to, the following data.

Reference Users

The Bidder shall demonstrate previous proven experience in Canada. Each tendered generating set or identical model shall have been installed in Canada and operated at the design and operating requirements as specified in this Specification. Bidder shall submit details listing for whom each unit was supplied, the date it was supplied and a contact person.

DD-NLH-001, Attachment 1 Page 15 of 88, Holyrood Blackstart Diesel Units Application

Page 17: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS _; I 2 CONTRACT 2013-56865AB

.2 Servicing of Equipment

Location of nearest service personnel and facilities

Equipment Data

Bidder shall complete n11 of the following equipment data, for each generating unit rating tendered:

(a) Exhaust flow (lOVANPR)

r4/rri'n

DD-NLH-001, Attachment 1 Page 16 of 88, Holyrood Blackstart Diesel Units Application

Page 18: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS I 3

CONTRACT 2013-56865AB

(b) Exhaust gas temperature at exhaust manifold exit as follows:

25% of engine NPR

'C 50% of engine NPR

'

75% of engine NPR

100% of engine NPR

(c) Engine emission data as follows:

I Engine Load 25%NPR 50% NPR

75% NPR

100% NPR

Exhaust Flow Rate mi/min Exhaust Mass , , . kg/hr Carbon Monoxide (CO) , i

., , gthr

Carbon Dioxide CO. -. , 9/hr NO + NO2 NO), - . , , . g/hr

I Sul•hur Dioxide SO2 . , g/hr Particulate . . g/hr Carbon in Particulate . . .:. - .

(d) Load Pick Up

(i)

Load pick up capability in % of NPR with a maximum 2% engine speed decrease

If load pick up must be staged, the following are the % loads which shall be applied to the unit at five (5) second intervals.

First load pick up

Second load pick up

Third load pick up ji

Fourth load pick up

(e) Generator Data as follows:

DD-NLH-001, Attachment 1 Page 17 of 88, Holyrood Blackstart Diesel Units Application

Page 19: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

A

V

A

Hz

et s

SPECIFICATIONS f - I 4 CONTRACT 2013-56865AB

Manufacturer

(ii) Rated Full Load Current

(iii) Exciter Field Resistance

(iv) Excitation Current at No Load

(v) Excitation Voltage at No Load

(„il Excitation Current at Full Load (0.8 pf) „v.,

(vii) Excitation Voltage at Full Load (0.8 pf)

(viii) PMG Output Frequency

(ix) PMG Output Voltage

(x) Generator efficiency as follows:

25% of engine NPR

50% of engine NPR

75% of engine NPR

100% of engine NPR

(xi) Generator Load Losses as follows:

25% of engine NPR

50% of engine NPR

75% of engine NPR

100% of engine NPR

(xii) Generator P.U. reactances as follows:

Direct axis saturated synchronous p.u.

Direct axis transient (Xd') p.u.

Direct axis sub-transient (Xd")

Xd)

DD-NLH-001, Attachment 1 Page 18 of 88, Holyrood Blackstart Diesel Units Application

Page 20: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

MVA

A

kV

-, kV

p.u.

p.u.

p.u.

p. U.

Leakage (Xi)

Negative sequence (X2)

Zero sequence (X0)

SPECIFICATIONS 1 I 5 CONTRACT 2013-56865A3

0

(1)

Switchgear and Transformer Data

Fault Current Rating

Continuous Current Rating

Winding Configuration HV

Winding Configuration LV

Voltage Rating HV

Voltage Rating LV

DD-NLH-001, Attachment 1 Page 19 of 88, Holyrood Blackstart Diesel Units Application

Page 21: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS P p 16 CONTRACT 2013-56865AB

E.2 SCHEDULE For each event below the dates entered by the Bidder in Column 2 shall agree with the dates required by Purchaser Column 1, These shall be subsequently agreed to by the Purchaser, and become the approved schedule. This schedule shall be submitted for each proposal.

DATE REQUIRED DATE CONFIRMED BY PURCHASER BY VENDOR

EVENT

Delivery of equipment Jan 17, 2014 to Holyrood Thermal Plant

Installation and commissioning Feb 21, 2014 of equipment.

Failure to guarantee or meet delivery dates outlined may result in rejection of bid.

E.3 GUARANTEES

Bidder shall provide the following performance data.

These values shall be guaranteed under the specified operating conditions and shall be binding on Vendor. Cost data shall be consistent with prices being charged Vendor in the current calendar year. Inconsistencies may result in rejection of proposal.

.1 Performance Data

(a) Prime ISO Power Rating at 0.8 P.F. kWe

(b) Overload Power Rating at 0.8 P.F. kWe

(c) All fuel performance guarantees are based on specified fuel as per Article C.4 - Fuel

YES

NO Specification of Appendix C Genset Specifications

(d) Lower Heating Value of Fuel on which the Specific Fuel Consumption values are based

kJ/kg

(e) Guaranteed Specific Fuel Consumptions, corrected to standard ISO conditions at 0,8 P.F:

25% of engine NPR g/kWhe 50% of engine NPR g/kWhe 75% of engine NPR g/kWhe 100% of engine NPR g/kWhe

Engine light loading capability as follows:

DD-NLH-001, Attachment 1 Page 20 of 88, Holyrood Blackstart Diesel Units Application

Page 22: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS I 7 CONTRACT 2013-56865AB

z

Minimum recommended light load kWe

Duration light load can be applied hrs

.2 Technical Support —

Location of on-call technical support Guaranteed emergency response time-to-site hrs

Buchans

English Hr. West

St. Anthony

hrs

hrs

SP 6 Additional Work

.1 Scope

Vendor shall supply:

• Engineering and Field Service

• The cable rental will be for the low voltage cable and the high voltage cable based on

60ft runs. The cable will be installed by Hydro

• Resistive and Reactive Load Bank Rentals for performing testing of system

Additional Work to be done under this Clause SP 4 shall comprise the supply of all labour,

construction plant and materials and the performance of all Work not included in scope of

Contract but deemed necessary for completion of the Project.

.2 General

The Contractor shall notify the Owner of any additional Work required. All, if any, Work shall be

performed as directed and scheduled by Owner. Cost of such Work shall be considered during

Tender Evaluation.

Scope of Work shall be agreed upon by Contractor and Owner or Owner's site representative.

The Contractor shall submit copies of material pricing, labor and rental rates to the Owner to

substantiate the cost of additional Work.

SP 7 Drawings

.1 Contractor shall perform the Work in strict accordance with Drawings.

DD-NLH-001, Attachment 1 Page 21 of 88, Holyrood Blackstart Diesel Units Application

Page 23: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

Me MEM NMI IMO

ormon MIS alivili1111111 MII.F111111.11111 Ims111•111111111•11 110011111=4110111 111111111-11110111111•111

■■■••■•mome 11111•1111111,1011,

1111111111111•16 11111111111111111111111

111111.111111•11111111 111■1111•11100 Owerposams•

N111111111116 011.11M/MONIe

c 4-4.C141,

WISNER,

,

- - ,

L'•-• -•;•■•••?. 1'. • -

,-, :A • 'Irf.,1 434 4

11110ATI 1 sum xisaams

:I), --• ••• ,, • ,, • • .,• .. • .

11113AW A4i

r ...

i v, if .. , 1

.,..,

4...,■■••• •••••■••-.- 7 ..i.,..!.:

„as

m"

Ailln I II ._ r ' T.• 0 .. •■••Elt

:. I , ,.1

_ .....w...I....,__ 01 ___ .

1111111111111 MIN ' '1 t ' UPS 1111

' ' .

'. ..r. • , . .......... . I- i -IP liwamiltumm ;.-6, 7 _ I

ir , ' -lki,, LI •

.

- __ pia, {' ' •-• - ilr": - - ' • - •

, ,i , ,

ii '

wan_

' '---.:-Lii-•.'".'

I I •

ictIJO4

L '73

'123 • 3 EizaJ

1171S9Sref-ri

EL: E-73 L

DD-NLH-001, Attachment 1 Page 22 of 88, Holyrood Blackstart Diesel Units Application

Page 24: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

ENCACCReqr P.49,0611 90205

MODEt TYPE PRI(INC; 44

.5516 14,3460 CMG 35 1

A

19500 [531 50;

- 121020 [480(101

t 14.31 9 [465 R2]

73:1,7 1248291

20218 79 64] - ENTRANCE POOP

440■4109 r4.1 4Z:J:155 PLATE 400IO2 PLATE 1098.15 [43.241

r E1.0RANC:F DOOR 245.2 [9 651 NEL TiLL DOOR ■44,5),.

20424

2904 5 14 35J

24048 11043] 82041] 1'441

4114,4 11112,001

1219 2 [4H no)

1322 2 152 mi

AIR LOUL,k,fi":; 882 7. 1.34 751 TTF

CABLE 51064175 40), [01 5)1141)

—AiR 38048E 50001140

L F01, L DR4111/ ',uPPLY 11711 11151 1811454154 (1 5 INCH '1141'.5

-

-r

Roff SIDE 0158

194. 014■3..

DD-NLH-001, Attachment 1 Page 23 of 88, Holyrood Blackstart Diesel Units Application

Page 25: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

ACCESS PLATE

ExTEFa0117 FL DOOR

01,1 ((MAO

2U84 i911 Cluj

1219.11 [All 1./11j

I.I/A11/ egar: ACCESS. DOOR

R1:1?1, 1R38.43]

( OP 1 ior4A1

; .3500 i,511.b1).1

12192.0 [48000)

AIR NTAKE LQI.NERS

\1- CABLE 1.11DRAGi 141.1h1

AIR INTAKE. 1..111L1VERS

TMETRIC

7327 7 1288.291

413 r1)1:R 100 DRY 'CARGO -009IA1NER.

ENTRANCI 110011 \

\ 1

— 2047 1 [80.89) —1

11:74.11A1OR TILL /1.7•'17 11; ATE

CAT(P,II!

:41I7,•.1.11•17

198-131, -1.

LEFT 01111E VIEW

DD-NLH-001, Attachment 1 Page 24 of 88, Holyrood Blackstart Diesel Units Application

Page 26: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

GINA= 196-0147

a'N METE1141196-0147,

or. -ntnR/ •A LAT4-11 I-Miff:Hi OuPT FA AC RI CEPTACI F. 24v RAI !ERIE S AND RACK/ (OPTIONAL) BATTERY HEATER PADS

(ORIIONAL)

FUEL DRAIN/ suPpLY FOR FUEL TRANSFER (1.5 INCH NHT)

FULL/WATER nERARATORS \

\1250 GALLON LOLL /AAR( Li L. 1.4STED/

\ \ DOUBLE WALL ruEL. TANK\

\ FULL TRANSFER SYTiTEM (OPTIONAL)

RSOD 11419.69)

EXTERIOR RILL TILT DOOR --. (OPTIONAL)

ENTRANCE DOOR- \

EXTERIOR EMERGENCY SUP (OPTiONAL)

• f;E.,NET<ATL)R

3515 4 TURBO ENGINE

EX I-RA SE! Of DA1 fEffliS (OPTIONAL)

, ENTRANCE DOOR

cRiDcAL CTRADE MUFFLER (2 PLACES)

4 INCH SOUND ITTSTDATION pANELS

812192 [84F1,00) 2 PI.ACES

FAHALIST (ESChARCF -RADIATOR. RIL ACCESS PLATE

INTERIOR '.>HAFf TITAN-IR / (oTTTDNAL)

BoTrom LOAD CARL CAEtErf,-,

24V DC LIGHT( - AG oGN (uPDONAE)

.I- RI L A t■NGUIS1-11;17

LURE OIL MAKE -UP SYSTEM (DPW:INN.)

TAK.F_ OUCT 11104 BELLOWS -

R9113.31837 3 RI AGES

L R744.5 1R79.31) 2 DOOR EACH SIDE

- CABLE STORAGE SOX 2 DOORS EACH SUE (FIF DONAL)

24M DC LrCHT/ AC LICHTS (OPTIONAL)

TOP VIEW

\ /

RADIATOR Fla (IACKET WATER)

RADIATOR TILL I;AFTERCOOLER)

-RADIATOR FilL ACCESS PLATE

RADIATOR (NORiZONTAL)

Fr

J

ENTRANCE DEWS

FIRE- FE FINCIPT,HFIR

iffr%1VV.V...1,n7: ON! 11.8,1111 ,,II,:i• 211,11 INCJI711111111C.-■-

=VIVO; ::,.11MM =1,0•1111:Ma•M= fr-MMAIW,..:4111•11.1 ,1111 • • •

[2-

MIN En NM IDE FIT:i MEI WO 3 6:: E.:

DD-NLH-001, Attachment 1 Page 25 of 88, Holyrood Blackstart Diesel Units Application

Page 27: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

CATERFILLAR X0.2000 RENTAL

Image shown may not reflect actual package

FEATURES

EPA TIER 2 and CARB certified for non-road mobile applications. Factory designed, certified prototype tested with torsional analysis. Production tested and delivered in a package that is ready to be connected to your fuel and power lines. Supported 100% by your Caterpillars dealer with warranty on parts and labor. Extended warranty available in some areas. The generator set is designed and manufactured in an ISO 9001:2000 compliant facility. Generator set and components meet or exceed the following specifications: AS1359, AS2789, ABGSM TIV13, 8S4999, DIN6271, DIN6280, EGSA101P, JEM1359, IEC 34/1, IS0304611, IS08528, NEMA MG1-22

CATERPILLAR SR4B GENERATOR Single bearing, wye-connected, static regulated, brushless permanent magnet excited generator designed to match the performance and output characteristics of the Caterpillar diesel engine driving it,

RELIABLE, FUEL EFFICIENT DIESEL ENGINE The compact, four-stroke-cycle diesel engine combines durability with minimum weight while providing dependability and economy. The fuel system operates on a variety of fuels.

STANDBY 2000 kW PRIME 1825 kW POWER MODULE 50/60 Hz

Frequency Voltage Standby kW (kVA)

Prime kW (kVAI

60 480/277V 200012500) 1825(2281)

50 400V 1440 (1800) 1310 (1638)

CATERPILLAR COOLING SYSTEM Sized compatible to rating with energy efficient fan and core.

CATERPILLAR SWITCHGEAR Provides single unit and/or multi-unit/utility paralleling components. Standby, load sense/load demand, import, export, and base load modes. Comes standard with Basler Utility Multi-function Relay IPS-100.

EXCLUSIVE CATERPILLAR DIGITAL VOLTAGE REGULATOR (CDVR) Three-phase sensing and adjustable Volts-per-Hertz regulation give precise control, excellent block loading, and constant voltage in the normal operating range.

ENVIRONMENTALLY FRIENDLY 110% spill containment of onboard engine fluids.

SOUND ATTENUATED CONTAINER For ease of transportation and protection. Meets 75 dB(A) at 50 ft or below per SAE J1074 measurement procedure at 110% prime load.

1..El158746-02

DD-NLH-001, Attachment 1 Page 26 of 88, Holyrood Blackstart Diesel Units Application

Page 28: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

CATERPILLAR' X02000 RENTAL

PIA

FACTORY INSTALLED STANDARD EQUIPMENT SYSTEM STANDARD EQUIPMENT

Engine EPA approved Tier 23516C Caterpillar engine Heavy duty air cleaner-With service inclicater 60-Arnp charging alternator Fuel filters ,=- Primary and duplex secondary with integral water separator and change over valve trubricating oil SY-stern with'spin-on,, full flow oil filters and Water cooled oil cooler Oil drain lines routed to engine rail Jacket water-heater

• Fuel cooler and priming PurnP ' Electronic ADEMTm A3 Controls 24V eleCtric Starting moters,with battery reek and cables _

Generator SR-48 brushless, permanent magnet excited, three-phase with Caterpillar digital voltage regulator (CDVF1), space heater, 6-lead design, Class H insulation operating at Class F temperature for extended life, winding temperature detectors and anti-condensation space heaters (120/240V 1,2 kW)

Containerized Module

40, ISO high cube container, CSC certified 3-aXle,. 40' ISO container chassis Seven (7') sound attenuated oir intake louvers and 4 lockable personnel do-ore with panic release

'

Side bus bar access door, external access load connection bus bars Shore power connection Via distribution black connections for jacket water heater, battery charger,

space heaters and generator condensate heaters Standard lighting 3 AC/4PC; one ft) single duplex service receptacle, 2 extern4break"-glaSs emergency

stop push buttons - 1,250 gal Neil tanjc,-UL Hated; double wall, 9 Fr runtime @ prime rating Sound attenuated 75 c18(A)@ BO ft Spill containment 110% of all engine fluids Four _(4) oversized maintenance free batteries, battery rock and 20 Amp batten/ charger Hospital grade, internally insulated, rectangular exhaust silencer with vertical discharge Vibration isolators corrosion resistant hardware and 'hinges External drain aceessto standard fluid Fire extinguisher* laty 2) Standard Cat rental decals and pointed standard Cat power module white Interior Walls 00 ceilings insulated with 100 mm of acoustic paneling Floor Of container insulated with atoustic glass and covered with galvanized steel

Cooling Standard cooling provides 43° C ambient capability i60 Hz1 at prime 4-10% rating Vertically mounted, separate ATAAC and ,IW cores with vertical air discharge

Generator Paralleling Control

Ct:storn switchgoar control With EiyIbP 3,3 genset mounted controller and waltmeunted paralleling controls , . Automatic start/stop with cool down tinter Protections : 25, 27,(59,40-: 22, 81 ON Utility Multi-function Wei( protections: 25,27/59, 32, 47, 50151, 62, 67, 81 0/1) 1.IMR is IEEE1647-2003 coMpliant in most applications Reverse compatibility inactule'provided for interface to legacy power modules Touch screen controls with event log Multi mode operation (island, multi island and utility parallel), load sharing-(mUlti-unit Only) Import & export control (utility parallel only), Manual and automatic paralleling capability Touch screen display (status and alarms) Metering display: voltage, current, frequency, power factor, kW, WHIM, kVAR, and synchrescope

Quality Standard genset and package factory tested UL, NEMA, ISO and IEEE standards O&M manuals

LEHE8746-02 2

DD-NLH-001, Attachment 1 Page 27 of 88, Holyrood Blackstart Diesel Units Application

Page 29: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

X0.2000 RENTAL

CATERPILLAR°

SPECIFICATIONS CAT SR4B GENERATOR Frame Size 825 Pitch 0 6667 No. of poles 4 Excitation Static regulated brushless PM excited Constructions Single bearing, close coupled Insulation Class H Enclosure Drip proof 11322 Alignment Pilot shaft Overspeed capability - % of rated 125% of rated Voltage regulator 3 phase sensing with Volts-per-Hertz Voltage regulation Less than ± ih% voltage gain Adjustable to compensate for engine speed droop and line loss Wave form deviation Less than 5% deviation Telephone Influence Factor (TIF) Less than 50 Harmonic Distortion (THD) Less than 5%

TECHNICAL DATA

CAT 3516C DIESEL ENGINE 3516C, 4-Stroke diesel Bore - mm (in) 170 (6.7) Stroke - mm (in) 190 (7.5) Displacement - L (Cu in) 69 (4,210) Compression ratio 15:1 Aspiration ATAAC Fuel system EUI Governor type Caterpillar ADEMm A3 Control System

Materials and specifications are subject to change without notice.

Generator Set Technical Data 50 Hz 80 Hz

Units Prime Standby Prime Standby

Performance Specification DM8754 DM8264

Power Rating kW (kVA) 1310 (1837) 1440 (1800) 182 ( '2811 2000 (2500)

Lubricating System Oil pan capacity L (gal) 401.3 (106) 401.3 (106)

Fuel System Fuel Consumption

100% load 75% load 50% 16ad

Fuel tank capacity Runnfng time © 75% rating

L (gal) L (gal) L (gal) L (gal) HoOrs

350,1 (92,5) 3722(985)

281,9 (74.5) 302.8 (80)

205.5 (54.3) 350,1 (92.4) 4731 (1,250)

16,7 15.6

4832 (127.6) 525,7 (138.9)

380 (100.4) 408.2 (107.8)

270.5 (71Z) 294.2 (77.7) 4731 (1,250)

12.5 11,5

Cooling System Radiator coolant capacity including engine L (gal) 630 (166) 630 (166)

- Air Requirements Combustion air flow Maximum air cleaner restriction Generator cooling air

ma/min (cfm) kPa (in H20) mlmin (cfm)

114.8 (4052) 118.1 (4173) 6.2 (24.9)

140 (5,933)

174.7 (6169) 180.3 16367) 62(249)

168 (4,995)

Exhaust System Exhaust flow at rated kW Exhaust stack temperature at rated kW -

dry exhaust

m'imin (cfm) °C 1°F)

311.3 (10,993) 320.8 (11,335)

5021 (935.8) 513.1 (955.6) 404 (14,260) 428.6 (15,137)

387 (728) 405 (762)

Noise Rating with enclosure) @ 7 meters (23 feet) (015 meters (50 feet)

dB(A) dB(A)

77 78 73 74

78 79 74 75

We ght

With Lube Oil With Fuel, Lube Oil Length Width Height and Coolant and Coolant

Model mm (in) mm (in) mm (in) kg (lb) kg (lb)

X02000 w/o Chassis 12 192 (480) 2438 (98) 2896 (114) 34 019 (75,000) 38 102 (84,000)

X02000 w/Chassis 12 192 (480) _ 2438 (96) 4267 (168) 38 102 (84,000) 42 184 (93,000)

RATING DEFINITIONS Standby Applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The generator on the generator set is peak prime rated (as defined in 1508528-3) at 30°C 186° F).

Prime - Applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and the generator set can supply 10% overload power for 1 hour in 12 hours.

L6HE137 45-02

DD-NLH-001, Attachment 1 Page 28 of 88, Holyrood Blackstart Diesel Units Application

Page 30: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

:\,,:z12000 RENTAL CATERPILLAR'

STANDARD FEATURES

GENERATOR SET EMCP 3.3 LOCAL CONTROL PANEL • Generator mounted EMCP 3.3 provides power

metering, protective relaying and engine and generator control and monitoring.

• Provides MODBUS datalink to paralleling control for monitoring of engine parameters.

• Convenient service access for Caterpillar service tools (not included).

• Integration with the CDVR provides enhanced system monitoring.

• Ability to view and reset diagnostics of all controls networked on J1939 datalink.

• Network modules via the control panel removes the need for a separate service tool for troubleshooting.

• Real-time clock allows for date and time stamping of diagnostics and events.

EMCP 3.3 ENGINE OPERATOR INTERFACE • Graphical display with positive image,

transflective LCD, adjustable white backlight/ contrast.

• Two LED status indicators (1 red, 1 amber). • Three engine control keys and status indicators

(Run/Auto/Stop). • Lamp test key. • Alarm acknowledgement key. • Display navigation keys. • Two shortcut keys: Engine Operating Parameters

and Generator Operating Parameters. • Fuel level monitoring and control.

CIRCUIT BREAKER • 3000A fixed type, 3 poles, genset mounted,

electrically operated, insulated case circuit breaker.

• Solid state trip unit for overload (time overcurrent) and fault (instantaneous) overcurrent protection.

• Includes DC shunt trip coil activated on any monitored engine or electrical fault, 100 KA-interrupting capacity at 480 VAC.

VOLTAGE REGULATION AND POWER FACTOR CONTROL CIRCUITRY • Generator mounted automatic voltage

regulator, microprocessor based. • Manual raise/lower voltage adjust capability

and VAR/power factor control circuitry for maintaining constant generator power factor while paralleled with the utility.

• Includes RFI suppression, exciter limiter and exciter diode monitoring.

• Voltage and power factor adjustments are performed on the setting screen of the HMI touch screen.

FUEL TANK • UL Listed 1250 gallon double walled. • Fuel transfer system

CURRENT TRANSFORMERS • CT's rated 3000:5 with secondaries wired

to shorting terminal strips.

POTENTIAL TRANSFORMERS • 4:1 ratio with primary and secondary fuse

protection.

BUS BARS • Three phase, plus full rated neutral, bus bars

are tin-plated copper with NEMA standard hole pattern for connection of customer load cables and generator cables.

• Bus bars are sized for full load capacity of the generator set at 0.8 power factor.

• Includes ground bus, tin-plated copper, for connection to the generator frame ground and field ground cable.

AC DISTRIBUTION • Provides 240 VAC for all module accessories. • Includes controls to de-energize jacket water

heaters and generator space heater when the engine is running.

SHORE POWER TWO (2) • One (1) shore power connection distribution

block for jacket water heaters. • One (1) for generator space, battery charger,

and fuel pump.

INTERNAL LIGHTING • Four (4) internal DC lights with one (1) timer

and two switches installed at each side of the container door.

• Three (3) internal AC lights. • One (1) single duplex service receptacle.

BATTERY CHARGER AND BATTERIES • 24 VDC/20A battery charger with float/equalize

modes and charging ammeter. • Maintenance free batteries.

EMERGENCY STOP PUSHBUTTON • Two external ESPs located near each

access door.

LEHE87,16-02 4

DD-NLH-001, Attachment 1 Page 29 of 88, Holyrood Blackstart Diesel Units Application

Page 31: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

CATERPILLAR' X122000 RENTAL - _ 7,arZ 711: - - --4MIXEM

MODES OF OPERATION

Caterpillar utility paralleling controls are intended for automatic or manual paralleling with a utility power source as a load management system, with provisions for standby operation feeding an isolated load network. Load management operation involves microprocessor-based automatic loading controls with soft loading, base load, Import/Export control and soft unloading. For Standby operation, the generator operates as an isochronous machine isolated from the utility supply. The controls allow for automatic operation, initiated locally o- remotely by the customer's SCADA system. Detailed modes of operation are listed below:

SINGLE UNIT ISLAND AND MULTI-UNIT ISLAND OPERATION 1. Utility Standby Mode (Normal)

a. The utility is providing power for the plant loads.

b. The Power Module Generator breaker is open.

c. The pm is in automatic standby mode to respond to a utility failure.

2. Emergency Mode (Emergency)

a. Utility Failure 1) The customer protective relaying senses

a utility abnormal condition. 2) A run request is sent to the Power Module

Generator plant. 3) The first Power Module Generator reach

rated to voltage and frequency is closed to the bus.

4) In Multi-Unit Island Mode, the remaining Power Module Generators are paralleled to the bus as they reach rated voltage and frequency. This function is performed via the ModBus Plus data link connected between the Power Modules.

5) Plant load is transferred to the Power Modules, which share load equally via ModBus Plus data link.

6) The system is now in Emergency Mode.

GENERATOR DEMAND PRIORITY CONTROL

The System Controls include a Generator Demand Priority Control function to automatically match the on-line Power Module Generator capacity to the loads in order to avoid unnecessary operation of all the Power Module Generators when the plant loads are low.

The following controls are provided for each Power Module Generator:

a. User-settable Generator Priority Selector b. Status indicator for the Generator Priority

selected c. Status indicator for Power Module Generator

on-line or off-line d. Generator Demand Priority Control Switch

(On/Off) e. User-settable Generator Remove Level

( )̀/0 as a function of single generator capacity) f. User-settable Generator Remove Time Delay g. User-settable Generator Add Level 1% as

a function of single generator capacity) h. User-set-table Generator Add Time Delay

Upon entrance into Emergency Mode, all generators will be started and paralleled to the bus. After the Remove Time Delay, Power Module Generators will be removed from the bus as a function of the generator percentage loading. Generators will be removed from the bus in descending priority order.

Should the generator percentage loading increase to the user-selected Generator Add Level after the user-selected Generator Add Time Delay, the next priority generator will be started, synchronized and paralleled to the bus. Should the Power Module Generator plant ever reach 100% loading, the next priority generator will be started and added to the bus, bypassing the Generator Add Time Delay.

LEFIE8746-02 5

DD-NLH-001, Attachment 1 Page 30 of 88, Holyrood Blackstart Diesel Units Application

Page 32: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

MI2000 RENTAL CATEVILLAR

MODES OF OPERATION (continued)

SINGLE UNIT IMPORT, EXPORT OR BASE LOAD OPERATION During periods of peak demand the system may be placed in operation using the operator interface panel on the front of the switchgear.

1. Entry-Local

a. The operator places the System Control Switch into Load Management.

b. The operator selects Import, Export or Base Load Operation.

c. The Load Management Setpoint is the amount of power Imported, Exported or Base-Loaded. A 4-12-20mA signal is provided by the customer and is linearly proportional to the utility load, with 12mA equaling 0 kW. The 4-12-20mA utility load signal is wired to one and only one Power Module. If the Power Module selected for Load Management is not available, the 4-12-20mA signal will be routed to a different Power Module.

d. The operator sets the Load Management Setpoint and Power Factor Setpoint.

e. A Run request signal is received by the Single Unit Power Module.

f. The Power Module Generator is started and will run for a predetermined warm-up time before it is synchronized and paralleled to the utility.

g. When the generator is on the bus, it is soft-ramp-loaded until the generator output reaches the Load Management Setpoint.

h. The generator output is dynamically adjusted to maintain the Load Management Setpoint.

i. Should the utility fail during Load Management Operation, the Protective Relay will cause the Paralleling Circuit Breaker 59r= to open and be locked out until the Lockout Relay is manually reset by an operator on site. The generator is allowed to run for the duration of the cooldown time.

2. Exit Local a. The Run Request signal is removed from

the power module. b. The generator is soft-ramp-unloaded until

the plant load is fully supported by the utility.

c. The Paralleling Circuit Breaker 52G is opened.

d. The generator is allowed to run for the duration of the cooldown time.

LEHE87464)2 6

DD-NLH-001, Attachment 1 Page 31 of 88, Holyrood Blackstart Diesel Units Application

Page 33: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

X 2000 RENTAL

CATERPILLAR

STANDARD PARALLELING CONTROL

GENERATOR PARALLELING CONTROLS The switchgear includes: • Single unit island mode. • Multiple unit island mode.

• Includes Load Sense/Load Demand control. • Load sharing capability is provided via

network communication. a Single unit utility parallel mode.

Selectable for Import/Export control. If import or export control is selected a 4-12- 20mA signal is required (provided by others) scalable to the utility contribution.

• 6 inch black and white HMI touch screen. • Reverse compatibility module provided for

interface to legacy designed Power Module Switchgear. Includes PLC, load share and voltage droop.

Incoming Utility Breaker Status Circuit - Circuit to accept customers contact from remote utility disconnect device. Customer to provide a normally open form 'a' contact to indicate when the local load network is connected to the utility grid.

Utility Transfer Trip Circuit - Circuit accepts input (normally open dry contact) from customer's system protective relay(s) or other controlling device. Operation of contacts causes tripping of the generator circuit breaker via the generator (software) 86 lock-out function and places the engine in cooldown mode. Circuit is disabled when operating in single unit or multiple unit island.

GENERATOR PARALLELING CONTROLS OPERATOR INTERFACE Graphical mimic one line diagram that shows generator with its respective circuit breaker in a one-line representation of the system. The graphics utilize black and white indicators and bar graphs while actively displaying the following information:

• Utility CB Open/Closed. Input contacts provided by others.

• Utility kW 4-12-20mA signal required and provided by customer that is scalable to the utility contribution.

• Generator CB Open/Closed/Tripped. • Generator Volts/Amps/kW/Frequency. • Engine Stopped/Running/Cooldown/Pre-Alarm/

Shutdown. • Engine ECS Position Stop/Auto/Run. • Utility Output kW. • System Summary Alarm.

Event logging is also included with up to 500 stored events.

GENERATOR METERING AND PROTECTION

Generator metering that will graphically display 30 Voltage, 30 Current, Frequency, Power Factor, kW, kVAR and a Synchroscope Display of EMCP 3.3 faults, CDVR or ADEM 3 will be provided via Modbus RTU interface to EMCP 3.3.

Generator/intertie Protective Relaying including: • Device 27/59 - Under/Over Voltage. • Device 810/U - Under/Over Frequency. • Device 40 - Loss of Excitation. • Device 32 - Reverse Power. • Device 25 - Synchronizing Check. • Device 15- Auto Synchronizer. • Device 65 - Governor Load Sharing, Soft

Loading Control. • Device 90 - VAR/PF and Cross Current

Compensation Controller.

PROGRAMMING AND DIAGNOSTICS Includes field programmable set points for engine control and monitoring variables and self-diagnosis of the EMCP 3.3 system component and wiring failures.

ENGINE CONTROL SWITCH Keypad selectable, four (4) positions - Off, Auto, Man, Cool: • Off for engine shutdown and resetting faults. • Auto for local or remote automatic operation

when initiated by switch operation or contact closure.

• Man for local starting and manual paralleling. • Cool for normal engine shutdown with timed

cool-down cycle.

CIRCUIT BREAKER CONTROL SWITCH

Heavy duty, three- (3) position spring return to center with momentary trip and close position and slip contacts for automatic closing. Includes circuit breaker position indicating lamps.

EMERGENCY STOP PUSHBUTTON • Mushroom head, twist to reset, causes engine

shutdown and tripping of the generator circuit breaker. Prevents engine starting when depressed.

LEHEE746-02 7

DD-NLH-001, Attachment 1 Page 32 of 88, Holyrood Blackstart Diesel Units Application

Page 34: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

ntM6Y :7Tirrialee

GIN I

• 1,1:i!%f To 1. -.ENP.RATc.fic

I

TiTT To r...•5_ ;■ f 1...NC•IN;

4.TNA -!';

-AVAII

'.111.901.5Z

SOS we. (141/001$

/WM 1Pli,fpv

rM'inaMV Mtn"

.._.ALL t t 11: A .

0,0111,1f PIOD3 OPP I ItIk

, ituf.f f i

rAY,Ali HIKE :0 (.0 '..,;ENt.'

REV,: I °IA.( fifgt Tow 11-'.- t• aht I "

ri:) THE Ta THE

‘e. ENs

T0721: F. HERE TO (o) rt.) THE :L.:0E1E

t,:+.1N-TKOt scREENs

X0.2000 RENTAL CATERPILLAR

STANDARD PARALLELING CONTROL (continued)

ELECTRONIC LOAD SHARING GOVERNOR • Includes speed adjustment, and auto load

share capability when in parallel with legacy power modules.

ALARM MODULE • Dedicates annunciator screens for warning and

shutdown faults. Includes external mounted horn and acknowledge push-button.

AUTOMATIC/MANUAL PARALLELING • Automatically synchronizes and parallels the

generator with another power source. • Includes provisions for manual permissive

paralleling.

HUMAN MACHINE INTERFACE (HMI) HIGHLIGHTS • Engine/Generator function is performed thru

the 6" HMI touch screen interface.

Overview Screen (Typical) Shows the generator status, generator metering data, bus metering data, ECS position, and generator/ utility breaker status.

LE HE8746-02 8

DD-NLH-001, Attachment 1 Page 33 of 88, Holyrood Blackstart Diesel Units Application

Page 35: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

f- 1.344 vu, au, WOE I

TO1:T. I: 7..) ‘-! '

'T 41.1

KATO. I awn H2

At.

\ ga.9,2 " f; rs,;:•r, afggi4o1.

./11-11, 611ti kr% • ,111 Cl. I)r twir

ARP, - 4000

• ;

EI H ..5.1.

Ai4A

izii threw illata541. 11111411.0VINI

TcrAH tiprz 74) f.,e) T■:# 7.■

5CREEN

i/FFs

uN 54' REV,: i,ENER..41.()/1

ANNI:S.i.14, SC REV;

Art r, 4 7,14 •."..41 0

;JAR 441 ; # ANP5

1,3 . MO'S 1,01 Vt44_ C Ann

200011 4401-ft

1- , 1 t.iVei$4

PM ly "no fIVI F^,..■ I I Id

I 8 1 . I I

• _.

XQ2000 RENTAL CUERPILLAFf

STANDARD PARALLELING CONTROL (continued)

Generator Control Screen (Typical) It allows the operator to observe the automatic synchronization and transfer of the load to and from the generator. Engine control allows the operator to run the engine in manual, or switch to automatic modes. Voltage and frequency offset adjustment allows the operator to control generator frequency and voltage.

RE LA 1'10'-itPhE 71.17 Et, TH.E

OE NE RA ttP. isEIAKiR kM3TRAC.4 AtrOWER

Generator Metering Screen (Typical) Allows the operator to view three phases of voltage and amperage for the bus and the generator.

-IP F■.4z. 1.1-4 t •-; LA -.. A.

4:4 Nt

IL --4:niRI TO /, Eif.RTC- It) N....E.."■1.1 QVLIOJEW jfl

rt,r. p.m; P.tN K1"NrIATOR 5CREEN

LEHE8746-02 9

DD-NLH-001, Attachment 1 Page 34 of 88, Holyrood Blackstart Diesel Units Application

Page 36: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

• . . •

•,' 'I, • •

▪ 1;-r-

• a.. ;•Cf. .z ;

•••

, ;', • • F■••;•,.. TA

lokrn: 7

'

T01..ICITI, HERE TO

00 TO MEN1.1

SCREEN

'

CV!' Vett id

TOT:(14. HERE TO c.,O

TO OVERVIEW

S( KEEN

TOI:CH HERE TO VIEW ADDIT:ONAL

ENCANE DATA

X0.2000 RENTAL CATERPILLAR

STANDARD PARALLELING CONTROL (continued)

Engine Monitoring Screen (Typical) Engine status is obtained directly from the EMCP 3. Engine starts and total hours can be used by the operator to determine when regular preventive maintenance is required. Other metering includes engine battery and oil filter health.

:•-•-,ECI 3 3- ENOINE

DATA

LEHE8746-02 101-10)

Information contained in this publication may be considered confidential. Discretion is recommenced when distributing.

Materials and specifications are subject to change without notice. CAT, CATERPILLAR, their respective logos, "Caterpillar Yellow, the "Power Edge" trade dress, as well as corporate and product identity used herein, are trademarks

of Caterpillar and may not be used without permission.

www,Cat-ElectricPower com

C 2010 Caterpillar All Rights Reserved,

Printed in U.S.A.

DD-NLH-001, Attachment 1 Page 35 of 88, Holyrood Blackstart Diesel Units Application

Page 37: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

PERFORMANCE DATA EMHB00436.1

DECEMBER 16, 2013 (MHE300436)-ENGINE (NAM00282)-GENSET (G5Y00544)- For Help Desk Phone Numbers Click here GENERATOR

Perf No: DM8454 Heat General Rejection

Altitude Emissions Regulatory Derate Cross Reference

Change Level: 01 General Supplementary Perf Param Notes Data Ref

View, PDF

SALES MODEL: 3516C COMBUSTION: DI

ENGINE POWER (BKW): 2,030.0 ENGINE SPEED (RPM): 1,800

GEN POWER WITH FAN (EKW): 1,825.0 HERTZ: 60

COMPRESSION RATIO: 14.7 FAN POWER (KW): 108,0

APPLICATION: PACKAGED GENSET ASPIRATION: TA

RATING LEVEL: PRIME AFTERCOOLER TYPE: ATAAC

SUB APPLICATION: STANDARD AFTERCOOLER CIRCUIT TYPE: JW+DC, ATAAC

PUMP QUANTITY: 2 INLET MANIFOLD AIR TEMP (C): 49

FUEL TYPE: DIESEL JACKET WATER TEMP (C): 99

MANIFOLD TYPE: DRY TURBO CONFIGURATION: PARALLEL

GOVERNOR TYPE: ADEM3 TURBO QUANTITY: 4

ELECTRONICS TYPE: ADEM3 TURBOCHARGER MODEL: GTA55188N-56T-1.12

CAMSHAFT TYPE: STANDARD CERTIFICATION YEAR: 2008

IGNITION TYPE: CI CRANKCASE BLOWBY RATE (M3/HR): 76.2

INJECTOR TYPE: EUI FUEL RATE (RATED RPM) NO LOAD (L/HR): 52,0

FUEL INJECTOR: 2664387 PISTON SPD @ RATED ENG SPD (M/SEC): 11.4

REF EXH STACK DIAMETER (MM): 305

MAX OPERATING ALTITUDE (M): 1,200

Gencral Performance Data Top

GENSET POWER WITH FAN

EKW

PERCENT LOAD

ENGINE POWER

BKW

BRAKE MEAN EFF PRES (B N EP)

KPA

BRAKE SPEC FUEL CONSUMPTN (BSFC)

GiBKW-HR

VOL FUEL CONSUMPTN (VFC)

LOIR

INLET MFLD PRES

KPA

INLET MFLD TEMP

DEG C

EXH EXH MFLD MFLD TEMP PRES

DEG C KPA

ENGINE OUTLET TEMP

DEG C

1,825,0 100 2029, 1,960 201=0 486.2 251.8 48,9 582.5 227.2 387.7

1,642.5 90 1,827 1,765 203,5 443.3 235,8 48.1 560.1 209.3 372.7

1,460.0 80 1,631 1,576 207.5 403.4 218.7 47.4 540.6 191,8 361.9

1,368.8 75 1,535 1,483 209.7 383.8 209,7 47.1 531.0 183,1 357.4

1,277.5 70 1,440 1,391 211.8 363,6 199.7 46.7 521.4 173.6 333.1

1,095.0 60 1,252 1,209 215,7 321.8 176.0 45.0 502.4 151,7 345.7

912,5 50 1,066 1,029 217,4 276.1 144,0 45.0 481.0 124,2 341,9

730.0 40 851 217.5 228,4 107.5 44.1 454,4 94,2 339=5

347,5 30 695 572 223.6 185.3 75.7 43.6 422.6 70.5 334.0

456.2 25 601 581 229.4 164.4 63.4 43.4 403,2 60,6 328.9

365.0 20 506 489 237,9 143.5 51.2 43.2 380,9 51,8 321.8

182.5 10 310 300 272.7 100.9 30.6 42.8 315,3 37,0

ENGINE WET ENGINE ENGINE

DD-NLH-001, Attachment 1 Page 36 of 88, Holyrood Blackstart Diesel Units Application

Page 38: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

GENSET POWER PERCENT ENGINE COMPRESSOR WITH LOAD POWER OUTLET PRF.S FAN

COMPRESSOR OUTLET TEMP

OUTLET WET

WET EXH INLET GAS VOL

AIR VOL FLOW LOW

RATE RATE

INLET AIR MASS FLOW RATE

WET EXH GAS MASS FLOW RATE

OUTLET OUTLET WET EXH DRY EXH VOL FLOW VOL FLOW RATE (0 RATE (0 DEG C AND DEG C AND 101 KPA) 101 KPA)

EKW %

BKW

(PA

DEG C

M3/MIN M3/MIN

KG/HR

KG/HR M3/MIN m3/mirv 1,825.0 100 2,029 266 224.3 177.5 406.1 12,341.1 12,748.6 167.8 155.6

1,642.5 90 1,827 249 211.6 172.1 381.9 11,918.6 12,290.0 161.5 150,3

1,460.0 80 1,631 232 199.3 165.6 359.9 11,432.4 11,770.2 154.8 144.5

1,368.8 75 1,535 222 1933. 161.9 348.4 11,160.2 11,482.3 150,9 141.2

1,277.5 70 1,440 212 186.8 157.7 336.0 10,848.2 11,153.6 146,6 137.3

1,095.0 60 1,252 188 171.5 146.8 307.7 10,063,5 10,333.6 135.8 127.5

912.5 50 1,066 155 150.7 130,9 271.0 8,931.5 9,163.1 120.4 113.2

730.0 40 881 115 126.0 111,8 229.3 7,588.9 7,780.6 102.2 96.3

547.5 30 695 84 103.4 95.4 193.3 6,445.9 6,601.1 87.0 82.1

456.2 25 601 70 93.0 88.2 176.7 5,946.8 6,084.6 80.1 75.8

365.0 20 506 58 83.0 81.5 160.5 5,487.3 5,607.7 73.7 59.9

182.5 10 310 35 65.1 70.0 128.8 4,703.5 4,788.2 63,2 60.4

Aeat Rejection Data Top

GENSET POWER WITH FAN

EKW

REJECTION PERCENT ENGINE

TO JACKET LOAD POWER WATER

% BKV`i KW

REJECTION TO ATMOSPHERE

KW

LOW HIGH EXH FROM REJECTION FROM WORK HEAT HEAT

TO EXH RECOVERY OIL TO 177C

COOLER AFTERCOOLER ENERGY VALUE VALUI ENERGY ENERI

KW KW KW KW KW KW KW

1,825.0 100 2,029 724 130 1,554 784 258 609 2,029 4,848 5,164

1,642.5 90 1,827 677 124 1,525 699 235 547 1,827 4,420 4,706

1,460.0 80 1,631 633 119 1,406 631 214 487 1,631 4,022 4,285

1,368.8 75 1,535 611 117 1,348 600 204 458 1,535 3,826 4,076

1,277.5 70 1,440 588 115 1,288 568 193 426 1,440 3,625 3,861

1,095.0 60 1,252 539 110 1,159 503 171 354 1,252 3,208 3,417

912.5 50 1,066 483 106 1,008 435 147 266 1,066 2,752 2,932

730.0 40 881 422 100 846 364 121 174 881 2,277 2,426

547.5 30 695 364 94.8 702 298 98.4 107 695 1,848 ,968

456.2 25 601 334 92.1 633 265 87.3 81.8 601 1,639 1,746

365.0 20 506 303 89.3 564 232 76.2 60.3 506 1,431 1,524

182.5 10 310 235 82.9 415 145 53.6 27.1 310 1,006 1,072

Emissi ns ai.a Top

Units Filter All Units

RATED SPEED POTENTIAL SITE VARIATION: 1800 RPM

GENSET POWER WITH FAN MA/ 1,825.0 1,368.8 912.5 456.2 182.5 ENGINE POWER 8KV'd 2,029 1,535 1,066 601 310

PERCENT LOAD % 100 75 50 25 10

TOTAL NOX AS NO2) 0/HR 16,211 8,787 5,621 4,219 3,018 TOTAL CO G/HR 1,310 758 1,119 1,803 1,832 TOTAL HC 0/115 463 490 508 414 450 PART MATTER G/HR 100.3 99.7 149.3 256,4 204.4 TOTAL NOX (AS NO2) (CORR 5% 02) M0/NM3 3,031.7 2,151.1 1,936.1 2,415,5 2,867.1

TOTAL CO (CORR 5% 02) MG/NM3 237.1 174.2 373.5 931,1 1,712,5 TOTAL HC (CORR 5% 02) MG/NM3 73,4 97.2 140,5 198,7 377.7 PART MATTER (CORR 5% 02) MG/NM3 15.6 20,0 46,6 122.2 158.8 TOTAL NOX (AS NO2) (CORR 5% 02) PPM 1,477 1,048 943 1,177 1,397 TOTAL CO (CORR 5% 02) PPM 190 139 299 745 1,370

DD-NLH-001, Attachment 1 Page 37 of 88, Holyrood Blackstart Diesel Units Application

Page 39: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

TOTAL HC (CORR 5% 02) PPM 137 181 262 371 705

TOTAL NOX (AS NO2) G/HP-HR 5.99 4,29 3.95 5.24 7.26

TOTAL CO G/HP-HR 0.48 0.37 0.79 2.24 4.40

TOTAL HC G/HP-HR 0.17 0.24 0.36 0.51 1.08

PART MATTER G/HP-HR 0.04 0.05 0.10 0.32 0.49

TOTAL NOX (AS NO2) LB/HR 35,74 19.37 12.39 9.30 6.65

TOTAL CO LB/HR 2,89 1.67 2.47 3.97 4.04

TOTAL FIC LB/HR 1.02 1.08 1.12 0.91 0.99

PART MATTER LB/HR 0.22 0.22 0,33 0.57 0.45

RATED SPEED NOMINAL DATA: 1800 RPM

GENSET POWER WITH FAN Et(1,11 1,625.0 1,368.8 912.5 456.2 182.5 ENGINE POWER 13101/ 2,029 1,535 1,066 601 310

PERCENT LOAD % 100 75 50 25 10

TOTAL NOX (AS NO2) G/I-,R 13,509 7,322 4,684 3,516 2,515

IOTAL CO G/HR 728 421 622 1,002 1,018

TOTAL HC G/HR 348 368 382 311 339

TOTAL CO2 KG/HR 1,261 998 717 426 259

PART MATTER G/HR 71,6 71.2 106.6 183.1 146.0

TOTAL NOX (AS NO2) (CORR 5% 02) MG/NM3 2,526.5 1,792.6 1,613.4 2,012.9 2,389.2

TOTAL CO (CORR 5% 02) MG/NM3 131.7 96.8 207.5 517.3 951.4

TOTAL I-IC (CORR 5% 02) MG/NM3 55.2 73.1 105.6 149.4 284.0 PART MATTER (CORR 5% 02) MG/NM3 11.1 14.3 33.3 87,3 113.4

TOTAL NOX (AS NO2) (CORR 5% 02) PPM 1,231 873 786 981 1,164

TOTAL CO (CORR 5% 02) PPM 105 77 166 414 761

TOTAL HC (CORR 5% 02) PPM 103 136 197 279 530

TOTAL NOX (AS NO2) G/HP-HR 4.99 3.57 3.29 4.37 6,05

TOTAL CO G/HP-HR 0.27 0.21 0,44 1,24 2.45

TOTAL HC G/HP-HR 0.13 0.18 0.27 0,39 0.81

PART MATTER G/HP-HR 0.03 0.03 0.07 0.23 0.35

TOTAL NOX (AS NO2) LB/HR 29.78 16.14 10.33 7.75 5.55

TOTAL CO LB/HR 1,60 0.93 1.37 2.21 2.24

TOTAL HC LB/HR 0,77 0.81 0.84 0,69 0.75

TOTAL CO2 LB/HR 2,781 2,199 1,581 939 570

PART MATTER LB/HR 0,16 0.16 0.24 0.40 0.32

OXYGEN IN EXH % 11.4 12.6 13.5 14.3 15.8

DRY SMOKE OPACITY % 0.4 0.5 1.8 3.8 3.1

BOSCH SMOKE NUMBER 0.18 0,23 0.60 1.25 1.14

Rngrulatory Inforc[n. tion Top

EPA TIER 2 2006 - 2010

GASEOUS EMISSIONS DATA MEASUREMENTS ARE CONSISTENT WITH THOSE DESCRIBED IN EPA 40 CFR PART 89 SUBPART 0 AID 150 8178 FOR MEASURING HC, CO, PM, AND NOX. GASEOUS EMISSIONS VALUES ARE WEIGHTED CYCLE AVERAGES AND ARE IN COMPLIANCE WITH THE NON-ROAD REGULATIONS.

Locality Agency Regulation Tier/Stage Max Limits - G/BKW - HR

U.S. (INCL CALIF) EPA NON-ROAD TIER 2 CO: 3.5 NOx + HC: 6.4 PM: 0.20

EPA EMERGENCY STATIONARY 2011 -

GASEOUS EMISSIONS DATA MEASUREMENTS ARE CONSISTENT WITH THOSE DESCRIBED IN EPA 40 CFR PART 60 SUBPART IIII AND ISO 8178 FOR MEASURING HC, CO, PM, AND NOX. GASEOUS EMISSIONS LIMIT VALUES ARE WEIGHTED CYCLE AVERAGES AND ARE IN COMPLIANCE WITH THE NON-ROAD REGULATIONS.

Locality Agency Regulation Tier/Stage

Max Limits - G/BKW - HR

U.S. (INCL CALIF) EPA STATIONARY EMERGENCY STATIONARY CO: 3.5 NOx + 6.4 PM: 0.20

DD-NLH-001, Attachment 1 Page 38 of 88, Holyrood Blackstart Diesel Units Application

Page 40: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

i\ltItude Derate Data Top

ALTITUDE CORRECTED POWER CAPABILITY (BKW)

AMBIENT OPERATING TEMP (C) 10 15 20 25 30 35 40 45 50 NORMAL

AL i11UDE (M)

2,030 2,030 2,030 2,030 2,030 2,030 2,030 2,030 2,030 2,030

250 2,030 2030, 2,030 2,030 2,030 2,030 2,030 2,030 2,030 2030,

500 2,030 2,030 2,030 2,030 2,030 2,030 2,030 2,030 2,030 2,030

750 2,030 2,030 2,030 2,030 2,030 2,030 2,030 2,014 1,983 2,030

1,000 2,030 2,030 2,030 2,030 2,030 2,015 1,982 1,951 1,921 2,030

1,250 2,030 2,030 2,030 2,017 1,984 1,952 1,920 1,890 1,861 2,030

1,500 2,030 2,021 1,987 1,954 1,921 1;890 1,860 1,831 1,802 2,013

1,750 1,992 1,957 1,924 1,892 1,860 1,830 1,801 1,773 1,745 1,961

2,000 1,928 1,895 1,862 1,831 1,801 1,772 1,744 1,716 1,690 1,909

2,250 1,866 1,834 1,803 1,772 1,743 1,715 1,687 1,661 1,635 1,858

2,500 1,806 1,774 1,744 1,715 1,687 1,659 1,633 1,607 1,582 1,808

2,750 1,747 1,716 1,687 1,659 1,632 1,605 1,579 1,555 1,531 1,759

3,000 1,689 1,660 1,632 1,604 1,578 1,552 1,527 1,503 1,480 1,711

3,250 1,633 1,605 1,578 1,551 1,526 1,501 1,477 1,454 1,431 1,664

3,500 1,579 1,551 1,525 1,499 1,475 1,451 1,427 1,405 1,383 1,618

3,750 1,526 1,499 1,473 1,449 1,425 1,402 1,379 1,358 1,337 1,573

4,000 1,474 1,448 1,423 1,400 1,376 1,354 1,333 1,312 1,291 1,528

4,250 1,423 1,399 1,375 1,352 1,329 1.308 1,287 1,267 1,247 1,435

4,500 1,374 1,350 1,327 1,305 1,283 1,263 1,242 1,223 1,204 1,442

Cross Rafare-iir,e Top

Engine Arrangement

Arrangement Number

1

3395408

Effective Serial Number

N111800001 KEN00001

Engineering Model

P5017 PS017

Engineering Model version

Test Specification Data Effective Engine Governor

Test Spec Setting Serial Arrangement Type BlJrnber

01(8521 LL5011 M-500001 2903313 ADEM3

,,+250 LL6076 KEN00001 3395408 ADEM3

Default Low Idle Speed

Default High Idle Speed

General No' e3 Top

DM8454 - 01

SOUND PRESSURE DATA FOR THIS RATING CAN BE FOUND IN PERFORMANCE NUMBER - DM8779

Supplementary Data Top

Type

CONVERTIBLE SECONDARY FREQUENCY

SOUND

Classification

50HZ

SOUND PRESSURE

Performance Number

D.M.5754

11%16,779

DD-NLH-001, Attachment 1 Page 39 of 88, Holyrood Blackstart Diesel Units Application

Page 41: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

Performance Parameter rnce Top

Parameters Reference: DM9600 - 05

PERFORMANCE DEFINITIONS

PERFORMANCE DEFINITIONS DM9600

APPLICATION: Engine performance tolerance values below are representative of a typical production engine tested in a calibrated dynamometer test cell at SAE .11995 standard reference conditions. Caterpillar maintains 1509001:2000 certified quality management systems for engine test Facilities to assure accurate calibration of test equipment. Engine test data Is corrected in accordance with SAE 31995. Additional reference material SAE J1228, 31349, ISO 8665, 30z6-1:2002E, 3046-3:1989, 1585, 2534, 2288, and 9249 may apq y in part or we similar to SAE 31995. Special engine rating request (SEAR) test data shall be noted.

PERFORMANCE PARAMETER TOLERANCE FACTORS: Power +/- 3% Torque +/- 3% Exhaust stack temperature +/- 8% Inlet airflow +/- 50/0 Intake manifold pressure-gage +/- 10% Exhaust flow +/- 6% Specific fuel consumption +/- 3% Fuel rate +/- 5% Heat rejection +/- 5% Heat rejection exhaust only +/- 10%

Torque Is included for truck and industrial applications, do not use for Gen Set or steady state applications.

On C7 - C18 engines, at speeds of 1100 RPM and under these values are provided for reference only, and may not meet the tolerance listed.

These values do not apply to C280/3600. For these models, see the tolerances listed below.

C280/3600 HEAT REJECTION TOLERANCE FACTORS: Heat rejection +/- 10% Heat rejection to Atmosphere +/- 50% Heat rejection to Lube Oil +/- 20% Heat rejection to Aftercooler +/- 5%

TEST CELL TRANSDUCER TOLERANCE FACTORS:

Torque +/- 0.5% Speed +/- 0.2% Fuel flow +/- 1.00/0 Temperature +/- 2.0 C degrees Intake manifold pressure +7- 0,1 kPa

OBSERVED ENGINE PERFORMANCE IS CORRECTED TO SAE 31995 REFERENCE AIR AND FUEL CONDITIONS.

REFERENCE ATMOSPHERIC INLET AIR

FOR 3500 ENGINES AND SMALLER SAE 31228 reference atmospheric pressure is 100 KPA (29.61 in hg) and standard temperature is 25 (77) at 60% relative humidity.

FOR 3600 ENGINES Engine rating obtained and presented in accordance with ISO 3046/1 and SAE 31995 JAN90 standard reference conditions of 25, 100 KPA 30% relative humidity and 150M altitude at the stated aftercooler water temperature.

DD-NLH-001, Attachment 1 Page 40 of 88, Holyrood Blackstart Diesel Units Application

Page 42: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

MEASUREMENT LOCATION FOR INLET AIR TEMPERATURE Location for air temperature measurement air cleaner inlet at stabilized operating conditions.

REFERENCE EXHAUST STACK DIAMETER The Reference Exhaust Stack Diameter published with this dataset is only used for the calculation of Smoke Opacity values displayed in this dataset. This value does not necessarily represent the actual stack diameter of the engine due to the variety of exhaust stack adapter options available. Consult the price list, engine order or general dimension drawings for the actual stack diameter size ordered or options available.

REFERENCE FUEL

DIESEL Reference fuel is #2 distillate diesel with a 35API gravity; A lower heating value is 42,780 KJ/KG (18,390 BTU/LB) when used at 29 (84,2), where the density is 838.9 G/Liter (7.001 Lbs/Gal).

GAS Reference natural gas fuel has a lower heating value of 33.74 KJ/L (905 BTU/CU Ft), Low BTU ratings are based on 18.64 KYL (500 BTU/ CU FT) lower heating value gas. Propane ratings are based on 87.56 KyL (2350 BTU/CU Ft) lower heating value gas,

ENGINE POWER (NET) IS THE CORRECTED FLYWHEEL POWER (GROSS) LESS EXTERNAL AUXILIARY LOAD Engine corrected gross output includes the power required to drive standard equipment; lube oil, scavenge lube oil, fuel transfer, common rail fuel, separate circuit aftercooler and jacket water pumps. Engine net power available for the external (flywheel) load Is calculated by subtracting the sum of auxiliary load from the corrected gross flywheel out put power. Typical auxiliary loads are radiator cooling fans, hydraulic pumps, air compressors and battery charging alternators.

ALTITUDE CAPABILITY Altitude capability is the maximum altitude above sea level at

1.!ard temperature and standard pressure at which the engine could develop full rated output power on the current performance data set. Standard temperature values versus altitude could be seen on TM2001.

Engines with ADEM MEU1 and HEUI fuel systems operating at conditions above the defined altitude capability derate for atmospheric pressure and temperature conditions outside the values defined, see TM2001. Mechanical governor controlled unit injector engines require a setting change for operation at conditions above the altitude defined on the engine performance sheet. See your Caterpillar technical representative for non standard ratings.

REGULATIONS AND PRODUCT COMPLIANCE TM! Emissions information Is presented at 'nominal and 'Potential Site Variation' values for standard ratings. No tolerances are applied to the emissions data. These values are subject to change at any time. The controlling federal and local emission requirements need te be verified by your Caterpillar technical representative. Log on to the Technology_and Solutions olviisIons (TSP.) „web page.khittp.,s://pdgt,c.at,pom/ccia/iayoutj for information including federal regulation applicability and time lines for implementation. Information for labeling and tagging requirements is also provided.

NOTES: Regulation watch covers regulations In effect and future regulation changes for world, federai, state and local. This page includes Items on the watch list where a regulation change or product change might be pending and may need attention of the engine product group. For additional emissions information log on to the TMI web page.

DD-NLH-001, Attachment 1 Page 41 of 88, Holyrood Blackstart Diesel Units Application

Page 43: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

Additional product information for specific market application Is available, Customer's may have special emission site requirements that need to be verified by the Caterpillar Product Group engineer,

HEAT REJECTION DEFINITIONS: Diesel Circuit Type and HHV Balance : DM9500

EMISSIONS DEFINMONS: Emissions DM1176

SOUND DEFINITIONS: Sound Power : DM8702

Sound Pressure : TM7080

RATING DEFINITIONS: Agriculture TM6008

Fire Pump : TM6009

Generator Set : TM 6035

Generator (Gas) : TM6041

Industrial Diesel : TM6010

IndustrIa' (Gas) : TM6040

Irrigation TM5749

Locomotive : TM6037

Marine Auxiliary TM6036

Marine Prop (Except 3600) : TM5747

Marine Prop (3600 only) : TM5748

MSHA : TM6042

Oil Field (Petroleum) : TM6011

Off-Highway Truck : TM6039

On-Highway Truck TM6038

Date Released : 11/23/11

DD-NLH-001, Attachment 1 Page 42 of 88, Holyrood Blackstart Diesel Units Application

Page 44: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

Voltage Regulation

Voltage level adustment: +1- 5.0% Voltage regulation, steady state: +/- 0.5% Voltage regulation with 3% speed change: +1- 0.5% Waveform deviation line - line, no load: less than 3.0% Telephone influence factor: less than 50

^

Field Resistance = 1,003 Oh

Generator Excitation

No Load Full Load, (rated) pf Series Parallel

Excitation voltage: 7,94 Volts 20,08 Volts Volts Excitation current 2.09 Amps 4.35 Amps Amps

!•-iort Circuit Ratio: 0.53 I Stator Resistance 0.0015 Ohms

GENERATOR DATA

DECEMBER 16, 2013 For Help Desk Phone Numbers Click here

Selected Model

Engine: 3516 Generator Frame: 825 Genset Rating (kW): 1825.0 Line Voltage: 480 Fuel: Diesel Generator Arrangement: 3123144 Genset Rating (kVA): 1825.0 Phase Voltage: 277 Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 1.0 Rated Current: 2195.1 Duty: PRIME Connection: SERIES STAR Application: EPG Status: Current

Nrersion: 40400 140308 P39714 /7345

Spec Information

I

Generator Specification

Frame: 825 Type: SR4B No. of Bearings: 1

Generator Efficiency

Per Unit Load kW Efficiency ° 0 Winding Type: FORM WOUND Flywheel: 21.0 0,25 456.3 92.5 Connection: SERIES STAR Housing: 00 0.5 912.5 95.5 Phases: 3 No. of Leads: 6 0.75 1368.8 96.3 Poles: 4 Wires per Lead; 8 1.0 1825.0 96,5 Sync Speed: 1800 Generator Pitch: 0.6667 1.1 2007,5 96.5

Reactances Per Unit Ohms SUBTRANSIENT - DIRECT AXIS X"d 0,1077 0.0136

SUBTRANSIENT - QUADRATURE AXIS X"4 0,0982 0.0124

TRANSIENT - SATURATED X'd 0.1743 0.0220

SYNCHRONOUS - DIRECT AXIS Xd 2.3985 0,3028

SYNCHRONOUS - QUADRATURE AXIS 1.1779 0.1487

NEGATIVE SEQUENCE X2 0.1030 0.0130

ZERO SEQUENCE Xo 0.0063 0.0008

Time Constants Seconds OPEN CIRCUIT TRANSIENT - DIRECT AXIS Tdo

SHORT CIRCUIT TRANSIENT - DIRECT AXIS T'd

OPEN CIRCUIT SUBSTRANSIENT - DIRECT AXIS T"do

SHORT CIRCUIT SUBSTRANSIENT - DIRECT AXIS rd

OPEN CIRCUIT SUBSTRANSIENT - QUADRATURE AXIS 1'40

SHORT CIRCUIT SUBSTRANSIENT - QUADRATURE AXIS rci

EXCITER TIME CONSTANT T,

ARMATURE SHORT CIRCUIT Ta

6.6330

0.4643

0.0074

0.0064

0.0057

0.0050

02125

0,0438

DD-NLH-001, Attachment 1 Page 43 of 88, Holyrood Blackstart Diesel Units Application

Page 45: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

c• CA

Jl = Coupling J2 = Rotor and Fan TOTAL J = J1 + J2 + J3

c>

J3 = Exciter End

Selected Model

Engine: 3516 Generator Frame: 825 Genset Rating (kW): 1825.0 Line Voltage: 480

Fuel: Diesel Generator Arrangement: 3123144 Genset Rating (kVA): 1825.0 Phase Voltage: 277

Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 1,0 Rated Current: 2195.1

Duty: PRIME Connection: SERIES STAR Application: EPG Status: Current

Version: 40400 140308 139714 /7345

Generator Mechanical Information

Center of Gravity

Dimension X F906.8 mm -35.7 IN.

1Dimension Y [0.0 mm ,0.0 EN. - iDimension Z 0.0 mm ;0.0 IN.

o "X" is measured from driven end of generator and parallel to rotor. Towards engine fan is positive. See General Information for details

• "Y" is measured vertically from rotor center line, Up is positive. • "Z" is measured to left and right of rotor center line. To the right is positive,

Generator WT = 4330 kg * Rotor WT = 1541 kg * Stator WT = 2789 kg

9,546 LB 3,397 LB 6,149 LB

Rotor Balance = 0.0508 mm deflection PTP

Overspeed Capacity = 150% of synchronous speed

Generator Torsional Data

K1 = Shaft Stiffness between 1(2 = Shaft Stiffness between J1 + J2 (Diameter 1) J2 + J3 (Diameter 2)

Ji KI Min Shaft Dia I J2 1(2 Min Shaft Dia 2 J3

LB IN. s2 265.5 MLB INIrad 6.2 IN. 456.1 LB IN. s2 57,5 MLB IN/tad 3.8 IN. 2,3 LB IN. s2

2.608 N m s2 30.0 MN mirad 157.5 mm 51.534 N m s2 6.5 MN mlrad 96.5 mm 0.257 N m s2

Total .1

481.5 LB IN. s2

54,399 N m s2

DD-NLH-001, Attachment 1 Page 44 of 88, Holyrood Blackstart Diesel Units Application

Page 46: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

Selected Model

Engine: 3516 Generator Frame: 825 Gensel Rating (kW): 1825.0 Line Voltage: 480

Fuel: Diesel Generator Arrangement: 3123144 Genset Rating (kVA): 1825.0 Phase Voltage: 277

Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 1.0 Rated Current: 2195.1

Duty: PRIME Connection: SERIES STAR Application: EPG Status: Current _ — Version: 40400 ;40308 /3974!734

Generator Cooling Requirements- Temperature - Insulation Data

Cooling Requirements: Temperature Data: (Ambient 40 °C)

Heat Dissipated: 66.2 kW Stator Rise: 80.0 °C

I Air Flow: 168.0 m3/min Rotor Rise: ovon n

.v

Insulation Class: H

Insulation Reg. as shipped: 100.0 ML) minimum at 40 °C

Thermal Limits of Generator

Frequency: 60 Hz Line to Line Voltage: 480 Volts

B BR 80/40 1893.0 kVA

F BR -105/40 2281.0 kVA

H BR - 125/40 2500.0 kVA

F PR - 130/40 2500.0 kVA

DD-NLH-001, Attachment 1 Page 45 of 88, Holyrood Blackstart Diesel Units Application

Page 47: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

2000.0 4000.0 6 ,o 8000.0 10000.1

SKVA

Selected Model

Engine: 3516 Generator Frame: 825 Genset Rating (kW): 1825.0 Line Voltage: 480

Fuel: Diesel Generator Arrangement: 3123144 Genset Rating (kVA): 1825.0 Phase Voltage: 277

Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 1.0 Rated Current: 2195.1

Duty: PRIME Connection: SERIES STAR Application: EPG Status: Current N'ersion: 40400 /40308 .'39714 /7345

Starting Capability & Current Decrement

Motor Starting Capability (0.4 pf)

Percent I SKVA Volt Dip 1

280

884 7.5 ;

1,212 ri 1,558 12,5

1,925 -- 15.0

SO

; 2,314 17.5

1 2,727 20.0 20 1 -- 3,167 — 22,5

-

4,137 - 10

4,675 I 30.0

r-1252 3215-- I 1 5,873 35,0 1

1 7,272 1 40.0

Current Decrement Data

Per: en t Volt Dip motor starting 50

E Time I Ari-iip Cycle

263112-;

. 1.0 ; 12,753

2.0 11,821 21000

; 3.0 1 11,407

10,687 ,

r1 7,5 1

9,1110-7 130

,

15.0 ; 1',786 ;

; 20,0 6,683

25.01 5,760 1

1 30,0 1 5,247

r— 35.0 — 1 5,485 5000

1 4010 1 5,852 1

; 45.0 ; 6,230 I;

Current Decrement

, 1 I i — ; ,

I i I .! i

i

10.0 20.0 30.0 400 50,0

E Titrie Cycle

AMP 25000

Instantaneous 3 Phase Fault Current: 20213 Amps Instantaneous Line - Line Fault Current: 17909 Amps

Instantaneous Line - Neutral Fault Current: 30076 Amps

DD-NLH-001, Attachment 1 Page 46 of 88, Holyrood Blackstart Diesel Units Application

Page 48: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

Line - Line Volt Open Circuit 1000

800

COO

400

200

-

40.0 80.0 120.0 180.0 200.0

Field Current

f- i

,

, ,

, I ,

,

4 ,

Selected Model

Engine: 3516 Generator Frame: 825 Genset Rating (kW): 1825.0 Line Voltage: 480 Fuel: Diesel Generator Arrangement: 3123144 Genset Rating (kVA): 1825.0 Phase Voltage: 277 Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 1.0 Rated Current: 2195.1 Duty: PRIME Connection: SERIES STAR Application: EPG Status: Current

Version: 40400 ,40308 i39714 /7345

Generator Output Characteristic Curves

Open Circuit Curve

, Field 1 Line -

Current I Line Volt

0.0

10.1 r 288 I :

T[ !

14" 14.2 384- -1

1 171 4.12

LiI 21.7 - 480

30.7 528

r 48.0 576

I 87.5 624 1 r

177.7 1 672

_

Short Circuit Curve

Armature Current Short Circuit 3500

Field '. Armature Current i Current . 2800

0.0 I. 0

2136 4 i 317 ._

27.5 1,537 21

I 31:5 1,756

I 35.4 1,976 1400 . 39.3 2,195 I

4:37.3 2:415 - 1 1

I 1 47.2 2.634 : 700

. 51.2 ' r--1 2,854 - I

: 55.1 3,073 !

0.0 20.0 40,0 80.0 0.0 100.0

Field Current

DD-NLH-001, Attachment 1 Page 47 of 88, Holyrood Blackstart Diesel Units Application

Page 49: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

Selected Model

Engine: 3516 Generator Frame: 825 Genset Rating (kW): 1825.0 Line Voltage: 480 Fuel: Diesel Generator Arrangement: 3123144 Genset Rating (kVA): 1825.0 Phase Voltage: 277 Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 1.0 Rated Current: 2195.1 Duty: PRIME Connection: SERIES STAR Application: EPG Status: Current

Version: 40400 ,40308 39714 345

General Information

DM7824 Caterpillar SR4B Generators (50 Hz, 60 Hz) Data for 360s, 440s, 450s, 490, 590, 660, 690, 820 and 860 frames. Caterpillar SR4B generators built by Leroy Somer-USA(& predecessors),

Refer to DM7821 for explanation of all generator data in Technical Marketing Information (TMI) except generator efficiency for which the explanation is given below.

GENERATOR EFFICIENCY Generator efficiency is the percentage of engine flywheel (or other prime mover) power that is converted into electrical output, The generator efficiency shown is calculated by the summation of all losses method, and is determined in accordance with the IEC Standard 60034. The efficiency considers only the generator. There is no consideration of engine or parasitic losses here.

Caterpillar Confidential: Green Content Owner: Commercial Processes Division Web Master(s): PSG Web Based Systems Support Current Date: December 16, 2013 11:23:12 AM 0 Caterpillar Inc. 2013 All Rights Reserved. Dat a_Privecy,_Statement.

DD-NLH-001, Attachment 1 Page 48 of 88, Holyrood Blackstart Diesel Units Application

Page 50: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

FITE 0&CRIPTI0N I Arrester Mounting Provision

lied Cover w/ Handhole wf 5kV 600 Amp Porcelain HV 8ushing

/4 Hole Spade

Pressure Vacuum Gauge

Tank Base iv/ Jacking and Rolling

Facilities

Changer elle Wye Switch

X0 Bushing

3PH Padmount Transformer 60liz 2500,0 kVA ONAN 65 AWR Oil NV 2400/4160Y72400Xr1007XAL 95 BIL LV 480v7277 30 OIL 5.76 %Ft Maximum Pad Opening 21.0* 77.0 Munsell Green Topcoat Mild Steel Construction

lTiATERIAL

NJ. 'DIMENSIONS ARE IN INCHES SUNBELT ,

1-800-433-3128

Transformer www.sunbeltusa.co

rtg Radiators Drain Valve with Sarno°,

Dual VOttage

7 Ground Pad .50-13 Tap

8 Ground S and Pad

Ground Strap and Pad

H Bushing High Setwrity Cabinet w/ Pentahead

Door Bolts V Bu upport

Lifting Lugs iguld Temperature Gauge

.2kV LV Bushing w/12 Hole Spade Supported

6 Magnetic Oil Level Gauge 17 Nan late

One Inch Upper Press. Conn. and FI

ug

Relief Valve

A C*017A66KC

Cabinet Removed

ALL TotERANcES UNLESS OTHERwiSk SPECIFIED ARE .1 0.25' ANGULAR l. 20EG

THIS DRAMMG HAS 8101 GEI4ERATED ROM A ID

75,4

L REVISIONS

,(11) 1,13) (4)

- 24.0 30.5

103.0 57.3

85.9

Radiators Not Shown

— 73.5 Tank —

24.0 1

15.5

50.0 Typ

Distribution Transformer Outline Drawing say. Three-Phase Pad-mounted Compartmental

Type Vda – TREF, SHFET e SCALE. !REV. OCM t2/8/20 12 1,P_3_21._/t/3F101M08 Li OF 11 1 Cl2

DD-NLH-001, Attachment 1 Page 49 of 88, Holyrood Blackstart Diesel Units Application

Page 51: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

!1 suaT Transfon IMF

1-800-433.3128 www.sunballusa.corn

II TrSUNBELT

ansformer

11 2500 e, 65'C I60Hz

;44C1 0 7A 6 CM _ 2400D/4160Y/2400 X 7200D/12470Y/7200 I ONAN b. 480Y/277 I 5,76 7,17 @85'C r If/ KY BIL 95 HV NEUTRAL IN BIL 95

HYVA1c h&NDUCTOR 3/Ck

KE7B11-2I17.7:',S 11* I PPM AT RI: 'i: wmoo CAM - PA) PORTIKIN IN& 3:1(■-!7-1

APPROX. VIT,;(3,5 N DS. DV SWITCH POSITION DELTA-WYE SWITCH CgalC°11 5616 Mgr:14160Y 2400 POS 1 a DELTA TANK & RI 4731 g71 2470Y 7200 POS 2 OD Yft Guaris: °L566 4232 IQc HZ ri

TOTAL 14579 xi ( xi (

H 10

TAP VOLTAGE El 174 Inn 14400 100

K3 ti

A 8314 iv

41

B 7970 181 13800 105 DI D

7520 7200

189 13200 109 . .. . :. • „.. .. 200 12470 116 . .

. . Al 6928 208 12000 1 20

WM

MA AMPS AT 2300 KVA %IZ AT BASE KVA AND RATED VOLTAGE STEP-UP TRANSFORMER

WM

10 11 12

NOTES: 1) ACTUAL PLATE IS A NEGATIVE OF THE ABOVE DRAWING. 2) ACTUAL VolZ TO BE STAMPED IN AFTER TESTING.

NAMEPLATE MATERIAL: ALUMINUM 20289E1,20

sr. t-CD ,Ccot)

CO 0

02 s- e-

0 CO

NJ. OWENSIONS ARE M INC-IS 70LERANCES UNLESS OTHERWISE SPECIFIED

ONE PLACE DECIMAL ± 1 TWO PLACE DECIMAL t Cle■

THREE PLACE DECIMAL t ,030 * CRITICAL DIMENSION ANGUL4R z 2° OCM

00017A66KCAA

DATE: I REF. 126/2012 I -1 E -"I'OIT; I 5;;:111 I

1189608A3611

T‘T'r LASER NAMEPLATE

DD-NLH-001, Attachment 1 Page 50 of 88, Holyrood Blackstart Diesel Units Application

Page 52: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

CONTRACT: 2013-56865AB PURCHASING TERMS AND CONDITIONS

Goods and Services

SCHEDULE B

PURCHASING TERMS AND CONDITIONS

(This will become Schedule B to the

Contract)

DD-NLH-001, Attachment 1 Page 51 of 88, Holyrood Blackstart Diesel Units Application

Page 53: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

nalcor CONTRACT: 2013-56865AB

PURCHASING TERMS AND CONDITIONS -Page I 1 Goods and Services

Effective: September 2013 1. GENERAL • Time is of the essence.

• An incomplete, conditional, unbalanced, obscure, altered or irregular tender may be rejected. Tender may be

rejected for failure to provide specifications or catalogue information, or both, for a product offered as an

equivalent.

• Tenders shall be irrevocable for the tender validity period, and the lowest or any Tender or part thereof will not

necessarily be accepted.

• Written Addenda will be used to amend or clarify tendering Specifications.

• Agreement includes Purchase Order, these Terms and Conditions, Specifications, Drawings and Vendor/Contractor's

Tender, with document precedence in the order named.

a Owner means the issuer of the Purchase Order and includes its agents.

• Vendor/Contractor means the Vendor/Contractor named on the Purchase Order and includes its subcontractors and

agents.

• Goods mean supply of specified manufactured articles.

• Work means supply of specified labour, equipment, materials, Goods and services.

• Work Site means all places where Work is to be performed.

• Communications and documentation shall be in English.

• Measurement units shall comply with Specifications.

• Work shall be governed by the laws of Newfoundland and Labrador and any action or proceeding arising from the

Work shall be determined exclusively by a court in Newfoundland and Labrador

• Agreement binds and benefits both parties, successors and permitted assigns.

2. TENDER CLOSING AND LATE RECEIPT OF TENDERS

Tender closing time is clearly stated on the Request for Quotation form or in a tender document. Tender responses

must be received prior to the closing time. Unless otherwise specified, tenders are accepted by fax. In the event that

due to extenuating circumstances, such as a postal or transportation labour dispute or inclement weather, a tender

is received late, the decision as to whether the tender will be accepted will be at the sole discretion of Nalcor

3. TENDER EVALUATION a) Evaluation will be based on total analysis including, but not limited to, price, quality, delivery, Tenderer's past

performance and its ability to meet Specifications, and legal, technical and financial considerations relevant to cost-

effective delivery.

b) If no tender meets Specifications, tenders may be evaluated on the basis of that which most closely meets

Specifications and is most cost-effective, except where not permitted by the Public Tender Act.

4. CONTRACTOR'S INVESTIGATIONS Contractor acknowledges that it has fully informed itself in regard to the conditions of the Site and in regard to the

local and other conditions affecting the performance of the Work

S. PRICING AND PAYMENT TERMS a) Prices should be in Canadian currency, payable at par in St. John's, Newfoundland. Unless otherwise provided in

Specifications, payment shall be net thirty (30) days from invoice date, subject to receipt of Goods in apparent

proper working condition and free from defects.

b) Vendor/Contractor's acceptance of final payment, releases Owner from claims of and liability to Vendor/Contractor

for Owner's acts, omissions or neglect.

c) Invoices shall separately identify the amounts of federal GST/HST.

6. PURCHASE ORDER CHANGES

DD-NLH-001, Attachment 1 Page 52 of 88, Holyrood Blackstart Diesel Units Application

Page 54: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

CONTRACT: 2013-56865AB PURCHASING TERMS AND CONDITIONS -Page I 2

Goods and Services Effective: September 2013

Changes shall be made by duly authorized written Change Order.

7. GOODS AND EQUIVALENTS a) Goods shall meet Specifications, be of standard proven contemporary design (not prototype) and be new, unless

otherwise approved by Owner in writing.

b) Equivalents approved by Owner in writing are acceptable.

8. DELIVERY Vendor/Contractor shall arrange design, manufacturing and shipping so that Goods or components thereof shall

arrive at F.O.B. Point in accordance with the date stipulated. Delivery occurs when Owner signs for receipt.

9. SHIPPING AND INSURANCE Vendor/Contractor shall adequately protect Goods against damage until delivery, and bear costs of loss or damage.

Itemized packing slip shall accompany each shipment.

10. INSURANCE Vendor/Contractor shall provide insurances as per Specifications.

11. ENVIRONMENTAL PROTECTION Owner uses an Environmental Management System (EMS) registered to the ISO 14001 Standard. Owner has an

environmental policy that commits to compliance with legal and other requirements, prevention of pollution and

continual improvement. Vendor/Contractor must be aware of actual or potential impacts associated with Goods or

Work provided. Vendor/Contractor shall protect the environment of the areas where the WORK is located. Work

shall be subject to inspection by Owner and relevant provincial and federal governments. Specific matters relating

to environmental protection shall be dealt with between Vendor/Contractor and Owner.

12. HAZARDOUS OR CONTROLLED PRODUCTS Vendor/Contractor shall not deliver or use a hazardous or controlled product as defined by the Hazardous Products

Act unless such product has a WHMIS label attached and is supplied with a Material Safety Data Sheet (MSDS).

Vendor/Contractor shall inform workers of all information concerning use, storage and handling of, or working in

proximity to, hazardous or controlled products.

13. PERMITS Unless otherwise provided for in Specifications, Vendor/Contractor shall obtain and pay for all permits and licences

and shall give all notices necessary or required for lawful performance of Work.

14. WORKMANSHIP Vendor/Contractor shall employ competent and skilful workers and provide best workmanship.

15. WORKER'S COMPENSATION If applicable, prior to starting work, Vendor/Contractor shall provide a Letter of Good Standing from the Workplace

Health, Safety and Compensation Commission.

16. OCCUPATIONAL HEALTH AND SAFETY

Contractor shall comply with all occupational health and safety requirements required by Law, and the Owner's

Corporate Safety and Health Program and Contractor Safety Management Program (CSMP).

17. INSPECTION AND ACCEPTANCE

DD-NLH-001, Attachment 1 Page 53 of 88, Holyrood Blackstart Diesel Units Application

Page 55: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

CONTRACT: 2013-56865AB PURCHASING TERMS AND CONDITIONS -Page 1 3

Goods and Services Effective: September 2013

Goods shall be subject to inspection and test by Owner during manufacture, if specified, and upon delivery, if

specified. If Specifications are not met, Goods may be rejected and returned at Vendor/Contractor's expense.

18. TITLE AND WARRANTY • Vendor/Contractor shall provide Owner with good and clear title to Goods and shall indemnify and save harmless

OWNER from and against any and all claims, damages, loss, costs and expenses arising from any title dispute.

Unless otherwise specified in the Specifications, Goods shall be guaranteed as to compliance with Specifications for

a period of twelve (12) months following Owner's acceptance. Vendor/Contractor agrees to promptly remedy

defects and deficiencies and to restore Goods to satisfactory operating condition, and including freight charges, all

without cost to Owner. Restored parts of Goods shall be guaranteed for a further period equal to the original

guarantee period and commencing from date of restoration. This guarantee shall be in addition to Owner's other

rights.

19. PATENTS Vendor/Contractor shall indemnify and save harmless Owner from all claims, costs and damages arising from

Owner's use of Goods provided by Vendor/Contractor resulting from or contributed to by infringement, or alleged

infringement, upon any patent, trademark or copyright.

20. PERFORMANCE Vendor/Contractor shall perform Work as an independent Vendor/Contractor and not as an employee or agent of

Owner.

21. SUBCONTRACTS AND ASSIGNMENTS Vendor/Contractor shall not assign this order and shall supply Goods and render invoice, unless otherwise

authorized by Owner. Vendor/Contractor shall be responsible for payment of all assessments for levies relating to

WORK performed by employees, agents or subcontractors of Vendor/Contractor.

22. NO WAIVER Agreement provisions may only be waived by Owner, in writing.

23. DUTIES AND TAXES • Tendered prices shall include all duties and taxes except federal GST/HST. Unless otherwise provided for in

Specifications, Owner will be the importer of record.

• If applicable, Non-Resident Withholding Tax will apply, unless Vendor/Contractor has provided a waiver from CCRA.

24. FORCE MAJEURE Neither party to the contract shall be considered in default in performance of its obligations hereunder to the extent

that performance of such obligations is delayed, hindered or prevented by Force Majeure. "Force Majeure" means

acts of God, acts of public enemies, acts of a competent governmental authority and includes any other cause which

could not have been avoided by the exercise of reasonable human foresight and skill.

25. TERMINATION • Owner shall have the right, in its sole discretion, upon written notice to Vendor/Contractor, to terminate the

contract in whole or in part without being subject to a claim for damages for such termination.

• Vendor/Contractor's obligations as to Work performed and bona fide obligations assumed prior to termination shall

continue after termination; and as full compensation, Vendor/Contractor will be paid for Work performed to

OWNER's satisfaction prior to termination and cancellation expenses judged necessary by Owner. Total payments

shall not exceed the Contract Price.

26. MECHANICS' LIEN ACT

DD-NLH-001, Attachment 1 Page 54 of 88, Holyrood Blackstart Diesel Units Application

Page 56: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

CONTRACT: 2013-56865AB PURCHASING TERMS AND CONDITIONS -Page 1 4

Goods and Services Effective: September 2013

Prior to release of any Mechanics' Lien holdback, if required, Vendor/Contractor shall provide a Release from All

Liabilities in a form acceptable to Owner.

27. CONFIDENTIALLY OF INFORMATION During the performance of the Contract, Vendor/Contractor may have access to Confidential Information.

Contractor acknowledges that Confidential Information is, as between the parties hereto, the sole and exclusive

property of Owner or its Affiliates, as the case may be, and Vendor/Contractor will not make, or enable, authorize,

permit or acquiesce in any other person making, any copy or abstract of any Confidential Information unless (i) such

copying or abstracting is done strictly in accordance with the Contract and for the sole purpose of undertaking the

Work in accordance with the Contract, or (ii) with the prior written consent of Owner.

DD-NLH-001, Attachment 1 Page 55 of 88, Holyrood Blackstart Diesel Units Application

Page 57: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

DD-NLH-001, Attachment 1 Page 56 of 88, Holyrood Blackstart Diesel Units Application

Page 58: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

PAYMENT CONTRACT - 2013-56865 AB

SCHEDULE D PAYMENT

(This will become Schedule D to the

Contract)

DD-NLH-001, Attachment 1 Page 57 of 88, Holyrood Blackstart Diesel Units Application

Page 59: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

PAYMENT Page Ji CONTRACT — 2013-56865 AB

CONTRACT TITLE: Install Holyrood Blackstart Capability

Page

P 1 General 1

P 2 Submittal of Billings 1

P 3 Delayed Payment 1

P 4 Payment for Materials 1

P 5 Diary Payments 1

Oct 2013— Rev

DD-NLH-001, Attachment 1 Page 58 of 88, Holyrood Blackstart Diesel Units Application

Page 60: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

PAYMENT Page 11

CONTRACT — 2013-56865 AB

Terms of Payment

P 1 General

.1 Subject always to the provision that Contractor's overall performance of the Work is in

accordance with the Contract and Contractor continues to satisfy Owner that all aspects of

the Work are being advanced so as to permit completion of the Work within the times set

out in the Contract Documents, including approved extensions thereto, then, in the above

event, and subject to Owner's approval for the Work shall be due and payable to Contractor for the amounts and at the times set out hereunder.

P 2 Submittal of Billings

.1 Contractor's progress billings shall be submitted promptly as provided herein and as agreed

with Owner and shall be in such form and supported by such documentation as Owner may

require to facilitate verification of the amounts billed therein. All billings shall include

Contractor's registration number for the Goods and Services Tax / Harmonized Sales Tax

(HST) and shall separately identify the amounts of HST, for which Contractor shall be

reimbursed. Payments shall be due and payable thirty (30) days following receipt of an

acceptable billing by Owner, provided that the amounts so billed are correct and properly payable under the Contract.

P 3 Delayed Payment

.1 Delay by Owner in making a payment when it becomes due and payable, shall not be

deemed to be a breach of the Contract by Owner, but, except where specifically otherwise provided for, such a delay will, (if the delay continues for more than fifteen (15) days

beyond the date upon which the payment is due and payable), entitle Contractor to interest on the amount overdue at the prime lending rate of the Owner's bank.

P 4 Payment for Materials

.1 Payment shall not be made in respect of Material delivered to the Site which has not been

incorporated in the Work other than payments for Material ordered specifically for Change Orders approved by Owner or unless otherwise provided by Owner in the Contract Documents.

P 5 Diary Payments

.1 Payment of the tendered lump sum price for term of contract shall be made in equal

monthly instalments, prorated for the number of months of the contract term within such year. Each payment shall be due and payable on the 28th of the month. Where Contractor is a Registrant under the Federal Goods and Services Tax/Harmonized Sale Tax, all invoices

Oct 2013 — Rev

DD-NLH-001, Attachment 1 Page 59 of 88, Holyrood Blackstart Diesel Units Application

Page 61: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

PAYMENT Page 12 CONTRACT — 2013-56865 AB

shall include Contractor's Registration Number and shall separately identify the amounts of

HST, for which Contractor will be reimbursed.

.2 The acceptance by Contractor of the final payment under the Contract shall operate as, and

shall be, a release to Owner and its agents from any and all claim of and liability to Contractor for anything done in relation to this Contract. If required by Owner, Contractor

shall, prior to final payment under this Contract, execute a Release from all Liabilities in a

form acceptable to Owner.

.3 Payment shall be due and payable thirty (30) days following receipt by Owner of an

acceptable billing. Where equal monthly payments apply, diary payments will be setup.

Diary Payment requires that the contractor submit the first invoice to Accounts Payable.

Payments for the term of the contract will be automatically generated based on the start

and end date of the contract.

Oct 2013 — Rev

DD-NLH-001, Attachment 1 Page 60 of 88, Holyrood Blackstart Diesel Units Application

Page 62: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

PAYMENT Page 11

CONTRACT — 2013-56865 AB

Terms of Payment-

6 month

lease

Additional 12 month

lease

1 XQ2000 months 6 200,000.00 1,200,000.00 12 200,000.00 2,400,000.00 2 LV Cable months 6 41,666.67 250,000.00 12 40,000.00 480,000.00 3 Transformers months 6 40,000.00 240,000.00 4 freight Is 1 350,000.00 350,000.00 5 eingineering Service Is 1 175,000.00 175,000.00 6 Resistive & Reactive Load

Bank Is 1 50,000.00 50,000.00 7 NGR's Is 1 80,000.00 80,000.00 8 Equipment Placement Is 1 15,000.00 15,000.00 9 Estimated 2 months double

shift rental rate 320 1,250.00 400,000.00

Monthly Payment Option 1 Total 6 393,333.33 2,360,000.00 12 240,000.00 2,880,000.00

Monthly Payment Option 2 Monthly Payment 6 281,666.67 1,690,000.00 12 240,000.00 2,880,000.00 IS Payment 1 670,000.00 670,000.00

2,360,000.00 2,880,000.00

Total Contract Value 5,240,000.00

Monthly Payment Option : Contractor agrees to 6 equal monthly payments to include items 1 thru 8 listed above.

Monthly Payment Option 2: Contractor agrees to 6 equal monthly payments for lease items 1 thru 3 listed above and a lump sum payment of one time charges items 4 thru 8 listed above.

Item 9 listed above is based on additional hours if required to be invoiced and approved as required.

Oct 2013 — Rev

DD-NLH-001, Attachment 1 Page 61 of 88, Holyrood Blackstart Diesel Units Application

Page 63: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

DD-NLH-001, Attachment 1 Page 62 of 88, Holyrood Blackstart Diesel Units Application

Page 64: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS CONTRACT 2013-56865AB

SCHEDULE E SPECIFICATIONS

(This will become Schedule E to the

Contract)

DD-NLH-001, Attachment 1 Page 63 of 88, Holyrood Blackstart Diesel Units Application

Page 65: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page I i CONTRACT 2013-56865AB

CONTRACT TITLE: Supply of Diesel Generators for Holyrood Blackstart Page

SP 1 Project Technical Conditions 3

SP 2 Genset Specifications 5

SP 3 Protection and Control Specifications 8

SP 4 Transformer Specification 1

SP 5 Information to be Supplied With Bid 1

SP 6 Additional Work 5

SP 7 Drawings 5

(1)

DD-NLH-001, Attachment 1 Page 64 of 88, Holyrood Blackstart Diesel Units Application

Page 66: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

DD-NLH-001, Attachment 1 Page 65 of 88, Holyrood Blackstart Diesel Units Application

Page 67: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 13 CONTRACT 2013-56865AB

SP 1 Project Technical Conditions

Contractor shall supply and assist in the commissioning and installation of the following equipment for an eighteen month rental period

• Eight XQ2000 Diesel Generators rated at 1,825KWe, complete with a 2 ohm neutral grounding resistor. • Eight wye - wye transformers as detailed in this technical specification • All low voltage (480VAC and below) wiring and connectors required for operation. • High voltage wiring, with connectors for connection to the supplied transformers. • Resistive and Reactive Load Bank Rentals (1MW resistive and 3 MVA Load bank reactive capability)

suitable for performing testing of system • Engineering and Field Services for installation, setup, commissioning and training during set-up and

commissioning • Also required is a 50/5A relay accuracy CT and a neutral protective relay with tap range of lA to 10A

and multiple timing selection as well as a trip contact wired to the diesel generator breaker. • Connect the eight diesel units with required low voltage control wiring as specified by Contractor for

operation of the eight units. • Connect wiring between each individual diesel unit and its transformer. Connect wires to the high side

of the transformer.

After an initial 6 month rental period, the Owner may choose to rent fewer than eight units and associated equipment for the duration of the contract. Rental prices shall be adjusted at that time to reflect this change. Contractor to indicate the discount per unit removed.

The Owner may choose to purchase one or more of the diesel units and associated transformer with wiring. Based on a lease to own option as provided in Contractors proposal for each diesel unit at the site.

The Owner requires equipment delivery to site by January 17, 2014. Unit installation and commissioning shall be completed by Feb 21, 2014.

8.1 General

.1 Each mobile unit shall be supplied in a sound attenuated, standard ISO container, complete with undercarriage. Sound levels shall be in the low 70s dBA at a distance of seven metres. The package shall be designed to survive in rugged environment with minimal maintenance, supplied with lockable doors.

.2 Each mobile unit shall be serviced, tested and ready for immediate connection to Owner's power system. Standard equipment on the mobile shall include, but not be limited to air cleaner with service indicator, fuel filter with service indicator, control panel, engine running hour meter, generator with voltage regulator, radiator, electronic governor, fan and belt guards, alternator, maintenance free starting batteries c/w heavy duty charger, crankcase emissions absorber, and copies of the O&M manuals c/w AC/DC schematics for the engine and switchgear.

.3 Contractor shall arrange for the receipt, and placement (under direction of a HYDRO site representative) of each generating unit and associated equipment in final position at each site.

.4 The equipment being supplied shall be capable of operating under the following general site conditions:

(a) Outside ambient air temperature +40°C to -40 °C.

(b) Maximum operating altitude 20 m above sea level;

(3)

DD-NLH-001, Attachment 1 Page 66 of 88, Holyrood Blackstart Diesel Units Application

Page 68: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 14 CONTRACT 2013-56865AB

(c) Maximum relative humidity of 100% in a sea-coast marine environment containing sulphur and salt elements;

(d) Maximum wind speed of 130 km/hr; and,

(e) The unit power rating shall be specified based on fuel as per Article C.4 — Fuel Specification of Appendix C — Genset Specifications.

Vender shall supply each engine so that it provides the rated kWe based on the worst case conditions for site, including ambient air pressure, temperature, relative humidity, and site specific fuel specifications, in accordance with ISO 3046 standards. In addition, all other critical performance data used in the calculation of ISO 3046 shall be considered.

.5 Contractor shall perform all necessary scheduled or preventive maintenance such as oil and filter changes prior to delivery.

.6 Contractor shall provide a maintenance schedule and consumables required to maintain the units during the rental period.

.7 Contractor shall have service personnel, spare parts warehouse and repair facilities in Atlantic Canada or be able to provide a comparable level of service. Inability to comply with this requirement may result in rejection of Tender.

Contractor shall have on-call service personnel stationed on the East Coast of Newfoundland and indicate a guaranteed time-to-site in response to loss of generation.

8.2 Operation and Maintenance Manuals .1 The following typical Drawings and design data, where all dimensions shall be in mm, shall be

furnished along with each copy of the Proposal:

(a) Typical outline and wiring Drawings showing overall and envelope dimensions, general plan and profile of each mobile generating unit;

(b) External connection and terminations Drawings;

(c) Control schematics (where applicable);

(d) Weights;

.2 Two weeks after receiving order, Contractor shall furnish two (2) copies of the following documents for Owners review and acceptance, for each generating unit and associated equipment, including external switchgear and transformers:

(a) Outline and dimensional Drawings of complete enclosures and transformers indicating weights, and centre of gravity;

(b) Electrical schematic diagrams;

(c) Shipping information;

(d) External connection Details;

(4)

DD-NLH-001, Attachment 1 Page 67 of 88, Holyrood Blackstart Diesel Units Application

Page 69: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 15 CONTRACT 2013-56865AB

(e) DC circuit schematics;

List of recommended site commissioning tests. Bidder shall submit an itemized list of tests to be conducted for final commissioning. This list shall reference the applicable codes and standards for such tests and be inclusive to confirm all guaranteed values of this Tender;

(g) Detailed technical literature;

(h) Any other information and Drawings in sufficient detail to enable Owner to finalize the general arrangement, placement details, bus work and schematics for the station wherein the equipment will be located and operated; and

(I)

All documents described above shall be certified that the design work on these has been frozen and that these documents are applicable to this Specification.

Owner reserves the right to request additional information, Drawings or other data, deemed necessary by the Owner. Such requests shall be promptly complied with and no additional cost shall be payable for this unless such requests can be proven to be unreasonable. Owner shall reject Drawings deemed of unsuitable standard and these shall be redrawn by the Contractor within the specified schedule at no extra cost to the Owner.

.3 Contractor shall furnish two (2) copies of the Operation and Maintenance, and Service manuals with the unit(s), to be returned with units at the end of the rental period. The manuals shall include the following information:

(a) All applicable Drawings, circuit diagrams and component lists;

(b) Equipment specifications;

(c) Operating parameters;

(d) Equipment operating procedures and troubleshooting guides;

(e) Control schematics (where applicable); and,

(f) Generating unit service manual(s).

SP 2 Genset Specifications

GENSET SPECIFICATIONS

The following comprises Owners current standard of acceptance for the supply of diesel gensets. Proposals that do not meet these specifications may be rejected at Owners discretion.

C./ Standards Unless otherwise stated in this Specification, all diesel gensets shall be designed, manufactured, tested,

(5)

DD-NLH-001, Attachment 1 Page 68 of 88, Holyrood Blackstart Diesel Units Application

Page 70: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 16

CONTRACT 2013-56865AB

and supplied in accordance with the latest edition of all applicable codes and standards as listed. In case of any conflict between codes, between standards, or between codes and standards, such conflict shall be brought to the attention of Owner for clarification and determination.

.1 International Standard Organization (ISO)

ISO 3046/1 Reciprocating Internal Combustion Engines; Performance Part 1:Standard Reference Conditions, Declarations of Power, Fuel and Lubricating Oil Consumptions and Test Methods

ISO 3046/2

Reciprocating Internal Combustion Engines; Performance Part 2: Test Methods

ISO 3046/3

Reciprocating Internal Combustion Engines; Performance Part 3: Test Measurements

ISO 3046/4

RAcipwating IntArnAl nom hi istinn Fngins4; PArinrni Ann° Part 4: Speed Governing

ISO 3046/5

Reciprocating Internal Combustion Engines; Performance Part 5: Torsional Vibrations

ISO 3046/6

Reciprocating Internal Combustion Engines; Performance Part 6: Overspeed Protection

ISO 3046/7

Reciprocating Internal Combustion Engines; Performance Part 7: Codes for Engine Power

ISO 9001

Quality Systems; Model for Quality Assurance in Design, Development, Production, Installation and Servicing

.2 Canadian Standards Association (CSA)

CSA C22.1 CSA C22.2 No.0.4 CSA C22.2 No.41 CSA C22.2 No.100 CSA C22.2 No.127

Canadian Electrical Code Part 1 Bonding and Grounding of Electrical Equipment Grounding and Bonding Equipment Motors and Generators Equipment Wires

.3 American National Standards Institute (ANSI)

ANSI/IEEE C37

Circuit Breakers, Switchgear, Relays and Fuses ANSI/IEEE STD.112

Standard Test Procedure for Polyphase Induction Motors and Generators

ANSI/IEEE C50.13

Requirements for Synchronous Generators

.4 American Society for Testing and Materials (ASTM)

D 240-76 Test for Heat of Combustion of Liquid Hydrocarbon Fuels by Bomb Calorimeter

C.2 Engine and Skid

.1 Engine

Each engine shall be a heavy duty compression ignition type operating at 1200 or 1800 rpm and delivering an ISO power as specified. Each engine shall be turbocharged and aftercooled.

The scope of supply for each unit shall include the equipment as listed below and any other

(6)

DD-NLH-001, Attachment 1 Page 69 of 88, Holyrood Blackstart Diesel Units Application

Page 71: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 17 CONTRACT 2013-56865AB

accessories normally provided or required for the safe, reliable and environmentally compliant operation of each generating unit:

(a) Four cycle, heavy duty, cold start compression ignition engine c/w auxiliaries, to run on No. 2 diesel fuel;

(b) AC synchronous generator, 60 Hz star winding configuration with a Permanent Magnet Generator (PMG) providing power for the automatic voltage regulator;

(c) Engine protective devices as specified in Appendix D - Protection and Control;

.z General Features

Each generating unit shall be equipped with the following features and auxiliary equipment:

(a) Crank case emission absorber(s) that shall drain all recovered oil back to the engine sump and prevent the release of gaseous emissions to the environment;

(b) Air intake filter(s), heavy duty dry type with replaceable filter element(s) and indicator(s) to show when filter element changes are required;

(c) Individual electronically governed fuel injection system;

(d) Local instrument panel displaying fuel pressure, lube oil pressure, and jacket water ternperature;

(e) Fuel priming pump on fuel system inlet to prime generating unit after servicing;

C.3 Fuel Supply System Each engine fuel supply system shall include:

(a) UL/ULC listed, double walled, internal day tank with sufficient capacity to provide eight hours of operation at 100% load. Day tank shall have access for filling both inside and outside the container and provide for filling from outside while the genset is in operation. The fill pipes shall be a minimum of two inches in diameter to accept a standard tank truck hose nozzle.

(b) Engine mounted, engine driven fuel pump, built-in type, equipped with a pressure operated bypass valve.

(c) Fuel filter housing(s) equipped with a pressure operated bypass valve, provisions for bleeding and purging fuel system.

(d) Suitable protection in all areas where leaking fuel could come into contact with a surface temperature of 150 °C or higher.

C.4 Fuel Specification Each engine shall be suitable for the continuous use of No. 2 diesel fuel as specified in National Standard of Canada, CAN/CGSB-3.517-2007.

(7)

DD-NLH-001, Attachment 1 Page 70 of 88, Holyrood Blackstart Diesel Units Application

Page 72: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 18 CONTRACT 2013-56865AB

C.5 Engine Sound and Power Levels (a) Sound power levels exterior to the enclosure shall be in the low 70s dBA at a distance of seven

metres.

C6 Synchronous Generator (a) Each AC synchronous generator shall be continuous prime power duty at the kWe unit rating

specified, 60 Hz., 0.8 pf., 3-phase, 4-wire and designed for ungrounded or grounded system operation. It shall have a minimum efficiency of 94% at 0.9 P.F. for the load range 50% to 100% of nameplate rating and an overload capability of 10% for two (2) hours.

(b) Each generator shall be open drip-proof, permanently lubricated two bearing design. Each generator shall be coupled to the diesel engine housing using a standard SAE adaptor, and to the flywheel using a flexible coupling (less pilot shaft).

(c) Each generator shall be a brushless design with full damper windings for parallel operation with other diesel generating units.

(d) Each generator shall be capable of continuous operation with a 30% load unbalance between highest and lowest phases without exceeding the allowable temperature rise, causing any harmful vibration, or inducing the generation of harmonic voltages.

(e) Each generator terminal box shall be provided with insulated bus bars for each phase and neutral connection. Generator leads shall have heavy-duty compression type connectors securely bolted to the bus bar. Each bus bar shall be of sufficient size to accommodate the Owner's power cable connections (standard 2-bolt NEMA type). The star point of each generator shall connect to the neutral bus bar and not be grounded prior to this point. Exciter field leads shall terminate in the engine junction box as per the drawings.

(f) Each exciter shall be direct coupled to the generator shaft. Each exciter shall be of an approved brushless type compatible with the Basler SSR automatic voltage regulator.

(9) Each generator design shall incorporate a single phase PMG pilot exciter. The PMG exciter shall provide AC input power to the automatic voltage regulator to maintain alternator voltage out to 200% load and 300% or more short circuit current. The PMG voltage shall be of such value that the automatic voltage regulator output can drive the generator exciter to its ceiling voltage, or saturation voltage.

(h) Include at 2ohm neutral grounding resistor on the generator.

C.7 Protection and Control Protection and control shall comply with Appendix D.

SP 3 Protection and Control Specifications

(8)

DD-NLH-001, Attachment 1 Page 71 of 88, Holyrood Blackstart Diesel Units Application

Page 73: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 19 CONTRACT 2013-56865A8

PROTECTION AND CONTROL SPECIFICATIONS

D.1 P&C: GENSET SPECIFICATIONS

The protection and control design guidelines for a prime power diesel fuelled, generating unit takes

into account all critical electrical and mechanical operating conditions and sets alarm and trip points

above normal engine and generator parameters. The type of automatic control and monitoring

implemented is based on HYDRO's standard equipment designs, including approved equipment types and manufacturers.

.1 PURPOSE

The purpose of the standard is to provide minimum acceptable protection and control design

guidelines for a prime power diesel fuelled generating unit with a nominal voltage rating of either 480V, 600V or 4160 volts.

.2 SCOPE

This standard covers the operational aspects of the engine and switchgear units as well as their

complementary control schemes such as start up and synchronizing and the requirements of the DC system as it applies to individual generating units.

.3 ENGINE PROTECTION

The engine shall be protected with both primary as well as secondary backup protection systems.

.3.1 Primary Protection System The primary engine protection system shall utilize the engine manufacturer's standard protection

devices and shall comprise the following minimum equipment, hard wired to the unit start and stop circuits:

(1) High Jacket Water Temperature Sensor (2) Lubricating Oil Pressure Sensor

(3) Low Coolant Level Sensor

(4) Engine Speed Sensor

(5) Combustion air intake shut off valve(s)

Note: Spare auxiliary Form C contacts shall also be available for the first three (3) engine sensor devices listed above.

(9)

DD-NLH-001, Attachment 1 Page 72 of 88, Holyrood Blackstart Diesel Units Application

Page 74: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page I 10 CONTRACT 2013-56865AB

.3.2 Secondary Backup Protection System

The secondary backup engine protection system shall utilize analog 4-20 ma transmitters, resistance

temperature detectors (RTDs), thermocouple(s) and discrete inputs wired to a programmable

electronic controller. This system will provide the secondary backup engine protection while giving the

operator enhanced engine information and diagnostics. This system comprises the following minimum

equipment, hard wired to the programmable electronic controller I/O:

(1) Coolant Temperature Sensor c/w Transmitter (engine jacket)

(2) Coolant Temperature Sensor c/w Transmitter (engine inlet)

(3) Coolant Level Sensor (discrete) (4) Exhaust Gas Temperature Thermocouple Sensor c/w Transmitter

(5) Lubricating Oil Pressure Trancriurizr

(6) Fuel Pressure Transducer

(7) Turbo Boost Pressure Transducer (if applicable)

(8) Engine Speed Sensor (flywheel)

These sensor inputs will be processed by the programmable electronic controller which in turn provides a single contact closure output to the engine trip and lockout circuits.

.3.3 Starting System An electric starting system shall include an engine mounted 24 VDC electric starting motor c/w heavy

duty electric starter solenoid interwired to the engine start circuit. The starting circuit shall be de-

energized via a speed switch when the engine has started and via a timer in the event of over cranking

i.e. failure of the engine to start. For an engine with a pneumatic starting system a 24 VDC solenoid shall be provided. Oil pressure sensing will be disabled until the unit has reached crank disconnect speed, which shall be 33 % of rated speed.

.3.4 Governing System

The governing system shall consist of a proportional control actuator or electronic fuel control

installed on the engine, as well as an electronic load sharing and/or speed control device installed in the switchgear control panel. The following auxiliary devices, necessary to make the governing system function in parallel with other units shall be supplied:

(1) Dedicated speed sensor

(2) Metering accuracy current transformers (CTs)

(3) Metering accuracy potential transformers (PTs) (4) Idle/Rated speed control switch

(5) Droop/lsochronous control switch

.3.5 Engine Control System The engine-mounted control system shall contain the following equipment:

(1) Local Emergency Stop Pushbutton

(2) Local Start Pushbutton

(10)

DD-NLH-001, Attachment 1 Page 73 of 88, Holyrood Blackstart Diesel Units Application

Page 75: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page I 11 CONTRACT 2013-56865AB

(3) Local Stop Pushbutton

Note: The term 'Local' refers to a control function at the engine location.

.4 GENERATOR PROTECTION

.4.1 Winding Temperature The generator shall have two (2) temperature sensing devices installed on each stator phase winding.

.4.2 Voltage Regulation One (1) automatic voltage regulator (AVR) shall be installed in the switchgear control panel. Power for

the AVR shall be supplied by a permanent magnet generator, which shall be a single phase design

rated 700 VA (min.), 120 V, 120 Hz. (max.). The voltage regulator shall utilize either droop or cross

current compensation circuits for parallel operation of two (2) or more units. A multi-turn

potentiometer shall be provided at the switchgear control panel for voltage adjust.

.5 SWITCHG EAR CONTROL PANEL

The front of the switchgear control panel shall have two (2) compartments, one at the top with a

hinged door for the protection, metering and control devices and wiring, and another at the bottom, also with a hinged door, for a drawout type circuit breaker and PTs. The rear compartment, accessible

via a removable plate, shall contain insulated bus bars, and the CTs.

.5.1 Digital Metering Unit The digital metering unit shall be a multi-function device, semi-flush mounted and located on the top

panel door. The power parameters displayed by the digital metering unit shall include but not be

limited to AC amps, volts, frequency, watts, vars, power factor, KWH, and kW demand.

An elapsed time meter, as well as DC ammeter and voltmeter are individual metering devices which

shall also be mounted on the top panel door.

DD-NLH-001, Attachment 1 Page 74 of 88, Holyrood Blackstart Diesel Units Application

Page 76: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Pa ge I 12 CONTRACT 2013-56865AB

.5.2 Control Switches

Control switches shall be provided for the following operating duty:

(1) Governor Mode (Droop/Isoch) (2) Engine Speed Mode (Idle/Rated) (3) Breaker Control (Trip/Close) (4) Synchronizing Mode (Auto/Manual) (5) Supervisory Control (Manual/PLC) (if applicable) (6) Engine Start Push Button (7) Engine Stop Push Button (8) Emergency Stop Push Button

.5.3 Annunciation System

A hard wired annunciation system shall be provided.

.5.4 Unit Breaker

A drawout type air circuit breaker shall be provided complete with the following minimum design features:

(1) Motor mechanism for spring charging. (2) DC closing solenoid for electrical closing. (3) DC trip solenoid for electrical tripping. (4) Four (4) spare sets of 'a' and 'b' breaker auxiliary contacts. (5) Anti-pumping feature. (6) Safety shutters and arc chute covers. (7) Terminal shield and interphase barriers. (8) Trip free opening feature. (9) Lock out preventing closing feature. (10)Open and close pushbuttons for manual operation.

Horizontal breaker terminals, both top & bottom shall also be provided to enable the extension of these terminals using high voltage insulated bus bars.

(12)

DD-NLH-001, Attachment 1 Page 75 of 88, Holyrood Blackstart Diesel Units Application

Page 77: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page I 13 CONTRACT 2013-56865AB

.5.5 Protective Relay A multi-function protective relay mounted on the unit control panel door shall provide the following

unit protection:

(1) Reverse Power

(2) 3-Phase Overcurrent c/w selectable trip curves

(3) Undervoltage and Overvoltage

(4) Underfrequency and Overfrequency

(5) Synchronizing Check c/w dead bus feature

(6) Generator Excitation

(7) Generator Differential (if applicable)

All unit protection parameters listed above would trip the unit breaker, except for the generator

differential which would trip the unit breaker and shut down the engine.

.5.6 Current and Potential Transformers All current and potential transformers shall be mounted in the switchgear control panel, except for

those required for generator differential protection which would be mounted in the generator

connection box.

The current transformer (CT) ratio chosen shall provide adequate secondary current for unit control

panel electrical devices. All CTs shall be of metering accuracy and have a nominal secondary rating of 5

amps.

CTs shall be provided in the switchgear control panel for the following electrical devices and functions:

(1) Automatic voltage regulator cross current compensation

(2) Electronic governor or load sharing module

(3) Digital metering

(4) Protective relay

The potential transformer (PT) primary rating chosen shall provide a nominal secondary voltage of 120

volts for control panel electrical devices. All PT's shall be of metering accuracy and sized according to

the connected burden.

PT's shall be provided in the switchgear control panel for the following electronic devices:

(1) Automatic Voltage Regulator

(2) Electronic Governor or Load Sharing Module

(3) Digital Metering

(4) Protective Relay

(5) Automatic Synchronizer

(6) Synchroscope

(13)

DD-NLH-001, Attachment 1 Page 76 of 88, Holyrood Blackstart Diesel Units Application

Page 78: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page I 14 CONTRACT 2013-56865AB

.5.7 Synchronizing

Diesel unit synchronizing shall be provided by an automatic synchronizer mounted in the unit control

panel and is interwired to the electronic governor or load sharing module. The automatic synchronizer

shall also have a system check feature for troubleshooting purposes.

The synchronizing check including dead bus feature of the multi-function protective relay shall be used

for verification of all synchronizing control which includes manual closure of the unit breaker under dead bus conditions.

Each diesel generator shall be able to synchronize with the grid, or another diesel generator supplied as part of this contract.

.5.8 Programmable Electronic Controller

A programmable electronic controller c/w digital display shall be provided at the switchgear control

panel to monitor and display the various discrete and analog sensing points on the diesel generating

unit. The controller shall provide programmable output contacts for alarm and trip functions including annunciation.

All programmable controller alarm and trip functions shall be considered as secondary backup

protection to the engine manufacturer's analog and/or discrete sensing devices, which provide primary engine protection.

.6 UNIT DC SYSTEM

The unit DC system shall comprise of the following minimum components:

(1) A wall mounted battery charger of sufficient capacity to charge the 24 VDC diesel engine starting batteries.

(2) A set of maintenance free batteries with sufficient capacity to handle all starting, and associated unit control circuits.

The unit DC system shall provide sufficient capacity for engine cranking during multiple start attempts,

as well as a regulated DC supply for the control equipment in the switchgear control panel.

D.2 P&C: SWITCHGEAR SET SPECIFICATIONS

The switchgear set, transformer and breaker combination set to be used in conjunction with the

generator set shall conform to the following specifications in addition to other requirements as noted on the applicable electrical reference drawing.

.1 Switchgear Cabinet

All equipment shall be total enclosed with no energized equipment exposed including bushings.

(14)

DD-NLH-001, Attachment 1 Page 77 of 88, Holyrood Blackstart Diesel Units Application

Page 79: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page I 15 CONTRACT 2013-56865AB

The cabinet shall be weather proof with lockable hinged doors. HV and LV cable entry shall be through the bottom.

It shall conform to CSA standards.

.2 Transformer

The transformer shall be sized to accommodate the capacity of the generating unit and meet the voltage and winding configuration as specified on the drawings

D.3 P&C: REFERENCES

-

.1 REFERENCE DRAWING

Equipment configuration shall conform to Figure D-1 "Mobile Diesel Generating Unit and Switchgear — Single Line Protection Diagram" Dwg # DG-14-002-D1

.2 REFERENCE STANDARD

Unless otherwise stated in this Specification, all equipment shall be designed, manufactured, tested, and supplied in accordance with the latest edition of all applicable codes and standards as listed. In case of any conflict between codes, between standards, or between codes and standards, such conflict shall be brought to the attention of Owner for clarification and determination.

.2.1 Recognized Standards Organizations CSA - Canadian Standards Association EEMAC - Electrical Equipment Manufacturers Association of Canada ANSI - American National Standards Institute NEMA - National Electrical Manufacturers Association IEC - International Electromechanical Commission

In case of conflict between CSA and other standards, CSA shall prevail.

(15)

DD-NLH-001, Attachment 1 Page 78 of 88, Holyrood Blackstart Diesel Units Application

Page 80: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

Ws Dro ving conloir s

Iefech pcoerty

of Noioundl ond and Lobrodot y

r° (MVO

and shol not be capiett.

used

or rislrbuled in oh* or in

pal ulhoul prict written myself Iran HOC. Use ol the dr ouirq

sh ort be restricted

to purposes

of prosecution of o conked with M

DRO .

4 3 C.T.'S

3-P.T.'S

CM

DIGITAL KWH METER I TEST

15kV, 1200A WITHDRAWABLE

BREAKER CI SWITCH

000

STOP ENGINE

H.V. 12.5kV WYE GROUNDED

(MINIMUM 2.5MVA) rrs'Y'l

L.V. TO SUIT GENERATION DELTA CONFIGURATION

0 (-)

(1""

6 ABOVE UNE WITHIN SWITCHGEAR

POWER CABLES

BELOW LINE WITHIN GENSET MO

BIL

E DIE

SE

L GE

NE

RA

TIN

G

UNIT

AND

SW

ITC

HG

EA

R

SIN

GLE

LINE

PR

OT

EC

TIO

N D

IAG

RA

M

DIE

SE

L G

EN

ER

ATIO

N

EN

GIN

EE

RIN

G S

TA

ND

AR

DS

*—I FUSES TRIP EIXR.

1 -P.T.'S A-Bo

,

ALARM

0 PROGRAMMABLE

CONTROLLER f--- > 0 SE I.—. < ce VI ul

LOW VOLTAGE BREAKER

8 —

4* .....„ _ ,

2-P.T.'S

ELECTRONIC /

\ / I AUTO

SYNCHRO ENGINE SAFETIES

HARDWIRED

ENGINE SAFETIES ANALOG

• /1

A-80,8-CO /

..."*".. 1 50/510

AO

00

..--I FUSES A I szvEnsjii

SURGE SUPPRESSOR 9

+ l

/

/

3 C.T.'S ELECTRONIC DIGITAL ACC ± 1% 0 35VA A

TEST GOVERNOR METER

SWITCH ME: CAI LOAD SHARING NOTE: CAPABIUTY

2-P.T.'S A-80,8-00 BOTH CT & PT RATIO

WOULD DEPEND ON VOLT. SENSING 41-4 FUSES 1 VOLTAGE AND kW SIZE

OF DIESEL GENERATOR AVR INPUT POWER FROM PMG IF UNIT IS SO FITTED

LEGEND:

0 * 5") Z P 0 0 1

1 0 o ts3 i

I CH

ECK

ED

I DRA

WN

C. M

UR

PH

Y

I I

ISS

UED

DRAFT

> -o 1:,.

TEST SWITCH

Ask POWER INPUT

FUSE gil

1 C.T. (BO) AVR AVR — AUTOMATIC VOLTAGE

REGULATOR ACC ±1% 0 35VA A CROSS CURRENT COMPENSATION TEST

SWITCH

2MW 40 0 00

ETM — ELAPSED TIME METER PMG — PERMANENT MAGNET

D.C. OUTPUT GENERATOR

EXCITER

DD-NLH-001, Attachment 1 Page 79 of 88, Holyrood Blackstart Diesel Units Application

Page 81: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 11 CONTRACT 2013-56865AB

SP 4 Transformer Specification

Each generating until will include a padmount transformer located outside and behind the diesel unit. Pad mount transformers PAD1283-S and PAD1289-S are acceptable solutions with the following general specifications:

Configuration wye — wye Primary Voltage: 480V Secondary Voltage: 4160V Impedance: 5% — 6%

Any other padmount transformer must be approved by the Owner prior to acceptance.

Contractor will supply appropriately rated cables and terminations for cables leading from the Diesel generators to the 480V side of the padmount transformers. Contractor will supply appropriately rated cables to connect from the 4160V side of the transformer to the riser pole. These cables must be a minimum of 60' long. Contractor to supply the connections from the cables to the 4160V side of the transformer.

SP 5 Information to be Supplied With Bid

INFORMATION TO BE SUPPLIED WITH BID

E.1 TECHNICAL PARTICULARS Bidder shall submit Drawings and design data as per Article B.2.1 of Appendix B — General Conditions with each copy of its Proposal. It shall also give details of the equipment it proposes to supply, including, but not limited to, the following data.

.1 Reference Users

The Bidder shall demonstrate previous proven experience in Canada. Each tendered generating set or identical model shall have been installed in Canada and operated at the design and operating requirements as specified in this Specification. Bidder shall submit details listing for whom each unit was supplied, the date it was supplied and a contact person.

DD-NLH-001, Attachment 1 Page 80 of 88, Holyrood Blackstart Diesel Units Application

Page 82: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 12 CONTRACT 2013-56865AB

.2 Servicing of Equipment

Location of nearest service personnel and facilities

.3 Equipment Data

Bidder shall complete all of the following equipment data, for each generating unit rating tendered:

(a)Exhaust flow (100%NPR) m3/min

(b)Exhaust gas temperature at exhaust manifold exit as follows:

25% of engine NPR 50% of engine NPR 75% of engine NPR 100% of engine NPR

(c)Engine emission data as follows:

Engine Load 25')/0NPR 50% NPR

75% NPR

100% NPR

Exhaust Flow Rate m3/min Exhaust Mass kg/hr Carbon Monoxide (CO) g/hr Carbon Dioxide (CO) g/hr NO + NO2 (N0x) g/hr Sulphur Dioxide (902) g/hr Particulate g/hr Carbon in Particulate %

(d)Load Pick Up

(I)

Load pick up capability in % of NPR with a maximum 2% engine speed decrease

°A)

(ii) If load pick up must be staged, the following are the % loads which shall be applied to the unit at five (5) second intervals.

First load pick up Second load pick up Third load pick up Fourth load pick up

(e)Generator Data as follows:

(i) Manufacturer

(ii) Rated Full Load Current A

DD-NLH-001, Attachment 1 Page 81 of 88, Holyrood Blackstart Diesel Units Application

Page 83: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 13 CONTRACT 2013-56865AB

(iii) Exciter Field Resistance c2

(iv) Excitation Current at No Load A

(v) Excitation Voltage at No Load V

(vi) Excitation Current at Full Load (0.8 pf) A

(vii) Excitation Voltage at Full Load (0.8 pf) V

(viii) PMG Output Frequency Hz

(ix) PMG Output Voltage

(x) Generator efficiency as follows:

25% of engine NPR

50% of engine NPR

75% of engine NPR

100% of engine NPR

(xi) Generator Load Losses as follows:

25% of engine NPR W

50% of engine NPR W

75% of engine NPR W

100% of engine NPR W

(xii) Generator P.U. reactances as follows:

Direct axis saturated synchronous (Xd)

Direct axis transient (Xd')

Direct axis sub-transient (Xd")

Leakage (X1)

Negative sequence (X2)

Zero sequence (X0)

p.u.

p.u.

p.u.

p.u.

p.u.

p.u.

(f)Switchgear and Transformer Data

Fault Current Rating MVA

Continuous Current Rating A

Winding Configuration HV

Winding Configuration LV

Voltage Rating HV kV

Voltage Rating LV kV

%I V

%

%

%

%

DD-NLH-001, Attachment 1 Page 82 of 88, Holyrood Blackstart Diesel Units Application

Page 84: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 14 CONTRACT 2013-56865A6

E.2 SCHEDULE For each event below the dates entered by the Bidder in Column 2 shall agree with the dates required by Owner Column 1. These shall be subsequently agreed to by the Owner, and become the approved schedule. This schedule shall be submitted for each proposal.

EVENT

Delivery of equipment to Holyrood Thermal Plant

Installation and commissioning of equipment.

DATE REQUIRED DATE CONFIRMED BY OWNER BY CONTRACTOR

Jan 17, 2014

Feb 21, 2014

Failure to guarantee or meet delivery dates outlined may result in rejection of bid.

E.3 GUARANTEES Bidder shall provide the following performance data.

These values shall be guaranteed under the specified operating conditions and shall be binding on Contractor. Cost data shall be consistent with prices being charged Contractor in the current calendar year. Inconsistencies may result in rejection of proposal.

.1 Performance Data

(a) Prime ISO Power Rating at 0.8 P.F. kWe

(b) Overload Power Rating at 0.8 P.F. kWe

(c) All fuel performance guarantees are based on specified fuel as per Article C.4 - Fuel

YES

NO Specification of Appendix C — Genset Specifications

(d) Lower Heating Value of Fuel on which the Specific Fuel Consumption values are based

kJ/kg

(e) Guaranteed Specific Fuel Consumptions, corrected to standard ISO conditions at 0.8 P.F:

25% of engine NPR g/kWhe 50% of engine NPR g/kWhe 75% of engine NPR g/kWhe 100% of engine NPR g/kWhe

(f) Engine light loading capability as follows:

DD-NLH-001, Attachment 1 Page 83 of 88, Holyrood Blackstart Diesel Units Application

Page 85: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 15 CONTRACT 2013-56865AB

Minimum recommended light load kWe Duration light load can be applied hrs

.2 Technical Support

Location of on-call technical support Guaranteed emergency response time-to-site Holyrood hrs

A Additinnal Wnrk

.1 Scope

Contractor shall supply:

• Engineering and Field Service

• The cable rental will be for the low voltage cable and the high voltage cable based on

60ft runs. The cable will be installed by Hydro

• Resistive and Reactive Load Bank Rentals for performing testing of system

Additional Work to be done under this Clause SP 4 shall comprise the supply of all labour,

construction plant and materials and the performance of all Work not included in scope of

Contract but deemed necessary for completion of the Project.

.2 General

The Contractor shall notify the Owner of any additional Work required. All, if any, Work shall be

performed as directed and scheduled by Owner. Cost of such Work shall be considered during

Tender Evaluation.

Scope of Work shall be agreed upon by Contractor and Owner or Owner's site representative.

The Contractor shall submit copies of material pricing, labor and rental rates to the Owner to

substantiate the cost of additional Work.

SP 7 Drawings

.1 Contractor shall perform the Work in strict accordance with Drawings.

.2 Drawings shall be referenced by a Drawing and revision number.

.3 Contractor's and Manufacturer's Drawings and revisions thereof shall be subject to review by

Owner. Such review shall in no respect relieve Contractor of its responsibility and liability under

the Contract. Fabrication, shipping or erection of Material and Construction Plant or any parts

thereof shall not start prior to Owner's review of such Drawings.

DD-NLH-001, Attachment 1 Page 84 of 88, Holyrood Blackstart Diesel Units Application

Page 86: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 16 CONTRACT 2013-56865AB

.4 Drawings bearing reference to the Project or Owner shall not be used by Contractor for any

other purpose without prior written approval of Owner.

.5 Owner, in its sole discretion, may make reasonable use or reuse of Drawings as required in

Owner interest.

.6 Contractor shall supply Drawings as follows:

(a) by email in the latest version of AutoCad (.dwg extension).

(b) by email — PDF files must be stamped and signed by engineer.

(c) Original paper drawings must be stamped and signed by engineer.

Drawings shall be in B1 or Al size formats with a minimum character height of 2 mm.

.7 Contractor shall submit Drawings for review by Owner in accordance with the Approved

Construction Schedule and, where required, the APEGN Act, RSM. 1990, Chapter E-12, as

amended.

.8 Drawings shall be provided for, but not be limited to, the following:

(a) parts embedded in concrete;

(b) parts to be connected to equipment supplied by others;

(c) piping;

(d) wiring diagrams; (e) parts in which adjustment has been allowed or which are subject to wear;

(f) assemblies showing plans and cross sections of the complete equipment components being

supplied;

(g) erection and lifting devices;

(h) layout and dimensional Drawings;

(i) bills of materials;

(j) characteristic curves, such as

i. curves;

ii. current transformer magnetization curves; and

iii. similar performance curves for equipment.

.9 Details on Drawings and Data shall be sufficient to allow Owner to independently assess

performance of all parts. Such details shall include, but not be limited to, material designations,

welding specifications, part numbers, dimensions, fits, tolerances and surface finishes for all

machined parts.

.10 Contractor shall allow fifteen (15) working days (from date of receipt to date of return dispatch)

for Owner to advise Contractor of review results.

.11 Contractor shall, upon receipt of review comments, promptly modify and resubmit or issue

Drawings as required. Modification and resubmission shall continue until such time as

Contractor is advised that review is complete.

DD-NLH-001, Attachment 1 Page 85 of 88, Holyrood Blackstart Diesel Units Application

Page 87: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 17 CONTRACT 2013-56865AB

.12 Owner's review shall not relieve Contractor of any contractual responsibilities.

.13 Two weeks prior to shipping, Contractor shall forward one (1) complete set of the latest

revisions of related Drawings.

.14 After Commissioning Acceptance, Contractor shall forward one (1) complete set of Drawings,

stamped "Final - As Built", which incorporate modifications made during erection, commissioning and testing.

.15 Contractor's Drawings shall be clearly marked as follows:

(a) NEWFOUNDLAND AND LABRADOR HYDRO

(b) Install Holyrood Blackstart Capability

(c) The title block of all Drawings shall have the following information clearly indicated: i. description of Drawing content; ii. name of major equipment or system of which Drawing content is part;

iii. Contractor's Drawing number;

iv. revision number and date of revision; v. date drawn;

vi. Owner's Drawing number from list forwarded to Contractor by Owner.

.16 Schematic and wiring diagrams shall use ANSI standard drafting symbols and ANSI device function designation systems.

.17 Drawings shall enable Owner to prepare and organize interfacing with the work of its own, or other contractors', forces.

DD-NLH-001, Attachment 1 Page 86 of 88, Holyrood Blackstart Diesel Units Application

Page 88: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page 11 CONTRACT 2013-56865AB

DRAWINGS

DD-NLH-001, Attachment 1 Page 87 of 88, Holyrood Blackstart Diesel Units Application

Page 89: DD-NLH-001 Holyrood Blackstart Diesel Units Application Page 1 of ...

SPECIFICATIONS Page I 1. CONTRACT 2013-56865AB

PREAMBLE

The Work shall be carried out in accordance with the Drawings listed below and any additional Drawings issued at a later date by Owner.

All Drawings are marked "For Tender Purposes Only" to identify them as Tender Drawings. The listed Drawings will be "Approved for Construction" and issued to Contractor within two (2) weeks of the acceptance of the Tender.

"Approved for Construction" Drawings may be revised by Owner during the progress of the Work to incorporate changes to design detail.

List of Drawings

Revision Drawing No. Title Number Date

DD-NLH-001, Attachment 1 Page 88 of 88, Holyrood Blackstart Diesel Units Application