dd-01
-
Upload
claudiotech76 -
Category
Documents
-
view
212 -
download
0
description
Transcript of dd-01
![Page 1: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/1.jpg)
INSTRUCTION MANUAL FOR DD-01
DIGITAL DIVERT CONTROL SYSTEM VERSION 4.1.
WITH MAIN PROGRAM 8.5 OR HIGHER
WARNING
The process medium may be hot or otherwise hazardous. Precautions when removing the sensor from the process line:
Make sure that the process line is not under pressure. Open a vent valve to the atmosphere. For a retractor/isolation valve the line pres-sure should be within specifications.
For a prism wash system, close a hand valve for the wash medium and disable the wash valve. Loosen the clamp or flange bolts cau-tiously, be prepared to tighten again. Be out of the way of any possible splash and ensure the possibility of escape.
Use shields and protective clothing adequate for the process medium. Do not rely on avoidance of contact with the process medium. After removal of the sensor, it may be necessary to mount a blind flange for security reasons.
Document/Revision No. IMD 1/5 Effective: June 20, 2005
This product manual is delivered to the end-user with a K-Patents product. Information in this manual is subject to change without notice. The latest manual version is freely available at http//www.kpatents.com/. You can also contact [email protected].
THE PASSWORD FOR PR-01-S IS 7 8 4 5 1 2 IN PROGRAM VERSIONS 4.0 AND HIGHER.
K-PATENTS OY
Postal address: P.O. Box 77 FIN-01511 Vantaa, Finland
Tel. + 358-9-825 6640 Fax +358-9-825 66461 E-mail: [email protected] http://www.kpatents.com/
K-PATENTS OY
Street address: Elannontie 5 FIN-01510 Vantaa, Finland
Tel. + 358-9-825 6640 Fax +358-9-825 66461
K-PATENTS,INC.
1804 Centre Point Circle, Suite 106, Naperville, IL 60563
Tel. 630-955 1545 Fax 630-955 1585 E-mail: [email protected] http://www.kpatents.com/
![Page 2: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/2.jpg)
1
1. TABLE OF CONTENTS
1 TABLE OF CONTENTS........................................................................................................................1
2 GENERAL INFORMATION .................................................................................................................2 2.1 Digital divert control system DD-01 .................................................................................................2 2.2 Operator panel...................................................................................................................................3 2.3 Alarms...............................................................................................................................................4 2.4 Prism wash ........................................................................................................................................4 2.5 Master divert control unit ..................................................................................................................5 2.6 Indicating transmitters.......................................................................................................................6 2.7 K-Patents digital divert control unit specifications............................................................................7
3 MOUNTING...........................................................................................................................................8 3.1 Wiring ...............................................................................................................................................8
4 START-UP ...........................................................................................................................................12 4.1 Divert control unit start-up ..............................................................................................................12 4.2 Divert control system trimming.......................................................................................................12
5 CALIBRATION....................................................................................................................................13 5.1 Refractometer concentration measurement .....................................................................................13 5.2 Refractometer activation for divert control .....................................................................................13 5.3 Signal difference alarm ...................................................................................................................14 5.4 Low alarms......................................................................................................................................14 5.5 Refractometer malfunction alarm....................................................................................................14 5.6 Prism wash ......................................................................................................................................14 5.7 Divert decision rules........................................................................................................................15
6 MAINTENANCE .................................................................................................................................17 6.1 Information flow..............................................................................................................................17 6.2 Divert control circuit boards ...........................................................................................................18 6.3 Diagnostic messages........................................................................................................................23 6.4 Diagnostic lights..............................................................................................................................23 6.5 Push-button assembly......................................................................................................................24 6.6 Fuses................................................................................................................................................24
7 DIVERT CONTROL LOGIC ...............................................................................................................25 7.1 Block diagram .................................................................................................................................25 7.2 Logical diagrams .............................................................................................................................26 7.3 Safety Decision Logics....................................................................................................................28
8 OPTIONAL CONFIGURATIONS.......................................................................................................30 8.1 Remote divert control unit...............................................................................................................30 8.2 Equipment .......................................................................................................................................30 8.3 Remote divert control unit in the control room ...............................................................................31 8.4 Wiring and mounting.......................................................................................................................32 8.5 Serial output ....................................................................................................................................34 8.6 Current output signal .......................................................................................................................34 8.7 External DC power supply ..............................................................................................................34
9 DIVERT CONTROL UNIT PARTS LISTS.........................................................................................35 9.1 Divert control unit and optional remote divert control unit.............................................................35 9.2 Remote divert control unit...............................................................................................................36
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 3: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/3.jpg)
2
2. GENERAL INFORMATION
The K-Patents Digital Black Liquor Divert Control System DD-01 provides a divert signal preventing black liquor with dangerously low solids to reach the black liquor burners. The system is built strictly according to the principles of Recommended Good Practice "Safe Firing of Black Liquor in Black Liquor Recovery Boil-ers" (BLRBAC August, 1982 and revisions April, 1991, and March, 2001).
2.1. DIGITAL DIVERT CONTROL SYSTEM DD-01
Figure 2.10 Complete Digital Divert Control System DD-01
The system consists of the following parts (Figure 2.10): Two K-Patents Process Refractometers PR-01-S (A & B) are installed in series in the main black liquor line. Each refractometer is complete with a Sensor, an Indicating transmitter and Interconnecting cables. Each refractometer provides also a 4-20 mA % solids output signal not used by the divert control system.
The Divert Control Unit DD-01 is contained in one enclosure with the same dimensions as the refractometer Indicating transmitter enclosure. The control unit includes:
�� an operator panel �� control logics �� contact outputs for prism wash, warnings, alarms and black liquor diversion �� Two isolation valves HIMP-2 (optional) for the refractometers above to allow removal of
the refractometers from a pipe with full flow and pressure. The isolation valve includes a prism wash nozzle and two check valves (one for prism wash, one for stuffing box flush).
�� A roofed mounting plate to mount the two Indicating transmitters and the Divert Control Unit together.
�� Two steam valves with steam traps for prism wash (pneumatic + solenoid valves). �� Two hand valves (one for prism wash, one for stuffing box flush). �� One alarm horn (supplied by the customer).
Note. BLRBAC (The Black Liquor Recovery Boiler Advisory Committee) recommends a spare sensor to be maintained in stock on-site.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 4: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/4.jpg)
3
2.2. OPERATOR PANEL
37
65
4
Figure 2.20 The operator panel.
The operator panel has a clear layout and the operator can see all information at one glance. The divert deci-sion is controlled from the operator panel which provides doubled security, since all information is simultane-ously shown both as LED indication in the Divert Control Unit and as a diagnostic messages in the Indicating Transmitters (Figure 2.20).
Each refractometer has a green OPERATING light (1), so the operator knows when he can rely on the refrac-tometer measurement. A refractometer will influence the divert decision only when the green OPERATING light is on. A malfunctioning refractometer is automatically taken out of operation. One green indicator light SAFE% SOLIDS (2) is based on the two refractometers and the divert decision rules (Section 5.7).
One red DIVERT light (3) that will be switched on when the SAFE% SOLIDS goes off. The DIVERT light indicates divert status of the divert relay. The divert relay has an output switch contact, for use in the Black Liquor Firing Tripping Logic. The relay is OFF in the DIVERT position, because a power failure will give a DIVERT decision.
A lockable OVERRIDE/AUTOMATIC switch (5) and a red OVERRIDE warning light (4) is ON always if switch in OVERRIDE position. If the SAFE% SOLIDS goes OFF and this switch is in the OVERRIDE posi-tion, then the OVERRIDE light is lit instead of the DIVERT light. One RESET push-button (6) for the DIVERT action. The DIVERT action always has to be manually reset. If the override switch is in Automatic position and SAFE% SOLIDS is off, the DIVERT action cannot be reset.
One EMERGENCY DIVERT push-button (7) to manually initiate DIVERT in an OVERRIDE or emergency situation. The DIVERT light is lit also after manual divert action. The EMERGENCY DIVERT button has a protective hinged cover, to prevent inadvertent use.
Two indicator lights (8) for the divert valve status TO BY-PASS/TO BURNER from microswitches on the valve. For intermediate valve positions both lights are off.
A row of four alarm lights (9) that indicate black liquor SOLIDS WARNING (at 60%), black liquor SOLIDS ALARM (below 58%), refractometer reading more than 2% absolute difference and refractometer malfunc-tion.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 5: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/5.jpg)
4
A light test button (10) switches all 11 lights on. An alarm reset button (11) resets the alarm lights. For normal operation the operator panel has four green lights on (A OPERATING/B OPERATING/ VALVE TO BURNER/SAFE% SOLIDS).
2.3. ALARMS
The divert control system has four alarms, audible and indicating:
1. Black liquor SOLIDS WARNING, yellow light (60% or below) 2. Black liquor SOLIDS ALARM, red light (58% or below) 3. Refractometers reading more than 2% absolute DIFFERENCE, yellow light 4. Refractometer MALFUNCTION, yellow light
The alarms 1, 2 and 4 are initiated by either refractometer. System contains also optional alarms, see wiring drawing 3.11.
The operator panel contains four indicator lights and an ALARM RESET button. The reset button will silence the audible alarm, but the visual indication will remain until the condition has returned to normal.
To avoid unnecessary alarms the following interlocks are implemented:
- A refractometer can initiate an alarm only when it is operating. - Alarm 4 can be initiated only if both refractometers are operating.
The parameters (2%, 58% and 60%) are default settings, which can be changed from the Indicating transmitter keyboard (Sections 5.3 and 5.4). The parameter for 2% can be decreased and the parameter for 58% and 60% can be increased.
2.4. PRISM WASH
For K-Patents Process Refractometer, the need of prism wash is reduced and even in some cases eliminated. The prism keeps clean due to the probe design features:
- The prism is flush mounted in a surface deflecting the black liquor main flow, which causes a strong mechanical cleaning action.
- The prism has the same temperature as the black liquor.
In any case, however, an automatic regular prism wash provides an efficient check that the refractometer re-acts. A steam wash of 3 seconds every half hour should be sufficient. Automatic single (one-of-two) diversion will occur if either of the refractometers is in wash cycle.
The Divert Control Unit contains two relays for prism wash, WASH A and WASH B. To follow the BLRBAC recommendation not to wash both prisms at the same time, there is an interlock. If both refractometers try to wash simultaneously, one will display "WAIT" and perform the wash when the other has finished.
K-Patents recommends to use a steam trap instead of preconditioning valve to remove condensate from the steam line. The wash times can be seen pressing soft keys "Display"/"System configuration"/"Wash times". To change the wash times, see Section 5.6.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 6: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/6.jpg)
5
2.5. MASTER DIVERT CONTROL UNIT
Figure 2.50 Operator’s panel and functions of the master divert control unit in the field with LED indications.
1. Black liquor SOLIDS WARNING (at 60%), Black liquor SOLIDS ALARM (be-low 58%), Refractometer reading more than 2% absolute difference, and Refractometer malfunction).
2. Each refractometer A and B has an OPERATING green light, A refractometer will influence the divert decision only when the green OPERATING light is on. A mal-functioning refractometer is automatically taken out of operation.
3. One green indicator light SAFE% SOLIDS, based on the two refractometers and the divert decision rules.
4. A red OVERRIDE warning light is on always if the override switch is switched on.
5. One red DIVERT light that will be switched on when the SAFE% SOLIDS goes off. The DIVERT light indicates divert status of the divert relay.
6. Two indicator lights for the divert valve status. TO BY-PASS/TO BURNER from microswitches on the valve. For intermedi-ate valve positions both lights are off.
7. A lockable Override/Automatic divert switch
8. A DIVERT RESET push-button.
9. An EMERGENCY DIVERT push-button.
10. A light test button switches all 11 lights on.
11. An alarm reset button resets the alarm lights.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 7: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/7.jpg)
6
2.6. INDICATING TRANSMITTERS
An Indicating transmitter in a Divert Control System is identical (both hardware and software) to a standard transmitter described in the PR-01-S Instruction manual.
A B C D
1 2 3
4 5 6
7 8 9
0 . - E N T E R R E S E T
P R O C E S S T E M P E R A T U R E22.1 ° C
AC O N C
T E S T 109.3In d iv e r t c o n tr o l o p e r a tio nS ta r tp r is mw a s h
R e m o v e dfr o m d ivc o n tr o l
C a lib r a te D is p la y
P R O C E S S IN S T R U M E N T SK -PT E N T S
4
52
3
1
Figure 2.60 The Indicating transmitter.
The display, Figure 2.60, will give the following additional information pertinent to the Divert system:
1. A or B in the upper right corner indicates that the transmitter is OPERATING in the divert system as re-fractometer A or B, Figure 2.10. If a or b is displayed instead, the refractometer is removed from divert con-trol operation. (If the upper right corner is empty, see Section 5.2). For A or B the corresponding green OPERATING light, Figure 2.20, is on, for a or b it is off. If you see a ? in this corner, see Section 5.2.
2. A softkey (B) defined by "Remove from divert control" or alternatively "Restore to divert control". The visible effects of pressing "Remove" for refractometer A is that the soft key changes to "Restore", A switches to a, and the green OPERATING light goes off. Further the "Remove" soft key disappears from refractometer B, because B must not be removed if it is the only refrac-tometer in operation.
Note. Always press "Remove" for a refractometer be-fore making service or switching the power off.
3. The "Normal operation" message is substituted by "In divert control operation" or "Removed from di-vert control". Those messages may change to "Sol-ids warning" or "Solids alarm" at low solids. An ad-ditional error message may occur: ** Divert control fault ** combined with a ? in the upper right corner, see Section 6.3.
4. The softkey "Display" (D) leads via "System con-figuration" (C) to "Divert control system" (D) which gives the following information:
Refractometer difference alarm limit in % solids Solids warning limit in % solids (default
value 60%) solids alarm limit in % solids (default value 58%) Divert rule and SW1/SW2 positions (Section 5.7)
5. The softkey "Calibrate" (C) gives possibilities to set up for divert control and calibration, see Chapter 5.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 8: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/8.jpg)
7
2.7. K-PATENTS DIGITAL DIVERT CONTROL UNIT SPECIFICATIONS
Model: DD-01
Enclosure: IP66 Nema 4X, dimensions 226 x 267 mm (8.91 x 10.5 in)
Supply: 24 V DC, provided by the Indicating transmitters
Ambient temperature: max 45 °C (113 °F)
Accessory: Roofed mounting plate for the Divert Control Unit and 2 Indicating transmitters, Figure 2.60.
Material: AISI 316, dimensions 916 x 488 mm (36 x 19.2 in)
Figure 2.70 Divert Control Unit Mounting Plate: Dimensions (mm/in)
Figure 2.71 Divert Control Unit and Indicating Transmitter Enclosures: Dimensions (mm/in)
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 9: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/9.jpg)
8
3. MOUNTING
For mounting of the process refractometer and the isolation valve, consult the separate Refractometer PR-01-S(-EX/FM) Manual.
3.1. WIRING
Wiring for the complete system, see Figure 3.10 and Figure 3.11 which describe also all cables and how each cable is connected.
The cables 1 and 2 are included in the delivery. The terminal strip positions of the Divert Control Unit are specified in Figure 3.11 and Figure 3.12.
Figure 3.10 Divert Control System Wiring Cables and Connections
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 10: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/10.jpg)
9
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Figure 3.11 Divert Control System Wiring and Connections
Effective: June 20, 2005
![Page 11: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/11.jpg)
10
Figure 3.12 Cable connections
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 12: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/12.jpg)
11
F1
F3 F4
X1
F2
D10 D12
D26D25D24D23D22D21D20D19
D13D11
D3
D4
D27 D28
IC8
D17
D16
D29
D31
D32
D30
D7
D9
D1
IC30
IC26
IC29
IC24
K4
IC25
TP4
D5
D15
D8
L1
IC27
IC28
RE1 RE8RE7RE6RE5RE4RE3RE2
IC2
IC16
IC13
IC22
IC12
IC23
K11K10
J1
TP1
V6
V5 V9
V8
V7
V4
V3
V2
V1
1
IC15 IC17
IC19
IC6
IC1
TP2
IC14
IC20
IC21
IC11
IC10
IC3
IC7
D6
C27
C30
R10
SW1
IC18
X2
C44
C52
C48
C43
C45R16
R8
R1
R2
R3
R4
R5
R6
R7
R26
R27R25
R28
R13R12
R11
R24R23R22R21R20R19R18R17
R15
R14
R9
C8
C26
C23
C24
C22
C25
C40
C50C51
C41
C42
C7
C12
C28
C6
C9
C5
C4
C3
C2
C1
C17
C16
C15
C37
C38
C13
C39
C31 C33C35
C36C34
C32
C18
C49
C47
C46
C29
C19
C20
C14
C21
C11C10
RN6
RN4
RN5
RN2
RN3
RN1
RN7
IC9
IC5IC4 J2
K12K9
D14
K8 K13
K3
K7K6K5 K14
K1 K2
D2
TP3
D18
DIVERT CONTROL UNIT
DANGER HIGH VOLTAGE
K-PATENTS PR-7310 Rev.C
37 403938363534333231302928
AC-POWER
27191817 26252423222120
1615
87654321SW
NL
14 1413 1312 1211 1110 109 98 8
SWGND
SGND
+5V
GND
OVERRIDEALARMSOLIDS
WARN.SOLIDS
REF.DIFF.NORM.
DIVERT
POSITIONVALVE
B
63mA 63mA
1A
1A
EXT24VSERIAL BUS BSERIAL BUS A
BURNERBYPASSHORNWASH WASH
A
Figure 3.13 Divert control circuit board, layout.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 13: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/13.jpg)
12
4. START-UP
For refractometer start-up consult the separate Refractometer PR-01-S(-EX/FM) Manual and the Mounting and start-up check list.
4.1. DIVERT CONTROL UNIT START-UP
1. Check the wiring and supply voltage. Note: Before the power is switched on, the DIVERT output relay is in DIVERT position.
2. Switch the power on for both Indicating transmitters. The control system is now in the DIVERT mode, and the red DIVERT light is on.
3. Press the LIGHT TEST button. All eleven lights should switch on.
4. The upper right corner of the Indicating transmitter displays should now state a or b respectively. If not, see Section 5.2.
If the message is "Removed from divert control" the refractometer is ready to "Restore to divert control", softkey B.
If the message is "Solids warning" or "Solids alarm" then "Restore" provokes an alarm. Press the ALARM RESET button.
For any other message, see Section 6.3.
5. Observe that the VALVE STATUS lights follow the position of the valve.
Now the Divert Control System is set for normal monitoring operation.
6. Check that the prism wash is working. Press the "Start prism wash", softkey A.
7. When the SAFE % SOLIDS has turned on and also the other conditions for safe boiler operation are satisfied, the DIVERT can be turned off using the RESET button.
4.2. DIVERT CONTROL SYSTEM TRIMMING
During the trimming of a new system, it is recommended to keep the key in the OVERRIDE position.
When the key is in the OVERRIDE position, the DIVERT action has to be initiated manually using the EMERGENCY DIVERT button. This should be done when the green SAFE %SOLIDS light turns off.
The trim procedures are described in Chapter 5, the measurement calibration in Section 5.1 and the prism wash in Section 5.6.
The key should be turned to the AUTOMATIC position only after it has been decided that sufficient experi-ence has been gained.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 14: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/14.jpg)
13
5. CALIBRATION
The K-Patents Divert Control System is calibrated by the manufacturer. This chapter contains instructions how to make the fine adjustment of the system.
5.1. REFRACTOMETER CONCENTRATION MEASUREMENT
For refractometer calibration consult also the separate Refractometer PR-01-S(-EX/FM) Manual.
The CONC% displays of the two Indicating transmitters have to show the same value. If there is a difference, this can be eliminated by changing the Bias for one of the refractometers. Key in the sequence Calibrate / Pa-rameters / CONC(RI) / Parameters / Bias. Comparison with sample determination can decide which one should be corrected.
Example: If the Indicating transmitter of A displays CONC% = 63.2% and B displays CONC% = 63.8%, the difference can be eliminated e.g. by lowering B by 0.6%. Read bias from the display of refractometer B. If bias = 52.923 then enter a new bias = 52.323.
Due to its digital measurement principle, the readings of the K-Patents Process Refractometer do not drift by time. Frequent recalibrations based on off-line moisture analysis must be avoided, as they will introduce ran-dom fluctuations to the refractometer readings.
If the concentration reading is noisy, the damping can be increased. Enter Calibrate / Parameters / CONC(RI) / Damping time. The Damping time is the time in seconds for the signal to reach half of its final value after a step change. Increase the damping time in small steps, and wait for the result.
5.2. REFRACTOMETER ACTIVATION FOR DIVERT CONTROL
When a refractometer is activated for Divert control, the upper right corner of the display shows alternatively A, a, B, b or ?. If the corner is blank the divert function must be activated by pressing the sequence Cali-brate/Parameters/Divert control/Divert control and select "1 Activated".
The program has to be version 4.0 or higher, otherwise "8 Divert control" is missing from the CALIBRATE menu. The program EPROM has then to be changed to an up-dated version.
The decision to display A (a) or alternatively B (b) is not programmed, it depends on to which SERIAL BUS port in the Divert unit (Figure 3.13) the Indicating transmitter is connected.
If a Divert activated refractometer is used in another type of application, the divert function has to be deacti-vated by selecting "0 Not activated". After de-activation all references to Divert functions disappear except "8 Divert control" in the CALIBRATE menu.
Note. If a message DIVERT CONTROL FAULT and a ? appear on the IT-R display, the reason is one of the following:
1. Cables between the IT-R and the terminals 8-14 on the DD-01 are not properly connected. Re-connect to fix.
2. Communication 485 component IC 17 (A) or IC 19 C (B) is broken on the PR-7310 board inside the DD-01. Replace board.
3. Communication 485 component IC 1r is broken on the PR-7010 board inside the IT-R. Replace board.
4. Dip switch 3. is in the “up” position which means that the PR-7310 card is configured to work in the remote mode. Change the dip switch back to low (=off) position.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 15: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/15.jpg)
14
5.3. SIGNAL DIFFERENCE ALARM
According to BLRBAC, if a difference of 2% solids (absolute value) or greater exists between refractometer readings, an alarm shall be activated.
The alarm limit 2% can be changed from the keyboard using the sequence Calibrate/Parameters/Divert con-trol/Ref. difference limit. If the deviation alarm trips seem too frequent, it may help to increase the signal damping, Section 5.1.
Note. If the two refractometers have different limit values, the lower value is used by alarm system.
5.4. LOW ALARMS
The low alarm limits are set from the keyboard of the Indicating transmitter. Enter sequence Cali-brate/Parameters/Divert control. The menu will show “3 Low conc warning limit” and “4 Low conc divert limit”. The latter has a double function: Both LOW SOLIDS ALARM and DIVERT limit.
The Indicating transmitter display will carry the messages “Solids warning” and “Solids alarm” when the cor-responding alarms occur.
Note. The alarm limits are set separately for the two refractometers. Each refractometer gives an alarm accord-ing to its own settings.
5.5. REFRACTOMETER MALFUNCTION ALARM
The built-in intelligent diagnostics of K-Patents Process Refractometer provides a tight control of the opera-tion. A full test cycle is completed with an interval less than one second. A description of the microprocessor implemented diagnostics is given below. For details consult the Instruction Manual of the refractometer PR-01-S. Only errors classified as Equipment malfunctions will cause alarm and removal from the Divert con-trol system. Process related faults will only cause a message in the Indicating transmitter display. See also Section 6.3 for additional diagnostics.
The most important test is to check the signal coming from the digital image sensor during measurement. Im-proper function of light source, optical components, image sensor and sensor driver are recognized by this test.
The compensation for temperature measurement is checked, both the temperature element and the A/D con-verter.
The cable between Sensor and Indicating transmitter is checked using a check sum method, thus recognizing short circuits, open circuits and excessive disturbances.
The microprocessor system has also a self-checking test program to ensure the proper operation of the CPU and the memories. The constants in the EEPROM memory are tested to be within strict limits of acceptance.
The performance of the microprocessor is of critical importance for the measurement control. A separate hardware watch-dog circuit ensures the proper microprocessor operation by checking that the microprocessor regularly sends out a predetermined pulse sequence. Another hardware circuit checks that the supply voltage to the microprocessor is within safe limits, to prevent any brownout stray output pulses.
5.6. PRISM WASH
A prerequisite for a proper function of the divert system, is that the prism wash works. The TEST value in the display should increase at least 20 steps during WASH, provided TEST is not close to its maximum value 248. See Sections 8.1, 8.5 and 9.2 in PR-01-S Instruction Manual.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 16: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/16.jpg)
15
WASH TIMES
The wash times can be seen by pressing Display/System configuration/Wash times. The values set at delivery are the following:
Preconditioning = 0 seconds Wash time = 3 seconds Recovery time = 30 seconds Interval = 20 min
The wash times are changed by pressing the sequence Calibrate/Parameters/Prism wash. Note maximum wash time is 30 seconds and maximum recovery time 30 seconds.
WASH CHECK
This function can be defined from the prism wash menu: Calibrate/Parameters/Prism wash/Wash test. A prism wash is accepted if:
a. TEST exceeds “TEST limit”
b. TEST increases more than “TEST difference”
The default values of “TEST limit” and “TEST difference” are zero (0), which makes the wash check inactive.
If the wash is not accepted, the diagnostic message will be “Prism wash failure”.
A “Wash retries” parameter can also be set to repeat the wash if the wash check fails. The default value is zero (0).
WASH STOP
Wash stop function can be defined from the prism wash menu. Wash can be prevented when the process tem-perature is below the set limit, thus indicating that the pipe is not in use. To activate the “wash stop” key se-quence: Calibrate/Parameters/1. Prism wash/Wash stop/1. Active and set the temperature limit.
The default value for wash stop is inactivate. When the wash is not accepted the diagnostics message is “Wash stop/temp. limit”.
EXTERNAL WASH STOP
An input switch can be configurated to an external wash stop to prevent the prism wash when the correspond-ing input switch is connected. “External wash stop”-message will show when automatic wash is activated from the soft keys. The input switch can be set to protect the refractometer e.g. if the process is stopped.
AUTOMATIC SINGLE DIVERSION CONTROL DURING PRISM WASH CYCLE
Automatic single (one-of-two) diversion control will take place if either of sensors are in prism WASH cycle.
5.7. DIVERT DECISION RULES
TWO REFRACTOMETERS IN OPERATION:
BLRBAC states the following: For the solids measurements, two refractometers in series must be used. When both refractometers are in service, the requirement for an automatic black liquor diversion can be satisfied by either of the following options:
1. If either refractometer reads dissolved solids content 58% (default) or below, an automatic black liquor diversion must take place.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 17: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/17.jpg)
16
2. When both refractometers read dissolved solids content 58% (default) or below, an auto-matic black liquor diversion must take place.
Either option is satisfactory.
The rules are listed in decreasing order of security. Only rule 1 satisfies the high safety requirements set by BLRBAC, August, 1982. On the other hand, the probability of false trips decreases with decreasing safety. It means that if false trips are too frequent, the rule 2 may be preferred at the cost of safety. The rule 2 has later been accepted by BLRBAC.
A third conceivable alternative is to base the decision on only one refractometer (the master) and use the other refractometer (the slave) for comparison only (and difference alarm). Concerning security and false trips, this rule is a compromise between rules 1 and 2.
The divert decision rule is selected by the switch SW on the divert control board (Figure 3.13). ON position is upwards.
Switch SW SW1 SW2
Rule
OFF OFF One-of-two (BLRBAC) Rule 1 ON OFF A master, B slave - OFF ON B master, A slave - ON ON Two-of-Two Rule 2
Table 5.70 Divert decision rule selection.
ONLY ONE REFRACTOMETER IN OPERATION:
When only one instrument is IN OPERATION the divert action takes place if this instrument reads 58 % or below. The status of SW (Table 5.70) has no influence on the divert decision in this case.
NO REFRACTOMETER IN OPERATION:
If both instruments are out of operation (due to malfunction or maintenance), then according to BLRBAC divert action must take place. See also Section 8.7 about external DC supply.
REMOTE DIVERT SWITCH CONFIGURATION
Switch SW Rule SW 3 OFF DD-01 normal operation ON Remote divert card activated
See Section 8.8.
See Section 5.2 if you have on the screen the message DIVERT CONTROL FAULT.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 18: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/18.jpg)
17
6. MAINTENANCE
As the Divert Control System is a pure digital system, no special maintenance is needed. The LIGHT TEST button on the operator panel (Figure 2.50) sends a signal to the microprocessor, and the microprocessor switches all 11 LED lights on as long as the button is pressed. This way not only the lights but also the proc-essing system is checked.
To assist the identification of a faulty component, the information flow and the circuit diagrams are given in Sections 6.1 and 6.2. Also the logic diagrams of Chapter 7 may be of help.
6.1. INFORMATION FLOW
The power and information flow of the total Divert system is shown by Figure 6.10. Additional information about the cable connections is found in Figures 3.10, 3.11 and 3.12.
Figure 6.10 Information and power flow.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 19: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/19.jpg)
18
6.2. DIVERT CONTROL CIRCUIT BOARDS
The component lay-out of the divert control circuit board is shown by Figure 3.12 and the circuit diagram by Figures 6.20 to 6.25.
Figure 6.20 Operator panel board, component layout.
Figure 6.21 Operator panel PR-7311 circuit diagram, page 2 of 2
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 20: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/20.jpg)
19
Figure 6.22 Operator panel PR-7311 circuit diagram, page 1 of 2.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 21: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/21.jpg)
20
A14
A13
A12
A11
A10
A9
A8
A7
A6
A5
A4
A3
A2
A1
A0
IO8
IO7
IO6
IO5
IO4
IO3
IO2
IO1
WCE
OE 5525732K x 8bit SRAM
IC4
1 2 3 4 5 6 7 8 9 10
11
12
13
15
16
17
18
19
20
21
22
23
24
25
26
27
A14
A13
A12
A11
A10
A9
A8
A7
A6
A5
A4
A3
A2
A1
A0
IO8
IO7
IO6
IO5
IO4
IO3
IO2
IO1
WCE
OE 5525732K x 8bit SRAM
IC5
1 2 3 4 5 6 7 8 9 10
11
12
13
15
16
17
18
19
20
21
22
23
24
25
26
27
8Q
7Q
6Q
5Q
4Q
3Q
2Q
1Q
8D
7D
6D
5D
4D
3D
2D
1D
COC
74HC573
IC3
1 2 3 4 5 6 7 8 911
12
13
14
15
16
17
18
19
8Q
7Q
6Q
5Q
4Q
3Q
2Q
1Q
8D
7D
6D
5D
4D
3D
2D
1D
COC
74HC573
IC7
1 2 3 4 5 6 7 8 911
12
13
14
15
16
17
18
19
100n
1 2
C25
100n
1 2
C14
1 2100n
C26
100n
1 2
C9
100n
1 2
C13
100n
1 2
C18
100n
C10
100n
1 2
C11
8Q
7Q
6Q
5Q
4Q
3Q
2Q
1Q
8D
7D
6D
5D
4D
3D
2D
1D
COC
74HC573
IC10
1 2 3 4 5 6 7 8 911
12
13
14
15
16
17
18
19
1HC32
IC2
9 10
8
1HC32
IC2
4 56
100n
1 2
C8
1HC32
IC2
12
13
11
100n
1 2
C22
MAX699
GNDRESET
WDI
VCCIC18
1 2
34
67
8
CTS0
TXD0
RXD0
P1.7
P1.6
P1.5
P1.4
P1.3
P1.2
P1.1
P1.0
T0IN
T1IN
T0OUT
T1OUT
INT4
INT1
INT0
INT3
INT2
P2.7
P2.6
P2.0
P2.4
P2.5
P2.2
P2.1
P2.3
UCS
LCS
PEREQ
ERROR
ALE
BHE
RD
WR
READY
DEN
DT
LOCK
HOLD
HOLDA
NCS
S0
S1
S2
RESIN
RESOUT
PDTMR
NMI
TEST
AD0
AD1
AD2
AD3
AD4
AD5
AD6
AD7
AD8
AD9
AD10
AD11
AD12
AD13
AD14
AD15
A16
A17
A18
A19
CLOCKOUT
CLKIN
OSCOUT
80C186EB
16bit MICROPROCESSOR
IC15
3
4 56 78 9 10
11
12
13
14
1516
17
18
1920212425262728
2930
31
32
33
34
35
36
37
38
39
40
41
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
66
67
68
69
70
71
72
73
74
75
76
77
78
7980818283
10K0
RN5
15
RN5
13
10K0RN11 2
RN5
18
RN5
14
RN4
15
10K0
RN4
1410K0
RN5
12
RN5
16
RN4
13
RN4
16
RN5
17
RN5
19
10R0R8
12
3K32R7
12
100n
1 2
C24
100n
1 2
C23
O8O9
O10
O11
O12
O13
O14
O15
PGM
VPP
NC
OECE
A15
A14
A13
A12
A11
A10
A9A8A7A6A5A4A3A2A1A0
O7O6O5O4O3O2O1O0
64K x 16bit EPROM
27C210
IC8
1 2
3 4 5 6 7 8 9 10
12
13
14
15
16
17
18
19
20
2122232425262728293132333435363738
39
OUT
VCC
N.C.
GND
Osc.
32.0MHz
X1
1 78
14
RD
WR
RESET
AD11
AD11
AD11
AD11
AD10
AD10
AD10
AD10
AD8
AD8
AD8
AD8
AD5
AD5
AD5
AD5
AD2
AD2
AD2
AD2
AD1
AD1
AD1
AD1
AD0
AD0
AD0
AD0
A13
A13
A13
A13
AD4
AD4
AD4
AD4
A18
A18
AD12
AD12
AD12
AD12
A17
A17
AD7
AD7
AD7
AD7
A9
A9
A9
A9
A8
A8
A8
A8
A7
A7
A7
A7
A6
A6
A6
A6
A5
A5
A5
A5
A4
A4
A4
A4
A3
A3
A3
A3
A2
A2
A2
A2
A1
A1
A1
A1
A0
A0
A15
A15
A15
A15
SDISP
AD13
AD13
AD13
AD13
A16
A16
AD3
AD3
AD3
AD3
A14
A14
A14
A14
AD6
AD6
AD6
AD6
AD14
AD14
AD14
AD14
AD9
AD9
AD9
AD9
AD15
AD15
AD15
AD15
A11
A11
A11
A11
A10
A10
A10
A10
A12
A12
A12
A12
RXD0
RESOUT
SRLY
ISOSW
ISOSW
SSER2
SSER2
TXD0
AD16
AD16
RXD1
TXD1
INT1
AD17
AD17
AD18
AD18
+5V
+5V
+5V
+5V
+5V
+5V
+5V
+5V
+5V
+5V
+5V
+5V
+5V
+5V
AD19
AD19
AD0-15
A0-9
14
28
14
28
30
11
14
7
84
65
63
43
22
64
42
23
21
40
10
10
10
20
20
20
VSS
VCC
Figure 6.23 Divert control board PR-7310 circuit diagram. Page 1 of 3.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 22: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/22.jpg)
21
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
&EN
A5
A3A4
A6A7A8
Y1Y2Y3Y4Y5Y6Y7Y8
A1A2
G1G2
HC541
1817161514131211
1 19 2 3 4 5 6 7 8 9
IC1
100n
1 2
C35
100n
1 2
C33
100n
1 2
C36
1+
1-
2-
2+
VO1
VO2
GND
VCC
Opto-isol.
HCPL2731
1 2 3 4
7 6 58IC29
100n
1 2
C38
1+
1-
2-
2+
VO1
VO2
GND
VCC
Opto-isol.
HCPL2731
IC24
1 2 3 4
7 6 58
1
23K3
R28 3K32
RN11 2
VCC
RD
WR
CS
RESET
DTR
RTS
X1
X2
TXD
INT
RXD
RI
CTS
DSR
DCD
VSS
D0
D1
D2
D3
D4
D5
D6
D7
A0
A1
A2
82510IC9
25262728 1 2 3 4 222324
20191817
1516
9 8 6 5 1310141112
721
RN11 3
RN11 6
VCC
GND
VOUT
0V
conv.
DC/DC
NME0505D
IC27
145 7
RN61 21K0
RN61 4
1+1-
2-2+
VO1
VO2
GND
VCC
Opto-isol.
HCPL2731
IC26
1 2 3 4
7 6 58
100u
1 2
C52
RN71 2
RN61 5RN61 3
RN71 3
33pF
1 2
C16
TP31 2
100n
1 2
C17
100n
1 2
C32
VCC
GND
VOUT
0V
conv.
DC/DC
NME0505D
145 7
IC28
1K0
RN71 4
100n
1 2
C34
100n
1 2
C42
12
500RR27
100n
1 2
C41
100n
1 2C6
100n
1 2
C37
D10
12
10R01 2R11
1HC32
IC2
1 23
D4
12
12D12
D3
12
SA5.0
1 2
D9
RO
RE
DE
DI
VCC
DO
DO
GND
LTC485
IC19
1 2 3 45678
100n
1 2
C39
J2
4
J2
1
R 1D
C1
HC2731Q
2Q
3Q
4Q
5Q
6Q
7Q
8Q
1D
2D
3D
4D
5D
6D
7D
8D
CLR
CPIC20
9 126 155 162 19
1 11 8 13 7 14 4 17 3 18
RN71 5
SA5.0
1 2
D5
RO
RE
DE
DI
VCC
DO
DO
GND
LTC485
IC17
1 2 3 45678
SA5.0
1 2
D8
SA5.0
1 2
D7
SA5.0
D6
1 2
K1A
2
K1A
1
RN21 9
3K32RN21 2
RN21 3
RN21 6
RN21 8
RN21 7
RN21 5
RN21 4
100n
C28
1 2
J146
J144
J140
J114
J112
J110
100n
1 2C1
100n
1 2C2
100n
1 2C3
12
R6
100n
1 2C4
12
R5
100n
1 2C5
12
R4
12
R3
K2A
2
K2A
1
J2
6
J2
2
J2
3
J2
5
12
R2
100R 1
2R1
100n
1 2
C31
X142
X132
X141
X131
1 2TP4
SA5.0
1 2D29
100n
1 2
C40
100n1
2
C50
12
D28
12
D27
SA5.0
1 2D30
100n
1 2
C51
12 1KR13
12
1KR12
RN11 7
100n
1 2
C12
&EN
A5
A3A4
A6A7A8
Y1Y2Y3Y4Y5Y6Y7Y8
A1A2
G1G2
HC541
IC6
1817161514131211
1 19 2 3 4 5 6 7 8 9
RN11 5
12
500RR26
1
23K3
R25
RN11 4
18.432MHz
X2
12
RR
T T
POWER
OFF
VCC
GND
+9V
-9V
C1+
C1-
C2+
C2-
LT1180
IC25
23
4 5 6
7 8910
11
12
13
14
15
16
17
18
K2A
3100n
1 2
C30
RN31 5
1k00RN31 3
RN31 2
1k00
RN31 4
100n
1 2
C27
SW8
SW1
1 2 3 4 5 6 7 8910
11
12
13
14
15
16
11
74HC05
IC23 1
213
11
74HC05
IC23
10
11
11
74HC05
IC23
89
11
74HC05
IC23
65
11
74HC05
IC23
43
K1A
3
1N4007
12D31
1N4007 12
D32
12
F3
12
F4
11
74HC05
IC23
21
33pF
1 2
C15
100n
1 2
C7
INT1
SGND
SGND
SER1+
TXD1
RTS
RTS
SER0-
KN2
KN2
A1
AD7
AD7
AD7
AD6
AD6
AD6
AD5
AD5
AD5
AD2
AD2
AD2
A2
KN1
KN1
ISOSW
RXD0
5VSER
AD1
AD1
AD1
WR
WR
DIP1
CTSI
DIP2
DIP3
DIP4
DIP5
AD4
AD4
AD4
DIP6
DIP7
RXD
RD
DIP8
SD
RXDI
TXDI
UARTS
UACTS
AD15
AD14
AD13
AD12
AD11
RTSI
TXD
AD10
KN6
KN6
KN5
KN5
RESET
KN4
KN4
KN3
KN3
AD9
TXD0
SER0+
AD8
SWGND
SER1-
CTS
+5V
+5V
+5V
+5V
+5V
+5V
+5V
+5V
+5V
+5V
+5V
+5V
BURNER
BYPASS
AD0
AD0
AD0
AD3
AD3
AD3
A3
RD
RD
SSER2
RESOUT
A1-3
AD0-15
EMERGENCY DIVERT
DIVERT RESET
OVERRIDE
ALARM RESET
LAMP TEST
BA
AD0-18
TEST POINT
TEST POINT
(10)
(10)
(8)
(8)
(9)
(9)
2010
7
14
2010
2010
Figure 6.24 Divert control board PR-7310 circuit diagram. Page 2 of 3.
Effective: June 20, 2005
![Page 23: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/23.jpg)
22
HC2731Q2Q3Q4Q5Q6Q7Q8Q
1D2D3D4D5D6D7D8D
CLR
CPIC11
2 5 6 9 12151619
1 11 3 4 7 8 13
14
17
18
1HC32
IC16
4 56
HC2731Q2Q3Q4Q5Q6Q7Q8Q
1D2D3D4D5D6D7D8D
CLR
CPIC21
2 5 6 9 12151619
1 11 3 4 7 8 13
14
17
18
+
. .
100u
1 2
C48
+
. .
2u2
1 2
C43
OSC
FB
VOUT
GND
VIN
SS
FRC
L4962
7
15
11
4 5121310
2
14IC30
4K64
1 2R14.
.
150uH
12
L1
. .
33n
1 2
C47
. .
2n2
1 2
C46
+
. .
220u
1 2
C44
K4
2
. .
BYV27/50
1 2
D2
+
. .
220u
1 2
C45
12
D23
.. 1A
12
F1
1 2
D1
.
.
1N4007
12
D16
K4
3
K4
1
K5
2
K5
1
.. 12
V1
RE2
K6
1
Q0
Q1
Q2
Q3
Q4
Q5
Q6
Q7
D7D6D5D4D3D2D1D0
GND
DCOM
ULN2803A
IC22
1 2 3 4 5 6 7 81112131415161718
10 9
12
D20
12
D26
K6
2
.. 12
V2
RE1
K7
1
K7
2
.. 12
V3
.. 12
V4
RE4
K8
1
K8
2
RE3
K10
2
.
.
1N4007
12
D18
K10
1
TP1
12
TP2
12
12 D14
4K7 12 R10
K2C2
K1C2
RE5
K2C1
K1C1
K2B2
4K7
12 R1712
D21
.. 12
V7
4K7
12 R22
K11
1
K11
2
.. 12
V8
12
D22
K12
1
K12
2
..
V9
.. 12
V5
12 D11
4K7
12 R23
12 D13
K9
1K9
3
..
12
V6
4K7
12 R24
..
1A
12
F2
4K7
12
R16
4K7
12
R9
12
D19
4K7
12 R18
. .
100n
1 2
C21
RE6RE7
1HC32
IC16
12
13
11
4K7
12 R19
RE8
12
D25
1HC32
IC16
9 10
8
4K7
12 R20
K9
2
12
D24
. .
100n
1 2
C20
15K0
1 2R15
. .
33nF
1 2
C49
. .
100n
1 2
C19
SA26
1 2
D15
.
.
1N4007
12
D17
K1B1
K3
1
K2B1
K3
2
J149
J147
K1B2
. .
100n
1 2
C29
4K7
12 R21
Q0
Q1
Q2
Q3
Q4
Q5
Q6
Q7
D7D6D5D4D3D2D1D0
GND
DCOM
ULN2803A
IC12
1 2 3 4 5 6 7 81112131415161718
109
HC2731Q2Q3Q4Q5Q6Q7Q8Q
1D2D3D4D5D6D7D8D
CLR
CPIC14
2 5 6 9 12151619
1 11 3 4 7 8 13
14
17
18
J1
30
J1
28
J1
32
J1
35
J1
37
J1
36
J1
38
J1
39
J1
25
J1
19
J1
21
J1
20
J1
22
J1
26
J1
27
J1
29
Q0
Q1
Q2
Q3
Q4
Q5
Q6
Q7
D7D6D5D4D3D2D1D0
GND
DCOM
ULN2803A
IC13
1 2 3 4 5 6 7 81112131415161718
10
9
1HC32
IC16
1 23
AD0
AD0
AD5
AD5
AD6
AD6
AD7
AD7
AD1
AD1
AD3
AD3
AD2
AD2
AD4
AD4
DIVERT
VBYPASS
SRLY
WARN
BURNER
OUT4
OUT5
OUT6
OUT8
EXT24V
BOPER
SAFE
OVERRIDE
SR224V
ALARM
REFRDIF
MALFUNC
L N
AOPER
VIO24V
VIO24V
VIO24V
VIO24V
VIO24V
VIO24V
GND
GND
RE6
RE6
RE5
RE5
RE2
RE2
RE1
RE1
SR124V
RE3
RE3
RE4
RE4
RE8
RE8
RE7
RE7
SDISP
WR
OUT7
P
P
AD11
AD10
AD8
+5V
+5V
+5V
+5V
+5V
+5V
AD12
RESET
AD13
AD14
AD9
AD15
RE1-8
LINE
AD0-18
(16)
(15)
BABA
(14)
(14)
(13)
(13)
(12)
(12)
(11)
(11)
912
8 8 8 8 8 8 8 85 5 5 5 5 5 5 5
16
16
16
16
16
16
16
161 1 1 1 1 1 1 1
7
14
1020
1020
1020
SOLIDS WARN.
SOLIDS ALARM
DIVERT/NORM
REF. DIFF
NO MALF.
B WASH
A WASH
HORN
SA5.0TEST POINT
TEST POINT
Figure 6.25 Divert Control board PR-7310 circuit diagram. Page 3 of 3. INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 24: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/24.jpg)
23
6.3. DIAGNOSTIC MESSAGES
For diagnostic messages in the Indicating transmitter display, see the PR-01-S manual. The following mes-sages appear only in divert systems:
- "In divert control operation" or "Removed from divert control", Section 2.6.
- "Solids warning" and "Solids alarm", Section 5.4.
- ** Divert control fault **
This message indicates that there is no communication to the divert control unit, probably cable error, Figure 3.12, cable 2.
If the instrument is not applied in a divert control system, de-activate the divert function, see end of Section 5.2.
Further the message ** Relay unit fault ** may appear. This indicates that the Relay unit PR-7080 functions are defined, but no Relay unit is connected. Normally a Relay unit is not used in a Divert system because the wash contacts are in the Divert control unit. Clear the relay functions by the key sequence Calibrate/Relay unit and select an "0 Not Defined" for all four relays. For using an optional relay unit, see PR-01-S Manual, sec-tion 9.1.
6.4. DIAGNOSTIC LIGHTS
The Divert circuit board, Figure 3.12, contains the following diagnostic LEDS:
D3 Processor cycles: should flash
D4 Processor reads serial bus: should flash
D10 Serial bus A input: should flash
D11 On if 24 V DC supply from A is OK
D12 Serial bus B input: should flash
D13 On if 24 V DC supply from B is OK
D14 On if external 24 V DC is applied
D19 Wash relay A on
D20 Wash relay B on
D21 Solids warning relay on
D22 Solids alarm relay on
D23 Divert relay on = not DIVERT (Section 2.2)
D24 Horn on
D25 Refractometer difference relay on = difference alarm
D26 Override
D27 Valve to bypass
D28 Valve to burner
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 25: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/25.jpg)
24
6.5. PUSH-BUTTON ASSEMBLY
Before removing the push button or the lockable Override/Automatic switch from the front panel turn the screw 1/4 to the left, Figure 6.50. This will release the contact element.
Figure 6.50 Securing and removal of the contact element.
6.6. FUSES
The following fuses are printed on circuit board PR-7130:
Fuse F1: Microfuse IEC 127-3/1 DC Power (24 VDC) main fuse. Protects UL 198G 1A, fast divert electronics againts wrong voltages especially from exter-nal DC supply.
Fuse F2: 5 x 20 mm fuse IEC 60127, 1A, fast
AC supply to solenoid valves. Protects cable and coil, if faults appear.
Fuses F3, F4: Microfuse IEC 127-3/1, Fuses protect switch of divert valve position UL 198G 63 mA, fast feedback. Any external voltage connected to these circuits causes fuse blow.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 26: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/26.jpg)
25
7. DIVERT CONTROL LOGIC
A logical description of the system is provided as a complement to the previous information about the elec-tronics.
7.1. BLOCK DIAGRAM
The block diagram Figure 7.10 shows the connections between the different logical subsystems.
Figure 7.10 Block diagram of the divert control system
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 27: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/27.jpg)
26
7.2. LOGICAL DIAGRAMS
Figure 7.20 The operation logics.
Figure 7.21 The divert decision logics.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 28: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/28.jpg)
27
Figure 7.22 The alarm decision logics.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 29: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/29.jpg)
28
Figure 7.23 The alarm system.
7.3. SAFETY DECISION LOGICS
The logical description of the Safety Decision Logics in Figure 7.10 is given by the following tables:
- Table 7.30 One - of - two
- Table 7.31 A master, B slave
- Table 7.32 Two - of - two
Note. NOT OPERATING includes the wash cycle.
See also Section 5.7.
A
<58
OPERATING
NOT OP
>58
OPERATING
NOT OP
B
<58 OPERATING
NOT OP
Unsafe
Unsafe
Unsafe
Unsafe
Unsafe
Safe
Unsafe
Unsafe
>58 OPERATING
NOT OP
Unsafe Unsafe
Safe
Unsafe
Safe
Safe
Safe
Unsafe
Table 7.30 One-of-two decision rule
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 30: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/30.jpg)
29
A
<58
OPERATING
NOT OP
>58
OPERATING
NOT OP
B
<58 OPERATING
NOT OP
Unsafe
Unsafe
Unsafe
Unsafe
Safe
Safe
Unsafe
Unsafe
>58 OPERATING
NOT OP
Unsafe
Unsafe
Safe
Unsafe
Safe
Safe
Safe
Unsafe
Table 7.31 A master, B slave
A
<58
OPERATING
NOT OP
>58
OPERATING
NOT OP
B
<58 OPERATING
NOT OP
Unsafe
Unsafe
Unsafe
Unsafe
Safe
Safe
Unsafe
Unsafe
>58 OPERATING
NOT OP
Safe
Unsafe
Safe
Unsafe
Safe
Safe
Safe
Unsafe
Table 7.32 Two-of-two decision rule
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 31: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/31.jpg)
30
8. OPTIONAL CONFIGURATIONS
8.1. REMOTE DIVERT CONTROL UNIT
The remote divert control unit is an option of the digital divert control system DD-01, see Figure 8.20.
The remote divert control unit operates as a main unit, which means that the master divert unit is for indication only. If the remote divert control unit is not in operation, the master divert unit in the field operates as a main unit.
The remote control unit communicates with the master divert unit in the field through a modem. Connection and wiring is made according to Figure 8.40.
For contact terminals see Figure 8.41. Contact terminals 24 and 25 are for communication OK signal.
8.2. EQUIPMENT
Figure 8.20 Complete remote divert control system.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 32: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/32.jpg)
31
8.3. REMOTE DIVERT CONTROL UNIT IN THE CONTROL ROOM
Figure 8.30 Operator’s panel and functions of the remote divert control in the control room.
The remote divert control unit contains all information for the deviation decision. The operation is clearly indicated with LED lights as follows:
1. A row of four alarms (indicating Black liq-uor SOLIDS WARNING (at 60%), Black liq-uor SOLIDS ALARM (below 58%), Refrac-tometer reading more than 2% absolute differ-ence, and Refractometer malfunction).
2. Each refractometer A and B has an OPERATING green light, so the operator knows when he can rely on the refractometer measurement.
A refractometer will influence the divert deci-sion only when the green OPERATING light is on. A malfunctioning refractometer is auto-matically taken out of operation.
3. One green indicator light SAFE% SOLIDS, based on the two refractometers and the divert decision rules.
4. A red OVERRIDE warning light.
5. One red DIVERT light that will be switched on when the SAFE% SOLIDS goes off, pro-viding OVERRIDE is off. The DIVERT light indicates divert status of the divert relay.
6. Two indicator lights for the divert valve status. TO BY-PASS/TO BURNER from mi-croswitches on the valve. For intermediate valve positions both lights are off.
7. A lockable Override/Automatic switch.
8. One RESET push-button for the DIVERT action. The DIVERT action always has to be manually reset. If the override swithc is in automatic position and SAFE% SOLIDS is off, the DIVERT cannot be reset.
9. EMERGENCY DIVERT push-button.
10. A light test button switches all 11 lights on.
11. An alarm reset button resets the alarm lights.
12. Communication to MASTER DIVERT ok, indication light blinking.
13. Power supply ok, indication light on.
Note when remote divert in use, master di-vert unit in the field is for indication only!
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 33: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/33.jpg)
32
8.4. WIRING AND MOUNTING
For wiring of the complete system, see Figure 8.40, which also specifies the cables and connections.
Figure 8.40 Digital Divert Control System with Remote Divert Control Unit Wiring.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 34: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/34.jpg)
33
Figure 8.41 Remote Divert Control Unit terminals.
Figure 8.42 Digital Divert Control System: Remote Divert Control Unit mounting.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 35: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/35.jpg)
34
8.5. SERIAL OUTPUT
Each Indicating transmitter has a serial output not used by the Divert Control unit. This serial output is select-able RS-232/RS-485 (see PR-01-S Manual) and contains concentration, temperature and error data. It contains also information whether the refractometer is in divert operation or not.
Possible uses of the Serial output: To communicate with a computer substituting the Divert Control unit.
8.6. CURRENT OUTPUT SIGNAL
Each Indicating transmitter provides a 4-20 mA output concentration signal not used by the Divert system. To calibrate this signal for suitable %Solids range, press Calibrate/Output signal/Current output, see PR-01-S Manual.
8.7. EXTERNAL DC POWER SUPPLY
The Divert Control unit may be connected to a DC power supply as a back-up. At AC power failure the refrac-tometers will black-out, but the Divert Control unit will still work. In this case the DIVERT signal can be pre-vented by turning the key to OVERRIDE. Terminals are 15 (+24VDC) and 16 (ground).
The power requirement is 24 VDC, 500 mA.
8.8. DIVERT CONTROL UNIT CARD IN THE REMOTE UNIT
In the remote unit the divert control card the third dip switch SW3 must be in the ON position (“up”).
See Figure 3.13 and Sections 5.2. and 5.7.
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 36: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/36.jpg)
35
9. DIVERT CONTROL UNIT PARTS LISTS
9.1. DIVERT CONTROL UNIT AND OPTIONAL REMOTE DIVERT CONTROL UNIT
ltem Pcs. Part No. Description Item Pcs. Part No. Description 1 1 Enclosure 6.1 2 PR-6551 Switch unit, green 1.1 7 Conduit hubs 1/2”
NPT-Type ST-1 (US) 6.2 1 PR-6551 Switch unit, red for Emer-
gency divert 2. 3.1 3.2 3.3
1 1 1 1
PR-7310 Divert Control Unit Card Modem transformer Modem card Modem cable
4 1 PR-7028 Ribbon cable 5 1 PR-7311 LED Display card
6.3 6.4 7.
1 1 1
PR-6551 PR-6552 PR-6501
Switch unit, green for Emer-gency divert reset Lock unit for Auto-matic/Override divert opera-tion Divert Fuse set: 9 fuses (3 x Microfuse 1A, fast IEC 127-3/1, UL 198G; 3 x 5x20mm Fuse 1A, fast; 3 x Microfuse 63 mA, fast IEC 127-3/1, UL 198G)
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005
![Page 37: dd-01](https://reader031.fdocuments.in/reader031/viewer/2022020418/5695d46e1a28ab9b02a16ab3/html5/thumbnails/37.jpg)
36
9.2. REMOTE DIVERT CONTROL UNIT
ltem Pcs. Part No. Description 6.1 2 PR-6551 Switch unit, green 6.2 1 PR-6551 Switch unit, red for Emergency divert 6.3 1 PR-6551 Switch unit, green for Emergency divert
reset 6.4 1 PR-6552 Lock unit for Automatic/Override divert
operation 8.1 1 PR-7310-RACK 8.2 RACK-modem 8.3 1 RACK Power 24V
INSTRUCTION MANUAL FOR DD-01 DOCUMENT/REVISION: IMD 1/5
Effective: June 20, 2005