ORIGINATOR: EMCC CO. LLC SLLC DOC No.: - Contract No. 15519.01 / EC10845
ADCO DOC. No. 30-99-27-5601 PROJ. No. P11550 Pages 1 of 60
ENGINEERING, PROCUREMENT AND CONSTRUCTION FOR POWER NETWORK UPGRADE AT ALL ADCO FIELDS
ADCO Document No. 30-99-27-5601
Typical Data Sheets for Packaged AC Units
3 18-Nov-15 HA ALA KT Issued for Approval 2 30-Apr-15 HA ALA KT Issued for Approval 1 22-Mar-15 HA ALA KT Issued for Approval B 23-Feb-15 HA ALA KT Issued for Approval A 17-Jan-15 HA ALA KT Issued for Review
REV. DATE ORIGINATOR REVIEWED APPROVED DESCRIPTION THIS DOCUMENT IS INTENDED FOR USE BY ADCO AND ITS NOMINATED CONSULTANTS, CONTRACTORS, MANUFACTURERS AND SUPPLIERS.
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 18/11/15
PAGE 2 OF 60
TABLE OF CONTENTS
1.0 PACKAGED AIE CONDITIONING UNIT-ASAB 33KV SUBSTATION .............................5
1.1 GENERAL ..............................................................................................................5
1.2 EQUIPMENT LOCATION CONDITION ..................................................................5
1.3 FAN SELECTION ...................................................................................................6
1.4 COOLING COIL SELECTION ................................................................................7
1.5 FILTER SELECTION ..............................................................................................8
1.6 CASING .................................................................................................................9
1.7 AIR COOLED CONDENSING PARTS ...................................................................9
1.8 COMMON PARTS ................................................................................................ 11
1.9 OVERALL DIMENSION WEIGHT ........................................................................ 11
1.10 INTERFACE WITH HVAC CONTROL PANEL ..................................................... 12
2.0 PACKAGED AIE CONDITIONING UNIT-BAB 33KV SUBSTATION.............................. 13
2.1 GENERAL ............................................................................................................ 13
2.2 EQUIPMENT LOCATION CONDITION ................................................................ 13
2.3 FAN SELECTION ................................................................................................. 14
2.4 COOLING COIL SELECTION .............................................................................. 15
2.5 FILTER SELECTION ............................................................................................ 16
2.6 CASING ............................................................................................................... 17
2.7 AIR COOLED CONDENSING PARTS ................................................................. 17
2.8 COMMON PARTS ................................................................................................ 19
2.9 OVERALL DIMENSION WEIGHT ........................................................................ 19
2.10 INTERFACE WITH HVAC CONTROL PANEL ..................................................... 20
3.0 PACKAGED AIE CONDITIONING UNIT-BAB LDC BUILDING ..................................... 21
3.1 GENERAL ............................................................................................................ 21
3.2 EQUIPMENT LOCATION CONDITION ................................................................ 21
3.3 FAN SELECTION ................................................................................................. 22
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 18/11/15
PAGE 3 OF 60
3.4 COOLING COIL SELECTION .............................................................................. 23
3.5 FILTER SELECTION ............................................................................................ 24
3.6 CASING ............................................................................................................... 25
3.7 AIR COOLED CONDENSING PARTS ................................................................. 25
3.8 COMMON PARTS ................................................................................................ 27
3.9 OVERALL DIMENSION WEIGHT ........................................................................ 27
3.10 INTERFACE WITH HVAC CONTROL PANEL ..................................................... 28
4.0 PACKAGED AIE CONDITIONING UNIT-BUHASA 33KV SUBSTATION ...................... 29
4.1 GENERAL ............................................................................................................ 29
4.2 EQUIPMENT LOCATION CONDITION ................................................................ 29
4.3 FAN SELECTION ................................................................................................. 30
4.4 COOLING COIL SELECTION .............................................................................. 31
4.5 FILTER SELECTION ............................................................................................ 32
4.6 CASING ............................................................................................................... 33
4.7 AIR COOLED CONDENSING PARTS ................................................................. 33
4.8 COMMON PARTS ................................................................................................ 35
4.9 OVERALL DIMENSION WEIGHT ........................................................................ 35
4.10 INTERFACE WITH HVAC CONTROL PANEL ..................................................... 36
5.0 PACKAGED AIE CONDITIONING UNIT-ASAB STATCOM BUILDING ........................ 37
5.1 GENERAL ............................................................................................................ 37
5.2 EQUIPMENT LOCATION CONDITION ................................................................ 37
5.3 FAN SELECTION ................................................................................................. 38
5.4 COOLING COIL SELECTION .............................................................................. 39
5.5 FILTER SELECTION ............................................................................................ 40
5.6 CASING ............................................................................................................... 41
5.7 AIR COOLED CONDENSING PARTS ................................................................. 41
5.8 COMMON PARTS ................................................................................................ 43
5.9 OVERALL DIMENSION WEIGHT ........................................................................ 43
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 18/11/15
PAGE 4 OF 60
5.10 INTERFACE WITH HVAC CONTROL PANEL ..................................................... 44
6.0 PACKAGED AIE CONDITIONING UNIT-BAB STATCOM BUILDING ........................... 45
6.1 GENERAL ............................................................................................................ 45
6.2 EQUIPMENT LOCATION CONDITION ................................................................ 45
6.3 FAN SELECTION ................................................................................................. 46
6.4 COOLING COIL SELECTION .............................................................................. 47
6.5 FILTER SELECTION ............................................................................................ 48
6.6 CASING ............................................................................................................... 49
6.7 AIR COOLED CONDENSING PARTS ................................................................. 49
6.8 COMMON PARTS ................................................................................................ 51
6.9 OVERALL DIMENSION WEIGHT ........................................................................ 51
6.10 INTERFACE WITH HVAC CONTROL PANEL ..................................................... 52
7.0 PACKAGED AIE CONDITIONING UNIT-BUHASA STATCOM BUILDING ................... 53
7.1 GENERAL ............................................................................................................ 53
7.2 EQUIPMENT LOCATION CONDITION ................................................................ 53
7.3 FAN SELECTION ................................................................................................. 54
7.4 COOLING COIL SELECTION .............................................................................. 55
7.5 FILTER SELECTION ............................................................................................ 56
7.6 CASING ............................................................................................................... 57
7.7 AIR COOLED CONDENSING PARTS ................................................................. 57
7.8 COMMON PARTS ................................................................................................ 59
7.9 OVERALL DIMENSION WEIGHT ........................................................................ 59
7.10 INTERFACE WITH HVAC CONTROL PANEL ..................................................... 60 *VTA - Vendor To Advise.
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 5 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
1.0 PACKAGED AIR CONDITIONING UNIT (ROOF TOP UNIT) – ASAB 33KV SS 1.1 General
Equipment Tag Number
No. Required, Operation/Stand by
Duty
Type
Manufacturer
Model No.
Applicable Code
Air Supply System
Electric Power Source
Total Power Rating
Max. Start Current/Operating Current
-
Set
-
-
-
-
-
(CAV/VAV)
(V/Ph/Hz)
KW
A
ACU-14,15,16
2 / 1
Continuous
Floor Mounted
SKM
-
As per
specification
CAV
415 / 3 / 50
VTA
VTA
ACU-14,15,16
2 / 1
Noted
Floor Mounted
SKM
PACV 54100SM Rated in
accordance with
AHRI 340/360
CAV
415/3/50 4 wire
167.2
603/389.5
1.2 Equipment Location Condition
Location
Elevation (above sea level)
Barometer
Ambient Temperature, Max./Min
Design Temperature, Max. /Min.
Indoor
Outdoor Roof
Ground
Weather Protection Required
Tropicalization Required
-
M
Bar
°C
°C
-
-
-
-
-
Onshore
100
1.0013
55.0 / 5.0
50.0 / 5.0
No
Yes
No
Yes
Yes
Onshore
100
1.0013
55.0 / 5.0
50.0 / 5.0
Not Applicable
Yes
No
Yes
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 6 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Unusual Condition Corrosive
Dust
Fumes
Others
Hazardous Area Classification
Noise Level
-
-
-
-
-
dB(A) @ 1m
Yes
Yes
No
Saline
Atmosphere
Not Classified
85
Yes
Yes
No
Saline
Atmosphere
Not Classified
84.8
1.3 Fan Section
Supply Fan No. Required per AHU, Operation/Stand-by
Type (Airfoil/Backward
Inclined/Backward/Forward)
Construction Type (DWDI/SWSI)
Supply Air Flow Rate
External Static Pressure
Internal Static Pressure
Total Static Pressure
Fan Speed
Vibration Isolator with Accessory
Bearing Type
Applicable Code
AMCA Certification
Set
-
-
l/s
Pa
Pa
Pa
Rpm
-
-
-
-
1 / NA
Forward
Curved
DWDI
As per
approved HLC
500
VTA
VTA
VTA
Yes
Ball or Pillow
Block
As per
specification
Yes
1 / NA
Backward
Curved
DWDI
14523.5lps
500
671
1171
1024
Yes
Ball or Pillow
Block
Noted
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 7 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Supply Fan Motor No. Required per Fan, Operation/Stand-by
Power Rating
Motor Enclosure/Ingress Protection
Motor Manufacturer
Motor Efficiency
Space Heater
-
KW
-
-
-
-
1 / NA
VTA
TEFC/IP55
Siemens
As per
specification
Yes
1 / NA
30KW motor
TEFC/IP55 Siemens-Europe
IE1
Yes
1.4 Cooling Coil Section
No. Required per AHU, Operation/Stand-by
Type
Applicable Code
Total Cooling Capacity
Air Flow Rate
Entering Air Temperature, DB/WB
Leaving Air Temperature, DB/WB
Material, Tube/Fin
Fin Spacing
Limit of Coil Face Air Velocity
Min. Number of Refrigerant Circuits
Liquid/Gas
Corrosion Protection
Saline Atmosphere
-
-
-
KW
l/s
◦C
◦C
-
Ea/inch
m/s
ea
-
-
-
1/ NA
Direct
Expansion
As per
specification
As per HLC.
As per HLC.
As per HLC.
As per HLC.
Cu / Al
Max. 12
2.5
VTA
R 134a
Aeris Coating-
5year warranty
Yes
1/ NA
Direct
Expansion
Performance is
in accordance
with AHRI-410.
272.65
14523.5
26.3/18.0
12.49/12.45
Cu / Al
Max. 12
2.18
4
R 134a
Aeris Coating-
5year warranty
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 8 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Hydrogen Sulphide
Min. Life of Cooling Coil
Condensate Drain
Drain Pan Material
-
Years
-
-
Yes
5
Yes
SS with Insulation
Yes
5
Yes
SS with Insulation
1.5 Filter Section
Pre Filter
Type
Efficiency
Thickness
Filter Face Velocity
Limit of Initial Pressure drop
Limit of Final Pressure drop
Final Filter Type
Efficiency
Thickness
Filter Face Velocity
Limit of Initial Pressure Drop
Limit of Final Pressure Drop
-
%
mm
m/s
Pa
Pa
-
%
Mm
m/s
Pa
Pa
Panel
G4
50
2.5
Depends on
Face Velocity
VTA
Bag
F8(En 779)
533
2.5
Depends on
Face Velocity
VTA
Panel
G4
50
<2.5
45[Clean] &
147[Mean]
250pa[Dirty]
Pleated
F8(En 779)
100mm
<2.5
120.5[Clean] &
247[Mean]
373.5pa[Dirty]
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 9 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
1.6 Casing
Type
Material (G-90 Galvanized Steel or
Aluminium)
Insulation Material
Density
Thickness
Painting
-
-
-
kg/m3
mm
Mfr/job Spec.
Double Wall
Galvanized
Steel
Fiber Glass
comply to
NFPA-90A, B
32
50
As per
specification
Double Wall
Galvanized
Steel
Fiber Glass
comply to
NFPA-90A, B
32
50
SKM Marine standard Painting
1.7 Air Cooled Condensing Parts Compressor
Make
Model
No. of Compressor per ACCU
Compressor Type,
(Reciprocating/Screw/Scroll/Hermetic/Semi-
hermetic)
COP (Coefficient of Performance)
Power Rating per Compressor
Capacity Control Steps per Compressor
-
-
Ea
-
-
-
%
VTA
VTA
VTA
Scroll
As per Final
Selection
As per Final
Selection
VTA
Copeland-USA
ZR 250 [SKM
model]
8
Scroll
2.74
125.2KW[Total]
1 [0-100]
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 10 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Min. Operating Capacity per Compressor
Vibration Isolator with Accessory
Crank case Heater requirement
Refrigerant
-
-
-
13%
As per standard
Yes
13%
As per SKM
Standard
Yes
Refrigerant Type
Refrigerant Charge
Condenser Coil No. of Circuits per ACCU
Material, Tube/Fin
Corrosion Protection for Saline Atmosphere
Hydrogen Sulphide Atmosphere
Condenser Fan Fan Type
No. of Fans per ACCU
Airflow Rate per Fan
Total Airflow Rate per ACCU
Total Power Rating of Fans per ACCU
Motor Insulation/Temp. Rise
-
kg
ea
-
-
-
-
Ea
l/s
l/s
kw
-
R134a
VTA
VTA; shall be
provided after
HLC approval.
Cu / Al
Aeris Coating-5
year warranty
Yes
Propeller-Al
alloy
VTA
VTA
VTA
VTA
F / B
R134a
28kg per
circuit[Approx]
4
Cu / Al
Aeris Coating-5
year warranty
Yes
Propeller-Al alloy
8
4917.68
39341.5
1.5
F / B
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 11 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Motor Enclosure/Ingress Protection
Motor Manufacturer
-
-
TEFC / IP55
Siemens
TEFC / IP55
Siemens
1.8 Common Parts
Control & Electrical Panel including Starter
Control & Electrical Panel Enclosure Class
Overload Relay Protection for Compressor
Overload Relay Protection for Condenser Fan
Security Grillers
Hilted Type Anchor
Disconnection Switch
Motorized Damper, SA
Eliminator
Access Door
Application section
Quantities
Marine Light and Sight Glass
Quantities
Q’ty of PDIS for each Filter Pres. Drop
-
-
-
-
-
-
-
-
-
-
-
-
-
Ea
ea
Yes
IP 55
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
All Sections
2 (Fan & Filter)
Yes
2
2
Yes
IP 55
Yes
Yes
Yes
Yes,
As applicable
By EMCC
By EMCC
Yes
Yes
Fan section
1 (Fan),
Access panel for
filter
Yes
1
2
1.9 Overall Dimension Weight
Dimensions, Length
Width
Height
Weight, Operating
mm
mm
mm
Kg
VTA
VTA
VTA
VTA
8614 [frame size]
2540
3236
9763
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 12 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
1.10 Interface with HVAC Control Panel
Start/Stop from HCP to LCP
Running Status Signal from LCP to HCP
Trip Signal from LCP to HCP
Temperature Setting Value
Signal(4˜20mA)from HCP to LCP
Compressor Control Signal(4˜20mA)from
HCP to LCP
Dirt indication of pre-filter
Dirt indication of final filter
-
-
-
-
-
-
-
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Digital on/off/trip
Yes,VFC provided
Yes,VFC provided
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 13 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
2.0 PACKAGED AIR CONDITIONING UNIT (ROOF TOP UNIT) – BAB 33KV SS 2.1 General
Equipment Tag Number
No. Required, Operation/Stand by
Duty
Type
Manufacturer
Model No.
Applicable Code
Air Supply System
Electric Power Source
Total Power Rating
Max. Start Current/Operating Current
-
Set
-
-
-
-
-
(CAV/VAV)
(V/Ph/Hz)
KW
A
ACU-27,28,29
2 / 1
Continuous
Floor Mounted
SKM
-
As per
specification
CAV
415 / 3 / 50
VTA
VTA
ACU-27,28,29
2 / 1
Noted
Floor Mounted
SKM
PACV 53095SM Rated in
accordance with
AHRI 340/360
CAV
415/3/50 4 wire
153.7
590/336
2.2 Equipment Location Condition
Location
Elevation (above sea level)
Barometer
Ambient Temperature, Max./Min
Design Temperature, Max. /Min.
Indoor
Outdoor Roof
Ground
Weather Protection Required
Tropicalization Required
-
M
Bar
°C
°C
-
-
-
-
-
Onshore
100
1.0013
55.0 / 5.0
50.0 / 5.0
No
Yes
No
Yes
Yes
Onshore
100
1.0013
55.0 / 5.0
50.0 / 5.0
Not Applicable
Yes
No
Yes
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 14 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Unusual Condition Corrosive
Dust
Fumes
Others
Hazardous Area Classification
Noise Level
-
-
-
-
-
dB(A) @ 1m
Yes
Yes
No
Saline
Atmosphere
No implication
on Package
Unit
85
Yes
Yes
No
Saline
Atmosphere
NA
85
2.3 Fan Section
Supply Fan No. Required per AHU, Operation/Stand-by
Type (Airfoil/Backward
Inclined/Backward/Forward)
Construction Type (DWDI/SWSI)
Supply Air Flow Rate
External Static Pressure
Internal Static Pressure
Total Static Pressure
Fan Speed
Vibration Isolator with Accessory
Bearing Type
Applicable Code
AMCA Certification
Set
-
-
l/s
Pa
Pa
Pa
Rpm
-
-
-
-
1 / NA
Forward
Curved
DWDI
As per
approved HLC
500
VTA
VTA
VTA
Yes
Ball or Pillow
Block
As per
specification
Yes
1 / NA
Backward
Curved
DWDI
13085.5lps
500
624.5
1124.5
1183
Yes
Ball or Pillow
Block
Noted
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 15 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Supply Fan Motor No. Required per Fan, Operation/Stand-by
Power Rating
Motor Enclosure/Ingress Protection
Motor Manufacturer
Motor Efficiency
Space Heater
-
KW
-
-
-
-
1 / NA
VTA
TEFC/IP55
Siemens
As per
specification
Yes
1 / NA
30KW motor
TEFC/IP55 Siemens-Europe
IE1
Yes
2.4 Cooling Coil Section
No. Required per AHU, Operation/Stand-by
Type
Applicable Code
Total Cooling Capacity
Air Flow Rate
Entering Air Temperature, DB/WB
Leaving Air Temperature, DB/WB
Material, Tube/Fin
Fin Spacing
Limit of Coil Face Air Velocity
Min. Number of Refrigerant Circuits
Liquid/Gas
Corrosion Protection
Saline Atmosphere
-
-
-
KW
l/s
◦C
◦C
-
Ea/inch
m/s
ea
-
-
-
1/ NA
Direct
Expansion
As per
specification
As per HLC.
As per HLC.
As per HLC.
As per HLC.
Cu / Al
Max. 12
2.5
VTA
R 134a
Aeris Coating-
5year warranty
Yes
1/ NA
Direct
Expansion
Performance is
in accordance
with AHRI-410.
246.98
13085.5
26.3/18.1
12.59/12.56
Cu / Al
Max. 12
2.01
3
R 134a
Aeris Coating-
5year warranty
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 16 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Hydrogen Sulphide
Min. Life of Cooling Coil
Condensate Drain
Drain Pan Material
-
Years
-
-
Yes
5
Yes
SS with Insulation
Yes
5
Yes
SS with Insulation
2.5 Filter Section
Pre Filter
Type
Efficiency
Thickness
Filter Face Velocity
Limit of Initial Pressure drop
Limit of Final Pressure drop
Final Filter Type
Efficiency
Thickness
Filter Face Velocity
Limit of Initial Pressure Drop
Limit of Final Pressure Drop
-
%
mm
m/s
Pa
Pa
-
%
Mm
m/s
Pa
Pa
Panel
G4
50
2.5
Depends on
Face Velocity
VTA
Bag
F8(En 779)
533
2.5
Depends on
Face Velocity
VTA
Panel
G4
50
<2.5
38 [Clean] &
143.5[Mean]
250pa[Dirty]
Pleated
F8(En 779)
100mm
<2.5
110.5[Clean] &
242[Mean]
373.5pa[Dirty]
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 17 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
2.6 Casing
Type
Material (G-90 Galvanized Steel or
Aluminium)
Insulation Material
Density
Thickness
Painting
-
-
-
kg/m3
mm
Mfr/job Spec.
Double Wall
Galvanized
Steel
Fiber Glass
comply to
NFPA-90A, B
32
50
As per
specification
Double Wall
Galvanized
Steel
Fiber Glass
comply to
NFPA-90A, B
32
50
SKM Marine standard Painting
2.7 Air Cooled Condensing Parts Compressor
Make
Model
No. of Compressor per ACCU
Compressor Type,
(Reciprocating/Screw/Scroll/Hermetic/Semi-
hermetic)
COP (Coefficient of Performance)
Power Rating per Compressor
Capacity Control Steps per Compressor
-
-
Ea
-
-
-
%
VTA
VTA
VTA
Scroll
As per Final
Selection
As per Final
Selection
VTA
Copeland-USA
ZR310 +ZR 250
[SKM model]
[5+1]
Scroll
2.72
114.7KW[Total]
1 [0-100]
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 18 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Min. Operating Capacity per Compressor
Vibration Isolator with Accessory
Crank case Heater requirement
Refrigerant
-
-
-
13%
As per standard
Yes
17%
As per SKM
Standard
Yes
Refrigerant Type
Refrigerant Charge
Condenser Coil No. of Circuits per ACCU
Material, Tube/Fin
Corrosion Protection forSaline Atmosphere
Hydrogen Sulphide Atmosphere
Condenser Fan Fan Type
No. of Fans per ACCU
Airflow Rate per Fan
Total Airflow Rate per ACCU
Total Power Rating of Fans per ACCU
Motor Insulation/Temp. Rise
Motor Enclosure/Ingress Protection
Motor Manufacturer
-
kg
ea
-
-
-
-
Ea
l/s
l/s
kw
-
-
-
R134a
VTA
VTA; shall be
provided after
HLC approval.
Cu / Al
Aeris Coating-5
year warranty
Yes
Propeller-Al alloy
VTA
VTA
VTA
VTA
F / B
TEFC / IP55
Siemens
R134a
38kg per circuit
[Approx.]
3
Cu / Al
Aeris Coating-5
year warranty
Yes
Propeller-Al alloy
6
4667.57
28005.4
1.5
F / B
TEFC / IP55
Siemens
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 19 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
2.8 Common Parts
Control & Electrical Panel including Starter
Control & Electrical Panel Enclosure Class
Overload Relay Protection for Compressor
Overload Relay Protection for Condenser Fan
Security Grillers
Hilted Type Anchor
Disconnection Switch
Motorized Damper, SA
Eliminator
Access Door
Application section
Quantities
Marine Light and Sight Glass for liquid,
moisture indicator
Quantities
Q’ty of PDIS for each Filter Pres. Drop
-
-
-
-
-
-
-
-
-
-
-
-
-
Ea
ea
Yes
IP 55
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
All Sections
2 (Fan & Filter)
Yes
2
2
Yes
IP 55
Yes
Yes
Yes
Yes,
As applicable
By EMCC
By EMCC
Yes
Yes
Fan section
1 (Fan),
Access panel for
filter
Yes
1
2
2.9 Overall Dimension Weight
Dimensions, Length
Width
Height
Weight, Operating
mm
mm
mm
Kg
VTA
VTA
VTA
VTA
7558 [frame size]
2540
3172
8903
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 20 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
2.10 Interface with HVAC Control Panel
Start/Stop from HCP to LCP
Running Status Signal from LCP to HCP
Trip Signal from LCP to HCP
Temperature Setting Value
Signal(4˜20mA)from HCP to LCP
Compressor Control Signal(4˜20mA)from
HCP to LCP
Dirt indication of pre-filter
Dirt indication of final filter
-
-
-
-
-
-
-
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Digital on/off/trip
Yes,VFC provided
Yes,VFC provided
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 21 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
3.0 PACKAGED AIR CONDITIONING UNIT (ROOF TOP UNIT) – BAB LDC BUILDING 3.1 General
Equipment Tag Number
No. Required, Operation/Stand by
Duty
Type
Manufacturer
Model No.
Applicable Code
Air Supply System
Electric Power Source
Total Power Rating
Max. Start Current/Operating Current
-
Set
-
-
-
-
-
(CAV/VAV)
(V/Ph/Hz)
KW
A
ACU-01, 02
1/ 1
Continuous
Floor Mounted
SKM
-
As per
specification
CAV
415 / 3 / 50
VTA
VTA
ACU-01, 02
1/1
Noted
Floor Mounted
SKM
PACV 53075SM Rated in
accordance with
AHRI 340/360
CAV
415/3/50 4 wire
118.6
494/280.5
3.2 Equipment Location Condition
Location
Elevation (above sea level)
Barometer
Ambient Temperature, Max./Min
Design Temperature, Max. /Min.
Indoor
Outdoor Roof
Ground
Weather Protection Required
Tropicalization Required
-
M
Bar
°C
°C
-
-
-
-
-
Onshore
100
1.0013
55.0 / 5.0
50.0 / 5.0
No
Yes
No
Yes
Yes
Onshore
100
1.0013
55.0 / 5.0
50.0 / 5.0
Not Applicable
Yes
No
Yes
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 22 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Unusual Condition Corrosive
Dust
Fumes
Others
Hazardous Area Classification
Noise Level
-
-
-
-
-
dB(A) @ 1m
Yes
Yes
No
Saline
Atmosphere
Not classified
Area
85
Yes
Yes
No
Saline
Atmosphere
NA
82.3
3.3 Fan Section
Supply Fan No. Required per AHU, Operation/Stand-by
Type (Airfoil/Backward
Inclined/Backward/Forward)
Construction Type (DWDI/SWSI)
Supply Air Flow Rate
External Static Pressure
Internal Static Pressure
Total Static Pressure
Fan Speed
Vibration Isolator with Accessory
Bearing Type
Applicable Code
AMCA Certification
Set
-
-
l/s
Pa
Pa
Pa
Rpm
-
-
-
-
1 / NA
Forward
Curved
DWDI
As per
approved HLC
500
VTA
VTA
VTA
Yes
Ball or Pillow
Block
As per
specification
Yes
1 / NA
Backward
Curved
DWDI
7931lps
500
621.75
1121.5
1481
Yes
Ball or Pillow
Block
Noted
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 23 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Supply Fan Motor No. Required per Fan, Operation/Stand-by
Power Rating
Motor Enclosure/Ingress Protection
Motor Manufacturer
Motor Efficiency
Space Heater
-
KW
-
-
-
-
1 / NA
VTA
TEFC/IP55
Siemens
As per
specification
Yes
1 / NA
15 KW motor
TEFC/IP55 Siemens-Europe
IE1
Yes
3.4 Cooling Coil Section
No. Required per AHU, Operation/Stand-by
Type
Applicable Code
Total Cooling Capacity
Air Flow Rate
Entering Air Temperature, DB/WB
Leaving Air Temperature, DB/WB
Material, Tube/Fin
Fin Spacing
Limit of Coil Face Air Velocity
Min. Number of Refrigerant Circuits
Liquid/Gas
Corrosion Protection
Saline Atmosphere
-
-
-
KW
l/s
◦C
◦C
-
Ea/inch
m/s
ea
-
-
-
1/ NA
Direct
Expansion
As per
specification
As per HLC.
As per HLC.
As per HLC.
As per HLC.
Cu / Al
Max. 12
2.5
VTA
R 134a
Aeris Coating-
5year warranty
Yes
1/ NA
Direct
Expansion
Performance is
in accordance
with AHRI-410.
200.97
7931
28.6/19.6
12.38/12.34
Cu / Al
Max. 12
2.0
3
R 134a
Aeris Coating-
5year warranty
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 24 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Hydrogen Sulphide
Min. Life of Cooling Coil
Condensate Drain
Drain Pan Material
-
Years
-
-
Yes
5
Yes
SS with Insulation
Yes
5
Yes
SS with Insulation
3.5 Filter Section
Pre Filter
Type
Efficiency
Thickness
Filter Face Velocity
Limit of Initial Pressure drop
Limit of Final Pressure drop
Final Filter Type
Efficiency
Thickness
Filter Face Velocity
Limit of Initial Pressure Drop
Limit of Final Pressure Drop
-
%
mm
m/s
Pa
Pa
-
%
Mm
m/s
Pa
Pa
Panel
G4
50
2.5
Depends on
Face Velocity
VTA
Bag
F8(En 779)
533
2.5
Depends on
Face Velocity
VTA
Panel
G4
50
<2.5
38.5[Clean] &
143.75[Mean]
250pa[Dirty]
Pleated
F8(En 779)
100mm
<2.5
110.5[Clean] &
242[Mean]
373.5pa[Dirty]
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 25 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
3.6 Casing
Type
Material (G-90 Galvanized Steel or
Aluminium)
Insulation Material
Density
Thickness
Painting
-
-
-
kg/m3
mm
Mfr/job Spec.
Double Wall
Galvanized
Steel
Fiber Glass
comply to
NFPA-90A, B
32
50
As per
specification
Double Wall
Galvanized
Steel
Fiber Glass
comply to
NFPA-90A, B
32
50
SKM Marine standard Painting
3.7 Air Cooled Condensing Parts Compressor
Make
Model
No. of Compressor per ACCU
Compressor Type,
(Reciprocating/Screw/Scroll/Hermetic/Semi-
hermetic)
COP (Coefficient of Performance)
Power Rating per Compressor
Capacity Control Steps per Compressor
-
-
Ea
-
-
-
%
VTA
VTA
VTA
Scroll
As per Final
Selection
As per Final
Selection
VTA
Copeland-USA
ZR 250 [SKM
model]
6
Scroll
2.64
94.6KW[Total]
1 [0-100]
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 26 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Min. Operating Capacity per Compressor
Vibration Isolator with Accessory
Crank case Heater requirement
Refrigerant
-
-
-
13%
As per standard
Yes
17%
As per SKM
Standard
Yes
Refrigerant Type
Refrigerant Charge
Condenser Coil No. of Circuits per ACCU
Material, Tube/Fin
Corrosion Protection forSaline Atmosphere
Hydrogen Sulphide Atmosphere
Condenser Fan Fan Type
No. of Fans per ACCU
Airflow Rate per Fan
Total Airflow Rate per ACCU
Total Power Rating of Fans per ACCU
Motor Insulation/Temp. Rise
Motor Enclosure/Ingress Protection
-
kg
ea
-
-
-
-
Ea
l/s
l/s
kw
-
-
R134a
VTA
VTA; shall be
provided after
HLC approval.
Cu / Al
Aeris Coating-5
year warranty
Yes
Propeller-Al
alloy
VTA
VTA
VTA
VTA
F / B
TEFC / IP55
R134a
28kg per circuit
[approx.]
3
Cu / Al
Aeris Coating-5
year warranty
Yes
Propeller-Al alloy
6
4318.3
25909.9
1.5
F / B
TEFC / IP55
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 27 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Motor Manufacturer - Siemens Siemens
3.8 Common Parts
Control & Electrical Panel including Starter
Control & Electrical Panel Enclosure Class
Overload Relay Protection for Compressor
Overload Relay Protection for Condenser Fan
Security Grillers
Hilted Type Anchor
Disconnection Switch
Motorized Damper, SA
Eliminator
Access Door
Application section
Quantities
Marine Light and Sight Glass for liquid,
moisture indicator
Quantities
Q’ty of PDIS for each Filter Pres. Drop
-
-
-
-
-
-
-
-
-
-
-
-
-
Ea
ea
Yes
IP 55
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
All Sections
2 (Fan & Filter)
Yes
2
2
Yes
IP 55
Yes
Yes
Yes
Yes,
As applicable
By EMCC
By EMCC
Yes
Yes
Fan section
1 (Fan),
Access panel for
filter
Yes
1
2
3.9 Overall Dimension Weight
Dimensions, Length
Width
Height
Weight, Operating
mm
mm
mm
Kg
VTA
VTA
VTA
VTA
5983 [frame size]
2540
2570
6525
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 28 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
3.10 Interface with HVAC Control Panel
Start/Stop from HCP to LCP
Running Status Signal from LCP to HCP
Trip Signal from LCP to HCP
Temperature Setting Value
Signal(4˜20mA)from HCP to LCP
Compressor Control Signal(4˜20mA)from
HCP to LCP
Dirt indication of pre-filter
Dirt indication of final filter
-
-
-
-
-
-
-
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Digital on/off/trip
Yes,VFC provided
Yes,VFC provided
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 29 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Bidder
4.0 PACKAGED AIR CONDITIONING UNIT (ROOF TOP UNIT) – BUHASA 33KV SS 4.1 General
Equipment Tag Number
No. Required, Operation/Stand by
Duty
Type
Manufacturer
Model No.
Applicable Code
Air Supply System
Electric Power Source
Total Power Rating
Max. Start Current/Operating Current
-
Set
-
-
-
-
-
(CAV/VAV)
(V/Ph/Hz)
KW
A
ACU-16,17,18
2 / 1
Continuous
Floor Mounted
SKM
-
As per
specification
CAV
415 / 3 / 50
VTA
VTA
ACU-16,17,18
2 / 1
Noted
Floor Mounted
SKM
PACV 53095SM Rated in
accordance with
AHRI 340/360
CAV
415/3/50 4 wire
146.00
577/322
4.2 Equipment Location Condition
Location
Elevation (above sea level)
Barometer
Ambient Temperature, Max./Min
Design Temperature, Max. /Min.
Indoor
Outdoor Roof
Ground
Weather Protection Required
Tropicalization Required
-
M
Bar
°C
°C
-
-
-
-
-
Onshore
100
1.0013
55.0 / 5.0
50.0 / 5.0
No
Yes
No
Yes
Yes
Onshore
100
1.0013
55.0 / 5.0
50.0 / 5.0
Not Applicable
Yes
No
Yes
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 30 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Unusual Condition Corrosive
Dust
Fumes
Others
Hazardous Area Classification
Noise Level
-
-
-
-
-
dB(A) @ 1m
Yes
Yes
No
Saline
Atmosphere
Not classified
area
85
Yes
Yes
No
Saline
Atmosphere
Not Classified
85
4.3 Fan Section
Supply Fan No. Required per AHU, Operation/Stand-by
Type (Airfoil/Backward
Inclined/Backward/Forward)
Construction Type (DWDI/SWSI)
Supply Air Flow Rate
External Static Pressure
Internal Static Pressure
Total Static Pressure
Fan Speed
Vibration Isolator with Accessory
Bearing Type
Applicable Code
AMCA Certification
Set
-
-
l/s
Pa
Pa
Pa
Rpm
-
-
-
-
1 / NA
Forward
Curved
DWDI
As per
approved HLC
500
VTA
VTA
VTA
Yes
Ball or Pillow
Block
As per
specification
Yes
1 / NA
Backward
Curved
DWDI
130502.5lps
500
575
1075
973
Yes
Ball or Pillow
Block
Noted
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 31 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Supply Fan Motor No. Required per Fan, Operation/Stand-by
Power Rating
Motor Enclosure/Ingress Protection
Motor Manufacturer
Motor Efficiency
Space Heater
-
KW
-
-
-
-
1 / NA
VTA
TEFC/IP55
Siemens
As per
specification
Yes
1 / NA
22KW motor
TEFC/IP55 Siemens-Europe
IE1
Yes
4.4 Cooling Coil Section
No. Required per AHU, Operation/Stand-by
Type
Applicable Code
Total Cooling Capacity
Air Flow Rate
Entering Air Temperature, DB/WB
Leaving Air Temperature, DB/WB
Material, Tube/Fin
Fin Spacing
Limit of Coil Face Air Velocity
Min. Number of Refrigerant Circuits
Liquid/Gas
Corrosion Protection
Saline Atmosphere
-
-
-
KW
l/s
◦C
◦C
-
Ea/inch
m/s
ea
-
-
-
1/ NA
Direct
Expansion
As per
specification
As per HLC.
As per HLC.
As per HLC.
As per HLC.
Cu / Al
Max. 12
2.5
VTA
R 134a
Aeris Coating-
5year warranty
Yes
1/ NA
Direct
Expansion
Performance is
in accordance
with AHRI-410.
250.48
13502.5
26.2/18.1
12.67/12.65
Cu / Al
Max. 12
1.82
3
R 134a
Aeris Coating-
5year warranty
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 32 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Hydrogen Sulphide
Min. Life of Cooling Coil
Condensate Drain
Drain Pan Material
-
Years
-
-
Yes
5
Yes
SS with Insulation
Yes
5
Yes
SS with Insulation
4.5 Filter Section
Pre Filter
Type
Efficiency
Thickness
Filter Face Velocity
Limit of Initial Pressure drop
Limit of Final Pressure drop
Final Filter Type
Efficiency
Thickness
Filter Face Velocity
Limit of Initial Pressure Drop
Limit of Final Pressure Drop
-
%
mm
m/s
Pa
Pa
-
%
Mm
m/s
Pa
Pa
Panel
G4
50
2.5
Depends on
Face Velocity
VTA
Bag
F8(En 779)
533
2.5
Depends on
Face Velocity
VTA
Panel
G4
50
<2.5
33[Clean] &
141[Mean]
250pa[Dirty]
Pleated
F8(En 779)
100mm
<2.5
100.5[Clean] &
237[Mean]
373.5pa[Dirty]
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 33 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
4.6 Casing
Type
Material (G-90 Galvanized Steel or
Aluminium)
Insulation Material
Density
Thickness
Painting
-
-
-
kg/m3
mm
Mfr/job Spec.
Double Wall
Galvanized
Steel
Fiber Glass
comply to
NFPA-90A, B
32
50
As per specification
Double Wall
Galvanized
Steel
Fiber Glass
comply to
NFPA-90A, B
32
50
SKM Marine standard Painting
4.7 Air Cooled Condensing Parts Compressor
Make
Model
No. of Compressor per ACCU
Compressor Type,
(Reciprocating/Screw/Scroll/Hermetic/Semi-
hermetic)
COP (Coefficient of Performance)
Power Rating per Compressor
Capacity Control Steps per Compressor
-
-
Ea
-
-
Kw
-
VTA
VTA
VTA
Scroll
As per Final
Selection
As per Final
Selection
VTA
Copeland-USA
ZR 310 + ZR 250
[SKM model]
5+1
Scroll
2.8
115KW[Total]
1 [0-100]
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 34 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Min. Operating Capacity per Compressor
Vibration Isolator with Accessory
Crank case Heater requirement
Refrigerant
%
-
-
13%
As per standard
Yes
17%
As per SKM
Standard
Yes
Refrigerant Type
Refrigerant Charge
Condenser Coil No. of Circuits per ACCU
Material, Tube/Fin
Corrosion Protection forSaline Atmosphere
Hydrogen Sulphide Atmosphere
Condenser Fan Fan Type
No. of Fans per ACCU
Airflow Rate per Fan
Total Airflow Rate per ACCU
Total Power Rating of Fans per ACCU
Motor Insulation/Temp. Rise
Motor Enclosure/Ingress Protection
-
kg
ea
-
-
-
-
Ea
l/s
l/s
kw
-
-
R134a
VTA
VTA; shall be
provided after
HLC approval.
Cu / Al
Aeris Coating-5
year warranty
Yes
Propeller-Al alloy
VTA
VTA
VTA
VTA
F / B
TEFC / IP55
R134a
38kg per circuit
[Approx]
3
Cu / Al
Aeris Coating-5
year warranty
Yes
Propeller-Al alloy
6
4667.57
28005.4
1.5
F / B
TEFC / IP55
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 35 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Motor Manufacturer - Siemens Siemens
4.8 Common Parts
Control & Electrical Panel including Starter
Control & Electrical Panel Enclosure Class
Overload Relay Protection for Compressor
Overload Relay Protection for Condenser Fan
Security Grillers
Hilted Type Anchor
Disconnection Switch
Motorized Damper, SA
Eliminator
Access Door
Application section
Quantities
Marine Light and Sight Glass for liquid,
moisture indicator
Quantities
Q’ty of PDIS for each Filter Pres. Drop
-
-
-
-
-
-
-
-
-
-
-
-
-
Ea
ea
Yes
IP 55
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
All Sections
2 (Fan & Filter)
Yes
2
2
Yes
IP 55
Yes
Yes
Yes
Yes,
As applicable
By EMCC
By EMCC
Yes
Yes
Fan section
1 (Fan),
Access panel for
filter
Yes
1
2
4.9 Overall Dimension Weight Dimensions, Length
Width
Height
Weight, Operating
mm
mm
mm
Kg
VTA
VTA
VTA
VTA
7711 [frame size]
2540
3553
9410
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 36 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
4.10 Interface with HVAC Control Panel
Start/Stop from HCP to LCP
Running Status Signal from LCP to HCP
Trip Signal from LCP to HCP
Temperature Setting Value
Signal(4˜20mA)from HCP to LCP
Compressor Control Signal(4˜20mA)from
HCP to LCP
Dirt indication of pre-filter
Dirt indication of final filter
-
-
-
-
-
-
-
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Digital on/off/trip
Yes,VFC provided
Yes,VFC provided
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 37 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Bidder
5.0 PACKAGED AIR CONDITIONING UNIT (ROOF TOP UNIT) – ASAB STATCOM 5.1 General
Equipment Tag Number
No. Required, Operation/Stand by
Duty
Type
Manufacturer
Model No.
Applicable Code
Air Supply System
Electric Power Source
Total Power Rating
Max. Start Current/Operating Current
-
Set
-
-
-
-
-
(CAV/VAV)
(V/Ph/Hz)
KW
A
ACU-12,13
1 / 1
Continuous
Floor Mounted
SKM
-
As per
specification
CAV
415 / 3 / 50
VTA
VTA
ACU-12,13
1 / 1
Noted
Floor Mounted
SKM
PACV 53085 SM Rated in
accordance with
AHRI 340/360
CAV
415/3/50 4 wire
132.2
559/304
5.2 Equipment Location Condition
Location
Elevation (above sea level)
Barometer
Ambient Temperature, Max./Min
Design Temperature, Max. /Min.
Indoor
Outdoor Roof
Ground
Weather Protection Required
Tropicalization Required
-
M
Bar
°C
°C
-
-
-
-
-
Onshore
100
1.0013
55.0 / 5.0
50.0 / 5.0
No
Yes
No
Yes
Yes
Onshore
100
1.0013
55.0 / 5.0
50.0 / 5.0
Not Applicable
Yes
No
Yes
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 38 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Unusual Condition Corrosive
Dust
Fumes
Others
Hazardous Area Classification
Noise Level
-
-
-
-
-
dB(A) @ 1m
Yes
Yes
No
Saline
Atmosphere
Not classified
area
85
Yes
Yes
No
Saline
Atmosphere
Not Classified
84.9
5.3 Fan Section
Supply Fan No. Required per AHU, Operation/Stand-by
Type (Airfoil/Backward
Inclined/Backward/Forward)
Construction Type (DWDI/SWSI)
Supply Air Flow Rate
External Static Pressure
Internal Static Pressure
Total Static Pressure
Fan Speed
Vibration Isolator with Accessory
Bearing Type
Applicable Code
AMCA Certification
Set
-
-
l/s
Pa
Pa
Pa
Rpm
-
-
-
-
1 / NA
Forward
Curved
DWDI
As per
approved HLC
500
VTA
VTA
VTA
Yes
Ball or Pillow
Block
As per
specification
Yes
1 / NA
Backward
Curved
DWDI
11708lps
500
725.5
1225.5
1171
Yes
Ball or Pillow
Block
Noted
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 39 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Supply Fan Motor No. Required per Fan, Operation/Stand-by
Power Rating
Motor Enclosure/Ingress Protection
Motor Manufacturer
Motor Efficiency
Space Heater
-
KW
-
-
-
-
1 / NA
VTA
TEFC/IP55
Siemens
As per
specification
Yes
1 / NA
22KW motor
TEFC/IP55 Siemens-Europe
IE1
Yes
5.4 Cooling Coil Section
No. Required per AHU, Operation/Stand-by
Type
Applicable Code
Total Cooling Capacity
Air Flow Rate
Entering Air Temperature, DB/WB
Leaving Air Temperature, DB/WB
Material, Tube/Fin
Fin Spacing
Limit of Coil Face Air Velocity
Min. Number of Refrigerant Circuits
Liquid/Gas
Corrosion Protection
Saline Atmosphere
-
-
-
KW
l/s
◦F
◦F
-
Ea/inch
m/s
ea
-
-
-
1/ NA
Direct
Expansion
As per
specification
As per HLC.
As per HLC.
As per HLC.
As per HLC.
Cu / Al
Max. 12
2.5
VTA
R 134a
Aeris Coating-
5year warranty
Yes
1/ NA
Direct
Expansion
performance is
in accordance
with AHRI-410.
221.11
11708
26.4/18.1
12.58/12.54
Cu / Al
Max. 12
2.36
3
R 134a
Aeris Coating-
5year warranty
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 40 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Hydrogen Sulphide
Min. Life of Cooling Coil
Condensate Drain
Drain Pan Material
-
Years
-
-
Yes
5
Yes
SS with Insulation
Yes
5
Yes
SS with Insulation
5.5 Filter Section
Pre Filter
Type
Efficiency
Thickness
Filter Face Velocity
Limit of Initial Pressure drop
Limit of Final Pressure drop
Final Filter Type
Efficiency
Thickness
Filter Face Velocity
Limit of Initial Pressure Drop
Limit of Final Pressure Drop
-
%
mm
m/s
Pa
Pa
-
%
Mm
m/s
Pa
Pa
Panel
G4
50
2.5
Depends on
Face Velocity
VTA
Bag
F8(En 779)
533
2.5
Depends on
Face Velocity
VTA
Panel
G4
50
<2.5
55[Clean] &
152[Mean]
250pa[Dirty]
Pleated
F8(En 779)
100mm
<2.5
130.5[Clean] &
252[Mean]
373.5pa[Dirty]
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 41 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
5.6 Casing
Type
Material (G-90 Galvanized Steel or
Aluminium)
Insulation Material
Density
Thickness
Painting
-
-
-
kg/m3
mm
Mfr/job Spec.
Double Wall
Galvanized
Steel
Fiber Glass
comply to
NFPA-90A, B
32
50
As per
specification
Double Wall
Galvanized
Steel
Fiber Glass
comply to
NFPA-90A, B
32
50
SKM Marine standard Painting
5.7 Air Cooled Condensing Parts Compressor
Make
Model
No. of Compressor per ACCU
Compressor Type,
(Reciprocating/Screw/Scroll/Hermetic/Semi-
hermetic)
COP (Coefficient of Performance)
Power Rating per Compressor
Capacity Control Steps per Compressor
Min. Operating Capacity per Compressor
-
-
Ea
-
-
KW
%
-
VTA
VTA
VTA
Scroll
As per Final
Selection
As per Final
Selection
VTA
13%
Copeland-USA
ZR 310 + ZR 250
[SKM model]
2+4
Scroll
2.74
101.2KW[Total]
1 [0-100]
18%
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 42 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Vibration Isolator with Accessory
Crank case Heater requirement
Refrigerant
-
-
As per standard
Yes
As per SKM
Standard
Yes
Refrigerant Type
Refrigerant Charge
Condenser Coil No. of Circuits per ACCU
Material, Tube/Fin
Corrosion Protection forSaline Atmosphere
Hydrogen Sulphide Atmosphere
Condenser Fan Fan Type
No. of Fans per ACCU
Airflow Rate per Fan
Total Airflow Rate per ACCU
Total Power Rating of Fans per ACCU
Motor Insulation/Temp. Rise
Motor Enclosure/Ingress Protection
Motor Manufacturer
-
kg
ea
-
-
-
-
Ea
l/s
l/s
kw
-
-
-
R134a
VTA
VTA; shall be
provided after
HLC approval.
Cu / Al
Aeris Coating-5
year warranty
Yes
Propeller-Al
alloy
VTA
VTA
VTA
VTA
F / B
TEFC / IP55
Siemens
R134a
35kg per
circuit[Approx]
3
Cu / Al
Aeris Coating-5
year warranty
Yes
Propeller-Al alloy
6
4667.57
28005.4
1.5
F / B
TEFC / IP55
Siemens
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 43 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
5.8 Common Parts
Control & Electrical Panel including Starter
Control & Electrical Panel Enclosure Class
Overload Relay Protection for Compressor
Overload Relay Protection for Condenser Fan
Security Grillers
Hilted Type Anchor
Disconnection Switch
Motorized Damper, SA
Eliminator
Access Door
Application section
Quantities
Marine Light and Sight Glass for liquid,
moisture indicator
Quantities
Q’ty of PDIS for each Filter Pres. Drop
-
-
-
-
-
-
-
-
-
-
-
-
-
Ea
ea
Yes
IP 55
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
All Sections
2 (Fan & Filter)
Yes
2
2
Yes
IP 55
Yes
Yes
Yes
Yes,
As applicable
By EMCC
By EMCC
Yes
Yes
Fan section
1 (Fan),
Access panel for
filter
Yes
1
2
5.9 Overall Dimension Weight
Dimensions, Length
Width
Height
Weight, Operating
mm
mm
mm
Kg
VTA
VTA
VTA
VTA
6237 [frame size]
2540
2893
7725
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 44 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
5.10 Interface with HVAC Control Panel
Start/Stop from HCP to LCP
Running Status Signal from LCP to HCP
Trip Signal from LCP to HCP
Temperature Setting Value
Signal(4˜20mA)from HCP to LCP
Compressor Control Signal(4˜20mA)from
HCP to LCP
Dirt indication of pre-filter
Dirt indication of final filter
-
-
-
-
-
-
-
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Digital on/off/trip
Yes,VFC provided
Yes,VFC provided
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 45 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Bidder
6.0 PACKAGED AIR CONDITIONING UNIT (ROOF TOP UNIT) – BAB STATCOM 6.1 General
Equipment Tag Number
No. Required, Operation/Stand by
Duty
Type
Manufacturer
Model No.
Applicable Code
Air Supply System
Electric Power Source
Total Power Rating
Max. Start Current/Operating Current
-
Set
-
-
-
-
-
(CAV/VAV)
(V/Ph/Hz)
KW
A
ACU-09,10
1 / 1
Continuous
Floor Mounted
SKM
-
As per
specification
CAV
415 / 3 / 50
VTA
VTA
ACU-09,10
1 / 1
Noted
Floor Mounted
SKM
PACV 53085SM Rated in
accordance with
AHRI 340/360
CAV
415/3/50 4 wire
132.7
559/304
6.2 Equipment Location Condition
Location
Elevation (above sea level)
Barometer
Ambient Temperature, Max./Min
Design Temperature, Max. /Min.
Indoor
Outdoor Roof
Ground
Weather Protection Required
Tropicalization Required
-
M
Bar
°C
°C
-
-
-
-
-
Onshore
100
1.0013
55.0 / 5.0
50.0 / 5.0
No
Yes
No
Yes
Yes
Onshore
100
1.0013
55.0 / 5.0
50.0 / 5.0
Not Applicable
Yes
No
Yes
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 46 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Unusual Condition Corrosive
Dust
Fumes
Others
Hazardous Area Classification
Noise Level
-
-
-
-
-
dB(A) @ 1m
Yes
Yes
No
Saline
Atmosphere
Not classified
area.
85
Yes
Yes
No
Saline
Atmosphere
Not Classified
84.9
6.3 Fan Section
Supply Fan No. Required per AHU, Operation/Stand-by
Type (Airfoil/Backward
Inclined/Backward/Forward)
Construction Type (DWDI/SWSI)
Supply Air Flow Rate
External Static Pressure
Internal Static Pressure
Total Static Pressure
Fan Speed
Vibration Isolator with Accessory
Bearing Type
Applicable Code
AMCA Certification
Set
-
-
l/s
Pa
Pa
Pa
Rpm
-
-
-
-
1 / NA
Forward
Curved
DWDI
As per
approved HLC
500
VTA
VTA
VTA
Yes
Ball or Pillow
Block
As per
specification
Yes
1 / NA
Backward
Curved
DWDI
11993lps
500
574
1074
1129
Yes
Ball or Pillow
Block
Noted
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 47 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Supply Fan Motor No. Required per Fan, Operation/Stand-by
Power Rating
Motor Enclosure/Ingress Protection
Motor Manufacturer
Motor Efficiency
Space Heater
-
KW
-
-
-
-
1 / NA
VTA
TEFC/IP55
Siemens
As per
specification
Yes
1 / NA
22KW motor
TEFC/IP55 Siemens-Europe
IE1
Yes
6.4 Cooling Coil Section
No. Required per AHU, Operation/Stand-by
Type
Applicable Code
Total Cooling Capacity
Air Flow Rate
Entering Air Temperature, DB/WB
Leaving Air Temperature, DB/WB
Material, Tube/Fin
Fin Spacing
Limit of Coil Face Air Velocity
Min. Number of Refrigerant Circuits
Liquid/Gas
Corrosion Protection
Saline Atmosphere
-
-
-
KW
l/s
◦F
◦F
-
Ea/inch
m/s
ea
-
-
-
1/ NA
Direct
Expansion
As per
specification
As per HLC.
As per HLC.
As per HLC.
As per HLC.
Cu / Al
Max. 12
2.5
VTA
R 134a
Aeris Coating-
5year warranty
Yes
1/ NA
Direct
Expansion
Performance is
in accordance
with AHRI-410.
227.27
11993
26.4/18.1
12.54/12.52
Cu / Al
Max. 12
1.76
3
R 134a
Aeris Coating-
5year warranty
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 48 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Hydrogen Sulphide
Min. Life of Cooling Coil
Condensate Drain
Drain Pan Material
-
Years
-
-
Yes
5
Yes
SS with Insulation
Yes
5
Yes
SS with Insulation
6.5 Filter Section
Pre Filter
Type
Efficiency
Thickness
Filter Face Velocity
Limit of Initial Pressure drop
Limit of Final Pressure drop
Final Filter Type
Efficiency
Thickness
Filter Face Velocity
Limit of Initial Pressure Drop
Limit of Final Pressure Drop
-
%
mm
m/s
Pa
Pa
-
%
Mm
m/s
Pa
Pa
Panel
G4
50
2.5
Depends on
Face Velocity
VTA
Bag
F8(En 779)
533
2.5
Depends on
Face Velocity
VTA
Panel
G4
50
<2.5
29[Clean] &
139[Mean]
250pa[Dirty]
Pleated
F8(En 779)
100mm
<2.5
96.5[Clean] &
235[Mean]
373.5pa[Dirty]
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 49 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
6.6 Casing
Type
Material (G-90 Galvanized Steel or
Aluminium)
Insulation Material
Density
Thickness
Painting
-
-
-
kg/m3
mm
Mfr/job Spec.
Double Wall
Galvanized
Steel
Fiber Glass
comply to
NFPA-90A, B
32
50
As per
specification
Double Wall
Galvanized
Steel
Fiber Glass
comply to
NFPA-90A, B
32
50
SKM Marine standard Painting
6.7 Air Cooled Condensing Parts Compressor
Make
Model
No. of Compressor per ACCU
Compressor Type,
(Reciprocating/Screw/Scroll/Hermetic/Semi-
hermetic)
COP (Coefficient of Performance)
Power Rating per Compressor
Capacity Control Steps per Compressor
Min. Operating Capacity per Compressor
-
-
Ea
-
-
Kw
%
-
VTA
VTA
VTA
Scroll
As per Final
Selection
As per Final
Selection
VTA
13%
Copeland-USA
ZR 310 + ZR 250
[SKM model]
2+4
Scroll
2.86
101.7KW[Total]
1 [0-100]
18%
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 50 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Vibration Isolator with Accessory
Crank case Heater requirement
Refrigerant
-
-
As per standard
Yes
As per SKM
Standard
Yes
Refrigerant Type
Refrigerant Charge
Condenser Coil No. of Circuits per ACCU
Material, Tube/Fin
Corrosion Protection forSaline Atmosphere
Hydrogen Sulphide Atmosphere
Condenser Fan Fan Type
No. of Fans per ACCU
Airflow Rate per Fan
Total Airflow Rate per ACCU
Total Power Rating of Fans per ACCU
Motor Insulation/Temp. Rise
Motor Enclosure/Ingress Protection
Motor Manufacturer
-
kg
ea
-
-
-
-
Ea
l/s
l/s
kw
-
-
-
R134a
VTA
VTA; shall be
provided after
HLC approval.
Cu / Al
Aeris Coating-5
year warranty
Yes
Propeller-Al
alloy
VTA
VTA
VTA
VTA
F / B
TEFC / IP55
Siemens
R134a
35kg per circuit
[approx.]
3
Cu / Al
Aeris Coating-5
year warranty
Yes
Propeller-Al alloy
6
4667.57
28005.4
1.5
F / B
TEFC / IP55
Siemens
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 51 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
6.8 Common Parts
Control & Electrical Panel including Starter
Control & Electrical Panel Enclosure Class
Overload Relay Protection for Compressor
Overload Relay Protection for Condenser Fan
Security Grillers
Hilted Type Anchor
Disconnection Switch
Motorized Damper, SA
Eliminator
Access Door
Application section
Quantities
Marine Light and Sight Glass for liquid,
moisture indicator
Quantities
Q’ty of PDIS for each Filter Pres. Drop
-
-
-
-
-
-
-
-
-
-
-
-
-
Ea
ea
Yes
IP 55
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
All Sections
2 (Fan & Filter)
Yes
2
2
Yes
IP 55
Yes
Yes
Yes
Yes,
As applicable
By EMCC
By EMCC
Yes
Yes
Fan section
1 (Fan),
Access panel for
filter
Yes
1
2
6.9 Overall Dimension Weight
Dimensions, Length
Width
Height
Weight, Operating
mm
mm
mm
Kg
VTA
VTA
VTA
VTA
7660 [frame size]
2540
3172
8880
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 52 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
6.10 Interface with HVAC Control Panel
Start/Stop from HCP to LCP
Running Status Signal from LCP to HCP
Trip Signal from LCP to HCP
Temperature Setting Value
Signal(4˜20mA)from HCP to LCP
Compressor Control Signal(4˜20mA)from
HCP to LCP
Dirt indication of pre-filter
Dirt indication of final filter
-
-
-
-
-
-
-
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Digital on/off/trip
Yes,VFC provided
Yes,VFC provided
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 53 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
7.0 PACKAGED AIR CONDITIONING UNIT (ROOF TOP UNIT) – BUHASA STATCOM 7.1 General
Equipment Tag Number
No. Required, Operation/Stand by
Duty
Type
Manufacturer
Model No.
Applicable Code
Air Supply System
Electric Power Source
Total Power Rating
Max. Start Current/Operating Current
-
Set
-
-
-
-
-
(CAV/VAV)
(V/Ph/Hz)
KW
A
ACU-14,15
1 / 1
Continuous
Floor Mounted
SKM
-
As per
specification
CAV
415 / 3 / 50
VTA
VTA
ACU-14,15
1 / 1
Noted
Floor Mounted
SKM
PACV 53085SM Rated in
accordance with
AHRI 340/360
CAV
415/3/50 4 wire
132.2
559/304
7.2 Equipment Location Condition
Location
Elevation (above sea level)
Barometer
Ambient Temperature, Max./Min
Design Temperature, Max. /Min.
Indoor
Outdoor Roof
Ground
Weather Protection Required
Tropicalization Required
-
M
Bar
°C
°C
-
-
-
-
-
Onshore
100
1.0013
55.0 / 5.0
50.0 / 5.0
No
Yes
No
Yes
Yes
Onshore
100
1.0013
55.0 / 5.0
50.0 / 5.0
Not Applicable
Yes
No
Yes
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 54 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Unusual Condition Corrosive
Dust
Fumes
Others
Hazardous Area Classification
Noise Level
-
-
-
-
-
dB(A) @ 1m
Yes
Yes
No
Saline
Atmosphere
Not classified
area
85
Yes
Yes
No
Saline
Atmosphere
Not Classified
84.9
7.3 Fan Section
Supply Fan No. Required per AHU, Operation/Stand-by
Type (Airfoil/Backward
Inclined/Backward/Forward)
Construction Type (DWDI/SWSI)
Supply Air Flow Rate
External Static Pressure
Internal Static Pressure
Total Static Pressure
Fan Speed
Vibration Isolator with Accessory
Bearing Type
Applicable Code
AMCA Certification
Set
-
-
l/s
Pa
Pa
Pa
Rpm
-
-
-
-
1 / NA
Forward
Curved
DWDI
As per
approved HLC
500
VTA
VTA
VTA
Yes
Ball or Pillow
Block
As per
specification
Yes
1 / NA
Backward
Curved
DWDI
11796lps
500
759
1259
1185
Yes
Ball or Pillow
Block
Noted
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 55 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Supply Fan Motor No. Required per Fan, Operation/Stand-by
Power Rating
Motor Enclosure/Ingress Protection
Motor Manufacturer
Motor Efficiency
Space Heater
-
KW
-
-
-
-
1 / NA
VTA
TEFC/IP55
Siemens
As per
specification
Yes
1 / NA
22KW motor
TEFC/IP55 Siemens-Europe
IE1
Yes
7.4 Cooling Coil Section
No. Required per AHU, Operation/Stand-by
Type
Applicable Code
Total Cooling Capacity
Air Flow Rate
Entering Air Temperature, DB/WB
Leaving Air Temperature, DB/WB
Material, Tube/Fin
Fin Spacing
Limit of Coil Face Air Velocity
Min. Number of Refrigerant Circuits
Liquid/Gas
Corrosion Protection
Saline Atmosphere
-
-
-
KW
l/s
◦F
◦F
-
Ea/inch
m/s
ea
-
-
-
1/ NA
Direct
Expansion
As per
specification
As per HLC.
As per HLC.
As per HLC.
As per HLC.
Cu / Al
Max. 12
2.5
VTA
R 134a
Aeris Coating-
5year warranty
Yes
1/ NA
Direct
Expansion
Performance is
in accordance
with AHRI-410.
221.76
11796
26.4/18.2
12.74/12.69
Cu / Al
Max. 12
2.46
3
R 134a
Aeris Coating-
5year warranty
Yes
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 56 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Hydrogen Sulphide
Min. Life of Cooling Coil
Condensate Drain
Drain Pan Material
-
Years
-
-
Yes
5
Yes
SS with Insulation
Yes
5
Yes
SS with Insulation
7.5 Filter Section
Pre Filter
Type
Efficiency
Thickness
Filter Face Velocity
Limit of Initial Pressure drop
Limit of Final Pressure drop
Final Filter Type
Efficiency
Thickness
Filter Face Velocity
Limit of Initial Pressure Drop
Limit of Final Pressure Drop
-
%
mm
m/s
Pa
Pa
-
%
Mm
m/s
Pa
Pa
Panel
G4
50
2.5
Depends on
Face Velocity
VTA
Bag
F8(En 779)
533
2.5
Depends on
Face Velocity
VTA
Panel
G4
50
<2.5
65[Clean] &
157[Mean]
250pa[Dirty]
Pleated
F8(En 779)
100mm
<2.5
136.5[Clean] &
255[Mean]
373.5pa[Dirty]
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 57 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
7.6 Casing
Type
Material (G-90 Galvanized Steel or
Aluminium)
Insulation Material
Density
Thickness
Painting
-
-
-
kg/m3
mm
Mfr/job Spec.
Double Wall
Galvanized
Steel
Fiber Glass
comply to
NFPA-90A, B
32
50
As per
specification
Double Wall
Galvanized
Steel
Fiber Glass
comply to
NFPA-90A, B
32
50
SKM Marine standard Painting
7.7 Air Cooled Condensing Parts Compressor
Make
Model
No. of Compressor per ACCU
Compressor Type,
(Reciprocating/Screw/Scroll/Hermetic/Semi-
hermetic)
COP (Coefficient of Performance)
Power Rating per Compressor
Capacity Control Steps per Compressor
Min. Operating Capacity per Compressor
Vibration Isolator with Accessory
-
-
Ea
-
Kw
-
%
VTA
VTA
VTA
Scroll
As per Final
Selection
As per Final
Selection
VTA
13%
As per standard
Copeland-USA
ZR 310 + ZR 250
[SKM model]
2+4
Scroll
2.71
101.2KW[Total]
1 [0-100]
18%
As per SKM
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 58 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
Crank case Heater requirement
Refrigerant
-
-
-
Yes
Standard
Yes
Refrigerant Type
Refrigerant Charge
Condenser Coil No. of Circuits per ACCU
Material, Tube/Fin
Corrosion Protection forSaline Atmosphere
Hydrogen Sulphide Atmosphere
Condenser Fan Fan Type
No. of Fans per ACCU
Airflow Rate per Fan
Total Airflow Rate per ACCU
Total Power Rating of Fans per ACCU
Motor Insulation/Temp. Rise
Motor Enclosure/Ingress Protection
Motor Manufacturer
-
kg
ea
-
-
-
-
Ea
l/s
l/s
kw
-
-
-
R134a
VTA
VTA; shall be
provided after
HLC approval.
Cu / Al
Aeris Coating-5
year warranty
Yes
Propeller-Al
alloy
VTA
VTA
VTA
VTA
F / B
TEFC / IP55
Siemens
R134a
35kg per
circuit[Approx]
3
Cu / Al
Aeris Coating-5
year warranty
Yes
Propeller-Al alloy
6
4667.57
28005.4
1.5
F / B
TEFC / IP55
Siemens
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 59 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
7.8 Common Parts
Control & Electrical Panel including Starter
Control & Electrical Panel Enclosure Class
Overload Relay Protection for Compressor
Overload Relay Protection for Condenser Fan
Security Grillers
Hilted Type Anchor
Disconnection Switch
Motorized Damper, SA
Eliminator
Access Door
Application section
Quantities
Marine Light and Sight Glass for liquid,
moisture indicator
Quantities
Q’ty of PDIS for each Filter Pres. Drop
-
-
-
-
-
-
-
-
-
-
-
-
-
Ea
ea
Yes
IP 55
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
All Sections
2 (Fan & Filter)
Yes
2
2
Yes
IP 55
Yes
Yes
Yes
Yes,
As applicable
By EMCC
By EMCC
Yes
Yes
Fan section
1 (Fan),
Access panel for
filter
Yes
1
2
7.9 Overall Dimension Weight
Dimensions, Length
Width
Height
Weight, Operating
mm
mm
mm
Kg
VTA
VTA
VTA
VTA
6339 [frame size]
2540
2817
7709
DOCUMENT TITLE:
TYPICAL DATA SHEETS FOR PACKAGED AC UNIT
Project No.: P11550
ADCO DOC NO. 30-99-27-5601
REV. 3 Date: 23/02/15
PAGE 60 OF 60
ADCO Bidder: ___________________ EPC of New Power upgrade at all ADCO
Field Design Data Unit Required Design
7.10 Interface with HVAC Control Panel Start/Stop from HCP to LCP Running Status Signal from LCP to HCP Trip Signal from LCP to HCP Temperature Setting Value
Signal(4˜20mA)from HCP to LCP Compressor Control Signal(4˜20mA)from
HCP to LCP Dirt indication of pre-filter Dirt indication of final filter
- - - - - - -
Yes Yes Yes Yes Yes Yes Yes
Yes Yes Yes Yes Digital on/off/trip
Yes,VFC provided Yes,VFC provided