ORIGINATOR: EMCC CO. LLC SLLC DOC No.: - Contract No. 15519.01 / EC10845 ADCO DOC. No. 30-99-27-5601 PROJ. No. P11550 Pages 1 of 60 ENGINEERING, PROCUREMENT AND CONSTRUCTION FOR POWER NETWORK UPGRADE AT ALL ADCO FIELDS ADCO Document No. 30-99-27-5601 Typical Data Sheets for Packaged AC Units 3 18-Nov-15 HA ALA KT Issued for Approval 2 30-Apr-15 HA ALA KT Issued for Approval 1 22-Mar-15 HA ALA KT Issued for Approval B 23-Feb-15 HA ALA KT Issued for Approval A 17-Jan-15 HA ALA KT Issued for Review REV. DATE ORIGINATOR REVIEWED APPROVED DESCRIPTION THIS DOCUMENT IS INTENDED FOR USE BY ADCO AND ITS NOMINATED CONSULTANTS, CONTRACTORS, MANUFACTURERS AND SUPPLIERS.

description

Data Sheet Packaged Unit- Rev 3

Transcript of Data Sheet Packaged Unit- Rev 3

Page 1: Data Sheet Packaged Unit- Rev 3

ORIGINATOR: EMCC CO. LLC SLLC DOC No.: - Contract No. 15519.01 / EC10845

ADCO DOC. No. 30-99-27-5601 PROJ. No. P11550 Pages 1 of 60

ENGINEERING, PROCUREMENT AND CONSTRUCTION FOR POWER NETWORK UPGRADE AT ALL ADCO FIELDS

ADCO Document No. 30-99-27-5601

Typical Data Sheets for Packaged AC Units

3 18-Nov-15 HA ALA KT Issued for Approval 2 30-Apr-15 HA ALA KT Issued for Approval 1 22-Mar-15 HA ALA KT Issued for Approval B 23-Feb-15 HA ALA KT Issued for Approval A 17-Jan-15 HA ALA KT Issued for Review

REV. DATE ORIGINATOR REVIEWED APPROVED DESCRIPTION THIS DOCUMENT IS INTENDED FOR USE BY ADCO AND ITS NOMINATED CONSULTANTS, CONTRACTORS, MANUFACTURERS AND SUPPLIERS.

Page 2: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 18/11/15

PAGE 2 OF 60

TABLE OF CONTENTS

1.0 PACKAGED AIE CONDITIONING UNIT-ASAB 33KV SUBSTATION .............................5

1.1 GENERAL ..............................................................................................................5

1.2 EQUIPMENT LOCATION CONDITION ..................................................................5

1.3 FAN SELECTION ...................................................................................................6

1.4 COOLING COIL SELECTION ................................................................................7

1.5 FILTER SELECTION ..............................................................................................8

1.6 CASING .................................................................................................................9

1.7 AIR COOLED CONDENSING PARTS ...................................................................9

1.8 COMMON PARTS ................................................................................................ 11

1.9 OVERALL DIMENSION WEIGHT ........................................................................ 11

1.10 INTERFACE WITH HVAC CONTROL PANEL ..................................................... 12

2.0 PACKAGED AIE CONDITIONING UNIT-BAB 33KV SUBSTATION.............................. 13

2.1 GENERAL ............................................................................................................ 13

2.2 EQUIPMENT LOCATION CONDITION ................................................................ 13

2.3 FAN SELECTION ................................................................................................. 14

2.4 COOLING COIL SELECTION .............................................................................. 15

2.5 FILTER SELECTION ............................................................................................ 16

2.6 CASING ............................................................................................................... 17

2.7 AIR COOLED CONDENSING PARTS ................................................................. 17

2.8 COMMON PARTS ................................................................................................ 19

2.9 OVERALL DIMENSION WEIGHT ........................................................................ 19

2.10 INTERFACE WITH HVAC CONTROL PANEL ..................................................... 20

3.0 PACKAGED AIE CONDITIONING UNIT-BAB LDC BUILDING ..................................... 21

3.1 GENERAL ............................................................................................................ 21

3.2 EQUIPMENT LOCATION CONDITION ................................................................ 21

3.3 FAN SELECTION ................................................................................................. 22

Page 3: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 18/11/15

PAGE 3 OF 60

3.4 COOLING COIL SELECTION .............................................................................. 23

3.5 FILTER SELECTION ............................................................................................ 24

3.6 CASING ............................................................................................................... 25

3.7 AIR COOLED CONDENSING PARTS ................................................................. 25

3.8 COMMON PARTS ................................................................................................ 27

3.9 OVERALL DIMENSION WEIGHT ........................................................................ 27

3.10 INTERFACE WITH HVAC CONTROL PANEL ..................................................... 28

4.0 PACKAGED AIE CONDITIONING UNIT-BUHASA 33KV SUBSTATION ...................... 29

4.1 GENERAL ............................................................................................................ 29

4.2 EQUIPMENT LOCATION CONDITION ................................................................ 29

4.3 FAN SELECTION ................................................................................................. 30

4.4 COOLING COIL SELECTION .............................................................................. 31

4.5 FILTER SELECTION ............................................................................................ 32

4.6 CASING ............................................................................................................... 33

4.7 AIR COOLED CONDENSING PARTS ................................................................. 33

4.8 COMMON PARTS ................................................................................................ 35

4.9 OVERALL DIMENSION WEIGHT ........................................................................ 35

4.10 INTERFACE WITH HVAC CONTROL PANEL ..................................................... 36

5.0 PACKAGED AIE CONDITIONING UNIT-ASAB STATCOM BUILDING ........................ 37

5.1 GENERAL ............................................................................................................ 37

5.2 EQUIPMENT LOCATION CONDITION ................................................................ 37

5.3 FAN SELECTION ................................................................................................. 38

5.4 COOLING COIL SELECTION .............................................................................. 39

5.5 FILTER SELECTION ............................................................................................ 40

5.6 CASING ............................................................................................................... 41

5.7 AIR COOLED CONDENSING PARTS ................................................................. 41

5.8 COMMON PARTS ................................................................................................ 43

5.9 OVERALL DIMENSION WEIGHT ........................................................................ 43

Page 4: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 18/11/15

PAGE 4 OF 60

5.10 INTERFACE WITH HVAC CONTROL PANEL ..................................................... 44

6.0 PACKAGED AIE CONDITIONING UNIT-BAB STATCOM BUILDING ........................... 45

6.1 GENERAL ............................................................................................................ 45

6.2 EQUIPMENT LOCATION CONDITION ................................................................ 45

6.3 FAN SELECTION ................................................................................................. 46

6.4 COOLING COIL SELECTION .............................................................................. 47

6.5 FILTER SELECTION ............................................................................................ 48

6.6 CASING ............................................................................................................... 49

6.7 AIR COOLED CONDENSING PARTS ................................................................. 49

6.8 COMMON PARTS ................................................................................................ 51

6.9 OVERALL DIMENSION WEIGHT ........................................................................ 51

6.10 INTERFACE WITH HVAC CONTROL PANEL ..................................................... 52

7.0 PACKAGED AIE CONDITIONING UNIT-BUHASA STATCOM BUILDING ................... 53

7.1 GENERAL ............................................................................................................ 53

7.2 EQUIPMENT LOCATION CONDITION ................................................................ 53

7.3 FAN SELECTION ................................................................................................. 54

7.4 COOLING COIL SELECTION .............................................................................. 55

7.5 FILTER SELECTION ............................................................................................ 56

7.6 CASING ............................................................................................................... 57

7.7 AIR COOLED CONDENSING PARTS ................................................................. 57

7.8 COMMON PARTS ................................................................................................ 59

7.9 OVERALL DIMENSION WEIGHT ........................................................................ 59

7.10 INTERFACE WITH HVAC CONTROL PANEL ..................................................... 60 *VTA - Vendor To Advise.

Page 5: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 5 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

1.0 PACKAGED AIR CONDITIONING UNIT (ROOF TOP UNIT) – ASAB 33KV SS 1.1 General

Equipment Tag Number

No. Required, Operation/Stand by

Duty

Type

Manufacturer

Model No.

Applicable Code

Air Supply System

Electric Power Source

Total Power Rating

Max. Start Current/Operating Current

-

Set

-

-

-

-

-

(CAV/VAV)

(V/Ph/Hz)

KW

A

ACU-14,15,16

2 / 1

Continuous

Floor Mounted

SKM

-

As per

specification

CAV

415 / 3 / 50

VTA

VTA

ACU-14,15,16

2 / 1

Noted

Floor Mounted

SKM

PACV 54100SM Rated in

accordance with

AHRI 340/360

CAV

415/3/50 4 wire

167.2

603/389.5

1.2 Equipment Location Condition

Location

Elevation (above sea level)

Barometer

Ambient Temperature, Max./Min

Design Temperature, Max. /Min.

Indoor

Outdoor Roof

Ground

Weather Protection Required

Tropicalization Required

-

M

Bar

°C

°C

-

-

-

-

-

Onshore

100

1.0013

55.0 / 5.0

50.0 / 5.0

No

Yes

No

Yes

Yes

Onshore

100

1.0013

55.0 / 5.0

50.0 / 5.0

Not Applicable

Yes

No

Yes

Yes

Page 6: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 6 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Unusual Condition Corrosive

Dust

Fumes

Others

Hazardous Area Classification

Noise Level

-

-

-

-

-

dB(A) @ 1m

Yes

Yes

No

Saline

Atmosphere

Not Classified

85

Yes

Yes

No

Saline

Atmosphere

Not Classified

84.8

1.3 Fan Section

Supply Fan No. Required per AHU, Operation/Stand-by

Type (Airfoil/Backward

Inclined/Backward/Forward)

Construction Type (DWDI/SWSI)

Supply Air Flow Rate

External Static Pressure

Internal Static Pressure

Total Static Pressure

Fan Speed

Vibration Isolator with Accessory

Bearing Type

Applicable Code

AMCA Certification

Set

-

-

l/s

Pa

Pa

Pa

Rpm

-

-

-

-

1 / NA

Forward

Curved

DWDI

As per

approved HLC

500

VTA

VTA

VTA

Yes

Ball or Pillow

Block

As per

specification

Yes

1 / NA

Backward

Curved

DWDI

14523.5lps

500

671

1171

1024

Yes

Ball or Pillow

Block

Noted

Yes

Page 7: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 7 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Supply Fan Motor No. Required per Fan, Operation/Stand-by

Power Rating

Motor Enclosure/Ingress Protection

Motor Manufacturer

Motor Efficiency

Space Heater

-

KW

-

-

-

-

1 / NA

VTA

TEFC/IP55

Siemens

As per

specification

Yes

1 / NA

30KW motor

TEFC/IP55 Siemens-Europe

IE1

Yes

1.4 Cooling Coil Section

No. Required per AHU, Operation/Stand-by

Type

Applicable Code

Total Cooling Capacity

Air Flow Rate

Entering Air Temperature, DB/WB

Leaving Air Temperature, DB/WB

Material, Tube/Fin

Fin Spacing

Limit of Coil Face Air Velocity

Min. Number of Refrigerant Circuits

Liquid/Gas

Corrosion Protection

Saline Atmosphere

-

-

-

KW

l/s

◦C

◦C

-

Ea/inch

m/s

ea

-

-

-

1/ NA

Direct

Expansion

As per

specification

As per HLC.

As per HLC.

As per HLC.

As per HLC.

Cu / Al

Max. 12

2.5

VTA

R 134a

Aeris Coating-

5year warranty

Yes

1/ NA

Direct

Expansion

Performance is

in accordance

with AHRI-410.

272.65

14523.5

26.3/18.0

12.49/12.45

Cu / Al

Max. 12

2.18

4

R 134a

Aeris Coating-

5year warranty

Yes

Page 8: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 8 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Hydrogen Sulphide

Min. Life of Cooling Coil

Condensate Drain

Drain Pan Material

-

Years

-

-

Yes

5

Yes

SS with Insulation

Yes

5

Yes

SS with Insulation

1.5 Filter Section

Pre Filter

Type

Efficiency

Thickness

Filter Face Velocity

Limit of Initial Pressure drop

Limit of Final Pressure drop

Final Filter Type

Efficiency

Thickness

Filter Face Velocity

Limit of Initial Pressure Drop

Limit of Final Pressure Drop

-

%

mm

m/s

Pa

Pa

-

%

Mm

m/s

Pa

Pa

Panel

G4

50

2.5

Depends on

Face Velocity

VTA

Bag

F8(En 779)

533

2.5

Depends on

Face Velocity

VTA

Panel

G4

50

<2.5

45[Clean] &

147[Mean]

250pa[Dirty]

Pleated

F8(En 779)

100mm

<2.5

120.5[Clean] &

247[Mean]

373.5pa[Dirty]

Page 9: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 9 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

1.6 Casing

Type

Material (G-90 Galvanized Steel or

Aluminium)

Insulation Material

Density

Thickness

Painting

-

-

-

kg/m3

mm

Mfr/job Spec.

Double Wall

Galvanized

Steel

Fiber Glass

comply to

NFPA-90A, B

32

50

As per

specification

Double Wall

Galvanized

Steel

Fiber Glass

comply to

NFPA-90A, B

32

50

SKM Marine standard Painting

1.7 Air Cooled Condensing Parts Compressor

Make

Model

No. of Compressor per ACCU

Compressor Type,

(Reciprocating/Screw/Scroll/Hermetic/Semi-

hermetic)

COP (Coefficient of Performance)

Power Rating per Compressor

Capacity Control Steps per Compressor

-

-

Ea

-

-

-

%

VTA

VTA

VTA

Scroll

As per Final

Selection

As per Final

Selection

VTA

Copeland-USA

ZR 250 [SKM

model]

8

Scroll

2.74

125.2KW[Total]

1 [0-100]

Page 10: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 10 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Min. Operating Capacity per Compressor

Vibration Isolator with Accessory

Crank case Heater requirement

Refrigerant

-

-

-

13%

As per standard

Yes

13%

As per SKM

Standard

Yes

Refrigerant Type

Refrigerant Charge

Condenser Coil No. of Circuits per ACCU

Material, Tube/Fin

Corrosion Protection for Saline Atmosphere

Hydrogen Sulphide Atmosphere

Condenser Fan Fan Type

No. of Fans per ACCU

Airflow Rate per Fan

Total Airflow Rate per ACCU

Total Power Rating of Fans per ACCU

Motor Insulation/Temp. Rise

-

kg

ea

-

-

-

-

Ea

l/s

l/s

kw

-

R134a

VTA

VTA; shall be

provided after

HLC approval.

Cu / Al

Aeris Coating-5

year warranty

Yes

Propeller-Al

alloy

VTA

VTA

VTA

VTA

F / B

R134a

28kg per

circuit[Approx]

4

Cu / Al

Aeris Coating-5

year warranty

Yes

Propeller-Al alloy

8

4917.68

39341.5

1.5

F / B

Page 11: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 11 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Motor Enclosure/Ingress Protection

Motor Manufacturer

-

-

TEFC / IP55

Siemens

TEFC / IP55

Siemens

1.8 Common Parts

Control & Electrical Panel including Starter

Control & Electrical Panel Enclosure Class

Overload Relay Protection for Compressor

Overload Relay Protection for Condenser Fan

Security Grillers

Hilted Type Anchor

Disconnection Switch

Motorized Damper, SA

Eliminator

Access Door

Application section

Quantities

Marine Light and Sight Glass

Quantities

Q’ty of PDIS for each Filter Pres. Drop

-

-

-

-

-

-

-

-

-

-

-

-

-

Ea

ea

Yes

IP 55

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

All Sections

2 (Fan & Filter)

Yes

2

2

Yes

IP 55

Yes

Yes

Yes

Yes,

As applicable

By EMCC

By EMCC

Yes

Yes

Fan section

1 (Fan),

Access panel for

filter

Yes

1

2

1.9 Overall Dimension Weight

Dimensions, Length

Width

Height

Weight, Operating

mm

mm

mm

Kg

VTA

VTA

VTA

VTA

8614 [frame size]

2540

3236

9763

Page 12: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 12 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

1.10 Interface with HVAC Control Panel

Start/Stop from HCP to LCP

Running Status Signal from LCP to HCP

Trip Signal from LCP to HCP

Temperature Setting Value

Signal(4˜20mA)from HCP to LCP

Compressor Control Signal(4˜20mA)from

HCP to LCP

Dirt indication of pre-filter

Dirt indication of final filter

-

-

-

-

-

-

-

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Digital on/off/trip

Yes,VFC provided

Yes,VFC provided

Page 13: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 13 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

2.0 PACKAGED AIR CONDITIONING UNIT (ROOF TOP UNIT) – BAB 33KV SS 2.1 General

Equipment Tag Number

No. Required, Operation/Stand by

Duty

Type

Manufacturer

Model No.

Applicable Code

Air Supply System

Electric Power Source

Total Power Rating

Max. Start Current/Operating Current

-

Set

-

-

-

-

-

(CAV/VAV)

(V/Ph/Hz)

KW

A

ACU-27,28,29

2 / 1

Continuous

Floor Mounted

SKM

-

As per

specification

CAV

415 / 3 / 50

VTA

VTA

ACU-27,28,29

2 / 1

Noted

Floor Mounted

SKM

PACV 53095SM Rated in

accordance with

AHRI 340/360

CAV

415/3/50 4 wire

153.7

590/336

2.2 Equipment Location Condition

Location

Elevation (above sea level)

Barometer

Ambient Temperature, Max./Min

Design Temperature, Max. /Min.

Indoor

Outdoor Roof

Ground

Weather Protection Required

Tropicalization Required

-

M

Bar

°C

°C

-

-

-

-

-

Onshore

100

1.0013

55.0 / 5.0

50.0 / 5.0

No

Yes

No

Yes

Yes

Onshore

100

1.0013

55.0 / 5.0

50.0 / 5.0

Not Applicable

Yes

No

Yes

Yes

Page 14: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 14 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Unusual Condition Corrosive

Dust

Fumes

Others

Hazardous Area Classification

Noise Level

-

-

-

-

-

dB(A) @ 1m

Yes

Yes

No

Saline

Atmosphere

No implication

on Package

Unit

85

Yes

Yes

No

Saline

Atmosphere

NA

85

2.3 Fan Section

Supply Fan No. Required per AHU, Operation/Stand-by

Type (Airfoil/Backward

Inclined/Backward/Forward)

Construction Type (DWDI/SWSI)

Supply Air Flow Rate

External Static Pressure

Internal Static Pressure

Total Static Pressure

Fan Speed

Vibration Isolator with Accessory

Bearing Type

Applicable Code

AMCA Certification

Set

-

-

l/s

Pa

Pa

Pa

Rpm

-

-

-

-

1 / NA

Forward

Curved

DWDI

As per

approved HLC

500

VTA

VTA

VTA

Yes

Ball or Pillow

Block

As per

specification

Yes

1 / NA

Backward

Curved

DWDI

13085.5lps

500

624.5

1124.5

1183

Yes

Ball or Pillow

Block

Noted

Yes

Page 15: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 15 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Supply Fan Motor No. Required per Fan, Operation/Stand-by

Power Rating

Motor Enclosure/Ingress Protection

Motor Manufacturer

Motor Efficiency

Space Heater

-

KW

-

-

-

-

1 / NA

VTA

TEFC/IP55

Siemens

As per

specification

Yes

1 / NA

30KW motor

TEFC/IP55 Siemens-Europe

IE1

Yes

2.4 Cooling Coil Section

No. Required per AHU, Operation/Stand-by

Type

Applicable Code

Total Cooling Capacity

Air Flow Rate

Entering Air Temperature, DB/WB

Leaving Air Temperature, DB/WB

Material, Tube/Fin

Fin Spacing

Limit of Coil Face Air Velocity

Min. Number of Refrigerant Circuits

Liquid/Gas

Corrosion Protection

Saline Atmosphere

-

-

-

KW

l/s

◦C

◦C

-

Ea/inch

m/s

ea

-

-

-

1/ NA

Direct

Expansion

As per

specification

As per HLC.

As per HLC.

As per HLC.

As per HLC.

Cu / Al

Max. 12

2.5

VTA

R 134a

Aeris Coating-

5year warranty

Yes

1/ NA

Direct

Expansion

Performance is

in accordance

with AHRI-410.

246.98

13085.5

26.3/18.1

12.59/12.56

Cu / Al

Max. 12

2.01

3

R 134a

Aeris Coating-

5year warranty

Yes

Page 16: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 16 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Hydrogen Sulphide

Min. Life of Cooling Coil

Condensate Drain

Drain Pan Material

-

Years

-

-

Yes

5

Yes

SS with Insulation

Yes

5

Yes

SS with Insulation

2.5 Filter Section

Pre Filter

Type

Efficiency

Thickness

Filter Face Velocity

Limit of Initial Pressure drop

Limit of Final Pressure drop

Final Filter Type

Efficiency

Thickness

Filter Face Velocity

Limit of Initial Pressure Drop

Limit of Final Pressure Drop

-

%

mm

m/s

Pa

Pa

-

%

Mm

m/s

Pa

Pa

Panel

G4

50

2.5

Depends on

Face Velocity

VTA

Bag

F8(En 779)

533

2.5

Depends on

Face Velocity

VTA

Panel

G4

50

<2.5

38 [Clean] &

143.5[Mean]

250pa[Dirty]

Pleated

F8(En 779)

100mm

<2.5

110.5[Clean] &

242[Mean]

373.5pa[Dirty]

Page 17: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 17 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

2.6 Casing

Type

Material (G-90 Galvanized Steel or

Aluminium)

Insulation Material

Density

Thickness

Painting

-

-

-

kg/m3

mm

Mfr/job Spec.

Double Wall

Galvanized

Steel

Fiber Glass

comply to

NFPA-90A, B

32

50

As per

specification

Double Wall

Galvanized

Steel

Fiber Glass

comply to

NFPA-90A, B

32

50

SKM Marine standard Painting

2.7 Air Cooled Condensing Parts Compressor

Make

Model

No. of Compressor per ACCU

Compressor Type,

(Reciprocating/Screw/Scroll/Hermetic/Semi-

hermetic)

COP (Coefficient of Performance)

Power Rating per Compressor

Capacity Control Steps per Compressor

-

-

Ea

-

-

-

%

VTA

VTA

VTA

Scroll

As per Final

Selection

As per Final

Selection

VTA

Copeland-USA

ZR310 +ZR 250

[SKM model]

[5+1]

Scroll

2.72

114.7KW[Total]

1 [0-100]

Page 18: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 18 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Min. Operating Capacity per Compressor

Vibration Isolator with Accessory

Crank case Heater requirement

Refrigerant

-

-

-

13%

As per standard

Yes

17%

As per SKM

Standard

Yes

Refrigerant Type

Refrigerant Charge

Condenser Coil No. of Circuits per ACCU

Material, Tube/Fin

Corrosion Protection forSaline Atmosphere

Hydrogen Sulphide Atmosphere

Condenser Fan Fan Type

No. of Fans per ACCU

Airflow Rate per Fan

Total Airflow Rate per ACCU

Total Power Rating of Fans per ACCU

Motor Insulation/Temp. Rise

Motor Enclosure/Ingress Protection

Motor Manufacturer

-

kg

ea

-

-

-

-

Ea

l/s

l/s

kw

-

-

-

R134a

VTA

VTA; shall be

provided after

HLC approval.

Cu / Al

Aeris Coating-5

year warranty

Yes

Propeller-Al alloy

VTA

VTA

VTA

VTA

F / B

TEFC / IP55

Siemens

R134a

38kg per circuit

[Approx.]

3

Cu / Al

Aeris Coating-5

year warranty

Yes

Propeller-Al alloy

6

4667.57

28005.4

1.5

F / B

TEFC / IP55

Siemens

Page 19: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 19 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

2.8 Common Parts

Control & Electrical Panel including Starter

Control & Electrical Panel Enclosure Class

Overload Relay Protection for Compressor

Overload Relay Protection for Condenser Fan

Security Grillers

Hilted Type Anchor

Disconnection Switch

Motorized Damper, SA

Eliminator

Access Door

Application section

Quantities

Marine Light and Sight Glass for liquid,

moisture indicator

Quantities

Q’ty of PDIS for each Filter Pres. Drop

-

-

-

-

-

-

-

-

-

-

-

-

-

Ea

ea

Yes

IP 55

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

All Sections

2 (Fan & Filter)

Yes

2

2

Yes

IP 55

Yes

Yes

Yes

Yes,

As applicable

By EMCC

By EMCC

Yes

Yes

Fan section

1 (Fan),

Access panel for

filter

Yes

1

2

2.9 Overall Dimension Weight

Dimensions, Length

Width

Height

Weight, Operating

mm

mm

mm

Kg

VTA

VTA

VTA

VTA

7558 [frame size]

2540

3172

8903

Page 20: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 20 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

2.10 Interface with HVAC Control Panel

Start/Stop from HCP to LCP

Running Status Signal from LCP to HCP

Trip Signal from LCP to HCP

Temperature Setting Value

Signal(4˜20mA)from HCP to LCP

Compressor Control Signal(4˜20mA)from

HCP to LCP

Dirt indication of pre-filter

Dirt indication of final filter

-

-

-

-

-

-

-

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Digital on/off/trip

Yes,VFC provided

Yes,VFC provided

Page 21: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 21 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

3.0 PACKAGED AIR CONDITIONING UNIT (ROOF TOP UNIT) – BAB LDC BUILDING 3.1 General

Equipment Tag Number

No. Required, Operation/Stand by

Duty

Type

Manufacturer

Model No.

Applicable Code

Air Supply System

Electric Power Source

Total Power Rating

Max. Start Current/Operating Current

-

Set

-

-

-

-

-

(CAV/VAV)

(V/Ph/Hz)

KW

A

ACU-01, 02

1/ 1

Continuous

Floor Mounted

SKM

-

As per

specification

CAV

415 / 3 / 50

VTA

VTA

ACU-01, 02

1/1

Noted

Floor Mounted

SKM

PACV 53075SM Rated in

accordance with

AHRI 340/360

CAV

415/3/50 4 wire

118.6

494/280.5

3.2 Equipment Location Condition

Location

Elevation (above sea level)

Barometer

Ambient Temperature, Max./Min

Design Temperature, Max. /Min.

Indoor

Outdoor Roof

Ground

Weather Protection Required

Tropicalization Required

-

M

Bar

°C

°C

-

-

-

-

-

Onshore

100

1.0013

55.0 / 5.0

50.0 / 5.0

No

Yes

No

Yes

Yes

Onshore

100

1.0013

55.0 / 5.0

50.0 / 5.0

Not Applicable

Yes

No

Yes

Yes

Page 22: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 22 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Unusual Condition Corrosive

Dust

Fumes

Others

Hazardous Area Classification

Noise Level

-

-

-

-

-

dB(A) @ 1m

Yes

Yes

No

Saline

Atmosphere

Not classified

Area

85

Yes

Yes

No

Saline

Atmosphere

NA

82.3

3.3 Fan Section

Supply Fan No. Required per AHU, Operation/Stand-by

Type (Airfoil/Backward

Inclined/Backward/Forward)

Construction Type (DWDI/SWSI)

Supply Air Flow Rate

External Static Pressure

Internal Static Pressure

Total Static Pressure

Fan Speed

Vibration Isolator with Accessory

Bearing Type

Applicable Code

AMCA Certification

Set

-

-

l/s

Pa

Pa

Pa

Rpm

-

-

-

-

1 / NA

Forward

Curved

DWDI

As per

approved HLC

500

VTA

VTA

VTA

Yes

Ball or Pillow

Block

As per

specification

Yes

1 / NA

Backward

Curved

DWDI

7931lps

500

621.75

1121.5

1481

Yes

Ball or Pillow

Block

Noted

Yes

Page 23: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 23 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Supply Fan Motor No. Required per Fan, Operation/Stand-by

Power Rating

Motor Enclosure/Ingress Protection

Motor Manufacturer

Motor Efficiency

Space Heater

-

KW

-

-

-

-

1 / NA

VTA

TEFC/IP55

Siemens

As per

specification

Yes

1 / NA

15 KW motor

TEFC/IP55 Siemens-Europe

IE1

Yes

3.4 Cooling Coil Section

No. Required per AHU, Operation/Stand-by

Type

Applicable Code

Total Cooling Capacity

Air Flow Rate

Entering Air Temperature, DB/WB

Leaving Air Temperature, DB/WB

Material, Tube/Fin

Fin Spacing

Limit of Coil Face Air Velocity

Min. Number of Refrigerant Circuits

Liquid/Gas

Corrosion Protection

Saline Atmosphere

-

-

-

KW

l/s

◦C

◦C

-

Ea/inch

m/s

ea

-

-

-

1/ NA

Direct

Expansion

As per

specification

As per HLC.

As per HLC.

As per HLC.

As per HLC.

Cu / Al

Max. 12

2.5

VTA

R 134a

Aeris Coating-

5year warranty

Yes

1/ NA

Direct

Expansion

Performance is

in accordance

with AHRI-410.

200.97

7931

28.6/19.6

12.38/12.34

Cu / Al

Max. 12

2.0

3

R 134a

Aeris Coating-

5year warranty

Yes

Page 24: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 24 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Hydrogen Sulphide

Min. Life of Cooling Coil

Condensate Drain

Drain Pan Material

-

Years

-

-

Yes

5

Yes

SS with Insulation

Yes

5

Yes

SS with Insulation

3.5 Filter Section

Pre Filter

Type

Efficiency

Thickness

Filter Face Velocity

Limit of Initial Pressure drop

Limit of Final Pressure drop

Final Filter Type

Efficiency

Thickness

Filter Face Velocity

Limit of Initial Pressure Drop

Limit of Final Pressure Drop

-

%

mm

m/s

Pa

Pa

-

%

Mm

m/s

Pa

Pa

Panel

G4

50

2.5

Depends on

Face Velocity

VTA

Bag

F8(En 779)

533

2.5

Depends on

Face Velocity

VTA

Panel

G4

50

<2.5

38.5[Clean] &

143.75[Mean]

250pa[Dirty]

Pleated

F8(En 779)

100mm

<2.5

110.5[Clean] &

242[Mean]

373.5pa[Dirty]

Page 25: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 25 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

3.6 Casing

Type

Material (G-90 Galvanized Steel or

Aluminium)

Insulation Material

Density

Thickness

Painting

-

-

-

kg/m3

mm

Mfr/job Spec.

Double Wall

Galvanized

Steel

Fiber Glass

comply to

NFPA-90A, B

32

50

As per

specification

Double Wall

Galvanized

Steel

Fiber Glass

comply to

NFPA-90A, B

32

50

SKM Marine standard Painting

3.7 Air Cooled Condensing Parts Compressor

Make

Model

No. of Compressor per ACCU

Compressor Type,

(Reciprocating/Screw/Scroll/Hermetic/Semi-

hermetic)

COP (Coefficient of Performance)

Power Rating per Compressor

Capacity Control Steps per Compressor

-

-

Ea

-

-

-

%

VTA

VTA

VTA

Scroll

As per Final

Selection

As per Final

Selection

VTA

Copeland-USA

ZR 250 [SKM

model]

6

Scroll

2.64

94.6KW[Total]

1 [0-100]

Page 26: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 26 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Min. Operating Capacity per Compressor

Vibration Isolator with Accessory

Crank case Heater requirement

Refrigerant

-

-

-

13%

As per standard

Yes

17%

As per SKM

Standard

Yes

Refrigerant Type

Refrigerant Charge

Condenser Coil No. of Circuits per ACCU

Material, Tube/Fin

Corrosion Protection forSaline Atmosphere

Hydrogen Sulphide Atmosphere

Condenser Fan Fan Type

No. of Fans per ACCU

Airflow Rate per Fan

Total Airflow Rate per ACCU

Total Power Rating of Fans per ACCU

Motor Insulation/Temp. Rise

Motor Enclosure/Ingress Protection

-

kg

ea

-

-

-

-

Ea

l/s

l/s

kw

-

-

R134a

VTA

VTA; shall be

provided after

HLC approval.

Cu / Al

Aeris Coating-5

year warranty

Yes

Propeller-Al

alloy

VTA

VTA

VTA

VTA

F / B

TEFC / IP55

R134a

28kg per circuit

[approx.]

3

Cu / Al

Aeris Coating-5

year warranty

Yes

Propeller-Al alloy

6

4318.3

25909.9

1.5

F / B

TEFC / IP55

Page 27: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 27 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Motor Manufacturer - Siemens Siemens

3.8 Common Parts

Control & Electrical Panel including Starter

Control & Electrical Panel Enclosure Class

Overload Relay Protection for Compressor

Overload Relay Protection for Condenser Fan

Security Grillers

Hilted Type Anchor

Disconnection Switch

Motorized Damper, SA

Eliminator

Access Door

Application section

Quantities

Marine Light and Sight Glass for liquid,

moisture indicator

Quantities

Q’ty of PDIS for each Filter Pres. Drop

-

-

-

-

-

-

-

-

-

-

-

-

-

Ea

ea

Yes

IP 55

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

All Sections

2 (Fan & Filter)

Yes

2

2

Yes

IP 55

Yes

Yes

Yes

Yes,

As applicable

By EMCC

By EMCC

Yes

Yes

Fan section

1 (Fan),

Access panel for

filter

Yes

1

2

3.9 Overall Dimension Weight

Dimensions, Length

Width

Height

Weight, Operating

mm

mm

mm

Kg

VTA

VTA

VTA

VTA

5983 [frame size]

2540

2570

6525

Page 28: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 28 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

3.10 Interface with HVAC Control Panel

Start/Stop from HCP to LCP

Running Status Signal from LCP to HCP

Trip Signal from LCP to HCP

Temperature Setting Value

Signal(4˜20mA)from HCP to LCP

Compressor Control Signal(4˜20mA)from

HCP to LCP

Dirt indication of pre-filter

Dirt indication of final filter

-

-

-

-

-

-

-

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Digital on/off/trip

Yes,VFC provided

Yes,VFC provided

Page 29: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 29 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Bidder

4.0 PACKAGED AIR CONDITIONING UNIT (ROOF TOP UNIT) – BUHASA 33KV SS 4.1 General

Equipment Tag Number

No. Required, Operation/Stand by

Duty

Type

Manufacturer

Model No.

Applicable Code

Air Supply System

Electric Power Source

Total Power Rating

Max. Start Current/Operating Current

-

Set

-

-

-

-

-

(CAV/VAV)

(V/Ph/Hz)

KW

A

ACU-16,17,18

2 / 1

Continuous

Floor Mounted

SKM

-

As per

specification

CAV

415 / 3 / 50

VTA

VTA

ACU-16,17,18

2 / 1

Noted

Floor Mounted

SKM

PACV 53095SM Rated in

accordance with

AHRI 340/360

CAV

415/3/50 4 wire

146.00

577/322

4.2 Equipment Location Condition

Location

Elevation (above sea level)

Barometer

Ambient Temperature, Max./Min

Design Temperature, Max. /Min.

Indoor

Outdoor Roof

Ground

Weather Protection Required

Tropicalization Required

-

M

Bar

°C

°C

-

-

-

-

-

Onshore

100

1.0013

55.0 / 5.0

50.0 / 5.0

No

Yes

No

Yes

Yes

Onshore

100

1.0013

55.0 / 5.0

50.0 / 5.0

Not Applicable

Yes

No

Yes

Yes

Page 30: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 30 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Unusual Condition Corrosive

Dust

Fumes

Others

Hazardous Area Classification

Noise Level

-

-

-

-

-

dB(A) @ 1m

Yes

Yes

No

Saline

Atmosphere

Not classified

area

85

Yes

Yes

No

Saline

Atmosphere

Not Classified

85

4.3 Fan Section

Supply Fan No. Required per AHU, Operation/Stand-by

Type (Airfoil/Backward

Inclined/Backward/Forward)

Construction Type (DWDI/SWSI)

Supply Air Flow Rate

External Static Pressure

Internal Static Pressure

Total Static Pressure

Fan Speed

Vibration Isolator with Accessory

Bearing Type

Applicable Code

AMCA Certification

Set

-

-

l/s

Pa

Pa

Pa

Rpm

-

-

-

-

1 / NA

Forward

Curved

DWDI

As per

approved HLC

500

VTA

VTA

VTA

Yes

Ball or Pillow

Block

As per

specification

Yes

1 / NA

Backward

Curved

DWDI

130502.5lps

500

575

1075

973

Yes

Ball or Pillow

Block

Noted

Yes

Page 31: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 31 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Supply Fan Motor No. Required per Fan, Operation/Stand-by

Power Rating

Motor Enclosure/Ingress Protection

Motor Manufacturer

Motor Efficiency

Space Heater

-

KW

-

-

-

-

1 / NA

VTA

TEFC/IP55

Siemens

As per

specification

Yes

1 / NA

22KW motor

TEFC/IP55 Siemens-Europe

IE1

Yes

4.4 Cooling Coil Section

No. Required per AHU, Operation/Stand-by

Type

Applicable Code

Total Cooling Capacity

Air Flow Rate

Entering Air Temperature, DB/WB

Leaving Air Temperature, DB/WB

Material, Tube/Fin

Fin Spacing

Limit of Coil Face Air Velocity

Min. Number of Refrigerant Circuits

Liquid/Gas

Corrosion Protection

Saline Atmosphere

-

-

-

KW

l/s

◦C

◦C

-

Ea/inch

m/s

ea

-

-

-

1/ NA

Direct

Expansion

As per

specification

As per HLC.

As per HLC.

As per HLC.

As per HLC.

Cu / Al

Max. 12

2.5

VTA

R 134a

Aeris Coating-

5year warranty

Yes

1/ NA

Direct

Expansion

Performance is

in accordance

with AHRI-410.

250.48

13502.5

26.2/18.1

12.67/12.65

Cu / Al

Max. 12

1.82

3

R 134a

Aeris Coating-

5year warranty

Yes

Page 32: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 32 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Hydrogen Sulphide

Min. Life of Cooling Coil

Condensate Drain

Drain Pan Material

-

Years

-

-

Yes

5

Yes

SS with Insulation

Yes

5

Yes

SS with Insulation

4.5 Filter Section

Pre Filter

Type

Efficiency

Thickness

Filter Face Velocity

Limit of Initial Pressure drop

Limit of Final Pressure drop

Final Filter Type

Efficiency

Thickness

Filter Face Velocity

Limit of Initial Pressure Drop

Limit of Final Pressure Drop

-

%

mm

m/s

Pa

Pa

-

%

Mm

m/s

Pa

Pa

Panel

G4

50

2.5

Depends on

Face Velocity

VTA

Bag

F8(En 779)

533

2.5

Depends on

Face Velocity

VTA

Panel

G4

50

<2.5

33[Clean] &

141[Mean]

250pa[Dirty]

Pleated

F8(En 779)

100mm

<2.5

100.5[Clean] &

237[Mean]

373.5pa[Dirty]

Page 33: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 33 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

4.6 Casing

Type

Material (G-90 Galvanized Steel or

Aluminium)

Insulation Material

Density

Thickness

Painting

-

-

-

kg/m3

mm

Mfr/job Spec.

Double Wall

Galvanized

Steel

Fiber Glass

comply to

NFPA-90A, B

32

50

As per specification

Double Wall

Galvanized

Steel

Fiber Glass

comply to

NFPA-90A, B

32

50

SKM Marine standard Painting

4.7 Air Cooled Condensing Parts Compressor

Make

Model

No. of Compressor per ACCU

Compressor Type,

(Reciprocating/Screw/Scroll/Hermetic/Semi-

hermetic)

COP (Coefficient of Performance)

Power Rating per Compressor

Capacity Control Steps per Compressor

-

-

Ea

-

-

Kw

-

VTA

VTA

VTA

Scroll

As per Final

Selection

As per Final

Selection

VTA

Copeland-USA

ZR 310 + ZR 250

[SKM model]

5+1

Scroll

2.8

115KW[Total]

1 [0-100]

Page 34: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 34 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Min. Operating Capacity per Compressor

Vibration Isolator with Accessory

Crank case Heater requirement

Refrigerant

%

-

-

13%

As per standard

Yes

17%

As per SKM

Standard

Yes

Refrigerant Type

Refrigerant Charge

Condenser Coil No. of Circuits per ACCU

Material, Tube/Fin

Corrosion Protection forSaline Atmosphere

Hydrogen Sulphide Atmosphere

Condenser Fan Fan Type

No. of Fans per ACCU

Airflow Rate per Fan

Total Airflow Rate per ACCU

Total Power Rating of Fans per ACCU

Motor Insulation/Temp. Rise

Motor Enclosure/Ingress Protection

-

kg

ea

-

-

-

-

Ea

l/s

l/s

kw

-

-

R134a

VTA

VTA; shall be

provided after

HLC approval.

Cu / Al

Aeris Coating-5

year warranty

Yes

Propeller-Al alloy

VTA

VTA

VTA

VTA

F / B

TEFC / IP55

R134a

38kg per circuit

[Approx]

3

Cu / Al

Aeris Coating-5

year warranty

Yes

Propeller-Al alloy

6

4667.57

28005.4

1.5

F / B

TEFC / IP55

Page 35: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 35 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Motor Manufacturer - Siemens Siemens

4.8 Common Parts

Control & Electrical Panel including Starter

Control & Electrical Panel Enclosure Class

Overload Relay Protection for Compressor

Overload Relay Protection for Condenser Fan

Security Grillers

Hilted Type Anchor

Disconnection Switch

Motorized Damper, SA

Eliminator

Access Door

Application section

Quantities

Marine Light and Sight Glass for liquid,

moisture indicator

Quantities

Q’ty of PDIS for each Filter Pres. Drop

-

-

-

-

-

-

-

-

-

-

-

-

-

Ea

ea

Yes

IP 55

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

All Sections

2 (Fan & Filter)

Yes

2

2

Yes

IP 55

Yes

Yes

Yes

Yes,

As applicable

By EMCC

By EMCC

Yes

Yes

Fan section

1 (Fan),

Access panel for

filter

Yes

1

2

4.9 Overall Dimension Weight Dimensions, Length

Width

Height

Weight, Operating

mm

mm

mm

Kg

VTA

VTA

VTA

VTA

7711 [frame size]

2540

3553

9410

Page 36: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 36 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

4.10 Interface with HVAC Control Panel

Start/Stop from HCP to LCP

Running Status Signal from LCP to HCP

Trip Signal from LCP to HCP

Temperature Setting Value

Signal(4˜20mA)from HCP to LCP

Compressor Control Signal(4˜20mA)from

HCP to LCP

Dirt indication of pre-filter

Dirt indication of final filter

-

-

-

-

-

-

-

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Digital on/off/trip

Yes,VFC provided

Yes,VFC provided

Page 37: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 37 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Bidder

5.0 PACKAGED AIR CONDITIONING UNIT (ROOF TOP UNIT) – ASAB STATCOM 5.1 General

Equipment Tag Number

No. Required, Operation/Stand by

Duty

Type

Manufacturer

Model No.

Applicable Code

Air Supply System

Electric Power Source

Total Power Rating

Max. Start Current/Operating Current

-

Set

-

-

-

-

-

(CAV/VAV)

(V/Ph/Hz)

KW

A

ACU-12,13

1 / 1

Continuous

Floor Mounted

SKM

-

As per

specification

CAV

415 / 3 / 50

VTA

VTA

ACU-12,13

1 / 1

Noted

Floor Mounted

SKM

PACV 53085 SM Rated in

accordance with

AHRI 340/360

CAV

415/3/50 4 wire

132.2

559/304

5.2 Equipment Location Condition

Location

Elevation (above sea level)

Barometer

Ambient Temperature, Max./Min

Design Temperature, Max. /Min.

Indoor

Outdoor Roof

Ground

Weather Protection Required

Tropicalization Required

-

M

Bar

°C

°C

-

-

-

-

-

Onshore

100

1.0013

55.0 / 5.0

50.0 / 5.0

No

Yes

No

Yes

Yes

Onshore

100

1.0013

55.0 / 5.0

50.0 / 5.0

Not Applicable

Yes

No

Yes

Yes

Page 38: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 38 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Unusual Condition Corrosive

Dust

Fumes

Others

Hazardous Area Classification

Noise Level

-

-

-

-

-

dB(A) @ 1m

Yes

Yes

No

Saline

Atmosphere

Not classified

area

85

Yes

Yes

No

Saline

Atmosphere

Not Classified

84.9

5.3 Fan Section

Supply Fan No. Required per AHU, Operation/Stand-by

Type (Airfoil/Backward

Inclined/Backward/Forward)

Construction Type (DWDI/SWSI)

Supply Air Flow Rate

External Static Pressure

Internal Static Pressure

Total Static Pressure

Fan Speed

Vibration Isolator with Accessory

Bearing Type

Applicable Code

AMCA Certification

Set

-

-

l/s

Pa

Pa

Pa

Rpm

-

-

-

-

1 / NA

Forward

Curved

DWDI

As per

approved HLC

500

VTA

VTA

VTA

Yes

Ball or Pillow

Block

As per

specification

Yes

1 / NA

Backward

Curved

DWDI

11708lps

500

725.5

1225.5

1171

Yes

Ball or Pillow

Block

Noted

Yes

Page 39: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 39 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Supply Fan Motor No. Required per Fan, Operation/Stand-by

Power Rating

Motor Enclosure/Ingress Protection

Motor Manufacturer

Motor Efficiency

Space Heater

-

KW

-

-

-

-

1 / NA

VTA

TEFC/IP55

Siemens

As per

specification

Yes

1 / NA

22KW motor

TEFC/IP55 Siemens-Europe

IE1

Yes

5.4 Cooling Coil Section

No. Required per AHU, Operation/Stand-by

Type

Applicable Code

Total Cooling Capacity

Air Flow Rate

Entering Air Temperature, DB/WB

Leaving Air Temperature, DB/WB

Material, Tube/Fin

Fin Spacing

Limit of Coil Face Air Velocity

Min. Number of Refrigerant Circuits

Liquid/Gas

Corrosion Protection

Saline Atmosphere

-

-

-

KW

l/s

◦F

◦F

-

Ea/inch

m/s

ea

-

-

-

1/ NA

Direct

Expansion

As per

specification

As per HLC.

As per HLC.

As per HLC.

As per HLC.

Cu / Al

Max. 12

2.5

VTA

R 134a

Aeris Coating-

5year warranty

Yes

1/ NA

Direct

Expansion

performance is

in accordance

with AHRI-410.

221.11

11708

26.4/18.1

12.58/12.54

Cu / Al

Max. 12

2.36

3

R 134a

Aeris Coating-

5year warranty

Yes

Page 40: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 40 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Hydrogen Sulphide

Min. Life of Cooling Coil

Condensate Drain

Drain Pan Material

-

Years

-

-

Yes

5

Yes

SS with Insulation

Yes

5

Yes

SS with Insulation

5.5 Filter Section

Pre Filter

Type

Efficiency

Thickness

Filter Face Velocity

Limit of Initial Pressure drop

Limit of Final Pressure drop

Final Filter Type

Efficiency

Thickness

Filter Face Velocity

Limit of Initial Pressure Drop

Limit of Final Pressure Drop

-

%

mm

m/s

Pa

Pa

-

%

Mm

m/s

Pa

Pa

Panel

G4

50

2.5

Depends on

Face Velocity

VTA

Bag

F8(En 779)

533

2.5

Depends on

Face Velocity

VTA

Panel

G4

50

<2.5

55[Clean] &

152[Mean]

250pa[Dirty]

Pleated

F8(En 779)

100mm

<2.5

130.5[Clean] &

252[Mean]

373.5pa[Dirty]

Page 41: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 41 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

5.6 Casing

Type

Material (G-90 Galvanized Steel or

Aluminium)

Insulation Material

Density

Thickness

Painting

-

-

-

kg/m3

mm

Mfr/job Spec.

Double Wall

Galvanized

Steel

Fiber Glass

comply to

NFPA-90A, B

32

50

As per

specification

Double Wall

Galvanized

Steel

Fiber Glass

comply to

NFPA-90A, B

32

50

SKM Marine standard Painting

5.7 Air Cooled Condensing Parts Compressor

Make

Model

No. of Compressor per ACCU

Compressor Type,

(Reciprocating/Screw/Scroll/Hermetic/Semi-

hermetic)

COP (Coefficient of Performance)

Power Rating per Compressor

Capacity Control Steps per Compressor

Min. Operating Capacity per Compressor

-

-

Ea

-

-

KW

%

-

VTA

VTA

VTA

Scroll

As per Final

Selection

As per Final

Selection

VTA

13%

Copeland-USA

ZR 310 + ZR 250

[SKM model]

2+4

Scroll

2.74

101.2KW[Total]

1 [0-100]

18%

Page 42: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 42 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Vibration Isolator with Accessory

Crank case Heater requirement

Refrigerant

-

-

As per standard

Yes

As per SKM

Standard

Yes

Refrigerant Type

Refrigerant Charge

Condenser Coil No. of Circuits per ACCU

Material, Tube/Fin

Corrosion Protection forSaline Atmosphere

Hydrogen Sulphide Atmosphere

Condenser Fan Fan Type

No. of Fans per ACCU

Airflow Rate per Fan

Total Airflow Rate per ACCU

Total Power Rating of Fans per ACCU

Motor Insulation/Temp. Rise

Motor Enclosure/Ingress Protection

Motor Manufacturer

-

kg

ea

-

-

-

-

Ea

l/s

l/s

kw

-

-

-

R134a

VTA

VTA; shall be

provided after

HLC approval.

Cu / Al

Aeris Coating-5

year warranty

Yes

Propeller-Al

alloy

VTA

VTA

VTA

VTA

F / B

TEFC / IP55

Siemens

R134a

35kg per

circuit[Approx]

3

Cu / Al

Aeris Coating-5

year warranty

Yes

Propeller-Al alloy

6

4667.57

28005.4

1.5

F / B

TEFC / IP55

Siemens

Page 43: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 43 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

5.8 Common Parts

Control & Electrical Panel including Starter

Control & Electrical Panel Enclosure Class

Overload Relay Protection for Compressor

Overload Relay Protection for Condenser Fan

Security Grillers

Hilted Type Anchor

Disconnection Switch

Motorized Damper, SA

Eliminator

Access Door

Application section

Quantities

Marine Light and Sight Glass for liquid,

moisture indicator

Quantities

Q’ty of PDIS for each Filter Pres. Drop

-

-

-

-

-

-

-

-

-

-

-

-

-

Ea

ea

Yes

IP 55

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

All Sections

2 (Fan & Filter)

Yes

2

2

Yes

IP 55

Yes

Yes

Yes

Yes,

As applicable

By EMCC

By EMCC

Yes

Yes

Fan section

1 (Fan),

Access panel for

filter

Yes

1

2

5.9 Overall Dimension Weight

Dimensions, Length

Width

Height

Weight, Operating

mm

mm

mm

Kg

VTA

VTA

VTA

VTA

6237 [frame size]

2540

2893

7725

Page 44: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 44 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

5.10 Interface with HVAC Control Panel

Start/Stop from HCP to LCP

Running Status Signal from LCP to HCP

Trip Signal from LCP to HCP

Temperature Setting Value

Signal(4˜20mA)from HCP to LCP

Compressor Control Signal(4˜20mA)from

HCP to LCP

Dirt indication of pre-filter

Dirt indication of final filter

-

-

-

-

-

-

-

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Digital on/off/trip

Yes,VFC provided

Yes,VFC provided

Page 45: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 45 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Bidder

6.0 PACKAGED AIR CONDITIONING UNIT (ROOF TOP UNIT) – BAB STATCOM 6.1 General

Equipment Tag Number

No. Required, Operation/Stand by

Duty

Type

Manufacturer

Model No.

Applicable Code

Air Supply System

Electric Power Source

Total Power Rating

Max. Start Current/Operating Current

-

Set

-

-

-

-

-

(CAV/VAV)

(V/Ph/Hz)

KW

A

ACU-09,10

1 / 1

Continuous

Floor Mounted

SKM

-

As per

specification

CAV

415 / 3 / 50

VTA

VTA

ACU-09,10

1 / 1

Noted

Floor Mounted

SKM

PACV 53085SM Rated in

accordance with

AHRI 340/360

CAV

415/3/50 4 wire

132.7

559/304

6.2 Equipment Location Condition

Location

Elevation (above sea level)

Barometer

Ambient Temperature, Max./Min

Design Temperature, Max. /Min.

Indoor

Outdoor Roof

Ground

Weather Protection Required

Tropicalization Required

-

M

Bar

°C

°C

-

-

-

-

-

Onshore

100

1.0013

55.0 / 5.0

50.0 / 5.0

No

Yes

No

Yes

Yes

Onshore

100

1.0013

55.0 / 5.0

50.0 / 5.0

Not Applicable

Yes

No

Yes

Yes

Page 46: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 46 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Unusual Condition Corrosive

Dust

Fumes

Others

Hazardous Area Classification

Noise Level

-

-

-

-

-

dB(A) @ 1m

Yes

Yes

No

Saline

Atmosphere

Not classified

area.

85

Yes

Yes

No

Saline

Atmosphere

Not Classified

84.9

6.3 Fan Section

Supply Fan No. Required per AHU, Operation/Stand-by

Type (Airfoil/Backward

Inclined/Backward/Forward)

Construction Type (DWDI/SWSI)

Supply Air Flow Rate

External Static Pressure

Internal Static Pressure

Total Static Pressure

Fan Speed

Vibration Isolator with Accessory

Bearing Type

Applicable Code

AMCA Certification

Set

-

-

l/s

Pa

Pa

Pa

Rpm

-

-

-

-

1 / NA

Forward

Curved

DWDI

As per

approved HLC

500

VTA

VTA

VTA

Yes

Ball or Pillow

Block

As per

specification

Yes

1 / NA

Backward

Curved

DWDI

11993lps

500

574

1074

1129

Yes

Ball or Pillow

Block

Noted

Yes

Page 47: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 47 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Supply Fan Motor No. Required per Fan, Operation/Stand-by

Power Rating

Motor Enclosure/Ingress Protection

Motor Manufacturer

Motor Efficiency

Space Heater

-

KW

-

-

-

-

1 / NA

VTA

TEFC/IP55

Siemens

As per

specification

Yes

1 / NA

22KW motor

TEFC/IP55 Siemens-Europe

IE1

Yes

6.4 Cooling Coil Section

No. Required per AHU, Operation/Stand-by

Type

Applicable Code

Total Cooling Capacity

Air Flow Rate

Entering Air Temperature, DB/WB

Leaving Air Temperature, DB/WB

Material, Tube/Fin

Fin Spacing

Limit of Coil Face Air Velocity

Min. Number of Refrigerant Circuits

Liquid/Gas

Corrosion Protection

Saline Atmosphere

-

-

-

KW

l/s

◦F

◦F

-

Ea/inch

m/s

ea

-

-

-

1/ NA

Direct

Expansion

As per

specification

As per HLC.

As per HLC.

As per HLC.

As per HLC.

Cu / Al

Max. 12

2.5

VTA

R 134a

Aeris Coating-

5year warranty

Yes

1/ NA

Direct

Expansion

Performance is

in accordance

with AHRI-410.

227.27

11993

26.4/18.1

12.54/12.52

Cu / Al

Max. 12

1.76

3

R 134a

Aeris Coating-

5year warranty

Yes

Page 48: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 48 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Hydrogen Sulphide

Min. Life of Cooling Coil

Condensate Drain

Drain Pan Material

-

Years

-

-

Yes

5

Yes

SS with Insulation

Yes

5

Yes

SS with Insulation

6.5 Filter Section

Pre Filter

Type

Efficiency

Thickness

Filter Face Velocity

Limit of Initial Pressure drop

Limit of Final Pressure drop

Final Filter Type

Efficiency

Thickness

Filter Face Velocity

Limit of Initial Pressure Drop

Limit of Final Pressure Drop

-

%

mm

m/s

Pa

Pa

-

%

Mm

m/s

Pa

Pa

Panel

G4

50

2.5

Depends on

Face Velocity

VTA

Bag

F8(En 779)

533

2.5

Depends on

Face Velocity

VTA

Panel

G4

50

<2.5

29[Clean] &

139[Mean]

250pa[Dirty]

Pleated

F8(En 779)

100mm

<2.5

96.5[Clean] &

235[Mean]

373.5pa[Dirty]

Page 49: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 49 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

6.6 Casing

Type

Material (G-90 Galvanized Steel or

Aluminium)

Insulation Material

Density

Thickness

Painting

-

-

-

kg/m3

mm

Mfr/job Spec.

Double Wall

Galvanized

Steel

Fiber Glass

comply to

NFPA-90A, B

32

50

As per

specification

Double Wall

Galvanized

Steel

Fiber Glass

comply to

NFPA-90A, B

32

50

SKM Marine standard Painting

6.7 Air Cooled Condensing Parts Compressor

Make

Model

No. of Compressor per ACCU

Compressor Type,

(Reciprocating/Screw/Scroll/Hermetic/Semi-

hermetic)

COP (Coefficient of Performance)

Power Rating per Compressor

Capacity Control Steps per Compressor

Min. Operating Capacity per Compressor

-

-

Ea

-

-

Kw

%

-

VTA

VTA

VTA

Scroll

As per Final

Selection

As per Final

Selection

VTA

13%

Copeland-USA

ZR 310 + ZR 250

[SKM model]

2+4

Scroll

2.86

101.7KW[Total]

1 [0-100]

18%

Page 50: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 50 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Vibration Isolator with Accessory

Crank case Heater requirement

Refrigerant

-

-

As per standard

Yes

As per SKM

Standard

Yes

Refrigerant Type

Refrigerant Charge

Condenser Coil No. of Circuits per ACCU

Material, Tube/Fin

Corrosion Protection forSaline Atmosphere

Hydrogen Sulphide Atmosphere

Condenser Fan Fan Type

No. of Fans per ACCU

Airflow Rate per Fan

Total Airflow Rate per ACCU

Total Power Rating of Fans per ACCU

Motor Insulation/Temp. Rise

Motor Enclosure/Ingress Protection

Motor Manufacturer

-

kg

ea

-

-

-

-

Ea

l/s

l/s

kw

-

-

-

R134a

VTA

VTA; shall be

provided after

HLC approval.

Cu / Al

Aeris Coating-5

year warranty

Yes

Propeller-Al

alloy

VTA

VTA

VTA

VTA

F / B

TEFC / IP55

Siemens

R134a

35kg per circuit

[approx.]

3

Cu / Al

Aeris Coating-5

year warranty

Yes

Propeller-Al alloy

6

4667.57

28005.4

1.5

F / B

TEFC / IP55

Siemens

Page 51: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 51 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

6.8 Common Parts

Control & Electrical Panel including Starter

Control & Electrical Panel Enclosure Class

Overload Relay Protection for Compressor

Overload Relay Protection for Condenser Fan

Security Grillers

Hilted Type Anchor

Disconnection Switch

Motorized Damper, SA

Eliminator

Access Door

Application section

Quantities

Marine Light and Sight Glass for liquid,

moisture indicator

Quantities

Q’ty of PDIS for each Filter Pres. Drop

-

-

-

-

-

-

-

-

-

-

-

-

-

Ea

ea

Yes

IP 55

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

All Sections

2 (Fan & Filter)

Yes

2

2

Yes

IP 55

Yes

Yes

Yes

Yes,

As applicable

By EMCC

By EMCC

Yes

Yes

Fan section

1 (Fan),

Access panel for

filter

Yes

1

2

6.9 Overall Dimension Weight

Dimensions, Length

Width

Height

Weight, Operating

mm

mm

mm

Kg

VTA

VTA

VTA

VTA

7660 [frame size]

2540

3172

8880

Page 52: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 52 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

6.10 Interface with HVAC Control Panel

Start/Stop from HCP to LCP

Running Status Signal from LCP to HCP

Trip Signal from LCP to HCP

Temperature Setting Value

Signal(4˜20mA)from HCP to LCP

Compressor Control Signal(4˜20mA)from

HCP to LCP

Dirt indication of pre-filter

Dirt indication of final filter

-

-

-

-

-

-

-

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Digital on/off/trip

Yes,VFC provided

Yes,VFC provided

Page 53: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 53 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

7.0 PACKAGED AIR CONDITIONING UNIT (ROOF TOP UNIT) – BUHASA STATCOM 7.1 General

Equipment Tag Number

No. Required, Operation/Stand by

Duty

Type

Manufacturer

Model No.

Applicable Code

Air Supply System

Electric Power Source

Total Power Rating

Max. Start Current/Operating Current

-

Set

-

-

-

-

-

(CAV/VAV)

(V/Ph/Hz)

KW

A

ACU-14,15

1 / 1

Continuous

Floor Mounted

SKM

-

As per

specification

CAV

415 / 3 / 50

VTA

VTA

ACU-14,15

1 / 1

Noted

Floor Mounted

SKM

PACV 53085SM Rated in

accordance with

AHRI 340/360

CAV

415/3/50 4 wire

132.2

559/304

7.2 Equipment Location Condition

Location

Elevation (above sea level)

Barometer

Ambient Temperature, Max./Min

Design Temperature, Max. /Min.

Indoor

Outdoor Roof

Ground

Weather Protection Required

Tropicalization Required

-

M

Bar

°C

°C

-

-

-

-

-

Onshore

100

1.0013

55.0 / 5.0

50.0 / 5.0

No

Yes

No

Yes

Yes

Onshore

100

1.0013

55.0 / 5.0

50.0 / 5.0

Not Applicable

Yes

No

Yes

Yes

Page 54: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 54 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Unusual Condition Corrosive

Dust

Fumes

Others

Hazardous Area Classification

Noise Level

-

-

-

-

-

dB(A) @ 1m

Yes

Yes

No

Saline

Atmosphere

Not classified

area

85

Yes

Yes

No

Saline

Atmosphere

Not Classified

84.9

7.3 Fan Section

Supply Fan No. Required per AHU, Operation/Stand-by

Type (Airfoil/Backward

Inclined/Backward/Forward)

Construction Type (DWDI/SWSI)

Supply Air Flow Rate

External Static Pressure

Internal Static Pressure

Total Static Pressure

Fan Speed

Vibration Isolator with Accessory

Bearing Type

Applicable Code

AMCA Certification

Set

-

-

l/s

Pa

Pa

Pa

Rpm

-

-

-

-

1 / NA

Forward

Curved

DWDI

As per

approved HLC

500

VTA

VTA

VTA

Yes

Ball or Pillow

Block

As per

specification

Yes

1 / NA

Backward

Curved

DWDI

11796lps

500

759

1259

1185

Yes

Ball or Pillow

Block

Noted

Yes

Page 55: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 55 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Supply Fan Motor No. Required per Fan, Operation/Stand-by

Power Rating

Motor Enclosure/Ingress Protection

Motor Manufacturer

Motor Efficiency

Space Heater

-

KW

-

-

-

-

1 / NA

VTA

TEFC/IP55

Siemens

As per

specification

Yes

1 / NA

22KW motor

TEFC/IP55 Siemens-Europe

IE1

Yes

7.4 Cooling Coil Section

No. Required per AHU, Operation/Stand-by

Type

Applicable Code

Total Cooling Capacity

Air Flow Rate

Entering Air Temperature, DB/WB

Leaving Air Temperature, DB/WB

Material, Tube/Fin

Fin Spacing

Limit of Coil Face Air Velocity

Min. Number of Refrigerant Circuits

Liquid/Gas

Corrosion Protection

Saline Atmosphere

-

-

-

KW

l/s

◦F

◦F

-

Ea/inch

m/s

ea

-

-

-

1/ NA

Direct

Expansion

As per

specification

As per HLC.

As per HLC.

As per HLC.

As per HLC.

Cu / Al

Max. 12

2.5

VTA

R 134a

Aeris Coating-

5year warranty

Yes

1/ NA

Direct

Expansion

Performance is

in accordance

with AHRI-410.

221.76

11796

26.4/18.2

12.74/12.69

Cu / Al

Max. 12

2.46

3

R 134a

Aeris Coating-

5year warranty

Yes

Page 56: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 56 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Hydrogen Sulphide

Min. Life of Cooling Coil

Condensate Drain

Drain Pan Material

-

Years

-

-

Yes

5

Yes

SS with Insulation

Yes

5

Yes

SS with Insulation

7.5 Filter Section

Pre Filter

Type

Efficiency

Thickness

Filter Face Velocity

Limit of Initial Pressure drop

Limit of Final Pressure drop

Final Filter Type

Efficiency

Thickness

Filter Face Velocity

Limit of Initial Pressure Drop

Limit of Final Pressure Drop

-

%

mm

m/s

Pa

Pa

-

%

Mm

m/s

Pa

Pa

Panel

G4

50

2.5

Depends on

Face Velocity

VTA

Bag

F8(En 779)

533

2.5

Depends on

Face Velocity

VTA

Panel

G4

50

<2.5

65[Clean] &

157[Mean]

250pa[Dirty]

Pleated

F8(En 779)

100mm

<2.5

136.5[Clean] &

255[Mean]

373.5pa[Dirty]

Page 57: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 57 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

7.6 Casing

Type

Material (G-90 Galvanized Steel or

Aluminium)

Insulation Material

Density

Thickness

Painting

-

-

-

kg/m3

mm

Mfr/job Spec.

Double Wall

Galvanized

Steel

Fiber Glass

comply to

NFPA-90A, B

32

50

As per

specification

Double Wall

Galvanized

Steel

Fiber Glass

comply to

NFPA-90A, B

32

50

SKM Marine standard Painting

7.7 Air Cooled Condensing Parts Compressor

Make

Model

No. of Compressor per ACCU

Compressor Type,

(Reciprocating/Screw/Scroll/Hermetic/Semi-

hermetic)

COP (Coefficient of Performance)

Power Rating per Compressor

Capacity Control Steps per Compressor

Min. Operating Capacity per Compressor

Vibration Isolator with Accessory

-

-

Ea

-

Kw

-

%

VTA

VTA

VTA

Scroll

As per Final

Selection

As per Final

Selection

VTA

13%

As per standard

Copeland-USA

ZR 310 + ZR 250

[SKM model]

2+4

Scroll

2.71

101.2KW[Total]

1 [0-100]

18%

As per SKM

Page 58: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 58 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

Crank case Heater requirement

Refrigerant

-

-

-

Yes

Standard

Yes

Refrigerant Type

Refrigerant Charge

Condenser Coil No. of Circuits per ACCU

Material, Tube/Fin

Corrosion Protection forSaline Atmosphere

Hydrogen Sulphide Atmosphere

Condenser Fan Fan Type

No. of Fans per ACCU

Airflow Rate per Fan

Total Airflow Rate per ACCU

Total Power Rating of Fans per ACCU

Motor Insulation/Temp. Rise

Motor Enclosure/Ingress Protection

Motor Manufacturer

-

kg

ea

-

-

-

-

Ea

l/s

l/s

kw

-

-

-

R134a

VTA

VTA; shall be

provided after

HLC approval.

Cu / Al

Aeris Coating-5

year warranty

Yes

Propeller-Al

alloy

VTA

VTA

VTA

VTA

F / B

TEFC / IP55

Siemens

R134a

35kg per

circuit[Approx]

3

Cu / Al

Aeris Coating-5

year warranty

Yes

Propeller-Al alloy

6

4667.57

28005.4

1.5

F / B

TEFC / IP55

Siemens

Page 59: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 59 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

7.8 Common Parts

Control & Electrical Panel including Starter

Control & Electrical Panel Enclosure Class

Overload Relay Protection for Compressor

Overload Relay Protection for Condenser Fan

Security Grillers

Hilted Type Anchor

Disconnection Switch

Motorized Damper, SA

Eliminator

Access Door

Application section

Quantities

Marine Light and Sight Glass for liquid,

moisture indicator

Quantities

Q’ty of PDIS for each Filter Pres. Drop

-

-

-

-

-

-

-

-

-

-

-

-

-

Ea

ea

Yes

IP 55

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

All Sections

2 (Fan & Filter)

Yes

2

2

Yes

IP 55

Yes

Yes

Yes

Yes,

As applicable

By EMCC

By EMCC

Yes

Yes

Fan section

1 (Fan),

Access panel for

filter

Yes

1

2

7.9 Overall Dimension Weight

Dimensions, Length

Width

Height

Weight, Operating

mm

mm

mm

Kg

VTA

VTA

VTA

VTA

6339 [frame size]

2540

2817

7709

Page 60: Data Sheet Packaged Unit- Rev 3

DOCUMENT TITLE:

TYPICAL DATA SHEETS FOR PACKAGED AC UNIT

Project No.: P11550

ADCO DOC NO. 30-99-27-5601

REV. 3 Date: 23/02/15

PAGE 60 OF 60

ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO

Field Design Data Unit Required Design

7.10 Interface with HVAC Control Panel Start/Stop from HCP to LCP Running Status Signal from LCP to HCP Trip Signal from LCP to HCP Temperature Setting Value

Signal(4˜20mA)from HCP to LCP Compressor Control Signal(4˜20mA)from

HCP to LCP Dirt indication of pre-filter Dirt indication of final filter

- - - - - - -

Yes Yes Yes Yes Yes Yes Yes

Yes Yes Yes Yes Digital on/off/trip

Yes,VFC provided Yes,VFC provided