Plate Heat ExchangerXGM032
Data sheet
Description Danfoss XGM plate heat exchangers have been developed specifically for District Energy applications like District Heating and Cooling ensuring you a reliable high efficient plate heat exchanger fulfilling your needs.
Main data:• Min.temperature−10°C• Max.temperature150°C• Max.workingpressure16bar(25baronrequest)• Standardrangeis1passversion
(2passversiononrequest)• Circulationwater/glycolicwaterupto50%• ConnectionsizeDN32
Approvals:• PressureEquipmentDirective(PED)97/23/EC• GOST/Russia
Ordering
1-pass gasketed heat exchangers type XGM032
PictureNo. of plates
ConnectionXGM032L XGM032M XGM032H
(n) Code No.
20
Thread G 1¼
004H7096 004H7087 004H7078
30 004H7097 004H7088 004H7079
40 004H7098 004H7089 004H7080
50 004H7099 004H7090 004H7081
60 004H7100 004H7091 004H7082
70 004H7101 004H7092 004H7083
80 004H7102 004H7093 004H7084
90 004H7103 004H7094 004H7085
100 004H7104 004H7095 004H7086
Note: Brackets has to be ordered separately.
XGM 032 H – 1 – 10
Numberofplates NumberofPasses(1=1-pass)
Channeltype(L-M-H)
Connectionsize(DN32)
Micro plate™ plates
Gasketed heat exchanger
2 VD.GS.U2.02 © Danfoss 03/2014 DEN-SMT/SI
Data sheet Plate Heat Exchanger XGM032
Accessories - BracketType Code No.
Brackets 004H7222
Accessories - EPDM GasketType Code No.
Gasket for XGM032, I-pack 10 pcs 004H7128
GasketforXGM032,I-pack250pcs 004H7129
Ordering - continuous
Accessories for gasketed heat exchanger type XGM Type Code No.
PlatesforXGM032HPN16,I-pack10pcs 004H7186
PlatesforXGM032MPN16,I-pack10pcs 004H7187
PlatesforXGM032LPN16,I-pack10pcs 004H7188
PlatesforXGM032HPN16,I-pack250pcs 004H7189
PlatesforXGM032MPN16,I-pack250pcs 004H7190
PlatesforXGM032LPN16,I-pack250pcs 004H7191
XGM032H:spec.plates1-passversions,includinggaskets.PN16 004H7204
XGM032M:spec.plates1-passversions,includinggaskets.PN16 004H7205
XGM032L:spec.plates1-passversions,includinggaskets.PN16 004H7206
XGM032H:spec.plates2-passversion,includinggasketsPN16 004H7219
XGM032M:spec.plates2-passversion,includinggasketsPN16 004H7220
XGM032L:spec.plates2-passversion,includinggasketsPN16 004H7221
Tailpieces for gasketed heat exchanger type XG Picture Description Connection Code No.¹⁾
Soldertailpieces G1¼A/22mm,28mm 004B1358
Weld-on tailpiecesG1¼A/DN25 003H6910
G1¼A/DN32 004B1343
1) One set contains 2 tailpieces with union nuts and gaskets
Accessories - InsulationsType coverage (plate nos) Code No.
20-40 004H7117
40-70 004H7118
70-100 004H7119
Technical data Max.workingpressure PN(bar) 16
Max.operatingtemperatureoC
150
Min.operatingtemperature1) −10
Flowmedium Circulationwater/glycolicwaterupto50%
Heattransferareaperplate,HTA m2 0,067
Max. no of plates pcs 100
Volume/Channel
Ltr
0,097
Primarysidevolume: (n/2)-1xvolume/channel
Secondarysidevolume: (n/2)xvolume/channel
Connection type Cylindricalexternalthreadacc.toDINISO228/1
Connectionsize G 1¼
Platematerial Stainlesssteel,mat.no.EN1.4401
Platethickness mm 0,3
Gasket type Glue free
Gasketmaterial,rubber EPDM
1) At flow temp. below 2 °C glycolic water must be used
Insulation properties
Type Coated steel sheet
and polyester insulation
Heat conductivity, λ W/mK 0,042
Max temperature
Permanent°C
150
Shorttermpeak 180
Wall thickness mm 30
Note:For more details about insulation please contact your Danfoss sales representative.
3VD.GS.U2.02 © Danfoss 03/2014DEN-SMT/SI
T11
T21
T12
T22
Data sheet Plate Heat Exchanger XGM032
Design and function
1-pass heat exchanger
T11-Primarysidein
T12-Primarysideout
T21-Secondarysidein
T22-Secondarysideout
Theheatexchangersaremadeofshape-pressedheatplatesbetweenwhichtheflowchannelsarecreated.Gasketsbetweentheplatesseparatetheflowchannelsfromeachothersothattheflowsdonotmix.Theheavyturbulenceandcounter-flowprincipleenablesefficientheattransfer.Thetaskoftheheatexchangeristotransferheatfromtheprimarytosecondaryflowthrough a heat transfer plate thus preventing theflowsfrommixingwitheachother.Theplateheatexchangerwithgasketscanbeopenedforcleaningandforreplacementofplatesandgaskets.Asteeplesoutputadjustmentcanbecarriedoutbychangingthenumberofplates.
Thechoiceofheatexchangerisdeterminedbythedesiredheatoutput,requiredtemperaturesandthepermittedpressurelosses.
Sizing DimensioningandselectionofheatexchangersshouldbecarriedoutwiththesupportoftheDanfossdimensioningprogramforheatexchangers.
Mounting Theheatexchangermustbemountedinverticalposition. Preparethefoundationfortheheatexchangerifnecessary,alwaysaccordingtolocalregulations.Itisrecommendedthatallpipesconnectedtotheheatexchangerareequippedwithshut-offvalvesformaintenancepurposes.
Thepipestobeconnectedmustbemountedsothatthestraincausedbythethermalexpansion,forinstance,doesnotharmtheheatexchanger.
Thepipesmustbeequippedwithbracketstoprevent any torsional stress concentration at the heat exchanger’s pipe connections.
Itisrecommendedthattheheatexchangerisequippedwithinsulation.
Asafetyvalvemustbeinstalledbetweentheheatexchangerandtheshut-offvalvesonthesecondary side of the heat exchanger. If the safetyvalveisnotinstalled,thermalexpansionoffluidmightdestroytheheatexchangerwhentheshut-offvalvesareclosed.
Dimensions
B
G
D
AE
C
Heat exchanger
Plate No. G B D C E HWeight
(kg)
20
570 180 470 63 65
48 32
30 71 34
40 94 37
50 117 39,5
60 140 41,5
70 163 44,5
80 186 46,5
90 209 48,5
100 232 50,5
4 VD.GS.U2.02 ProducedbyDanfossA/S©03/2014
Data sheet Plate Heat Exchanger XGM032
Dimensions (continuous)
B
H
I
G
Insulation
Code No. G B I HWeight
(kg)
004H7117
615 270 50
360 10
004H7118 460 12
004H7119 560 14
154
Ø14
180
146
159
121
130
20
5290
122
91910