DATA SHEET: TEMBREAK 2 GS160-SCJ MCCB

4
Standard Optional - Not Available TB2 Lite 160 DATA SHEET: TEMBREAK 2 GS160-SCJ MCCB MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, NEMA AB-1 Frame Reference Quantity Unit Condition Max in ( A) of Frame Model S160 Number of Poles 3, 4 Type SCJ Nominal current ratings I n (A) 50°C 25,40,63,80 100,125,160 Electrical characteristics Rated operational voltage U e (V) AC 50/60 Hz 525 DC 250 Rated insulation voltage U i (V) 690 Rated impulse withstand voltage U imp (kV) 8 Ultimate breaking capacity I cu (kA) 690V AC - (IEC, JIS, AS/NZS) 525V AC 7.5 440V AC 15 400/415V AC 25 220/240V AC 35 250V DC 20 Service breaking capacity I cs (kA) 690V AC - (IEC, JIS, AS/NZS) 525V AC 4 440V AC 7.5 400/415V AC 13 220/240V AC 18 250V DC 10 Rated breaking capacity (NEMA) (kA) 480V AC 7.5 240VAC 35 Protection Fixed thermal, fixed magnetic - Adjustable thermal, fixed magnetic Utilisation category A Installation Front connection (FC) Extension bar (FB) Cable clamp (FW) Rear connection (RC) Plug-in (PM) - DIN rail mounting (DA) Dimensions height (mm) 130 width (mm) 3 pole, (1 pole) 75 4 pole 100 depth (mm) 68 Weight weight (kg) 3 pole, (1 pole) 0.8 4 pole 1.0 Operation Direct Opening Action Toggle operation Door mounted (HS) / Breaker mounted handle (HB) Motor operation - Endurance Electrical cycles 415V AC 10,000 cycles 20,000 Page 1 of 3 Factory-fit at time of order 14,000 ≤125A 160

Transcript of DATA SHEET: TEMBREAK 2 GS160-SCJ MCCB

Standard • Optional - Not Available

TB2 Lite 160

DATA SHEET: TEMBREAK 2 GS160-SCJ MCCB MCCB Electrical Characteristics to IEC 60947-2, EN 60947-2, JIS C 8201-2-1 ANN.1, NEMA AB-1

Frame Reference Quantity Unit Condition

Max in ( A) of Frame

Model S160Number of Poles 3, 4Type SCJ

Nominal current ratings

In (A) 50°C 25,40,63,80 , 16,20,25,32 25,40,63,80100,125,160 0 40,50,63,80, 100,125,160

Electrical characteristics

Rated operational voltage Ue (V) AC 50/60 Hz 525DC 250

Rated insulation voltage U i (V) 690Rated impulse withstand voltage U imp (kV) 8

Ultimate breaking capacity I cu (kA) 690V AC - 6 6(IEC, JIS, AS/NZS) 525V AC 7.5

440V AC 15400/415V AC 25220/240V AC 35250V DC 20

Service breaking capacity I cs (kA) 690V AC - 3 3(IEC, JIS, AS/NZS) 525V AC 4 4

440V AC 7.5400/415V AC 13220/240V AC 18250V DC 10

Rated breaking capacity (NEMA) (kA) 480V AC 7.5240VAC 35

Protection

Fixed thermal, fixed magnetic -

Adjustable thermal, fixed magneticUtilisation category A A A

Installation

Front connection (FC)Extension bar (FB) • • •Cable clamp (FW)Rear connection (RC) •Plug-in (PM) - - -DIN rail mounting (DA) •Dimensions height (mm) 130

width (mm) 3 pole, (1 pole) 754 pole 100

depth (mm) 68Weight weight (kg) 3 pole, (1 pole) 0.8

4 pole 1.0

Operation

Direct Opening ActionToggle operation Door mounted (HS) / Breaker mounted handle (HB) •Motor operation - - -

Endurance Electrical cycles 415V AC 10,000cycles 20,000 0 20,000 20,000

Page 1 of 3Factory-fit at time of order14,000 ≤125A

160

CL CL

LH LH LH LHLH

Front connected

Rear connectedDrilling plan (front view)

M4 0.7Tapped hole

M4 0.7Mounting screw

Panel cutout (front view)Detail of connecting part

Mounting plate(max. t3.2)

Panel cutout dimensions shown give an allowance of 1.0mm or more around the handle escutcheon.

Studs are horizontaldirection only

2550

C D

E

A

3P

25

111

114

4P

ø20

37.5

3P 4P

37.5

38.577 102

38.5

25 25 25

B

C D

A

B

10252

114

68

102

F

95

3P4P

7.7

25 25 25

102

52

45

CL CL CL CLCL

LH LHLH

LH LH

Preparation of conductor With extension bars

(optional)Drilling plan (front view)

M4 0.7Tapped hole

Interpole barrier (removable)

Mounting hole

M4 0.7Mounting screw

M5 0.8 screw (25-40A)M8 screw (63-160A)

1

257550

102

7.7

24

9568

52

3P22

10.5

3P

10075

5013

0

4P

25

111

4P

N

P4P3

8.5

5.63

173570

114

Note: For the extension bars: Straight bars or spread bars can be supplied depending oncurrent rating. Refer to order codes for details.

LH25 25 25 25 25

ø8.3

45 45

17

8.5

36.5

35

5

35 35ø8.3

284

48

Rated current (A) A B C D E16-50 10.5 6.5 4 13 1663-160 12.5 8.5 4 13 16

F45

6.5(m

ax.)

9(max

.)16.5(max.)max.t5

14(max.)max.t5

ø5.5(25-40A)ø9(63-160A)

ø5.5(25-40A)ø9(63-160A)

DATA SHEET: TEMBREAK 2 GS160-SCJ MCCBOutline Dimensions GS160-SCJ

ASL: Arrangement Standard Line HL: Handle Frame Centre Line CL: Handle Centre Line

Page 2 of 3

Page 3 of 3

DATA SHEET: TEMBREAK 2 GS160-SCJ MCCB

Time/Current Characteristic Curves GS160-SCJ

Manufacturer/Tillverkare: GARO AB Box 203

DokumenUdocument

Forsakran om overensstammelse/ Declaration of conformity Avdelning/department Produkt/Product Ansvarig/prepared

I �ernion

Robert Nyden

Utgava datum/edition date

2018-08-22

Sida/page 1 av/of 1

S-335 25 GNOSJOSweden

Telephone: Internet:

+46 (0)370 33 28 00www.garo.se

Agent established within EC/Ombud etablerad inom EG Telephone: Internet:

Agent of equipment/Materielslag: Moulded Case Circuit Breaker, MCCB/Effektbrytare, MCCB

Trade Mark/V arumarke: GARO

Type Designation/Typbeteckning: GS160SCJ , SJ ,GS400-NE, 3- and 4-pole, GS250-NE, 3- and 4-pole

We hereby declare that our product fulfils the requirements of following EC directives/ Vi intygar harmed att var produkt uppfyller krav enligt foljande EU direktiv:

[8] The Low Voltage Directive (LVD) 2014/35/EU / Lagspanningsdirektivet (L VD) 2014/35/EU.

[8] Electromagnetic compatibility (EMC) 2014/30/EU / Elektromagnetisk kompatibilitet (EMC) 2014/30/EU. D Radio Equipment Directive 2014/53/EU (RED) 2014/30/EU / Radiodirektivet (RED) 2014/53/EU. [8] RoHS Directive (RoHS) 2011/65/EU / RoHS direktivet (RoHS) 2011/65/EU. D No electromagnetic compatibility (EMC 2014/30/EU) immunity or emission tests are required on the assembly / Produkten innehaller inte elektroniska apparater som paverkas enligt forbehallen enligt direktivet (EMC) 2014/30/EU.

The following harmonised standards (latest edition) or technical specifications which comply with good engineering practice in safety matters in force within the EC have been used in the design:/ Foljande harmoniserade standarder (senaste utgava) eller tekniska specifikationer som uppfyller god sakerhetsteknik praxis inom EG bar anvants i konstruktionen: EN 60947-1 and/och 60947-2

[8] The equipment confirms completely with the above stated harmonised standards or technical specifications./ Materielen overensstammer belt med ovan angivna harmoniserade standarder eller tekniska specifikationer.

Or/Eller D The equipment confirms only partially with the above stated harmonised standards or technical

specifications but complies with good practice in safety matters in force within the EC./ Materielen overensstammer endast delvis med ovan angivna harmoniserade standarder eller tekniska specifikationer, men uppfyller god sakerhetsteknisk praxis inom EG.

We have product surveillance according to CENELEC's harmonised reguirements, documents CCA-201.

GARO AB Company/FO,etag

Sign/Underskri�

Product Manager/Produktchef Position/Befattning

Robert Nyden Sign in printed letters/Namnfortydligande

2018-08-22 Date/Datum